Easy Modbus
  1. Home
  2. Modbus register maps
  3. Aermec
  4. LCG series DC inverter air conditioners (built-in Modbus)

Split AC unit (VRF / split AC gateway built in) · Modbus register map

Aermec LCG series DC inverter air conditioners (built-in Modbus) Modbus register map

Updated 17 November 2026

Short answer

The indoor-unit controller of Aermec LCG units answers Modbus RTU directly, so no extra gateway is needed. Holding registers carry on/off, mode, fan speed, setpoint, louvre position and temperatures; coils carry feature flags (turbo, silent, locks, energy saving) and a long list of indoor, outdoor and inverter-drive fault bits. Up to 255 units can share a BMS line.

This page lists 114 Modbus registers for the Aermec LCG series DC inverter air conditioners (built-in Modbus) — 30 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Aermec’s own free documentation (linked below) and checked against it.

Manufacturer
Aermec
Model
LCG series DC inverter air conditioners (built-in Modbus)
Equipment type
Split AC unit (VRF / split AC gateway built in)
Registers
114 (30 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
LCG
Source document
Modbus Protocol User manual LCG · 5385758_02 · rev. 2024-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Aermec LCG series DC inverter air conditioners (built-in Modbus)

Integration in brief

Read words 2-25 for on/off, mode, fan, setpoint and louvres and word 4/49 for indoor and outdoor temperature; read coils 0-215 for status and fault bits. Write word 2 (0xAA/0x55), 17, 19 and 20 to control the unit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2Unit On/OffUINT16On/offRead/write
HR 17Set modeUINT16ModeRead/write
HR 19Set fan speedUINT16Fan speedRead/write
HR 20Set tempUINT16SetpointRead/write
HR 4Ambient tempINT16Indoor temperatureRead
HR 49Outdoor ambient tempINT16Outdoor temperatureRead
CO 151Compressor statusBITCompressor runningRead
CO 95Error output statusBITError outputRead

Enable Modbus control & writes

The Modbus interface is built into the indoor-unit controller; the unit address and BMS mode are set from the wired controller (see the unit's service manual).

Byte order & addressing

Network setup

Watch out for

Aermec LCG series DC inverter air conditioners (built-in Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

114 of 114 shown
Aermec LCG series DC inverter air conditioners (built-in Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO8doc Bit8ODU flag present1 = yes.BITRead
CO9doc Bit9Master wired controller flag1 = yes.BITRead
CO13doc Bit13Slave wired controller flag1 = yes.BITRead
CO17doc Bit17Remote lock1 = locked by remote monitoring or the charging system.BITRead/write
CO19doc Bit19Remote mode shield1 = mode changes from the unit are blocked.BITRead/write
CO20doc Bit20Remote On/Off shield1 = on/off from the unit is blocked.BITRead/write
CO21doc Bit21Remote energy saving shield1 = shield on.BITRead/write
CO24doc Bit24Absence mode1 = on.BITRead/write
CO25doc Bit25Healthy function1 = on.BITRead/write
CO26doc Bit26I-Demand comfort/energy saving1 = on.BITRead/write
CO27doc Bit27Turbo1 = on.BITRead/write
CO28doc Bit28E-heating permission0 = electric heater allowed, 1 = not allowed.BITRead/write
CO29doc Bit29X-fan1 = on.BITRead/write
CO30doc Bit30Silent1 = on.BITRead/write
CO31doc Bit31Low temp drying mode1 = on.BITRead/write
CO32doc Bit32Energy saving under cooling1 = on. Write together with bit 33.BITRead/write
CO33doc Bit33Energy saving under heating1 = on. Write together with bit 32.BITRead/write
CO34doc Bit34Buttons lock (child lock)1 = on.BITRead/write
CO35doc Bit35On/Off memory0 = memorize, 1 = do not memorize.BITRead/write
CO36doc Bit36°C/°F flag1 = °F, 0 = °C.BITRead/write
CO40doc Bit40Timer status1 = timer set.BITRead
CO46doc Bit46Gate control system present1 = yes.BITRead
CO47doc Bit47Human body sensing module present1 = yes.BITRead
CO49doc Bit49Timer On flag1 = active.BITRead
CO50doc Bit50Timer Off flag1 = active.BITRead
CO51doc Bit51Indoor ambient source0 = return-air sensor, 1 = wired controller sensor.BITRead
CO55doc Bit55Low standby power control1 = mode 2, 0 = mode 1.BITRead
CO65doc Bit65Wired controller temp sensor error1 = error.BITRead
CO70doc Bit70Wired controller memory chip error1 = error.BITRead
CO72doc Bit72Cancel timer1 = cancel.BITRead/write
CO74doc Bit74Up & down swing mode0 = simple swing, 1 = fixed angle and small-area swing.BITRead/write
CO91doc Bit91Electric heating1 = yes.BITRead
CO92doc Bit92Water pump1 = on.BITRead
CO93doc Bit93Fresh air valve switch1 = on.BITRead
CO95doc Bit95Error output status1 = yes.BITRead
CO97doc Bit97Indoor evaporator temp sensor error1 = error.BITRead
CO98doc Bit98Indoor return air temp sensor error1 = error.BITRead
CO99doc Bit99Light board ambient temp sensor error1 = error.BITRead
CO101doc Bit101Water overflow protection1 = active.BITRead
CO102doc Bit102IDU memory chip error1 = error.BITRead
CO104doc Bit104Jumper cap error1 = error.BITRead
CO105doc Bit105Indoor fan error1 = error.BITRead
CO112doc Bit112Card in/out status1 = card in.BITRead
CO113doc Bit113People in room1 = yes.BITRead
CO114doc Bit114Static pressure type0 = low static, 1 = high static.BITRead
CO120doc Bit120Comm failure with master wired controller1 = failure.BITRead
CO121doc Bit121Comm failure with slave wired controller1 = failure.BITRead
CO122doc Bit122Comm failure with ODU1 = failure.BITRead
CO147doc Bit147Outdoor fan status1 = on.BITRead
CO150doc Bit1504-way valve status1 = on.BITRead
CO151doc Bit151Compressor status1 = on.BITRead
CO152doc Bit152Discharge temperature protection1 = active.BITRead
CO153doc Bit153Refrigerant shortage protection1 = active.BITRead
CO154doc Bit154DC fan motor protection1 = active.BITRead
CO156doc Bit156Over power protection1 = active.BITRead
CO157doc Bit157Overload protection1 = active.BITRead
CO158doc Bit158Low pressure protection1 = active.BITRead
CO159doc Bit159High pressure protection1 = active.BITRead
CO160doc Bit160Evaporator anti-freezing protection1 = active.BITRead
CO161doc Bit161Outdoor ambient temp sensor error1 = error.BITRead
CO162doc Bit162Discharge temp sensor error1 = error.BITRead
CO163doc Bit163Condenser temp sensor error1 = error.BITRead
CO164doc Bit164Outdoor coil pipe temp sensor error1 = error.BITRead
CO166doc Bit166ODU memory chip error1 = error.BITRead
CO174doc Bit174Drive communication failure1 = failure.BITRead
CO176doc Bit176SAVE status1 = yes.BITRead
CO177doc Bit177Cooling only flag0 = heat pump, 1 = cooling only.BITRead
CO179doc Bit179System defrosting1 = defrosting.BITRead
CO182doc Bit182Low power consumption status1 = ready.BITRead
CO183doc Bit183AC input phase sequence protection1 = active.BITRead
CO184doc Bit184Drive DC bus undervoltage1 = failure.BITRead
CO185doc Bit185Drive DC bus overvoltage1 = failure.BITRead
CO186doc Bit186Drive AC input current protection1 = failure.BITRead
CO187doc Bit187Drive IPM protection1 = failure.BITRead
CO188doc Bit188Drive PFC protection1 = failure.BITRead
CO190doc Bit190Compressor phase loss protection1 = failure.BITRead
CO191doc Bit191Drive module reset1 = failure.BITRead
CO192doc Bit192Compressor over-current protection1 = failure.BITRead
CO193doc Bit193Compressor power protection1 = failure.BITRead
CO194doc Bit194Drive current check circuit failure1 = failure.BITRead
CO195doc Bit195Compressor out-of-step protection1 = failure.BITRead
CO198doc Bit198Drive module high temperature1 = failure.BITRead
CO199doc Bit199Drive module temp sensor failure1 = failure.BITRead
CO201doc Bit201Compressor low field (flux weakening)1 = active.BITRead
CO202doc Bit202Drive frequency limit1 = active.BITRead
CO203doc Bit203Drive frequency reduction1 = active.BITRead
CO204doc Bit204Drive AC input low voltage1 = active.BITRead
CO205doc Bit205Drive under charge1 = under charge, 0 = charged.BITRead
CO207doc Bit207Drive AC input power typeFlag 1/0; meaning not given.BITRead
CO208doc Bit208Drive storage chip failure1 = failure.BITRead
CO210doc Bit210Drive charge circuit failure1 = failure.BITRead
CO211doc Bit211Drive AC input voltage abnormal1 = failure.BITRead
CO212doc Bit212Compressor temp sensor failure1 = failure.BITRead
CO213doc Bit213Drive AC zero-cross protection1 = failure.BITRead
CO214doc Bit214Temperature drift protection1 = failure.BITRead
CO215doc Bit215Current sensor connection protection1 = failure (sensor not on U or V phase).BITRead
HR2doc Word 2Unit On/Off0xAA (170) = on, 0x55 (85) = off.UINT16Read/write85 = Off (0x55); 170 = On (0xAA)
HR4doc Word 4Ambient tempIndoor ambient temperature.INT16× 0.1°CRead
HR5doc Word 5IDU Addr.1-16 with a central controller, 1-255 in PC address mode.UINT16Read
HR17doc Word 17Set modeUINT16Read/write1 = Cooling; 2 = Heating; 3 = Drying; 4 = Fan only; 5 = Auto
HR19doc Word 19Set fan speedUINT16Read/write0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Turbo
HR20doc Word 20Set temp16-30 °C; reads 12 in low-temp drying and 8 in absence mode.UINT16°CRead/write
HR22doc Word 22Up & down swingUINT16Read/write0 = Off; 1 = Swing 1-5; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 7 = Swing 3-5; 8 = Swing 2-5; 9 = Swing 2-4; 10 = Swing 1-4; 11 = Swing 1-3
HR23doc Word 23Left & right swingUINT16Read/write0 = Off (default after power-on); 1 = Swing, same direction; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 12 = 15 position (as printed); 13 = Swing, opposite direction
HR24doc Word 24Fresh air valve status0-10: fresh air valve mode.UINT16Read/write
HR25doc Word 25Sleep modeUINT16Read/write0 = No sleep mode; 1 = Sleep mode 1; 2 = Sleep mode 2; 3 = Sleep mode 3
HR34doc Word 34Clean function0 = no clean function, 10-39 = contamination grade.UINT16Read/write
HR35doc Word 35Energy saving cooling lower limitLowest setpoint allowed when cooling energy saving is on (16-30).UINT16°CRead/write
HR36doc Word 36Energy saving heating upper limitHighest setpoint allowed when heating energy saving is on (16-30).UINT16°CRead/write
HR39doc Word 39Selection of ambient temp sensorUINT16Read1 = Return-air sensor; 2 = Wired controller sensor; 3 = Return air for cool/dry/fan, wired controller for heat/auto
HR49doc Word 49Outdoor ambient temp-100 to 155.INT16°CRead
HR77doc Word 77DRED functionUINT16Read1 = DRED1 mode; 2 = DRED2 mode; 3 = DRED3 mode
HR82doc Word 82Return air tempAmbient temperature at the return-air port.INT16× 0.1°CRead
HR83doc Word 83Light board tempAmbient temperature at the display (light) board.INT16× 0.1°CRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Aermec LCG series DC inverter air conditioners (built-in Modbus)

