Easy Modbus
  1. Home
  2. Modbus register maps
  3. Remeha
  4. GTW-08 Modbus gateway for Remeha / De Dietrich appliances

Boiler / heat pump gateway · Modbus register map

Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus register map

Updated 17 November 2026

Short answer

The GTW-08 is a small gateway that sits on the appliance's L-Bus and answers Modbus RTU for a BMS. Through it the BMS can read flow, return, flue and outside temperatures, water pressure, status codes and errors, set system power or temperature demands, run heating zones manually, configure cascades and define a fallback demand. This map covers the 16-bit registers of the English section.

This page lists 109 Modbus registers for the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Remeha’s own free documentation (linked below) and checked against it.

Manufacturer
Remeha
Model
GTW-08 Modbus gateway for Remeha / De Dietrich appliances
Equipment type
Boiler / heat pump gateway
Registers
109 (35 writable)
Transport
Modbus RTU
Default unit ID
100
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
GTW-08 Modbus, GTW08, De Dietrich GTW-08, BDR Thermea GTW-08
Source document
GTW-08 Modbus - Configuration manual (multilingual; English section) · 7854678 - v.01 · rev. 2023-09-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances

Integration in brief

Set the gateway's rotary address and DIP baud/parity, then read 400/401/409/411 for temperatures, pressure and status. To control, write 258 (algorithm type), 256 power and/or 257 temperature, and 259 heat demand type (7 heating, 8 cooling).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 400Flow temperature (AM016)INT16Flow temperatureRead
HR 401Return temperature (AM018)INT16Return temperatureRead
HR 409Primary circuit water pressure (AM019)UINT16Water pressureRead
HR 411Appliance main status (AM012)UINT16Main statusRead
HR 531Current error presentUINT16Any error presentRead
HR 258Algorithm typeUINT16Control mode (monitor / power / temperature)Read/write
HR 257System temperature requestUINT16Temperature requestRead/write
HR 259Heat demand typeUINT16Heat demand typeRead/write

Enable Modbus control & writes

Connect the GTW-08 to the appliance L-Bus. Rotary knob 0-F sets the Modbus address 100-115 (default 100). DIP switches 1-2 set the baud rate (9600 default, 19200, 38400, 57600) and switches 3-4 the parity (none default, odd, even).

Communication loss & watchdog

Registers 21020-21025 define a fallback heat demand (keep, adjust or cancel) used when communication between the gateway and the BMS is lost, with a period in minutes in 21022.

