- GTW-08 Modbus gateway for Remeha / De Dietrich appliances
Boiler / heat pump gateway · Modbus register map
Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus register map
Updated 17 November 2026
The GTW-08 is a small gateway that sits on the appliance's L-Bus and answers Modbus RTU for a BMS. Through it the BMS can read flow, return, flue and outside temperatures, water pressure, status codes and errors, set system power or temperature demands, run heating zones manually, configure cascades and define a fallback demand. This map covers the 16-bit registers of the English section.
This page lists 109 Modbus registers for the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Remeha’s own free documentation (linked below) and checked against it.
- Manufacturer
- Remeha
- Model
- GTW-08 Modbus gateway for Remeha / De Dietrich appliances
- Equipment type
- Boiler / heat pump gateway
- Registers
- 109 (35 writable)
- Transport
- Modbus RTU
- Default unit ID
- 100
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- GTW-08 Modbus, GTW08, De Dietrich GTW-08, BDR Thermea GTW-08
Integration notes: Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances
Set the gateway's rotary address and DIP baud/parity, then read 400/401/409/411 for temperatures, pressure and status. To control, write 258 (algorithm type), 256 power and/or 257 temperature, and 259 heat demand type (7 heating, 8 cooling).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 400 | Flow temperature (AM016) | INT16 | Flow temperature | Read |
| HR 401 | Return temperature (AM018) | INT16 | Return temperature | Read |
| HR 409 | Primary circuit water pressure (AM019) | UINT16 | Water pressure | Read |
| HR 411 | Appliance main status (AM012) | UINT16 | Main status | Read |
| HR 531 | Current error present | UINT16 | Any error present | Read |
| HR 258 | Algorithm type | UINT16 | Control mode (monitor / power / temperature) | Read/write |
| HR 257 | System temperature request | UINT16 | Temperature request | Read/write |
| HR 259 | Heat demand type | UINT16 | Heat demand type | Read/write |
Enable Modbus control & writes
Connect the GTW-08 to the appliance L-Bus. Rotary knob 0-F sets the Modbus address 100-115 (default 100). DIP switches 1-2 set the baud rate (9600 default, 19200, 38400, 57600) and switches 3-4 the parity (none default, odd, even).
Communication loss & watchdog
Registers 21020-21025 define a fallback heat demand (keep, adjust or cancel) used when communication between the gateway and the BMS is lost, with a period in minutes in 21022.
Byte order & addressing
- Reads use function 03; writes use 06 or 16. 8-bit values must still be read and written as whole registers.
- Exception code 0x0B means the gateway has not yet read that value from the appliance; retry.
Network setup
- Use the use-case tables (p. 15) to combine 256/257/258/259: e.g. 258 = 0, 256 = 60, 257 = 5000, 259 = 7 heats to 50 °C without exceeding 60 % power.
- A zone is put in manual by writing 649 = 1 and a setpoint in 648 or 664.
Watch out for
- The status LED blinks orange on a Modbus error; fixed red means no Modbus communication.
Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 128 | Devices connected | 8-bit value in the low byte. | UINT16 | Read | ||||
| HR | 129 | Board 1 device type | 0xZZYY: ZZ category, YY number in category. | UINT16 | Read | ||||
| HR | 135 | Board 2 device type | 0xZZYY: ZZ category, YY number in category. | UINT16 | Read | ||||
| HR | 141 | Board 3 device type | 0xZZYY: ZZ category, YY number in category. | UINT16 | Read | ||||
| HR | 147 | Board 4 device type | 0xZZYY: ZZ category, YY number in category. | UINT16 | Read | ||||
| HR | 153 | Board 5 device type | 0xZZYY: ZZ category, YY number in category. | UINT16 | Read | ||||
| HR | 159 | Board 6 device type | 0xZZYY: ZZ category, YY number in category. | UINT16 | Read | ||||
| HR | 165 | Board 7 device type | 0xZZYY: ZZ category, YY number in category. | UINT16 | Read | ||||
| HR | 171 | Board 8 device type | 0xZZYY: ZZ category, YY number in category. | UINT16 | Read | ||||
| HR | 189 | Zones detected | 8-bit value in the low byte. | UINT16 | Read | ||||
| HR | 256 | System power request | 8-bit value in the low byte. 0-100 % of system output. | UINT16 | % | Read/write | |||
| HR | 257 | System temperature request | Flow temperature request. | UINT16 | × 0.01 | °C | Read/write | ||
| HR | 258 | Algorithm type | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Remote management of temperature and power; 1 = Remote management of power; 2 = Remote management of temperature; 3 = Remote monitoring only | |||
| HR | 259 | Heat demand type | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Standby; 7 = Heating; 8 = Cooling | |||
| HR | 275 | Heat demand bitfield (zones) | Per-zone heat demand flags. | BITMAP16 | Read | bit 0 = Direct zones allowed to run; bit 1 = Mixing circuits allowed to run; bit 2 = All valves open / pump running within safety; bit 3 = Manual heat demand active; bit 4 = Cooling allowed; bit 5 = DHW circuits allowed to run; bit 6 = Heat engine active | |||
| HR | 277 | Error list, all connected devices | UINT16 | Read | |||||
| HR | 279 | Output status 1 (all devices) | BITMAP16 | Read | bit 0 = Flame on; bit 1 = Heat pump on; bit 2 = Electrical backup 1 on; bit 3 = Electrical backup 2 on; bit 4 = DHW electrical backup on; bit 5 = Service required; bit 6 = Power down / reset; bit 7 = Water pressure low | ||||
| HR | 280 | Output status 2 (all devices) | BITMAP16 | Read | bit 0 = Pump; bit 1 = 3-way valve open; bit 2 = 3-way valve; bit 3 = 3-way valve closed; bit 4 = DHW active; bit 5 = CH active; bit 6 = Cooling active | ||||
| HR | 384 | Outside temperature | INT16 | × 0.01 | °C | Read | |||
| HR | 385 | Seasonal mode | 8-bit value in the low byte. | UINT16 | Read | 0 = Winter; 1 = Frost protection; 2 = Summer neutral band; 3 = Summer | |||
| HR | 400 | Flow temperature (AM016) | Appliance flow temperature. | INT16 | × 0.01 | °C | Read | ||
| HR | 401 | Return temperature (AM018) | Water entering the appliance. | INT16 | × 0.01 | °C | Read | ||
| HR | 402 | Flue gas temperature (AM036) | INT16 | × 0.01 | °C | Read | |||
| HR | 403 | Heat pump flow temperature (HM001) | INT16 | × 0.01 | °C | Read | |||
| HR | 404 | Heat pump return temperature (HM002) | INT16 | × 0.01 | °C | Read | |||
| HR | 408 | DHW flow temperature setpoint (DM004) | UINT16 | × 0.01 | °C | Read | |||
| HR | 409 | Primary circuit water pressure (AM019) | 8-bit value in the low byte. | UINT16 | × 0.1 | bar | Read | ||