What Modbus registers does the Aermec LCG series DC inverter air conditioners (built-in Modbus) have?

This map lists 114 registers: 96 coils, 18 holding registers. 30 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Aermec LCG series DC inverter air conditioners (built-in Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The protocol says registers are words numbered from 0 and coils are bits numbered from 0 (Byte0.0 = bit 0). Word n is wire address n and Bit n is coil n; the example frames agree (read starting at word 1 sends 0x0001, coil 5 sends 0x0005).

What are the minimum Modbus registers to integrate the Aermec LCG series DC inverter air conditioners (built-in Modbus)?

Start with HR 2 Unit On/Off (On/off); HR 17 Set mode (Mode); HR 19 Set fan speed (Fan speed); HR 20 Set temp (Setpoint); HR 4 Ambient temp (Indoor temperature); HR 49 Outdoor ambient temp (Outdoor temperature); CO 151 Compressor status (Compressor running); CO 95 Error output status (Error output).

How do I enable Modbus control of the Aermec LCG series DC inverter air conditioners (built-in Modbus)?

The Modbus interface is built into the indoor-unit controller; the unit address and BMS mode are set from the wired controller (see the unit's service manual).

Where is the official Aermec LCG series DC inverter air conditioners (built-in Modbus) Modbus documentation?

The source is Modbus Protocol User manual LCG (5385758_02), revision 2024-01, published free by Aermec at https://www.aermec.com/download?id=14523.

More Aermec Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Modbus Protocol User manual LCG · 5385758_02 · rev. 2024-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.