Heat pump (via ISG Modbus TCP gateway) · Modbus register map
Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i) Modbus register map
Updated 17 November 2026
Stiebel Eltron heat pumps are not polled directly: the Internet Service Gateway (ISG) with the paid Modbus TCP/IP extension acts as a Modbus TCP server for the WPM heat pump manager behind it. All data points are single 16-bit registers with a fixed scaling per data type. This map covers the WPM system values (input registers 501-608), the writable operating mode and setpoints (holding 1501-1521), status flags and output states (2501-2547), heat and energy counters per system and per heat pump (3501-3655), and the shared SG Ready registers (4001-4003, 5001-5002).
This page lists 335 Modbus registers for the Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i) — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Stiebel Eltron’s own free documentation (linked below) and checked against it.
- Manufacturer
- Stiebel Eltron
- Model
- Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)
- Equipment type
- Heat pump (via ISG Modbus TCP gateway)
- Registers
- 335 (24 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- ISG web Modbus TCP/IP, ISG plus Modbus TCP/IP, WPMsystem, WPM 3, WPM 3i
Integration notes: Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)
Connect a Modbus TCP master to the ISG on port 502, unit ID 1, and read input registers with FC 04 and holding registers with FC 03/06/16. Remember the 1-based numbering: wire address = printed number - 1. Read outside temperature (507), flow/return (515/516), DHW actual/set (522/523), status flags (2501) and fault status (2504); write the operating mode (1501) and comfort/ECO setpoints (1502-1511).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 506 | Outside temperature | INT16 | Outside temperature (check offset) | Read |
| IR 514 | Actual flow temperature | INT16 | Actual flow temperature | Read |
| IR 521 | Actual DHW temperature | INT16 | Actual DHW temperature | Read |
| IR 2500 | Operating status | BITMAP16 | Operating status flags | Read |
| IR 2503 | Fault status | UINT16 | Fault status | Read |
| HR 1500 | Operating mode | UINT16 | Operating mode | Read/write |
| HR 1501 | Comfort temperature HC 1 | INT16 | Comfort temperature HC 1 | Read/write |
| HR 1509 | Comfort temperature DHW | INT16 | Comfort DHW setpoint | Read/write |
| IR 3502 | VD HEATING TOTAL MWh heat all HPs | UINT16 | Total compressor heating heat, MWh part | Read |
Enable Modbus control & writes
The ISG web or ISG plus needs the Modbus TCP/IP software extension and, for the ISG web, the Basic service package. With a WPM connected, check for the extension in SERVICEWELT under DIAGNOSIS > SYSTEM > ISG; if Modbus TCP/IP is not listed, update the ISG firmware or contact Stiebel Eltron service.
Byte order & addressing
- All values are single 16-bit registers; there are no 32-bit values in this map. Totals are spread over a kWh and an MWh register.
- Faults can only be acknowledged in SERVICEWELT, not over Modbus.
- The Modbus interface cannot be combined with other ISG software interfaces, except read-only use alongside the EMI energy management extension.
- Change either the operating mode or the setpoints of a mode over Modbus and leave the other fixed, so new setpoints take effect immediately.
Network setup
- Default ISG address 192.168.0.126 when connected straight to a PC; behind a router it takes a DHCP address. Set the IP under the Profile tab in SERVICEWELT.
- Unit ID is fixed at 1; TCP port 502.
- Test with outside temperature against the controller display to confirm the 1-register offset.
Watch out for
- An ISG must not share a CAN bus with a DCo-aktiv GSM module; communication to the WPM can fail.
- 1520 = 1 is a full factory reset of the system; all settings are lost.
Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 500doc 501 | Actual temperature FE7 | Room temperature measured by an FE7 remote control. | INT16 | × 0.1 | °C | Read | ||
| IR | 501doc 502 | Set temperature FE7 | Room setpoint at the FE7 remote control. | INT16 | × 0.1 | °C | Read | ||
| IR | 502doc 503 | Actual temperature FEK | Room temperature measured by an FEK remote control. Listed for WPM 3 and WPM 3i. | INT16 | × 0.1 | °C | Read | ||
| IR | 503doc 504 | Set temperature FEK | Room setpoint at the FEK remote control. Listed for WPM 3 and WPM 3i. | INT16 | × 0.1 | °C | Read | ||
| IR | 504doc 505 | Relative humidity | Room humidity from the FEK remote control. Listed for WPM 3 and WPM 3i. | INT16 | × 0.1 | % | Read | ||
| IR | 505doc 506 | Dew point temperature | Room dew point from the FEK remote control. Listed for WPM 3 and WPM 3i. | INT16 | × 0.1 | °C | Read | ||
| IR | 506doc 507 | Outside temperature | Outdoor air temperature sensor. | INT16 | × 0.1 | °C | Read | ||
| IR | 507doc 508 | Actual temperature HK 1 | Heating circuit 1 actual temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 508doc 509 | Set temperature HK 1 (WPM 3i) | Heating circuit 1 setpoint as reported by a WPM 3i. Listed for WPM 3i. | INT16 | × 0.1 | °C | Read | ||
| IR | 509doc 510 | Set temperature HK 1 | Heating circuit 1 setpoint. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 510doc 511 | Actual temperature HK 2 | Heating circuit 2 actual temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 511doc 512 | Set temperature HK 2 | Heating circuit 2 setpoint. | INT16 | × 0.1 | °C | Read | ||
| IR | 512doc 513 | Actual flow temperature WP | Heat pump flow temperature, if a flow sensor (MFG) is fitted. | INT16 | × 0.1 | °C | Read | ||
| IR | 513doc 514 | Actual flow temperature NHZ | Flow temperature after the booster heater, if an MFG is fitted. | INT16 | × 0.1 | °C | Read | ||
| IR | 514doc 515 | Actual flow temperature | System flow temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 515doc 516 | Actual return temperature | System return temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 516doc 517 | Set fixed temperature | Setpoint used in fixed-value operation. | INT16 | × 0.1 | °C | Read | ||
| IR | 517doc 518 | Actual buffer temperature | Buffer cylinder temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 518doc 519 | Set buffer temperature | Buffer cylinder setpoint. | INT16 | × 0.1 | °C | Read | ||
| IR | 519doc 520 | Heating pressure | Heating water pressure, if a flow sensor (MFG) is fitted. | INT16 | × 0.01 | bar | Read | ||
| IR | 520doc 521 | Flow rate | Heating water flow rate, if an MFG is fitted. | INT16 | × 0.1 | l/min | Read | ||
| IR | 521doc 522 | Actual DHW temperature | Domestic hot water cylinder temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 522doc 523 | Set DHW temperature | Domestic hot water setpoint. | INT16 | × 0.1 | °C | Read | ||
| IR | 523doc 524 | Actual temperature fan cooling | Fan-convector cooling actual value (unit printed as K). | INT16 | × 0.1 | K | Read | ||
| IR | 524doc 525 | Set temperature fan cooling | Fan-convector cooling setpoint (unit printed as K). | INT16 | × 0.1 | K | Read | ||
| IR | 525doc 526 | Actual temperature area cooling | Surface cooling actual value (unit printed as K). | INT16 | × 0.1 | K | Read | ||
| IR | 526doc 527 | Set temperature area cooling | Surface cooling setpoint (unit printed as K). | INT16 | × 0.1 | K | Read | ||
| IR | 527doc 528 | Collector temperature | Solar thermal collector temperature. Listed for WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 528doc 529 | Cylinder temperature (solar) | Solar cylinder temperature. Listed for WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 529doc 530 | Runtime solar | Solar thermal operating hours. Listed for WPM 3. | UINT16 | h | Read | |||
| IR | 530doc 531 | Actual temperature external heat source | External (second) heat source actual temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 531doc 532 | Set temperature external heat source | External heat source setpoint (unit printed as K). Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | K | Read | ||
| IR | 532doc 533 | Application limit HZG | Lower application limit for heating. | INT16 | × 0.1 | °C | Read | ||
| IR | 533doc 534 | Application limit WW | Lower application limit for DHW. | INT16 | × 0.1 | °C | Read | ||
| IR | 534doc 535 | Runtime external heat source | External heat source operating hours. Listed for WPMsystem and WPM 3. | UINT16 | h | Read | |||
| IR | 535doc 536 | Source temperature | Heat source (brine/air) temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 536doc 537 | Min source temperature | Minimum permitted source temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 537doc 538 | Source pressure | Heat source circuit pressure. | INT16 | × 0.01 | bar | Read | ||
| IR | 538doc 539 | Hot gas temperature | Compressor discharge temperature. Listed for WPM 3i. | INT16 | × 0.1 | °C | Read | ||
| IR | 539doc 540 | High pressure | Refrigerant high pressure. Listed for WPM 3i. | INT16 | × 0.1 | bar | Read | ||
| IR | 540doc 541 | Low pressure | Refrigerant low pressure. Listed for WPM 3i. | INT16 | × 0.1 | bar | Read | ||
| IR | 541doc 542 | Return temperature HP 1 | Heat pump 1 return temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 542doc 543 | Flow temperature HP 1 | Heat pump 1 flow temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 543doc 544 | Hot gas temperature HP 1 | Heat pump 1 compressor discharge temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 544doc 545 | Low pressure HP 1 | Heat pump 1 refrigerant low pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 545doc 546 | Mean pressure HP 1 | Heat pump 1 refrigerant mean pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 546doc 547 | High pressure HP 1 | Heat pump 1 refrigerant high pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 547doc 548 | WP water flow rate HP 1 | Heat pump 1 water flow rate. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | l/min | Read | ||
| IR | 548doc 549 | Return temperature HP 2 | Heat pump 2 return temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 549doc 550 | Flow temperature HP 2 | Heat pump 2 flow temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 550doc 551 | Hot gas temperature HP 2 | Heat pump 2 compressor discharge temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 551doc 552 | Low pressure HP 2 | Heat pump 2 refrigerant low pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 552doc 553 | Mean pressure HP 2 | Heat pump 2 refrigerant mean pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 553doc 554 | High pressure HP 2 | Heat pump 2 refrigerant high pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 554doc 555 | WP water flow rate HP 2 | Heat pump 2 water flow rate. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | l/min | Read | ||
| IR | 555doc 556 | Return temperature HP 3 | Heat pump 3 return temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 556doc 557 | Flow temperature HP 3 | Heat pump 3 flow temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 557doc 558 | Hot gas temperature HP 3 | Heat pump 3 compressor discharge temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 558doc 559 | Low pressure HP 3 | Heat pump 3 refrigerant low pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 559doc 560 | Mean pressure HP 3 | Heat pump 3 refrigerant mean pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 560doc 561 | High pressure HP 3 | Heat pump 3 refrigerant high pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 561doc 562 | WP water flow rate HP 3 | Heat pump 3 water flow rate. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | l/min | Read | ||
| IR | 562doc 563 | Return temperature HP 4 | Heat pump 4 return temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 563doc 564 | Flow temperature HP 4 | Heat pump 4 flow temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 564doc 565 | Hot gas temperature HP 4 | Heat pump 4 compressor discharge temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 565doc 566 | Low pressure HP 4 | Heat pump 4 refrigerant low pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 566doc 567 | Mean pressure HP 4 | Heat pump 4 refrigerant mean pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 567doc 568 | High pressure HP 4 | Heat pump 4 refrigerant high pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 568doc 569 | WP water flow rate HP 4 | Heat pump 4 water flow rate. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | l/min | Read | ||
| IR | 569doc 570 | Return temperature HP 5 | Heat pump 5 return temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 570doc 571 | Flow temperature HP 5 | Heat pump 5 flow temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 571doc 572 | Hot gas temperature HP 5 | Heat pump 5 compressor discharge temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 572doc 573 | Low pressure HP 5 | Heat pump 5 refrigerant low pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 573doc 574 | Mean pressure HP 5 | Heat pump 5 refrigerant mean pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 574doc 575 | High pressure HP 5 | Heat pump 5 refrigerant high pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 575doc 576 | WP water flow rate HP 5 | Heat pump 5 water flow rate. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | l/min | Read | ||
| IR | 576doc 577 | Return temperature HP 6 | Heat pump 6 return temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 577doc 578 | Flow temperature HP 6 | Heat pump 6 flow temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 578doc 579 | Hot gas temperature HP 6 | Heat pump 6 compressor discharge temperature. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | °C | Read | ||
| IR | 579doc 580 | Low pressure HP 6 | Heat pump 6 refrigerant low pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 580doc 581 | Mean pressure HP 6 | Heat pump 6 refrigerant mean pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 581doc 582 | High pressure HP 6 | Heat pump 6 refrigerant high pressure. Listed for WPMsystem and WPM 3. | INT16 | × 0.01 | bar | Read | ||
| IR | 582doc 583 | WP water flow rate HP 6 | Heat pump 6 water flow rate. Listed for WPMsystem and WPM 3. | INT16 | × 0.1 | l/min | Read | ||
| IR | 583doc 584 | Room actual temperature HC 1 | Room temperature for heating circuit 1. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 584doc 585 | Room set temperature HC 1 | Room setpoint for heating circuit 1. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 585doc 586 | Relative humidity HC 1 | Room humidity for heating circuit 1. Listed for WPMsystem. | INT16 | × 0.1 | % | Read | ||
| IR | 586doc 587 | Dew point temperature HC 1 | Room dew point for heating circuit 1. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 587doc 588 | Room actual temperature HC 2 | Room temperature for heating circuit 2. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 588doc 589 | Room set temperature HC 2 | Room setpoint for heating circuit 2. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 589doc 590 | Relative humidity HC 2 | Room humidity for heating circuit 2. Listed for WPMsystem. | INT16 | × 0.1 | % | Read | ||
| IR | 590doc 591 | Dew point temperature HC 2 | Room dew point for heating circuit 2. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 591doc 592 | Room actual temperature HC 3 | Room temperature for heating circuit 3. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 592doc 593 | Room set temperature HC 3 | Room setpoint for heating circuit 3. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 593doc 594 | Relative humidity HC 3 | Room humidity for heating circuit 3. Listed for WPMsystem. | INT16 | × 0.1 | % | Read | ||
| IR | 594doc 595 | Dew point temperature HC 3 | Room dew point for heating circuit 3. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 595doc 596 | Room actual temperature HC 4 | Room temperature for heating circuit 4. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 596doc 597 | Room set temperature HC 4 | Room setpoint for heating circuit 4. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 597doc 598 | Relative humidity HC 4 | Room humidity for heating circuit 4. Listed for WPMsystem. | INT16 | × 0.1 | % | Read | ||
| IR | 598doc 599 | Dew point temperature HC 4 | Room dew point for heating circuit 4. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 599doc 600 | Room actual temperature HC 5 | Room temperature for heating circuit 5. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 600doc 601 | Room set temperature HC 5 | Room setpoint for heating circuit 5. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 601doc 602 | Relative humidity HC 5 | Room humidity for heating circuit 5. Listed for WPMsystem. | INT16 | × 0.1 | % | Read | ||
| IR | 602doc 603 | Dew point temperature HC 5 | Room dew point for heating circuit 5. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 603doc 604 | Room set temperature cooling circuit 1 | Room cooling setpoint for cooling circuit 1. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 604doc 605 | Room set temperature cooling circuit 2 | Room cooling setpoint for cooling circuit 2. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 605doc 606 | Room set temperature cooling circuit 3 | Room cooling setpoint for cooling circuit 3. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 606doc 607 | Room set temperature cooling circuit 4 | Room cooling setpoint for cooling circuit 4. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 607doc 608 | Room set temperature cooling circuit 5 | Room cooling setpoint for cooling circuit 5. Listed for WPMsystem. | INT16 | × 0.1 | °C | Read | ||
| IR | 2500doc 2501 | Operating status | Packed system status flags. | BITMAP16 | Read | bit 0 = HC 1 pump; bit 1 = HC 2 pump; bit 2 = Heat-up program; bit 3 = NHZ stages running; bit 4 = HP in heating mode; bit 5 = HP in DHW mode; bit 6 = Compressor running; bit 7 = Summer mode active; bit 8 = Cooling mode active; bit 9 = At least one IWS in defrost mode; bit 10 = Silent mode 1 active; bit 11 = Silent mode 2 active (HP off) | |||
| IR | 2501doc 2502 | Power-off (utility release) | Utility (EVU) release flag; German original EVU-FREIGABE. | BITMAP16 | Read | bit 0 = Power-off (EVU release) | |||
| IR | 2502doc 2503 | Operating status compressors | Packed compressor, buffer pump and booster heater flags. | BITMAP16 | Read | bit 0 = Compressor 1; bit 1 = Compressor 2; bit 2 = Compressor 3; bit 3 = Compressor 4; bit 4 = Compressor 5; bit 5 = Compressor 6; bit 6 = Buffer charging pump 1; bit 7 = Buffer charging pump 2; bit 8 = Buffer charging pump 3; bit 9 = Buffer charging pump 4; bit 10 = Buffer charging pump 5; bit 11 = Buffer charging pump 6; bit 12 = NHZ 1; bit 13 = NHZ 2 | |||
| IR | 2503doc 2504 | Fault status | 1 = system fault present; acknowledge only via SERVICEWELT. | UINT16 | Read | 0 = No fault; 1 = Fault | |||
| IR | 2505doc 2506 | Defrost initiated | 1 = defrost has been started. | UINT16 | Read | 0 = Off; 1 = Initiated | |||
| IR | 2506doc 2507 | Active error | Number of the active fault. | UINT16 | Read | ||||
| IR | 2507doc 2508 | Message number | Number of the active message. | UINT16 | Read | ||||
| IR | 2508doc 2509 | Heating circuit pump 1 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2509doc 2510 | Heating circuit pump 2 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2510doc 2511 | Heating circuit pump 3 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2511doc 2512 | Buffer charging pump 1 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2512doc 2513 | Buffer charging pump 2 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2513doc 2514 | DHW charging pump status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2514doc 2515 | Source pump status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2515doc 2516 | Fault output status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2516doc 2517 | DHW circulation pump status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2517doc 2518 | WE 2 DHW status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2518doc 2519 | WE 2 heating status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2519doc 2520 | Cooling mode status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2520doc 2521 | Mixer open HC 2 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2521doc 2522 | Mixer close HC 2 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2522doc 2523 | Mixer open HC 3 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2523doc 2524 | Mixer close HC 3 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2524doc 2525 | NHZ 1 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2525doc 2526 | NHZ 2 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2526doc 2527 | NHZ 1/2 status | Output state reported by the WPM: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2527doc 2528 | Heating circuit pump 4 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2528doc 2529 | Heating circuit pump 5 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2529doc 2530 | Buffer charging pump 3 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2530doc 2531 | Buffer charging pump 4 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2531doc 2532 | Buffer charging pump 5 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2532doc 2533 | Buffer charging pump 6 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2533doc 2534 | Diff. controller pump 1 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2534doc 2535 | Diff. controller pump 2 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2535doc 2536 | Pool pump primary status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2536doc 2537 | Pool pump secondary status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2537doc 2538 | Mixer open HC 4 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2538doc 2539 | Mixer close HC 4 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2539doc 2540 | Mixer open HC 5 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2540doc 2541 | Mixer close HC 5 status | Output state reported by the WPE extension: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2541doc 2542 | Compressor 1 status | Output state reported by the heat pump: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2542doc 2543 | Compressor 2 status | Output state reported by the heat pump: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2543doc 2544 | Compressor 3 status | Output state reported by the heat pump: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2544doc 2545 | Compressor 4 status | Output state reported by the heat pump: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2545doc 2546 | Compressor 5 status | Output state reported by the heat pump: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 2546doc 2547 | Compressor 6 status | Output state reported by the heat pump: 0 = off, 1 = on. | UINT16 | Read | ||||
| IR | 3500doc 3501 | VD HEATING DAY kWh heat all HPs | Today heat output for heating by compressor, all heat pumps. | UINT16 | kWh | Read | |||
| IR | 3501doc 3502 | VD HEATING TOTAL kWh heat all HPs | Total heat output for heating by compressor, all heat pumps, kWh part. | UINT16 | kWh | Read | |||
| IR | 3502doc 3503 | VD HEATING TOTAL MWh heat all HPs | Total heat output for heating by compressor, all heat pumps, MWh part. | UINT16 | MWh | Read | |||
| IR | 3503doc 3504 | VD DHW DAY kWh heat all HPs | Today heat output for DHW by compressor, all heat pumps. | UINT16 | kWh | Read | |||
| IR | 3504doc 3505 | VD DHW TOTAL kWh heat all HPs | Total heat output for DHW by compressor, all heat pumps, kWh part. | UINT16 | kWh | Read | |||
| IR | 3505doc 3506 | VD DHW TOTAL MWh heat all HPs | Total heat output for DHW by compressor, all heat pumps, MWh part. | UINT16 | MWh | Read | |||
| IR | 3506doc 3507 | NHZ HEATING TOTAL kWh heat all HPs | Total heat output for heating by booster heater, all heat pumps, kWh part. | UINT16 | kWh | Read | |||
| IR | 3507doc 3508 | NHZ HEATING TOTAL MWh heat all HPs | Total heat output for heating by booster heater, all heat pumps, MWh part. | UINT16 | MWh | Read | |||
| IR | 3508doc 3509 | NHZ DHW TOTAL kWh heat all HPs | Total heat output for DHW by booster heater, all heat pumps, kWh part. | UINT16 | kWh | Read | |||
| IR | 3509doc 3510 | NHZ DHW TOTAL MWh heat all HPs | Total heat output for DHW by booster heater, all heat pumps, MWh part. | UINT16 | MWh | Read | |||
| IR | 3510doc 3511 | VD HEATING DAY kWh power consumption all HPs | Today electricity used for heating by compressor, all heat pumps. | UINT16 | kWh | Read | |||
| IR | 3511doc 3512 | VD HEATING TOTAL kWh power consumption all HPs | Total electricity used for heating by compressor, all heat pumps, kWh part. | UINT16 | kWh | Read | |||
| IR | 3512doc 3513 | VD HEATING TOTAL MWh power consumption all HPs | Total electricity used for heating by compressor, all heat pumps, MWh part. | UINT16 | MWh | Read | |||
| IR | 3513doc 3514 | VD DHW DAY kWh power consumption all HPs | Today electricity used for DHW by compressor, all heat pumps. | UINT16 | kWh | Read | |||
| IR | 3514doc 3515 | VD DHW TOTAL kWh power consumption all HPs | Total electricity used for DHW by compressor, all heat pumps, kWh part. | UINT16 | kWh | Read | |||
| IR | 3515doc 3516 | VD DHW TOTAL MWh power consumption all HPs | Total electricity used for DHW by compressor, all heat pumps, MWh part. | UINT16 | MWh | Read | |||
| IR | 3516doc 3517 | Runtime VD HEATING | Operating hours, compressor heating. | UINT16 | h | Read | |||
| IR | 3517doc 3518 | Runtime VD DHW | Operating hours, compressor DHW. | UINT16 | h | Read | |||
| IR | 3518doc 3519 | Runtime VD COOLING | Operating hours, compressor cooling. | UINT16 | h | Read | |||
| IR | 3519doc 3520 | Runtime NHZ 1 | Operating hours, booster heater 1. | UINT16 | h | Read | |||
| IR | 3520doc 3521 | Runtime NHZ 2 | Operating hours, booster heater 2. | UINT16 | h | Read | |||
| IR | 3521doc 3522 | Runtime NHZ 1/2 | Operating hours, booster heater 1/2. | UINT16 | h | Read | |||
| IR | 3522doc 3523 | VD HEATING DAY kWh heat HP 1 | Today heat output for heating by compressor, heat pump 1. | UINT16 | kWh | Read | |||
| IR | 3523doc 3524 | VD HEATING TOTAL kWh heat HP 1 | Total heat output for heating by compressor, heat pump 1, kWh part. | UINT16 | kWh | Read | |||
| IR | 3524doc 3525 | VD HEATING TOTAL MWh heat HP 1 | Total heat output for heating by compressor, heat pump 1, MWh part. | UINT16 | MWh | Read | |||
| IR | 3525doc 3526 | VD DHW DAY kWh heat HP 1 | Today heat output for DHW by compressor, heat pump 1. | UINT16 | kWh | Read | |||
| IR | 3526doc 3527 | VD DHW TOTAL kWh heat HP 1 | Total heat output for DHW by compressor, heat pump 1, kWh part. | UINT16 | kWh | Read | |||
| IR | 3527doc 3528 | VD DHW TOTAL MWh heat HP 1 | Total heat output for DHW by compressor, heat pump 1, MWh part. | UINT16 | MWh | Read | |||
| IR | 3528doc 3529 | NHZ HEATING TOTAL kWh heat HP 1 | Total heat output for heating by booster heater, heat pump 1, kWh part. | UINT16 | kWh | Read | |||
| IR | 3529doc 3530 | NHZ HEATING TOTAL MWh heat HP 1 | Total heat output for heating by booster heater, heat pump 1, MWh part. | UINT16 | MWh | Read | |||
| IR | 3530doc 3531 | NHZ DHW TOTAL kWh heat HP 1 | Total heat output for DHW by booster heater, heat pump 1, kWh part. | UINT16 | kWh | Read | |||
| IR | 3531doc 3532 | NHZ DHW TOTAL MWh heat HP 1 | Total heat output for DHW by booster heater, heat pump 1, MWh part. | UINT16 | MWh | Read | |||
| IR | 3532doc 3533 | VD HEATING DAY kWh power consumption HP 1 | Today electricity used for heating by compressor, heat pump 1. | UINT16 | kWh | Read | |||
| IR | 3533doc 3534 | VD HEATING TOTAL kWh power consumption HP 1 | Total electricity used for heating by compressor, heat pump 1, kWh part. | UINT16 | kWh | Read | |||
| IR | 3534doc 3535 | VD HEATING TOTAL MWh power consumption HP 1 | Total electricity used for heating by compressor, heat pump 1, MWh part. | UINT16 | MWh | Read | |||
| IR | 3535doc 3536 | VD DHW DAY kWh power consumption HP 1 | Today electricity used for DHW by compressor, heat pump 1. | UINT16 | kWh | Read | |||
| IR | 3536doc 3537 | VD DHW TOTAL kWh power consumption HP 1 | Total electricity used for DHW by compressor, heat pump 1, kWh part. | UINT16 | kWh | Read | |||
| IR | 3537doc 3538 | VD DHW TOTAL MWh power consumption HP 1 | Total electricity used for DHW by compressor, heat pump 1, MWh part. | UINT16 | MWh | Read | |||
| IR | 3538doc 3539 | Runtime VD 1 HEATING HP 1 | Operating hours, compressor 1 heating, heat pump 1. | UINT16 | h | Read | |||
| IR | 3539doc 3540 | Runtime VD 2 HEATING HP 1 | Operating hours, compressor 2 heating, heat pump 1. | UINT16 | h | Read | |||
| IR | 3540doc 3541 | Runtime VD 1/2 HEATING HP 1 | Operating hours, compressor 1/2 heating, heat pump 1. | UINT16 | h | Read | |||
| IR | 3541doc 3542 | Runtime VD 1 DHW HP 1 | Operating hours, compressor 1 DHW, heat pump 1. | UINT16 | h | Read | |||
| IR | 3542doc 3543 | Runtime VD 2 DHW HP 1 | Operating hours, compressor 2 DHW, heat pump 1. | UINT16 | h | Read | |||
| IR | 3543doc 3544 | Runtime VD 1/2 DHW HP 1 | Operating hours, compressor 1/2 DHW, heat pump 1. | UINT16 | h | Read | |||
| IR | 3544doc 3545 | Runtime VD COOLING HP 1 | Operating hours, compressor cooling, heat pump 1. | UINT16 | h | Read | |||
| IR | 3545doc 3546 | Runtime NHZ 1 (booster heater) | Operating hours of booster heater stage 1. | UINT16 | h | Read | |||
| IR | 3546doc 3547 | Runtime NHZ 2 (booster heater) | Operating hours of booster heater stage 2. | UINT16 | h | Read | |||
| IR | 3547doc 3548 | Runtime NHZ 1/2 (booster heater) | Operating hours of booster heater stage 1/2. | UINT16 | h | Read | |||
| IR | 3548doc 3549 | VD HEATING DAY kWh heat HP 2 | Today heat output for heating by compressor, heat pump 2. | UINT16 | kWh | Read | |||
| IR | 3549doc 3550 | VD HEATING TOTAL kWh heat HP 2 | Total heat output for heating by compressor, heat pump 2, kWh part. | UINT16 | kWh | Read | |||
| IR | 3550doc 3551 | VD HEATING TOTAL MWh heat HP 2 | Total heat output for heating by compressor, heat pump 2, MWh part. | UINT16 | MWh | Read | |||
| IR | 3551doc 3552 | VD DHW DAY kWh heat HP 2 | Today heat output for DHW by compressor, heat pump 2. | UINT16 | kWh | Read | |||
| IR | 3552doc 3553 | VD DHW TOTAL kWh heat HP 2 | Total heat output for DHW by compressor, heat pump 2, kWh part. | UINT16 | kWh | Read | |||
| IR | 3553doc 3554 | VD DHW TOTAL MWh heat HP 2 | Total heat output for DHW by compressor, heat pump 2, MWh part. | UINT16 | MWh | Read | |||
| IR | 3554doc 3555 | VD HEATING DAY kWh power consumption HP 2 | Today electricity used for heating by compressor, heat pump 2. | UINT16 | kWh | Read | |||
| IR | 3555doc 3556 | VD HEATING TOTAL kWh power consumption HP 2 | Total electricity used for heating by compressor, heat pump 2, kWh part. | UINT16 | kWh | Read | |||
| IR | 3556doc 3557 | VD HEATING TOTAL MWh power consumption HP 2 | Total electricity used for heating by compressor, heat pump 2, MWh part. | UINT16 | MWh | Read | |||
| IR | 3557doc 3558 | VD DHW DAY kWh power consumption HP 2 | Today electricity used for DHW by compressor, heat pump 2. | UINT16 | kWh | Read | |||
| IR | 3558doc 3559 | VD DHW TOTAL kWh power consumption HP 2 | Total electricity used for DHW by compressor, heat pump 2, kWh part. | UINT16 | kWh | Read | |||
| IR | 3559doc 3560 | VD DHW TOTAL MWh power consumption HP 2 | Total electricity used for DHW by compressor, heat pump 2, MWh part. | UINT16 | MWh | Read | |||
| IR | 3560doc 3561 | Runtime VD 1 HEATING HP 2 | Operating hours, compressor 1 heating, heat pump 2. | UINT16 | h | Read | |||
| IR | 3561doc 3562 | Runtime VD 2 HEATING HP 2 | Operating hours, compressor 2 heating, heat pump 2. | UINT16 | h | Read | |||
| IR | 3562doc 3563 | Runtime VD 1/2 HEATING HP 2 | Operating hours, compressor 1/2 heating, heat pump 2. | UINT16 | h | Read | |||
| IR | 3563doc 3564 | Runtime VD 1 DHW HP 2 | Operating hours, compressor 1 DHW, heat pump 2. | UINT16 | h | Read | |||
| IR | 3564doc 3565 | Runtime VD 2 DHW HP 2 | Operating hours, compressor 2 DHW, heat pump 2. | UINT16 | h | Read | |||
| IR | 3565doc 3566 | Runtime VD 1/2 DHW HP 2 | Operating hours, compressor 1/2 DHW, heat pump 2. | UINT16 | h | Read | |||
| IR | 3566doc 3567 | Runtime VD COOLING HP 2 | Operating hours, compressor cooling, heat pump 2. | UINT16 | h | Read | |||
| IR | 3567doc 3568 | VD HEATING DAY kWh heat HP 3 | Today heat output for heating by compressor, heat pump 3. | UINT16 | kWh | Read | |||
| IR | 3568doc 3569 | VD HEATING TOTAL kWh heat HP 3 | Total heat output for heating by compressor, heat pump 3, kWh part. | UINT16 | kWh | Read | |||
| IR | 3569doc 3570 | VD HEATING TOTAL MWh heat HP 3 | Total heat output for heating by compressor, heat pump 3, MWh part. | UINT16 | MWh | Read | |||
| IR | 3570doc 3571 | VD DHW DAY kWh heat HP 3 | Today heat output for DHW by compressor, heat pump 3. | UINT16 | kWh | Read | |||
| IR | 3571doc 3572 | VD DHW TOTAL kWh heat HP 3 | Total heat output for DHW by compressor, heat pump 3, kWh part. | UINT16 | kWh | Read | |||
| IR | 3572doc 3573 | VD DHW TOTAL MWh heat HP 3 | Total heat output for DHW by compressor, heat pump 3, MWh part. | UINT16 | MWh | Read | |||
| IR | 3573doc 3574 | VD HEATING DAY kWh power consumption HP 3 | Today electricity used for heating by compressor, heat pump 3. | UINT16 | kWh | Read | |||
| IR | 3574doc 3575 | VD HEATING TOTAL kWh power consumption HP 3 | Total electricity used for heating by compressor, heat pump 3, kWh part. | UINT16 | kWh | Read | |||
| IR | 3575doc 3576 | VD HEATING TOTAL MWh power consumption HP 3 | Total electricity used for heating by compressor, heat pump 3, MWh part. | UINT16 | MWh | Read | |||
| IR | 3576doc 3577 | VD DHW DAY kWh power consumption HP 3 | Today electricity used for DHW by compressor, heat pump 3. | UINT16 | kWh | Read | |||
| IR | 3577doc 3578 | VD DHW TOTAL kWh power consumption HP 3 | Total electricity used for DHW by compressor, heat pump 3, kWh part. | UINT16 | kWh | Read | |||
| IR | 3578doc 3579 | VD DHW TOTAL MWh power consumption HP 3 | Total electricity used for DHW by compressor, heat pump 3, MWh part. | UINT16 | MWh | Read | |||
| IR | 3579doc 3580 | Runtime VD 1 HEATING HP 3 | Operating hours, compressor 1 heating, heat pump 3. | UINT16 | h | Read | |||
| IR | 3580doc 3581 | Runtime VD 2 HEATING HP 3 | Operating hours, compressor 2 heating, heat pump 3. | UINT16 | h | Read | |||
| IR | 3581doc 3582 | Runtime VD 1/2 HEATING HP 3 | Operating hours, compressor 1/2 heating, heat pump 3. | UINT16 | h | Read | |||
| IR | 3582doc 3583 | Runtime VD 1 DHW HP 3 | Operating hours, compressor 1 DHW, heat pump 3. | UINT16 | h | Read | |||
| IR | 3583doc 3584 | Runtime VD 2 DHW HP 3 | Operating hours, compressor 2 DHW, heat pump 3. | UINT16 | h | Read | |||
| IR | 3584doc 3585 | Runtime VD 1/2 DHW HP 3 | Operating hours, compressor 1/2 DHW, heat pump 3. | UINT16 | h | Read | |||
| IR | 3585doc 3586 | Runtime VD COOLING HP 3 | Operating hours, compressor cooling, heat pump 3. | UINT16 | h | Read | |||
| IR | 3586doc 3587 | VD HEATING DAY kWh heat HP 4 | Today heat output for heating by compressor, heat pump 4. | UINT16 | kWh | Read | |||
| IR | 3587doc 3588 | VD HEATING TOTAL kWh heat HP 4 | Total heat output for heating by compressor, heat pump 4, kWh part. | UINT16 | kWh | Read | |||
| IR | 3588doc 3589 | VD HEATING TOTAL MWh heat HP 4 | Total heat output for heating by compressor, heat pump 4, MWh part. | UINT16 | MWh | Read | |||
| IR | 3589doc 3590 | VD DHW DAY kWh heat HP 4 | Today heat output for DHW by compressor, heat pump 4. | UINT16 | kWh | Read | |||
| IR | 3590doc 3591 | VD DHW TOTAL kWh heat HP 4 | Total heat output for DHW by compressor, heat pump 4, kWh part. | UINT16 | kWh | Read | |||
| IR | 3591doc 3592 | VD DHW TOTAL MWh heat HP 4 | Total heat output for DHW by compressor, heat pump 4, MWh part. | UINT16 | MWh | Read | |||
| IR | 3592doc 3593 | VD HEATING DAY kWh power consumption HP 4 | Today electricity used for heating by compressor, heat pump 4. | UINT16 | kWh | Read | |||
| IR | 3593doc 3594 | VD HEATING TOTAL kWh power consumption HP 4 | Total electricity used for heating by compressor, heat pump 4, kWh part. | UINT16 | kWh | Read | |||
| IR | 3594doc 3595 | VD HEATING TOTAL MWh power consumption HP 4 | Total electricity used for heating by compressor, heat pump 4, MWh part. | UINT16 | MWh | Read | |||
| IR | 3595doc 3596 | VD DHW DAY kWh power consumption HP 4 | Today electricity used for DHW by compressor, heat pump 4. | UINT16 | kWh | Read | |||
| IR | 3596doc 3597 | VD DHW TOTAL kWh power consumption HP 4 | Total electricity used for DHW by compressor, heat pump 4, kWh part. | UINT16 | kWh | Read | |||
| IR | 3597doc 3598 | VD DHW TOTAL MWh power consumption HP 4 | Total electricity used for DHW by compressor, heat pump 4, MWh part. | UINT16 | MWh | Read | |||
| IR | 3598doc 3599 | Runtime VD 1 HEATING HP 4 | Operating hours, compressor 1 heating, heat pump 4. | UINT16 | h | Read | |||
| IR | 3599doc 3600 | Runtime VD 2 HEATING HP 4 | Operating hours, compressor 2 heating, heat pump 4. | UINT16 | h | Read | |||
| IR | 3600doc 3601 | Runtime VD 1/2 HEATING HP 4 | Operating hours, compressor 1/2 heating, heat pump 4. | UINT16 | h | Read | |||
| IR | 3601doc 3602 | Runtime VD 1 DHW HP 4 | Operating hours, compressor 1 DHW, heat pump 4. | UINT16 | h | Read | |||
| IR | 3602doc 3603 | Runtime VD 2 DHW HP 4 | Operating hours, compressor 2 DHW, heat pump 4. | UINT16 | h | Read | |||
| IR | 3603doc 3604 | Runtime VD 1/2 DHW HP 4 | Operating hours, compressor 1/2 DHW, heat pump 4. | UINT16 | h | Read | |||
| IR | 3604doc 3605 | Runtime VD COOLING HP 4 | Operating hours, compressor cooling, heat pump 4. | UINT16 | h | Read | |||
| IR | 3605doc 3606 | VD HEATING DAY kWh heat HP 5 | Today heat output for heating by compressor, heat pump 5. | UINT16 | kWh | Read | |||
| IR | 3606doc 3607 | VD HEATING TOTAL kWh heat HP 5 | Total heat output for heating by compressor, heat pump 5, kWh part. | UINT16 | kWh | Read | |||
| IR | 3607doc 3608 | VD HEATING TOTAL MWh heat HP 5 | Total heat output for heating by compressor, heat pump 5, MWh part. | UINT16 | MWh | Read | |||
| IR | 3608doc 3609 | VD DHW DAY kWh heat HP 5 | Today heat output for DHW by compressor, heat pump 5. | UINT16 | kWh | Read | |||
| IR | 3609doc 3610 | VD DHW TOTAL kWh heat HP 5 | Total heat output for DHW by compressor, heat pump 5, kWh part. | UINT16 | kWh | Read | |||
| IR | 3610doc 3611 | VD DHW TOTAL MWh heat HP 5 | Total heat output for DHW by compressor, heat pump 5, MWh part. | UINT16 | MWh | Read | |||
| IR | 3611doc 3612 | VD HEATING DAY kWh power consumption HP 5 | Today electricity used for heating by compressor, heat pump 5. | UINT16 | kWh | Read | |||
| IR | 3612doc 3613 | VD HEATING TOTAL kWh power consumption HP 5 | Total electricity used for heating by compressor, heat pump 5, kWh part. | UINT16 | kWh | Read | |||
| IR | 3613doc 3614 | VD HEATING TOTAL MWh power consumption HP 5 | Total electricity used for heating by compressor, heat pump 5, MWh part. | UINT16 | MWh | Read | |||
| IR | 3614doc 3615 | VD DHW DAY kWh power consumption HP 5 | Today electricity used for DHW by compressor, heat pump 5. | UINT16 | kWh | Read | |||
| IR | 3615doc 3616 | VD DHW TOTAL kWh power consumption HP 5 | Total electricity used for DHW by compressor, heat pump 5, kWh part. | UINT16 | kWh | Read | |||
| IR | 3616doc 3617 | VD DHW TOTAL MWh power consumption HP 5 | Total electricity used for DHW by compressor, heat pump 5, MWh part. | UINT16 | MWh | Read | |||
| IR | 3617doc 3618 | Runtime VD 1 HEATING HP 5 | Operating hours, compressor 1 heating, heat pump 5. | UINT16 | h | Read | |||
| IR | 3618doc 3619 | Runtime VD 2 HEATING HP 5 | Operating hours, compressor 2 heating, heat pump 5. | UINT16 | h | Read | |||
| IR | 3619doc 3620 | Runtime VD 1/2 HEATING HP 5 | Operating hours, compressor 1/2 heating, heat pump 5. | UINT16 | h | Read | |||
| IR | 3620doc 3621 | Runtime VD 1 DHW HP 5 | Operating hours, compressor 1 DHW, heat pump 5. | UINT16 | h | Read | |||
| IR | 3621doc 3622 | Runtime VD 2 DHW HP 5 | Operating hours, compressor 2 DHW, heat pump 5. | UINT16 | h | Read | |||
| IR | 3622doc 3623 | Runtime VD 1/2 DHW HP 5 | Operating hours, compressor 1/2 DHW, heat pump 5. | UINT16 | h | Read | |||
| IR | 3623doc 3624 | Runtime VD COOLING HP 5 | Operating hours, compressor cooling, heat pump 5. | UINT16 | h | Read | |||
| IR | 3624doc 3625 | VD HEATING DAY kWh heat HP 6 | Today heat output for heating by compressor, heat pump 6. | UINT16 | kWh | Read | |||
| IR | 3625doc 3626 | VD HEATING TOTAL kWh heat HP 6 | Total heat output for heating by compressor, heat pump 6, kWh part. | UINT16 | kWh | Read | |||
| IR | 3626doc 3627 | VD HEATING TOTAL MWh heat HP 6 | Total heat output for heating by compressor, heat pump 6, MWh part. | UINT16 | MWh | Read | |||
| IR | 3627doc 3628 | VD DHW DAY kWh heat HP 6 | Today heat output for DHW by compressor, heat pump 6. | UINT16 | kWh | Read | |||
| IR | 3628doc 3629 | VD DHW TOTAL kWh heat HP 6 | Total heat output for DHW by compressor, heat pump 6, kWh part. | UINT16 | kWh | Read | |||
| IR | 3629doc 3630 | VD DHW TOTAL MWh heat HP 6 | Total heat output for DHW by compressor, heat pump 6, MWh part. | UINT16 | MWh | Read | |||
| IR | 3630doc 3631 | VD HEATING DAY kWh power consumption HP 6 | Today electricity used for heating by compressor, heat pump 6. | UINT16 | kWh | Read | |||
| IR | 3631doc 3632 | VD HEATING TOTAL kWh power consumption HP 6 | Total electricity used for heating by compressor, heat pump 6, kWh part. | UINT16 | kWh | Read | |||
| IR | 3632doc 3633 | VD HEATING TOTAL MWh power consumption HP 6 | Total electricity used for heating by compressor, heat pump 6, MWh part. | UINT16 | MWh | Read | |||
| IR | 3633doc 3634 | VD DHW DAY kWh power consumption HP 6 | Today electricity used for DHW by compressor, heat pump 6. | UINT16 | kWh | Read | |||
| IR | 3634doc 3635 | VD DHW TOTAL kWh power consumption HP 6 | Total electricity used for DHW by compressor, heat pump 6, kWh part. | UINT16 | kWh | Read | |||
| IR | 3635doc 3636 | VD DHW TOTAL MWh power consumption HP 6 | Total electricity used for DHW by compressor, heat pump 6, MWh part. | UINT16 | MWh | Read | |||
| IR | 3636doc 3637 | Runtime VD 1 HEATING HP 6 | Operating hours, compressor 1 heating, heat pump 6. | UINT16 | h | Read | |||
| IR | 3637doc 3638 | Runtime VD 2 HEATING HP 6 | Operating hours, compressor 2 heating, heat pump 6. | UINT16 | h | Read | |||
| IR | 3638doc 3639 | Runtime VD 1/2 HEATING HP 6 | Operating hours, compressor 1/2 heating, heat pump 6. | UINT16 | h | Read | |||
| IR | 3639doc 3640 | Runtime VD 1 DHW HP 6 | Operating hours, compressor 1 DHW, heat pump 6. | UINT16 | h | Read | |||
| IR | 3640doc 3641 | Runtime VD 2 DHW HP 6 | Operating hours, compressor 2 DHW, heat pump 6. | UINT16 | h | Read | |||
| IR | 3641doc 3642 | Runtime VD 1/2 DHW HP 6 | Operating hours, compressor 1/2 DHW, heat pump 6. | UINT16 | h | Read | |||
| IR | 3642doc 3643 | Runtime VD COOLING HP 6 | Operating hours, compressor cooling, heat pump 6. | UINT16 | h | Read | |||
| IR | 3643doc 3644 | Runtime VD HEATING HP 1 | Operating hours, compressor heating, heat pump 1. | UINT16 | h | Read | |||
| IR | 3644doc 3645 | Runtime VD DHW HP 1 | Operating hours, compressor DHW, heat pump 1. | UINT16 | h | Read | |||
| IR | 3645doc 3646 | Runtime VD HEATING HP 2 | Operating hours, compressor heating, heat pump 2. | UINT16 | h | Read | |||
| IR | 3646doc 3647 | Runtime VD DHW HP 2 | Operating hours, compressor DHW, heat pump 2. | UINT16 | h | Read | |||
| IR | 3647doc 3648 | Runtime VD HEATING HP 3 | Operating hours, compressor heating, heat pump 3. | UINT16 | h | Read | |||
| IR | 3648doc 3649 | Runtime VD DHW HP 3 | Operating hours, compressor DHW, heat pump 3. | UINT16 | h | Read | |||
| IR | 3649doc 3650 | Runtime VD HEATING HP 4 | Operating hours, compressor heating, heat pump 4. | UINT16 | h | Read | |||
| IR | 3650doc 3651 | Runtime VD DHW HP 4 | Operating hours, compressor DHW, heat pump 4. | UINT16 | h | Read | |||
| IR | 3651doc 3652 | Runtime VD HEATING HP 5 | Operating hours, compressor heating, heat pump 5. | UINT16 | h | Read | |||
| IR | 3652doc 3653 | Runtime VD DHW HP 5 | Operating hours, compressor DHW, heat pump 5. | UINT16 | h | Read | |||
| IR | 3653doc 3654 | Runtime VD HEATING HP 6 | Operating hours, compressor heating, heat pump 6. | UINT16 | h | Read | |||
| IR | 3654doc 3655 | Runtime VD DHW HP 6 | Operating hours, compressor DHW, heat pump 6. | UINT16 | h | Read | |||
| IR | 5000doc 5001 | SG Ready operating state | Resulting SG Ready state 1-4. | UINT16 | Read | 1 = State 1: heating must not start, frost protection only; 2 = State 2: normal automatic/programmed operation; 3 = State 3: accelerated mode with raised heating/DHW setpoints; 4 = State 4: immediate switch to maximum heating/DHW setpoints | |||
| IR | 5001doc 5002 | Controller identification | Type code of the connected controller. | UINT16 | Read | 103 = LWZ 303/403 Integral/SOL, LWA 403, LWZ 304/404 Trend/FLEX, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus/Trend/Smart, LWZ 8 S Trend; 104 = LWZ 304/404 SOL, LWZ 504, LWZ 5/8 CS Premium, VCR-I 8 CS Premium CN; 390 = WPM 3; 391 = WPM 3i; 449 = WPMsystem | |||
| HR | 1500doc 1501 | Operating mode | Selects the controller operating mode. | UINT16 | Read/write | 0 = Emergency operation; 1 = Standby mode; 2 = Programmed operation; 3 = Comfort mode; 4 = ECO mode; 5 = DHW mode | |||
| HR | 1501doc 1502 | Comfort temperature HC 1 | Comfort room setpoint, heating circuit 1. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1502doc 1503 | ECO temperature HC 1 | ECO (setback) room setpoint, heating circuit 1. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1503doc 1504 | Heating curve rise HC 1 | Heating curve slope, heating circuit 1. | INT16 | × 0.01 | Read/write | |||
| HR | 1504doc 1505 | Comfort temperature HC 2 | Comfort room setpoint, heating circuit 2. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1505doc 1506 | ECO temperature HC 2 | ECO room setpoint, heating circuit 2. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1506doc 1507 | Heating curve rise HC 2 | Heating curve slope, heating circuit 2. | INT16 | × 0.01 | Read/write | |||
| HR | 1507doc 1508 | Fixed value operation | Fixed flow setpoint 20-70 °C; 0x9000 switches the function off. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1508doc 1509 | Dual mode temp HZG | Bivalence point for heating; observe application limits. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1509doc 1510 | Comfort temperature DHW | Comfort hot water setpoint. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1510doc 1511 | ECO temperature DHW | ECO hot water setpoint. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1511doc 1512 | DHW stages | Heat pump stages used for DHW; respect the number fitted. | UINT16 | Read/write | ||||
