VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway Modbus register map

Updated 17 November 2026

Short answer

Modbus RTU server for Samsung commercial air conditioners, wired to the indoor unit's remote-controller bus. Holding registers cover on/off, mode, fan, both vanes, setpoint, external temperature input, window contact, alarm and error code, return-air temperature and gateway configuration.

This page lists 27 Modbus registers for the Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Equipment type
VRF / split AC gateway
Registers
27 (15 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSSAM001R000, Intesis Samsung Modbus
Source document
Intesis INMBSSAM001R000 Modbus RTU (EIA-485) Interface for Samsung air conditioners - User's Manual · User's Manual v1.5 EN · rev. 2024-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway

Integration in brief

Set address and baud on SW3/SW4, connect to the Samsung remote bus, then write 0-4 and poll 5, 10, 11 and 66.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit On/OffUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 4AC unit temperature setpointUINT16SetpointRead/write
HR 5AC unit temperature referenceUINT16Control temperatureRead
HR 10AC unit alarm statusUINT16Alarm flagRead
HR 11Error codeUINT16Error codeRead

Enable Modbus control & writes

No separate enable step; check register 7 (gateway disablement) reads the enabled state for your firmware.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

27 of 27 shown
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit On/OffUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speedAvailable speeds depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Low; 2 = Mid; 3 = High
HR3AC unit vane positionUINT16Read/write0 = Auto; 10 = Swing
HR4AC unit temperature setpoint18..30 °C (65..86 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR5AC unit temperature reference10..38 °C. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Gateway disablementValues as printed in this manual; see notes. Non-volatile.UINT16Read/write0 = Gateway disabled (printed as default); 1 = Gateway enabled
HR8AC remote control disablementNon-volatile.UINT16Read/write0 = Remote controller enabled; 1 = Remote controller disabled
HR9AC unit operation timeHours in On state, 0..65535. Non-volatile.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm; 1 = Alarm
HR11Error codeSamsung error code; see manual section 7.UINT16Read0 = No error; 65535 = Gateway or remote cannot talk to the indoor unit (-1)
HR13Open Window switch-off timeoutMinutes from window open to unit off, 0..30 (default 30).UINT16minRead/write
HR14Modbus RTU baud rateRate set on SW3/SW4 (2400..115200, default 9600).UINT16Read
HR15Modbus slave addressAddress set on SW3, 1..63.UINT16Read
HR21Max number of fan speedsUINT16Read
HR22External ambient temperature (from Modbus)Modbus-side room temperature; 0x8000 = none. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR23AC real temperature setpointSetpoint actually applied to the unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR26AC unit left/right vane positionUINT16Read/write0 = Auto; 10 = Swing
HR49Device IDReads 0x1200.UINT16Read
HR50Software versionUINT16Read
HR66Return path temperatureSW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR67Number of indoor units connectedUINT16Read
HR81Error addressIndoor unit that reports the error.UINT16Read
HR97Block periodic sendingsBlocked = only changed values are forwarded. Firmware 0.3+.UINT16Read/write0 = Non-blocked; 1 = Blocked
HR98Master/Slave (gateway)Role on the F3F4/V1V2 bus.UINT16Read/write0 = Slave; 1 = Master
HR99Reset / reboot deviceUINT16Write1 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway have?

This map lists 27 registers: 27 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' (base 0) and a 'PLC address' (base 1); the protocol address is the wire address and is used for 'documented'.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway?

Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Control temperature); HR 10 AC unit alarm status (Alarm flag); HR 11 Error code (Error code).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway?

No separate enable step; check register 7 (gateway disablement) reads the enabled state for your firmware.

Where is the official Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway Modbus documentation?

The source is Intesis INMBSSAM001R000 Modbus RTU (EIA-485) Interface for Samsung air conditioners - User's Manual (User's Manual v1.5 EN), revision 2024-01, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbssam001r000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Intesis INMBSSAM001R000 Modbus RTU (EIA-485) Interface for Samsung air conditioners - User's Manual · User's Manual v1.5 EN · rev. 2024-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.