VRF / split AC gateway · Modbus register map

Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus register map

Updated 17 November 2026

Short answer

The UTY-VMSX connects a single Fujitsu indoor unit to an RS-485 Modbus RTU network as a slave. Input registers report mode, on/off, setpoint, room temperature, fan, louvres, errors and lockouts; holding registers send commands, where 0 always means 'no change'. All values are single 16-bit registers.

This page lists 43 Modbus registers for the Fujitsu General UTY-VMSX Modbus converter (one indoor unit) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fujitsu General’s own free documentation (linked below) and checked against it.

Manufacturer
Fujitsu General
Model
UTY-VMSX Modbus converter (one indoor unit)
Equipment type
VRF / split AC gateway
Registers
43 (16 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
UTY-VMSX
Source document
Interface specification - Modbus convertor UTY-VMSX · 9708438047-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Fujitsu General UTY-VMSX Modbus converter (one indoor unit)

Integration in brief

Poll input registers 53-58 (30054-30059) with FC04 for mode, on/off, setpoint, fan, room temperature and error. Control with FC06 to holding registers 1-4 (40002-40005); 0 in any command register means no change.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 53Operation mode statusUINT16Operation modeRead
IR 54On/Off statusUINT16On/off statusRead
IR 55Set temperatureUINT16SetpointRead
IR 57Indoor (room) temperatureUINT16Room temperatureRead
IR 58Indoor unit errorBITMAP16Indoor unit errorRead
HR 2On/Off commandUINT16On/off commandRead/write
HR 3Set temperature commandUINT16Setpoint commandRead/write

Enable Modbus control & writes

No enable step is described; the converter answers as soon as its address and speed are set.