Byte order & addressing

Network setup

Watch out for

Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

109 of 109 shown
Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR128Devices connected8-bit value in the low byte.UINT16Read
HR129Board 1 device type0xZZYY: ZZ category, YY number in category.UINT16Read
HR135Board 2 device type0xZZYY: ZZ category, YY number in category.UINT16Read
HR141Board 3 device type0xZZYY: ZZ category, YY number in category.UINT16Read
HR147Board 4 device type0xZZYY: ZZ category, YY number in category.UINT16Read
HR153Board 5 device type0xZZYY: ZZ category, YY number in category.UINT16Read
HR159Board 6 device type0xZZYY: ZZ category, YY number in category.UINT16Read
HR165Board 7 device type0xZZYY: ZZ category, YY number in category.UINT16Read
HR171Board 8 device type0xZZYY: ZZ category, YY number in category.UINT16Read
HR189Zones detected8-bit value in the low byte.UINT16Read
HR256System power request8-bit value in the low byte. 0-100 % of system output.UINT16%Read/write
HR257System temperature requestFlow temperature request.UINT16× 0.01°CRead/write
HR258Algorithm type8-bit value in the low byte.UINT16Read/write0 = Remote management of temperature and power; 1 = Remote management of power; 2 = Remote management of temperature; 3 = Remote monitoring only
HR259Heat demand type8-bit value in the low byte.UINT16Read/write0 = Standby; 7 = Heating; 8 = Cooling
HR275Heat demand bitfield (zones)Per-zone heat demand flags.BITMAP16Readbit 0 = Direct zones allowed to run; bit 1 = Mixing circuits allowed to run; bit 2 = All valves open / pump running within safety; bit 3 = Manual heat demand active; bit 4 = Cooling allowed; bit 5 = DHW circuits allowed to run; bit 6 = Heat engine active
HR277Error list, all connected devicesUINT16Read
HR279Output status 1 (all devices)BITMAP16Readbit 0 = Flame on; bit 1 = Heat pump on; bit 2 = Electrical backup 1 on; bit 3 = Electrical backup 2 on; bit 4 = DHW electrical backup on; bit 5 = Service required; bit 6 = Power down / reset; bit 7 = Water pressure low
HR280Output status 2 (all devices)BITMAP16Readbit 0 = Pump; bit 1 = 3-way valve open; bit 2 = 3-way valve; bit 3 = 3-way valve closed; bit 4 = DHW active; bit 5 = CH active; bit 6 = Cooling active
HR384Outside temperatureINT16× 0.01°CRead
HR385Seasonal mode8-bit value in the low byte.UINT16Read0 = Winter; 1 = Frost protection; 2 = Summer neutral band; 3 = Summer
HR400Flow temperature (AM016)Appliance flow temperature.INT16× 0.01°CRead
HR401Return temperature (AM018)Water entering the appliance.INT16× 0.01°CRead
HR402Flue gas temperature (AM036)INT16× 0.01°CRead
HR403Heat pump flow temperature (HM001)INT16× 0.01°CRead
HR404Heat pump return temperature (HM002)INT16× 0.01°CRead
HR408DHW flow temperature setpoint (DM004)UINT16× 0.01°CRead
HR409Primary circuit water pressure (AM019)8-bit value in the low byte.UINT16× 0.1barRead
HR411Appliance main status (AM012)8-bit value in the low byte.UINT16Read0 = Standby; 1 = Heat demand; 2 = Generator start; 3 = Generator CH; 4 = Generator DHW; 5 = Generator stop; 6 = Pump post run; 7 = Cooling active; 8 = Controlled stop; 9 = Blocking mode; 10 = Locking mode; 11 = Load test min; 12 = Load test CH max; 13 = Load test DHW max; 15 = Manual heat demand; 16 = Frost protection; 17 = Deaeration; 18 = Control unit cooling; 19 = Reset in progress; 20 = Auto filling; 21 = Halted; 22 = Forced calibration; 23 = Factory test; 24 = Hydronic balancing; 200 = Device mode; 254 = Unknown
HR412Appliance sub status (AM014)Sub-status code; table 17 of the manual.UINT16Read
HR413Relative power (AM024)UINT16%Read
HR459Pump speed (AM010)UINT16× 0.1%Read/write
HR512Service required (AM011)8-bit value in the low byte.UINT16Read0 = No; 1 = Yes
HR513Service notification8-bit value in the low byte.UINT16Read0 = None; 1 = A; 2 = B; 3 = C; 4 = Custom; 5 = D
HR531Current error present8-bit value in the low byte.UINT16Read0 = No error; 1 = At least one error on any appliance
HR532Board 1 error code0xFFFF = no error, 0xFFFE = device not available.UINT16Read
HR533Board 1 error typeUINT16Read0 = Locking; 3 = Blocking; 6 = Warning
HR534Board 2 error code0xFFFF = no error, 0xFFFE = device not available.UINT16Read
HR535Board 2 error typeUINT16Read0 = Locking; 3 = Blocking; 6 = Warning
HR536Board 3 error code0xFFFF = no error, 0xFFFE = device not available.UINT16Read
HR537Board 3 error typeUINT16Read0 = Locking; 3 = Blocking; 6 = Warning
HR538Board 4 error code0xFFFF = no error, 0xFFFE = device not available.UINT16Read
HR539Board 4 error typeUINT16Read0 = Locking; 3 = Blocking; 6 = Warning
HR540Board 5 error code0xFFFF = no error, 0xFFFE = device not available.UINT16Read
HR541Board 5 error typeUINT16Read0 = Locking; 3 = Blocking; 6 = Warning
HR542Board 6 error code0xFFFF = no error, 0xFFFE = device not available.UINT16Read
HR543Board 6 error typeUINT16Read0 = Locking; 3 = Blocking; 6 = Warning
HR544Board 7 error code0xFFFF = no error, 0xFFFE = device not available.UINT16Read
HR545Board 7 error typeUINT16Read0 = Locking; 3 = Blocking; 6 = Warning
HR546Board 8 error code0xFFFF = no error, 0xFFFE = device not available.UINT16Read
HR547Board 8 error typeUINT16Read0 = Locking; 3 = Blocking; 6 = Warning
HR641Zone 1 function typeZone function code; next zones every 512 registers.UINT16Read
HR645Zone 1 device type0xZZYY: ZZ category, YY number (00 CU-GH, 01 CU-OH, 02 EHC, 19 SCB...).UINT16Read
HR648Zone 1 fixed flow temperature setpointUsed when the zone runs on a fixed flow setpoint.UINT16× 0.01°CRead/write
HR649Zone 1 operating mode8-bit value in the low byte.UINT16Read/write0 = Scheduling; 1 = Manual; 2 = Off
HR664Zone 1 manual room temperature setpointUINT16× 0.1°CRead/write
HR674Zone 1 heating curve gradient8-bit value in the low byte.UINT16× 0.1Read/write
HR675Zone 1 heating curve comfort footpointUINT16× 0.1°CRead/write
HR1100Zone 1 flow or DHW temperature (CM040)INT16× 0.01°CRead
HR1101Zone 1 flow temperature setpoint (CM070)UINT16× 0.01°CRead
HR1102Zone 1 room temperature setpoint (CM190)INT16× 0.1°CRead
HR1107Zone 1 current activity (CM130)8-bit value in the low byte.UINT16Read0 = Off; 1 = Eco; 2 = Comfort; 3 = Anti legionella
HR1108Zone 1 operating mode (CM120)8-bit value in the low byte.UINT16Read0 = Scheduling; 1 = Manual; 2 = Off; 3 = Temporary
HR1110Zone 1 pump status (CM050)8-bit value in the low byte.UINT16Read0 = No; 1 = Yes
HR7000Node number of the device8-bit value in the low byte.UINT16Read/write
HR7001Cascade mode (NP014)8-bit value in the low byte.UINT16Read/write0 = Automatic; 1 = Heating; 2 = Cooling
HR7002Cascade type (NP006)8-bit value in the low byte.UINT16Read/write0 = Traditional; 1 = Parallel
HR7009Cascade management type (NP011)8-bit value in the low byte.UINT16Read/write0 = Temperature; 1 = Power
HR7011Start order permutation (NP223)8-bit value in the low byte.UINT16Read/write0 = Fixed time; 1 = Operating hours
HR7012Producer switch interval (NP281)UINT16hRead/write
HR7014Power control strategy (NP225)8-bit value in the low byte.UINT16Read/write0 = Late on, early off; 1 = Early on, late off; 2 = Late on, late off
HR7015Preferred producer for CH (NP227)8-bit value in the low byte.UINT16Read/write
HR7016Non-preferred producer for CH (NP228)8-bit value in the low byte.UINT16Read/write
HR7017Late-on value (NP282)8-bit value in the low byte.UINT16%Read/write
HR7018Late-off value (NP283)8-bit value in the low byte.UINT16%Read/write
HR7019Early-on value (NP284)8-bit value in the low byte.UINT16%Read/write
HR7020Early-off value (NP285)8-bit value in the low byte.UINT16%Read/write
HR7023Primary pump type (NP287)8-bit value in the low byte.UINT16Read/write0 = No pump; 1 = On/off; 2 = PWM; 3 = 0-10 V
HR7024Secondary pump type (NP288)8-bit value in the low byte.UINT16Read/write0 = No pump; 1 = On/off; 2 = PWM; 3 = 0-10 V
HR7101Cascade flow temperature (NM001)INT16× 0.01°CRead
HR7102Producers recognised in cascade (NM028)8-bit value in the low byte.UINT16Read
HR7103Cascade stages available (NM022)8-bit value in the low byte.UINT16Read
HR7104Cascade stages required (NM023)8-bit value in the low byte.UINT16Read
HR7105Cascade power request: power8-bit value in the low byte.UINT16%Read
HR7106Cascade power request: temperatureINT16× 0.01°CRead
HR7107Cascade power request: heat demand8-bit value in the low byte.UINT16Read0 = Automatic; 1 = Heating; 2 = Cooling; 3 = Process heat; 4 = Screed drying; 5 = DHW medium priority; 6 = DHW low priority; 7 = Heating; 8 = Cooling; 9 = Electrical active; 10 = Electrical reactive
HR7108Cascade calculated setpoint: power8-bit value in the low byte.UINT16%Read
HR7109Cascade calculated setpoint: temperatureINT16× 0.01°CRead
HR7110Cascade calculated setpoint: heat demand8-bit value in the low byte.UINT16Read0 = Automatic; 1 = Heating; 2 = Cooling; 3 = Process heat; 4 = Screed drying; 5 = DHW medium priority; 6 = DHW low priority; 7 = Heating; 8 = Cooling; 9 = Electrical active; 10 = Electrical reactive
HR7155Requested cascade power percentage (NM170)INT16× 0.1%Read
HR7157Cascade primary pump status (NM166)8-bit value in the low byte.UINT16Read0 = Inactive; 1 = Active
HR7158Cascade secondary pump status (NM167)8-bit value in the low byte.UINT16Read0 = Inactive; 1 = Active
HR7159Cascade state (NM163)8-bit value in the low byte.UINT16Read0 = Standby; 1 = Heat demand; 2 = Generator start; 3 = Generator CH; 4 = Generator DHW; 5 = Generator stop; 6 = Pump post run; 7 = Cooling active; 8 = Controlled stop; 9 = Blocking mode; 10 = Locking mode; 11 = Load test min; 12 = Load test CH max; 13 = Load test DHW max; 14 = Custom load test; 15 = Manual heat demand; 16 = Frost protection; 17 = Deaeration; 18 = Control unit cooling; 19 = Reset in progress; 20 = Auto filling; 21 = Halted; 22 = Forced calibration; 23 = Factory test; 24 = Hydronic balancing; 200 = Device mode; 254 = Unknown
HR7164Cascade return temperature, LLH secondary (NM165)INT16× 0.01°CRead
HR7168Cascade flow temperature, LLH secondary (EM012)INT16× 0.01°CRead
HR7169Cascade return temperature, LLH secondary (EM013)INT16× 0.01°CRead
HR7200Producer activation order (NP231)8-bit value in the low byte.UINT16Read/write
HR7202Identified producer state8-bit value in the low byte.UINT16Read/write0 = Not connected; 1 = Available; 2 = Not available
HR7207Active producers in cascade (NM113)UINT16Read
HR7209Producer main status (EM058)8-bit value in the low byte.UINT16Read0 = Standby; 1 = Heat demand; 2 = Generator start; 3 = Generator CH; 4 = Generator DHW; 5 = Generator stop; 6 = Pump post run; 7 = Cooling active; 8 = Controlled stop; 9 = Blocking mode; 10 = Locking mode; 11 = Load test min; 12 = Load test CH max; 13 = Load test DHW max; 14 = Custom load test; 15 = Manual heat demand; 16 = Frost protection; 17 = Deaeration; 18 = Control unit cooling; 19 = Reset in progress; 20 = Auto filling; 21 = Halted; 22 = Forced calibration; 23 = Factory test; 24 = Hydronic balancing; 200 = Device mode; 254 = Unknown
HR9230Instantaneous COP (HM031)Hybrid systems.UINT16× 0.001Read
HR9231COP switch-over threshold (HM032)COP at which the system swaps heat pump and boiler.UINT16× 0.001Read
HR21020BMS fallback heat demand mode8-bit value in the low byte.UINT16Read/write0 = BMS fallback HD mode; 1 = Use fallback HD
HR21021BMS fallback heat demand configuration8-bit value in the low byte.UINT16Read/write0 = Cancel directly; 1 = Never cancel; 2 = Maintain fallback HD
HR21022BMS fallback heat demand period8-bit value in the low byte.UINT16minRead/write
HR21023Fallback power setpoint8-bit value in the low byte.UINT16%Read/write
HR21024Fallback temperature setpointINT16× 0.01°CRead/write
HR21025Fallback heat demand type8-bit value in the low byte.UINT16Read/write0 = None; 1 = DHW primary; 2 = DHW high priority; 3 = Process heat; 4 = Screed drying; 5 = DHW medium priority; 6 = DHW low priority; 7 = Central heating; 8 = Cooling; 9 = Electrical active; 10 = Electrical reactive
HR21026SCB 0-10 V / PWM input function (EP014)8-bit value in the low byte.UINT16Read/write0 = Off; 1 = Temperature control; 2 = Power control
HR210270-10 V input value (AM028)8-bit value in the low byte.UINT16× 0.1VRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances

What Modbus registers does the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances have?

This map lists 109 registers: 109 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual's read example sends start register 0x0020 and calls it register 32, so the decimal register numbers in the tables go on the wire unchanged.

What are the minimum Modbus registers to integrate the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances?

Start with HR 400 Flow temperature (AM016) (Flow temperature); HR 401 Return temperature (AM018) (Return temperature); HR 409 Primary circuit water pressure (AM019) (Water pressure); HR 411 Appliance main status (AM012) (Main status); HR 531 Current error present (Any error present); HR 258 Algorithm type (Control mode (monitor / power / temperature)); HR 257 System temperature request (Temperature request); HR 259 Heat demand type (Heat demand type).

How do I enable Modbus control of the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances?

Connect the GTW-08 to the appliance L-Bus. Rotary knob 0-F sets the Modbus address 100-115 (default 100). DIP switches 1-2 set the baud rate (9600 default, 19200, 38400, 57600) and switches 3-4 the parity (none default, odd, even).

What happens when the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances loses Modbus communication?

Registers 21020-21025 define a fallback heat demand (keep, adjust or cancel) used when communication between the gateway and the BMS is lost, with a period in minutes in 21022.

Where is the official Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus documentation?

The source is GTW-08 Modbus - Configuration manual (multilingual; English section) (7854678 - v.01), revision 2023-09-15, published free by Remeha at https://tools.remeha.nl/wp-content/uploads/sites/11/2024/07/configuratiehandleiding-GTW-08.pdf.

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: GTW-08 Modbus - Configuration manual (multilingual; English section) · 7854678 - v.01 · rev. 2023-09-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.