| HR | 1512doc 1513 | Dual mode temp WW | Bivalence point for DHW. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1513doc 1514 | Set flow temperature area cooling | Flow setpoint for surface cooling. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1514doc 1515 | Flow temp hysteresis area cooling | Flow temperature hysteresis for surface cooling. | INT16 | × 0.1 | K | Read/write | ||
| HR | 1515doc 1516 | Set room temperature area cooling | Room setpoint for surface cooling. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1516doc 1517 | Set flow temperature fan cooling | Flow setpoint for fan-convector cooling. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1517doc 1518 | Flow temp hysteresis fan cooling | Flow temperature hysteresis for fan cooling. | INT16 | × 0.1 | K | Read/write | ||
| HR | 1518doc 1519 | Set room temperature fan cooling | Room setpoint for fan cooling. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1519doc 1520 | Reset | Resets the fault list, a heat pump, or the whole system. | UINT16 | Read/write | 1 = System reset (factory reset, all settings lost); 2 = Fault list reset; 3 = Heat pump reset | |||
| HR | 1520doc 1521 | Restart ISG | Restarts the ISG or emulates the service key. | UINT16 | Read/write | 0 = Off; 1 = Restart; 2 = Service key | |||
| HR | 4000doc 4001 | Switch SG Ready on and off | Enables or disables SG Ready. Language tables disagree on which code means on; check on site. | UINT16 | Read/write | ||||
| HR | 4001doc 4002 | SG Ready input 1 | Virtual SG Ready contact written by the BMS. | UINT16 | Read/write | 0 = Switched off; 1 = Switched on | |||
| HR | 4002doc 4003 | SG Ready input 2 | Virtual SG Ready contact written by the BMS. | UINT16 | Read/write | 0 = Switched off; 1 = Switched on |
Notes on this map
- Stiebel Eltron does not host this software documentation publicly (its own download path for it returns 404). The linked copy is a retailer mirror: the multilingual Stiebel Eltron document unchanged, with one shop cover page added in front, so PDF page numbers are one higher than the printed page numbers.
- Data types from the document: type 2 = signed, value x 0.1 (temperatures, most pressures and flows); type 6 = unsigned 0-65535, x 1; type 7 = signed, value x 0.01; type 8 = unsigned 0-255, x 1. Write by sending the engineering value divided by the same factor (20.3 °C -> 203).
- Unavailable objects return 32768 (0x8000). Not every object exists on every controller; the WPMsystem / WPM 3 / WPM 3i columns are noted in descriptions where a register is not listed for all three.
- Energy counters are split into a kWh register (0-999) and an MWh register: total = MWh x 1000 + kWh. Day counters are single kWh registers.
- Registers 524-527 and 532 (cooling and external heat source temperatures) are printed with the unit K in both the German and English tables; they are kept as published.
- Left out: BUS-STATUS (2505) because it is typed as unsigned 0-65535 while its codes are negative (-1 to -4).
- SG Ready on/off (4001): the language tables of the same document disagree on the coding (German and Italian: 0 = off, 1 = on; English: 0 = on, 1 = off). No value labels are given here; test on site which code switches the function on.
- Holding register 1508 (fixed value operation) accepts 20-70 °C; writing 0x9000 turns the function off. The document says this works on WPMsystem, WPM 3 from software 39005 and WPM 3i from software 39106; older software can only activate and adjust it.
- Integral ventilation units (LWZ/LWA) use a different register set and are mapped separately (stiebel-eltron/isg-modbus-lwz-ventilation-units).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)
What Modbus registers does the Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i) have?
This map lists 335 registers: 311 input registers, 24 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document states that ISG addressing is 1-based and gives the example that register 30501 is reached as address 501 with function code 04, so the wire address is the printed number minus one: outside temperature, printed 507, is requested at input register address 506. The document also warns that, depending on the configuration, an offset of 1 may have to be allowed for, so check outside temperature against the controller display first.
What are the minimum Modbus registers to integrate the Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)?
Start with IR 506 Outside temperature (Outside temperature (check offset)); IR 514 Actual flow temperature (Actual flow temperature); IR 521 Actual DHW temperature (Actual DHW temperature); IR 2500 Operating status (Operating status flags); IR 2503 Fault status (Fault status); HR 1500 Operating mode (Operating mode); HR 1501 Comfort temperature HC 1 (Comfort temperature HC 1); HR 1509 Comfort temperature DHW (Comfort DHW setpoint); IR 3502 VD HEATING TOTAL MWh heat all HPs (Total compressor heating heat, MWh part).
How do I enable Modbus control of the Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)?
The ISG web or ISG plus needs the Modbus TCP/IP software extension and, for the ISG web, the Basic service package. With a WPM connected, check for the extension in SERVICEWELT under DIAGNOSIS > SYSTEM > ISG; if Modbus TCP/IP is not listed, update the ISG firmware or contact Stiebel Eltron service.
Where is the official Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i) Modbus documentation?
The source is Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP (A 321798-44755-9770). Stiebel Eltron doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.heizungsdiscount24.de/pdf/Stiebel-Eltron-Internet-Service-Gateway-ISG-Connect-Software-Dokumentation.pdf. It may be an older revision, so check it against the live unit.
More Stiebel Eltron Modbus register maps
Other ac & vrf gateways register maps
- VRF / split AC gateway
Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
Airzone Aidoo Pro units configured for Modbus output and connected to a direct-expansion AC unit; register table 'Registers for Direct Expansion units' of the Aidoo - Modbus integration manual (v. 201). The air-to-water table in the same manual is not covered.
Also known as: Aidoo Pro, Aidoo Pro Modbus, Airzone Aidoo Modbus - VRF / split AC gateway
Fujitsu General UTY-VMSX Modbus converter (one indoor unit)
Fujitsu General UTY-VMSX Modbus RTU converter, one per indoor unit, per interface specification part no. 9708438047-05.
Also known as: UTY-VMSX - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32
All ac & vrf gateways Modbus register maps →
Source: Software documentation - Software extension for Internet Service Gateway - Modbus TCP/IP · A 321798-44755-9770 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.