| HR | 411 | Appliance main status (AM012) | 8-bit value in the low byte. | UINT16 | Read | 0 = Standby; 1 = Heat demand; 2 = Generator start; 3 = Generator CH; 4 = Generator DHW; 5 = Generator stop; 6 = Pump post run; 7 = Cooling active; 8 = Controlled stop; 9 = Blocking mode; 10 = Locking mode; 11 = Load test min; 12 = Load test CH max; 13 = Load test DHW max; 15 = Manual heat demand; 16 = Frost protection; 17 = Deaeration; 18 = Control unit cooling; 19 = Reset in progress; 20 = Auto filling; 21 = Halted; 22 = Forced calibration; 23 = Factory test; 24 = Hydronic balancing; 200 = Device mode; 254 = Unknown | |||
| HR | 412 | Appliance sub status (AM014) | Sub-status code; table 17 of the manual. | UINT16 | Read | ||||
| HR | 413 | Relative power (AM024) | UINT16 | % | Read | ||||
| HR | 459 | Pump speed (AM010) | UINT16 | × 0.1 | % | Read/write | |||
| HR | 512 | Service required (AM011) | 8-bit value in the low byte. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 513 | Service notification | 8-bit value in the low byte. | UINT16 | Read | 0 = None; 1 = A; 2 = B; 3 = C; 4 = Custom; 5 = D | |||
| HR | 531 | Current error present | 8-bit value in the low byte. | UINT16 | Read | 0 = No error; 1 = At least one error on any appliance | |||
| HR | 532 | Board 1 error code | 0xFFFF = no error, 0xFFFE = device not available. | UINT16 | Read | ||||
| HR | 533 | Board 1 error type | UINT16 | Read | 0 = Locking; 3 = Blocking; 6 = Warning | ||||
| HR | 534 | Board 2 error code | 0xFFFF = no error, 0xFFFE = device not available. | UINT16 | Read | ||||
| HR | 535 | Board 2 error type | UINT16 | Read | 0 = Locking; 3 = Blocking; 6 = Warning | ||||
| HR | 536 | Board 3 error code | 0xFFFF = no error, 0xFFFE = device not available. | UINT16 | Read | ||||
| HR | 537 | Board 3 error type | UINT16 | Read | 0 = Locking; 3 = Blocking; 6 = Warning | ||||
| HR | 538 | Board 4 error code | 0xFFFF = no error, 0xFFFE = device not available. | UINT16 | Read | ||||
| HR | 539 | Board 4 error type | UINT16 | Read | 0 = Locking; 3 = Blocking; 6 = Warning | ||||
| HR | 540 | Board 5 error code | 0xFFFF = no error, 0xFFFE = device not available. | UINT16 | Read | ||||
| HR | 541 | Board 5 error type | UINT16 | Read | 0 = Locking; 3 = Blocking; 6 = Warning | ||||
| HR | 542 | Board 6 error code | 0xFFFF = no error, 0xFFFE = device not available. | UINT16 | Read | ||||
| HR | 543 | Board 6 error type | UINT16 | Read | 0 = Locking; 3 = Blocking; 6 = Warning | ||||
| HR | 544 | Board 7 error code | 0xFFFF = no error, 0xFFFE = device not available. | UINT16 | Read | ||||
| HR | 545 | Board 7 error type | UINT16 | Read | 0 = Locking; 3 = Blocking; 6 = Warning | ||||
| HR | 546 | Board 8 error code | 0xFFFF = no error, 0xFFFE = device not available. | UINT16 | Read | ||||
| HR | 547 | Board 8 error type | UINT16 | Read | 0 = Locking; 3 = Blocking; 6 = Warning | ||||
| HR | 641 | Zone 1 function type | Zone function code; next zones every 512 registers. | UINT16 | Read | ||||
| HR | 645 | Zone 1 device type | 0xZZYY: ZZ category, YY number (00 CU-GH, 01 CU-OH, 02 EHC, 19 SCB...). | UINT16 | Read | ||||
| HR | 648 | Zone 1 fixed flow temperature setpoint | Used when the zone runs on a fixed flow setpoint. | UINT16 | × 0.01 | °C | Read/write | ||
| HR | 649 | Zone 1 operating mode | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Scheduling; 1 = Manual; 2 = Off | |||
| HR | 664 | Zone 1 manual room temperature setpoint | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 674 | Zone 1 heating curve gradient | 8-bit value in the low byte. | UINT16 | × 0.1 | Read/write | |||
| HR | 675 | Zone 1 heating curve comfort footpoint | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 1100 | Zone 1 flow or DHW temperature (CM040) | INT16 | × 0.01 | °C | Read | |||
| HR | 1101 | Zone 1 flow temperature setpoint (CM070) | UINT16 | × 0.01 | °C | Read | |||
| HR | 1102 | Zone 1 room temperature setpoint (CM190) | INT16 | × 0.1 | °C | Read | |||
| HR | 1107 | Zone 1 current activity (CM130) | 8-bit value in the low byte. | UINT16 | Read | 0 = Off; 1 = Eco; 2 = Comfort; 3 = Anti legionella | |||
| HR | 1108 | Zone 1 operating mode (CM120) | 8-bit value in the low byte. | UINT16 | Read | 0 = Scheduling; 1 = Manual; 2 = Off; 3 = Temporary | |||
| HR | 1110 | Zone 1 pump status (CM050) | 8-bit value in the low byte. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 7000 | Node number of the device | 8-bit value in the low byte. | UINT16 | Read/write | ||||
| HR | 7001 | Cascade mode (NP014) | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Automatic; 1 = Heating; 2 = Cooling | |||
| HR | 7002 | Cascade type (NP006) | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Traditional; 1 = Parallel | |||
| HR | 7009 | Cascade management type (NP011) | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Temperature; 1 = Power | |||
| HR | 7011 | Start order permutation (NP223) | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Fixed time; 1 = Operating hours | |||
| HR | 7012 | Producer switch interval (NP281) | UINT16 | h | Read/write | ||||
| HR | 7014 | Power control strategy (NP225) | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Late on, early off; 1 = Early on, late off; 2 = Late on, late off | |||
| HR | 7015 | Preferred producer for CH (NP227) | 8-bit value in the low byte. | UINT16 | Read/write | ||||
| HR | 7016 | Non-preferred producer for CH (NP228) | 8-bit value in the low byte. | UINT16 | Read/write | ||||
| HR | 7017 | Late-on value (NP282) | 8-bit value in the low byte. | UINT16 | % | Read/write | |||
| HR | 7018 | Late-off value (NP283) | 8-bit value in the low byte. | UINT16 | % | Read/write | |||
| HR | 7019 | Early-on value (NP284) | 8-bit value in the low byte. | UINT16 | % | Read/write | |||
| HR | 7020 | Early-off value (NP285) | 8-bit value in the low byte. | UINT16 | % | Read/write | |||
| HR | 7023 | Primary pump type (NP287) | 8-bit value in the low byte. | UINT16 | Read/write | 0 = No pump; 1 = On/off; 2 = PWM; 3 = 0-10 V | |||
| HR | 7024 | Secondary pump type (NP288) | 8-bit value in the low byte. | UINT16 | Read/write | 0 = No pump; 1 = On/off; 2 = PWM; 3 = 0-10 V | |||
| HR | 7101 | Cascade flow temperature (NM001) | INT16 | × 0.01 | °C | Read | |||
| HR | 7102 | Producers recognised in cascade (NM028) | 8-bit value in the low byte. | UINT16 | Read | ||||
| HR | 7103 | Cascade stages available (NM022) | 8-bit value in the low byte. | UINT16 | Read | ||||
| HR | 7104 | Cascade stages required (NM023) | 8-bit value in the low byte. | UINT16 | Read | ||||
| HR | 7105 | Cascade power request: power | 8-bit value in the low byte. | UINT16 | % | Read | |||
| HR | 7106 | Cascade power request: temperature | INT16 | × 0.01 | °C | Read | |||
| HR | 7107 | Cascade power request: heat demand | 8-bit value in the low byte. | UINT16 | Read | 0 = Automatic; 1 = Heating; 2 = Cooling; 3 = Process heat; 4 = Screed drying; 5 = DHW medium priority; 6 = DHW low priority; 7 = Heating; 8 = Cooling; 9 = Electrical active; 10 = Electrical reactive | |||
| HR | 7108 | Cascade calculated setpoint: power | 8-bit value in the low byte. | UINT16 | % | Read | |||
| HR | 7109 | Cascade calculated setpoint: temperature | INT16 | × 0.01 | °C | Read | |||
