Easy Modbus
  1. Home
  2. Modbus register maps
  3. Intesis (HMS Networks)
  4. INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus register map

Updated 19 November 2026

Short answer

Gateway that sits on the Mitsubishi Heavy Industries Superlink bus and exposes up to 128 (or 48) indoor units as a fixed Modbus map: 20 registers per unit address with on/off, mode, setpoint, fan, louver, room temperature, error and lock, plus a few all-unit commands. Modbus RTU (RS-485 or RS-232) and Modbus TCP.

This page lists 20 Modbus registers for the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Equipment type
VRF / split AC gateway
Registers
20 (13 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink
Source document
Intesis Modbus Server - Mitsubishi Heavy Industries AC User's Manual · User's Manual r1.0 eng · rev. 2012-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway

Integration in brief

Enable the indoor units in LinkBoxMB, set the SLK selector (New = Superlink-II, Old = Superlink-I), then poll each unit's 20-register block. Write single registers (FC06) for on/off, mode, setpoint and fan.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0IU communication statusUINT16Unit communication statusRead
HR 1IU on/offUINT16On/offRead/write
HR 2IU operation modeUINT16ModeRead/write
HR 3IU setpoint temperatureUINT16Setpoint (°C)Read/write
HR 4IU fan speedUINT16Fan speedRead/write
HR 7IU room temperatureUINT16Room temperature (°C)Read
HR 9IU error codeUINT16Error codeRead
HR 2994Hardware communication statusUINT16Gateway hardware communication statusRead

Enable Modbus control & writes

Each indoor unit must be enabled in the LinkBoxMB Devices list and the configuration file sent to the gateway.

Communication loss & watchdog

A per-unit communication-error signal is raised when a unit stops answering within the 'Timeout response' set in LinkBoxMB (2000..10000 ms).

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

20 of 20 shown
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1IU communication statusIndoor unit address 0 shown; see notes.UINT16Read0 = Communication OK; 1 = Communication error
HR1doc 2IU on/offUINT16Read/write0 = Off; 1 = On
HR2doc 3IU operation modeUINT16Read/write0 = Cool; 1 = Heat; 2 = Fan; 3 = Auto; 4 = Dry
HR3doc 4IU setpoint temperatureWhole °C, 16..30.UINT16°CRead/write
HR4doc 5IU fan speedUINT16Read/write0 = Low; 1 = Medium; 2 = High; 3 = Powerful
HR5doc 6IU remote controller lockUINT16Read/write0 = Remote controller locked; 1 = Remote controller unlocked
HR6doc 7IU louver controlReads Swing while the louver moves between positions.UINT16Read/write0 = Swing; 1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4
HR7doc 8IU room temperatureWhole °C, 0..30.UINT16°CRead
HR8doc 9IU filter signUINT16Read0 = Off; 1 = On
HR9doc 10IU error code0 = no error; 1..99 = MHI E-code number (e.g. 9 = E9 drain trouble).UINT16Read0 = No error
HR10doc 11IU compressor statusUINT16Read0 = Off; 1 = On
HR11doc 12IU filter sign resetReads back 0.UINT16Write1 = Clear filter alarm
HR12doc 13IU remote controller error resetReads back 0.UINT16Write1 = Clear remote controller error
HR13doc 14IU thermo on/off statusInverter units only.UINT16Read0 = Off; 1 = On
HR2994doc 2995Hardware communication statusUINT16Read0 = No hardware communication error; 1 = Hardware communication error
HR2995doc 2996All units on/offUINT16Write0 = Off; 1 = On
HR2996doc 2997All units operation modeUINT16Write0 = Cool; 1 = Heat; 2 = Fan; 3 = Auto; 4 = Dry
HR2997doc 2998All units setpointWhole °C, 16..30.UINT16°CWrite
HR2998doc 2999All units fan speedUINT16Write0 = Low; 1 = Medium; 2 = High; 3 = Powerful
HR2999doc 3000All units remote controller lockUINT16Write0 = Remote controller locked; 1 = Remote controller unlocked

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway

What Modbus registers does the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway have?

This map lists 20 registers: 20 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables say 'base addr is 1': printed register 1 is wire address 0. Indoor unit with Superlink address n (0..127) uses printed n x 20 + 1 .. n x 20 + 14, so wire n x 20 + 0..13. This file lists unit address 0 (printed 1..14, wire 0..13) and the all-unit block (printed 2995..3000).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway?

Start with HR 0 IU communication status (Unit communication status); HR 1 IU on/off (On/off); HR 2 IU operation mode (Mode); HR 3 IU setpoint temperature (Setpoint (°C)); HR 4 IU fan speed (Fan speed); HR 7 IU room temperature (Room temperature (°C)); HR 9 IU error code (Error code); HR 2994 Hardware communication status (Gateway hardware communication status).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway?

Each indoor unit must be enabled in the LinkBoxMB Devices list and the configuration file sent to the gateway.

What happens when the Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway loses Modbus communication?

A per-unit communication-error signal is raised when a unit stops answering within the 'Timeout response' set in LinkBoxMB (2000..10000 ms).

Where is the official Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway Modbus documentation?

The source is Intesis Modbus Server - Mitsubishi Heavy Industries AC User's Manual (User's Manual r1.0 eng), revision 2012-05, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsmhixxxo000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Intesis Modbus Server - Mitsubishi Heavy Industries AC User's Manual · User's Manual r1.0 eng · rev. 2012-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.