Byte order & addressing

Network setup

Watch out for

Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

43 of 43 shown
Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Converter baud rateUINT16Read0 = 9600 bps; 1 = 19200 bps
IR1doc 30002Converter slave addressBits 0-7: address 1-247.UINT16Read
IR2doc 30003Converter model name infoEncoded model name characters (bits 0-7 and 8-15).UINT16Read
IR6doc 30007Converter software versionFour 4-bit fields of the version string.UINT16Read
IR8doc 30009Converter errorBits 8-11 error sub-code, bits 12-15 error code section.BITMAP16Readbit 0 = Error (1 = error)
IR53doc 30054Operation mode statusUINT16Read1 = Auto; 2 = Cool; 3 = Dry; 4 = Heat; 5 = Fan
IR54doc 30055On/Off statusUINT16Read1 = Stop; 2 = Operation
IR55doc 30056Set temperatureBits 0-8 hold the setpoint x4 (0.25 °C steps).UINT16× 0.25°CRead
IR56doc 30057Fan speed statusUINT16Read1 = Auto; 2 = Quiet; 3 = Low; 4 = Med; 5 = High; 6 = Med-Low; 7 = Med-High
IR57doc 30058Indoor (room) temperatureBits 0-8 hold the temperature x4 (0.25 °C steps).UINT16× 0.25°CRead
IR58doc 30059Indoor unit errorBits 8-11 error sub-code, bits 12-15 error code section.BITMAP16Readbit 0 = Error (1 = error)
IR59doc 30060Vertical louvre positionUINT16Read1 = Swing; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4
IR60doc 30061Horizontal louvre positionUINT16Read1 = Swing; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5
IR61doc 30062Remote controller prohibition status1 = that remote function is locked out.BITMAP16Readbit 0 = All operations; bit 1 = Timer setting; bit 2 = Room temperature setting; bit 3 = Operation mode setting; bit 4 = Start/stop; bit 5 = Start only; bit 6 = Filter reset
IR62doc 30063Filter signUINT16Read0 = No sign; 1 = Filter sign
IR63doc 30064Economy mode statusUINT16Read1 = Normal operation; 2 = Save operation
IR64doc 30065Antifreeze statusUINT16Read1 = Normal operation; 2 = Antifreeze operation
IR65doc 30066Setpoint limits status (Cool/Dry)0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C.UINT16Read
IR66doc 30067Setpoint limits status (Heat)0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C.UINT16Read
IR67doc 30068Setpoint limits status (Auto)0 = no limit; bits 0-7 upper and bits 8-15 lower limit, each x4 in °C.UINT16Read
IR68doc 30069Indoor unit special statusBITMAP16Readbit 0 = Normal status (0 = special status); bit 1 = Defrosting; bit 2 = Oil recovery; bit 3 = Pump down
IR69doc 30070External thermo-off statusUINT16Read1 = Release; 2 = Thermo-off
IR70doc 30071Demand statusUINT16Read1 = No operation; 2 = DRM 1; 3 = DRM 2; 4 = DRM 3
IR71doc 30072Human detection auto saveUINT16Read0 = No operation; 1 = Operation
IR72doc 30073Human detection auto save timeBits 0-10, set in 15-minute steps.UINT16minRead
IR73doc 30074Human detection auto offUINT16Read0 = No operation; 1 = Operation
IR74doc 30075Human detection auto off timeBits 0-10, set in 60-minute steps.UINT16minRead
HR1doc 40002Operation mode commandUINT16Read/write0 = No change; 1 = Auto; 2 = Cool; 3 = Dry; 4 = Heat; 5 = Fan
HR2doc 40003On/Off commandUINT16Read/write0 = No change; 1 = Stop; 2 = Operation
HR3doc 40004Set temperature commandWrite (°C x 4) x 2 + 1, e.g. 20 °C = 161; 0 = no change.UINT16Read/write
HR4doc 40005Fan speed commandUINT16Read/write0 = No change; 1 = Auto; 2 = Quiet; 3 = Low; 4 = Med; 5 = High; 6 = Med-Low; 7 = Med-High
HR5doc 40006Vertical louvre commandUINT16Read/write0 = No change; 1 = Swing; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4
HR6doc 40007Horizontal louvre commandUINT16Read/write0 = No change; 1 = Swing; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5
HR7doc 40008Remote controller prohibition commandBit 0 must be 1 for the other bits to apply.BITMAP16Read/writebit 0 = Apply change (1 = change); bit 1 = Inhibit all operations; bit 2 = Inhibit timer setting; bit 3 = Inhibit room temperature setting; bit 4 = Inhibit operation mode setting; bit 5 = Inhibit start/stop; bit 6 = Inhibit start only; bit 7 = Inhibit filter reset
HR8doc 40009Filter sign resetUINT16Read/write0 = No change; 1 = Reset
HR9doc 40010Economy mode commandUINT16Read/write0 = No change; 1 = Normal operation; 2 = Save operation
HR10doc 40011Antifreeze commandUINT16Read/write0 = No change; 1 = Release; 2 = Antifreeze operation
HR11doc 40012Upper setpoint limit (Cool/Dry)Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.UINT16Read/write
HR12doc 40013Lower setpoint limit (Cool/Dry)Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.UINT16Read/write
HR13doc 40014Upper setpoint limit (Heat)Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.UINT16Read/write
HR14doc 40015Lower setpoint limit (Heat)Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.UINT16Read/write
HR15doc 40016Upper setpoint limit (Auto)Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.UINT16Read/write
HR16doc 40017Lower setpoint limit (Auto)Coded like 40004: bit 0 change flag, bits 1-8 °C x4, 0 = no limit.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Fujitsu General UTY-VMSX Modbus converter (one indoor unit)

What Modbus registers does the Fujitsu General UTY-VMSX Modbus converter (one indoor unit) have?

This map lists 43 registers: 27 input registers, 16 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The specification states the rule: the frame address is the remainder of the register number divided by 10000, minus 1. Its example sends 35555 as 5554. So 30054 is input register 53 and 40002 is holding register 1.

What are the minimum Modbus registers to integrate the Fujitsu General UTY-VMSX Modbus converter (one indoor unit)?

Start with IR 53 Operation mode status (Operation mode); IR 54 On/Off status (On/off status); IR 55 Set temperature (Setpoint); IR 57 Indoor (room) temperature (Room temperature); IR 58 Indoor unit error (Indoor unit error); HR 2 On/Off command (On/off command); HR 3 Set temperature command (Setpoint command).

How do I enable Modbus control of the Fujitsu General UTY-VMSX Modbus converter (one indoor unit)?

No enable step is described; the converter answers as soon as its address and speed are set.

Where is the official Fujitsu General UTY-VMSX Modbus converter (one indoor unit) Modbus documentation?

The source is Interface specification - Modbus convertor UTY-VMSX (9708438047-05), published free by Fujitsu General at https://www.fujitsu-general.com/datafiles/W9708438047-0501_IF_En_UTY-VMSX.pdf.

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →