- UTY-VMSX Modbus converter (one indoor unit)
VRF / split AC gateway · Modbus register map
Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus register map
Updated 17 November 2026
The UTY-VMSX connects a single Fujitsu indoor unit to an RS-485 Modbus RTU network as a slave. Input registers report mode, on/off, setpoint, room temperature, fan, louvres, errors and lockouts; holding registers send commands, where 0 always means 'no change'. All values are single 16-bit registers.
This page lists 43 Modbus registers for the Fujitsu General UTY-VMSX Modbus converter (one indoor unit) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fujitsu General’s own free documentation (linked below) and checked against it.
- Manufacturer
- Fujitsu General
- Model
- UTY-VMSX Modbus converter (one indoor unit)
- Equipment type
- VRF / split AC gateway
- Registers
- 43 (16 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- UTY-VMSX
Integration notes: Fujitsu General UTY-VMSX Modbus converter (one indoor unit)
Poll input registers 53-58 (30054-30059) with FC04 for mode, on/off, setpoint, fan, room temperature and error. Control with FC06 to holding registers 1-4 (40002-40005); 0 in any command register means no change.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 53 | Operation mode status | UINT16 | Operation mode | Read |
| IR 54 | On/Off status | UINT16 | On/off status | Read |
| IR 55 | Set temperature | UINT16 | Setpoint | Read |
| IR 57 | Indoor (room) temperature | UINT16 | Room temperature | Read |
| IR 58 | Indoor unit error | BITMAP16 | Indoor unit error | Read |
| HR 2 | On/Off command | UINT16 | On/off command | Read/write |
| HR 3 | Set temperature command | UINT16 | Setpoint command | Read/write |
Enable Modbus control & writes
No enable step is described; the converter answers as soon as its address and speed are set.
Byte order & addressing
- Address rule: frame address = (register mod 10000) - 1.
- Setpoint writes need bit 0 set: (°C x 4) x 2 + 1.
- Most status values start at 1 (filter sign and the human-detection flags start at 0); command registers add 0 = no change.
Network setup
- One UTY-VMSX per indoor unit; up to 31 converters per BMS line without a repeater, 247 with.
- 3-wire RS-485, max 1000 m.
Watch out for
- An FC04 read of a function the indoor unit does not have returns 0, not an exception.
Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Converter baud rate | UINT16 | Read | 0 = 9600 bps; 1 = 19200 bps | ||||
| IR | 1doc 30002 | Converter slave address | Bits 0-7: address 1-247. | UINT16 | Read | ||||
| IR | 2doc 30003 | Converter model name info | Encoded model name characters (bits 0-7 and 8-15). | UINT16 | Read | ||||
| IR | 6doc 30007 | Converter software version | Four 4-bit fields of the version string. | UINT16 | Read | ||||
| IR | 8doc 30009 | Converter error | Bits 8-11 error sub-code, bits 12-15 error code section. | BITMAP16 | Read | bit 0 = Error (1 = error) | |||
| IR | 53doc 30054 | Operation mode status | UINT16 | Read | 1 = Auto; 2 = Cool; 3 = Dry; 4 = Heat; 5 = Fan | ||||
| IR | 54doc 30055 | On/Off status | UINT16 | Read | 1 = Stop; 2 = Operation | ||||
| IR | 55doc 30056 | Set temperature | Bits 0-8 hold the setpoint x4 (0.25 °C steps). | UINT16 | × 0.25 | °C | Read | ||
| IR | 56doc 30057 | Fan speed status | UINT16 | Read | 1 = Auto; 2 = Quiet; 3 = Low; 4 = Med; 5 = High; 6 = Med-Low; 7 = Med-High | ||||
| IR | 57doc 30058 | Indoor (room) temperature | Bits 0-8 hold the temperature x4 (0.25 °C steps). | UINT16 | × 0.25 | °C | Read | ||
| IR | 58doc 30059 | Indoor unit error | Bits 8-11 error sub-code, bits 12-15 error code section. | BITMAP16 | Read | bit 0 = Error (1 = error) | |||
| IR | 59doc 30060 | Vertical louvre position | UINT16 | Read | 1 = Swing; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4 | ||||
| IR | 60doc 30061 | Horizontal louvre position | UINT16 | Read | 1 = Swing; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5 | ||||
| IR | 61doc 30062 | Remote controller prohibition status | 1 = that remote function is locked out. | BITMAP16 | Read | bit 0 = All operations; bit 1 = Timer setting; bit 2 = Room temperature setting; bit 3 = Operation mode setting; bit 4 = Start/stop; bit 5 = Start only; bit 6 = Filter reset | |||
| IR | 62doc 30063 | Filter sign | UINT16 | Read | 0 = No sign; 1 = Filter sign | ||||
| IR | 63doc 30064 | Economy mode status | UINT16 | Read | 1 = Normal operation; 2 = Save operation | ||||
| IR | 64doc 30065 | Antifreeze status | UINT16 | Read | 1 = Normal operation; 2 = Antifreeze operation | ||||
| IR | 65doc 30066 | Setpoint limits status (Cool/Dry) | 0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C. | UINT16 | Read | ||||
| IR | 66doc 30067 | Setpoint limits status (Heat) | 0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C. | UINT16 | Read | ||||
| IR | 67doc 30068 | Setpoint limits status (Auto) | 0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C. | UINT16 | Read | ||||
| IR | 68doc 30069 | Indoor unit special status | BITMAP16 | Read | bit 0 = Normal status (0 = special status); bit 1 = Defrosting; bit 2 = Oil recovery; bit 3 = Pump down | ||||
| IR | 69doc 30070 | External thermo-off status | UINT16 | Read | 1 = Release; 2 = Thermo-off | ||||
| IR | 70doc 30071 | Demand status | UINT16 | Read | 1 = No operation; 2 = DRM 1; 3 = DRM 2; 4 = DRM 3 | ||||
| IR | 71doc 30072 | Human detection auto save | UINT16 | Read | 0 = No operation; 1 = Operation | ||||
| IR | 72doc 30073 | Human detection auto save time | Bits 0-10, set in 15-minute steps. | UINT16 | min | Read | |||
| IR | 73doc 30074 | Human detection auto off | UINT16 | Read | 0 = No operation; 1 = Operation | ||||
| IR | 74doc 30075 | Human detection auto off time | Bits 0-10, set in 60-minute steps. | UINT16 | min | Read | |||
| HR | 1doc 40002 | Operation mode command | UINT16 | Read/write | 0 = No change; 1 = Auto; 2 = Cool; 3 = Dry; 4 = Heat; 5 = Fan | ||||
| HR | 2doc 40003 | On/Off command | UINT16 | Read/write | 0 = No change; 1 = Stop; 2 = Operation | ||||
| HR | 3doc 40004 | Set temperature command | Write (°C x 4) x 2 + 1, e.g. 20 °C = 161; 0 = no change. | UINT16 | Read/write | ||||
| HR | 4doc 40005 | Fan speed command | UINT16 | Read/write | 0 = No change; 1 = Auto; 2 = Quiet; 3 = Low; 4 = Med; 5 = High; 6 = Med-Low; 7 = Med-High | ||||
| HR | 5doc 40006 | Vertical louvre command | UINT16 | Read/write | 0 = No change; 1 = Swing; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4 | ||||
| HR | 6doc 40007 | Horizontal louvre command | UINT16 | Read/write | 0 = No change; 1 = Swing; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5 | ||||
| HR | 7doc 40008 | Remote controller prohibition command | Bit 0 must be 1 for the other bits to apply. | BITMAP16 | Read/write | bit 0 = Apply change (1 = change); bit 1 = Inhibit all operations; bit 2 = Inhibit timer setting; bit 3 = Inhibit room temperature setting; bit 4 = Inhibit operation mode setting; bit 5 = Inhibit start/stop; bit 6 = Inhibit start only; bit 7 = Inhibit filter reset | |||
| HR | 8doc 40009 | Filter sign reset | UINT16 | Read/write | 0 = No change; 1 = Reset | ||||
| HR | 9doc 40010 | Economy mode command | UINT16 | Read/write | 0 = No change; 1 = Normal operation; 2 = Save operation | ||||
| HR | 10doc 40011 | Antifreeze command | UINT16 | Read/write | 0 = No change; 1 = Release; 2 = Antifreeze operation | ||||
| HR | 11doc 40012 | Upper setpoint limit (Cool/Dry) | Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | Lower setpoint limit (Cool/Dry) | Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit. | UINT16 | Read/write | ||||
| HR | 13doc 40014 | Upper setpoint limit (Heat) | Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit. | UINT16 | Read/write | ||||
| HR | 14doc 40015 | Lower setpoint limit (Heat) | Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit. | UINT16 | Read/write | ||||
| HR | 15doc 40016 | Upper setpoint limit (Auto) | Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit. | UINT16 | Read/write | ||||
| HR | 16doc 40017 | Lower setpoint limit (Auto) | Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit. | UINT16 | Read/write |
Notes on this map
- Function codes: 03 and 04 read, 06 and 16 write. If the indoor unit lacks a function or cannot report a value, an FC04 read returns 0.
- Serial settings per the spec: 9600 or 19200 bps, 8 data bits, parity even/odd/none, 2 stop bits with no parity or 1 with parity. No factory default address or speed is printed; they are set on the converter.
- Temperatures in input registers are x4 (0.25 °C steps). Temperature commands use bit 0 as a 'change' flag and bits 1-8 as the value x4, so 20 °C is written as 161; the spec prints a table for 18-30 °C.
- The setpoint limit registers 30066-30068 pack two values (upper in bits 0-7, lower in bits 8-15) so they are listed raw.
- Write all six limit registers 40012-40017 together with FC16 when switching between 'no limit' and 'limit', and keep each lower limit below its upper limit.
- Model name (30003) and software version (30007) are packed character codes; the spec does not give a character table, so they are listed raw.
- Not listed: holding registers 40018-40022 (external thermo-off and human-detection settings), whose rows are hard to align reliably in the printed table.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Fujitsu General UTY-VMSX Modbus converter (one indoor unit)
What Modbus registers does the Fujitsu General UTY-VMSX Modbus converter (one indoor unit) have?
This map lists 43 registers: 27 input registers, 16 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The specification states the rule: the frame address is the remainder of the register number divided by 10000, minus 1. Its example sends 35555 as 5554. So 30054 is input register 53 and 40002 is holding register 1.
What are the minimum Modbus registers to integrate the Fujitsu General UTY-VMSX Modbus converter (one indoor unit)?
Start with IR 53 Operation mode status (Operation mode); IR 54 On/Off status (On/off status); IR 55 Set temperature (Setpoint); IR 57 Indoor (room) temperature (Room temperature); IR 58 Indoor unit error (Indoor unit error); HR 2 On/Off command (On/off command); HR 3 Set temperature command (Setpoint command).
How do I enable Modbus control of the Fujitsu General UTY-VMSX Modbus converter (one indoor unit)?
No enable step is described; the converter answers as soon as its address and speed are set.
Where is the official Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus documentation?
The source is Interface specification - Modbus convertor UTY-VMSX (9708438047-05), published free by Fujitsu General at https://www.fujitsu-general.com/datafiles/W9708438047-0501_IF_En_UTY-VMSX.pdf.
Other ac & vrf gateways register maps
- VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA
All ac & vrf gateways Modbus register maps →
Source: Interface specification - Modbus convertor UTY-VMSX · 9708438047-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.