- Home
- Modbus register maps
- Intesis (HMS Networks)
- INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
VRF / split AC gateway · Modbus register map
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus register map
Updated 19 November 2026
Gateway that sits on the Mitsubishi Heavy Industries Superlink bus and exposes up to 128 (or 48) indoor units as a fixed Modbus map: 20 registers per unit address with on/off, mode, setpoint, fan, louver, room temperature, error and lock, plus a few all-unit commands. Modbus RTU (RS-485 or RS-232) and Modbus TCP.
This page lists 20 Modbus registers for the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
- Equipment type
- VRF / split AC gateway
- Registers
- 20 (13 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink
Integration notes: Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Enable the indoor units in LinkBoxMB, set the SLK selector (New = Superlink-II, Old = Superlink-I), then poll each unit's 20-register block. Write single registers (FC06) for on/off, mode, setpoint and fan.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | IU communication status | UINT16 | Unit communication status | Read |
| HR 1 | IU on/off | UINT16 | On/off | Read/write |
| HR 2 | IU operation mode | UINT16 | Mode | Read/write |
| HR 3 | IU setpoint temperature | UINT16 | Setpoint (°C) | Read/write |
| HR 4 | IU fan speed | UINT16 | Fan speed | Read/write |
| HR 7 | IU room temperature | UINT16 | Room temperature (°C) | Read |
| HR 9 | IU error code | UINT16 | Error code | Read |
| HR 2994 | Hardware communication status | UINT16 | Gateway hardware communication status | Read |
Enable Modbus control & writes
Each indoor unit must be enabled in the LinkBoxMB Devices list and the configuration file sent to the gateway.
Communication loss & watchdog
A per-unit communication-error signal is raised when a unit stops answering within the 'Timeout response' set in LinkBoxMB (2000..10000 ms).
Byte order & addressing
- Printed addresses are 1-based: subtract 1 for the wire address.
- Only FC06 is supported for writes (no FC16).
- Mode codes differ from most other Intesis maps: 0 = Cool, 1 = Heat, 2 = Fan, 3 = Auto, 4 = Dry.
Network setup
- Configure Modbus (TCP and/or RTU, RS-485 on C1 or RS-232 on C2, baud 1200..38400, parity, slave number) in LinkBoxMB over the console port.
- Superlink connects to the A-B terminals (no polarity), max 1000 m, no loop wiring.
- Set the SLK selector to NEW for Superlink-II systems or OLD for Superlink-I.
Watch out for
- With SC-SL2NA / SC-SL3NA central controllers present, unconnected indoor units must be deregistered and the remote lock rights adjusted (see manual section 1).
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | IU communication status | Indoor unit address 0 shown; see notes. | UINT16 | Read | 0 = Communication OK; 1 = Communication error | |||
| HR | 1doc 2 | IU on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2doc 3 | IU operation mode | UINT16 | Read/write | 0 = Cool; 1 = Heat; 2 = Fan; 3 = Auto; 4 = Dry | ||||
| HR | 3doc 4 | IU setpoint temperature | Whole °C, 16..30. | UINT16 | °C | Read/write | |||
| HR | 4doc 5 | IU fan speed | UINT16 | Read/write | 0 = Low; 1 = Medium; 2 = High; 3 = Powerful | ||||
| HR | 5doc 6 | IU remote controller lock | UINT16 | Read/write | 0 = Remote controller locked; 1 = Remote controller unlocked | ||||
| HR | 6doc 7 | IU louver control | Reads Swing while the louver moves between positions. | UINT16 | Read/write | 0 = Swing; 1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4 | |||
| HR | 7doc 8 | IU room temperature | Whole °C, 0..30. | UINT16 | °C | Read | |||
| HR | 8doc 9 | IU filter sign | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9doc 10 | IU error code | 0 = no error; 1..99 = MHI E-code number (e.g. 9 = E9 drain trouble). | UINT16 | Read | 0 = No error | |||
| HR | 10doc 11 | IU compressor status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11doc 12 | IU filter sign reset | Reads back 0. | UINT16 | Write | 1 = Clear filter alarm | |||
| HR | 12doc 13 | IU remote controller error reset | Reads back 0. | UINT16 | Write | 1 = Clear remote controller error | |||
| HR | 13doc 14 | IU thermo on/off status | Inverter units only. | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 2994doc 2995 | Hardware communication status | UINT16 | Read | 0 = No hardware communication error; 1 = Hardware communication error | ||||
| HR | 2995doc 2996 | All units on/off | UINT16 | Write | 0 = Off; 1 = On | ||||
| HR | 2996doc 2997 | All units operation mode | UINT16 | Write | 0 = Cool; 1 = Heat; 2 = Fan; 3 = Auto; 4 = Dry | ||||
| HR | 2997doc 2998 | All units setpoint | Whole °C, 16..30. | UINT16 | °C | Write | |||
| HR | 2998doc 2999 | All units fan speed | UINT16 | Write | 0 = Low; 1 = Medium; 2 = High; 3 = Powerful | ||||
| HR | 2999doc 3000 | All units remote controller lock | UINT16 | Write | 0 = Remote controller locked; 1 = Remote controller unlocked |
Notes on this map
- Only indoor unit address 0 is listed. For unit address n add n x 20 to each wire address (unit 127 on/off: printed 2542, wire 2541).
- The manual says registers are 2-byte big-endian values but does not say signed or unsigned; all listed values are non-negative, so UINT16 is used.
- Temperatures are whole °C (no x10).
- Writes must use function 06 (single register). Reads use 03 or 04. A poll range containing an invalid address returns an exception.
- Error code numbers match MHI remote-controller E codes (value 40 = E40 high pressure); full table on p. 26 of the manual.
- INMBSMHI048O000 serves unit addresses 00..47 only.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
What Modbus registers does the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway have?
This map lists 20 registers: 20 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables say 'base addr is 1': printed register 1 is wire address 0. Indoor unit with Superlink address n (0..127) uses printed n x 20 + 1 .. n x 20 + 14, so wire n x 20 + 0..13. This file lists unit address 0 (printed 1..14, wire 0..13) and the all-unit block (printed 2995..3000).
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway?
Start with HR 0 IU communication status (Unit communication status); HR 1 IU on/off (On/off); HR 2 IU operation mode (Mode); HR 3 IU setpoint temperature (Setpoint (°C)); HR 4 IU fan speed (Fan speed); HR 7 IU room temperature (Room temperature (°C)); HR 9 IU error code (Error code); HR 2994 Hardware communication status (Gateway hardware communication status).
How do I enable Modbus control of the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway?
Each indoor unit must be enabled in the LinkBoxMB Devices list and the configuration file sent to the gateway.
What happens when the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway loses Modbus communication?
A per-unit communication-error signal is raised when a unit stops answering within the 'Timeout response' set in LinkBoxMB (2000..10000 ms).
Where is the official Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus documentation?
The source is Intesis Modbus Server - Mitsubishi Heavy Industries AC User's Manual (User's Manual r1.0 eng), revision 2012-05, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsmhixxxo000.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
LG PAHCMS000 AHU Communication Kit for discharge (supply) air control with up to four LG outdoor units, installation manual IM_AHU_Comm_Kit_PAHCMS000_11_23.
Also known as: PAHCMS000, LG AHU Communication Kit discharge air, LG AHU comm kit PAHCMS000 Modbus - VRF / split AC gateway
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
RTD-NET on the Daikin P1/P2 bus (VRV, Sky Air, VAM/VKM), up to 16 indoor units as one group; RTD-10 with the same firmware uses the same layout.
Also known as: RTD-NET, RTD-10, Daikin RTD-NET - Heat pump (via ISG Modbus TCP gateway)
Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)
Stiebel Eltron heat pumps run by a WPMsystem, WPM 3 or WPM 3i manager, reached through an ISG web (229336) or ISG plus (233493) with the Modbus TCP/IP software extension.
Also known as: ISG web Modbus TCP/IP, ISG plus Modbus TCP/IP, WPMsystem, WPM 3, WPM 3i - VRF / split AC gateway
Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
Airzone Aidoo Pro units configured for Modbus output and connected to a direct-expansion AC unit; register table 'Registers for Direct Expansion units' of the Aidoo - Modbus integration manual (v. 201). The air-to-water table in the same manual is not covered.
Also known as: Aidoo Pro, Aidoo Pro Modbus, Airzone Aidoo Modbus - VRF / split AC gateway
Fujitsu General UTY-VMSX Modbus converter (one indoor unit)
Fujitsu General UTY-VMSX Modbus RTU converter, one per indoor unit, per interface specification part no. 9708438047-05.
Also known as: UTY-VMSX - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA
All ac & vrf gateways Modbus register maps →
Source: Intesis Modbus Server - Mitsubishi Heavy Industries AC User's Manual · User's Manual r1.0 eng · rev. 2012-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.