| HR | 7110 | Cascade calculated setpoint: heat demand | 8-bit value in the low byte. | UINT16 | Read | 0 = Automatic; 1 = Heating; 2 = Cooling; 3 = Process heat; 4 = Screed drying; 5 = DHW medium priority; 6 = DHW low priority; 7 = Heating; 8 = Cooling; 9 = Electrical active; 10 = Electrical reactive | |||
| HR | 7155 | Requested cascade power percentage (NM170) | INT16 | × 0.1 | % | Read | |||
| HR | 7157 | Cascade primary pump status (NM166) | 8-bit value in the low byte. | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| HR | 7158 | Cascade secondary pump status (NM167) | 8-bit value in the low byte. | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| HR | 7159 | Cascade state (NM163) | 8-bit value in the low byte. | UINT16 | Read | 0 = Standby; 1 = Heat demand; 2 = Generator start; 3 = Generator CH; 4 = Generator DHW; 5 = Generator stop; 6 = Pump post run; 7 = Cooling active; 8 = Controlled stop; 9 = Blocking mode; 10 = Locking mode; 11 = Load test min; 12 = Load test CH max; 13 = Load test DHW max; 14 = Custom load test; 15 = Manual heat demand; 16 = Frost protection; 17 = Deaeration; 18 = Control unit cooling; 19 = Reset in progress; 20 = Auto filling; 21 = Halted; 22 = Forced calibration; 23 = Factory test; 24 = Hydronic balancing; 200 = Device mode; 254 = Unknown | |||
| HR | 7164 | Cascade return temperature, LLH secondary (NM165) | INT16 | × 0.01 | °C | Read | |||
| HR | 7168 | Cascade flow temperature, LLH secondary (EM012) | INT16 | × 0.01 | °C | Read | |||
| HR | 7169 | Cascade return temperature, LLH secondary (EM013) | INT16 | × 0.01 | °C | Read | |||
| HR | 7200 | Producer activation order (NP231) | 8-bit value in the low byte. | UINT16 | Read/write | ||||
| HR | 7202 | Identified producer state | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Not connected; 1 = Available; 2 = Not available | |||
| HR | 7207 | Active producers in cascade (NM113) | UINT16 | Read | |||||
| HR | 7209 | Producer main status (EM058) | 8-bit value in the low byte. | UINT16 | Read | 0 = Standby; 1 = Heat demand; 2 = Generator start; 3 = Generator CH; 4 = Generator DHW; 5 = Generator stop; 6 = Pump post run; 7 = Cooling active; 8 = Controlled stop; 9 = Blocking mode; 10 = Locking mode; 11 = Load test min; 12 = Load test CH max; 13 = Load test DHW max; 14 = Custom load test; 15 = Manual heat demand; 16 = Frost protection; 17 = Deaeration; 18 = Control unit cooling; 19 = Reset in progress; 20 = Auto filling; 21 = Halted; 22 = Forced calibration; 23 = Factory test; 24 = Hydronic balancing; 200 = Device mode; 254 = Unknown | |||
| HR | 9230 | Instantaneous COP (HM031) | Hybrid systems. | UINT16 | × 0.001 | Read | |||
| HR | 9231 | COP switch-over threshold (HM032) | COP at which the system swaps heat pump and boiler. | UINT16 | × 0.001 | Read | |||
| HR | 21020 | BMS fallback heat demand mode | 8-bit value in the low byte. | UINT16 | Read/write | 0 = BMS fallback HD mode; 1 = Use fallback HD | |||
| HR | 21021 | BMS fallback heat demand configuration | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Cancel directly; 1 = Never cancel; 2 = Maintain fallback HD | |||
| HR | 21022 | BMS fallback heat demand period | 8-bit value in the low byte. | UINT16 | min | Read/write | |||
| HR | 21023 | Fallback power setpoint | 8-bit value in the low byte. | UINT16 | % | Read/write | |||
| HR | 21024 | Fallback temperature setpoint | INT16 | × 0.01 | °C | Read/write | |||
| HR | 21025 | Fallback heat demand type | 8-bit value in the low byte. | UINT16 | Read/write | 0 = None; 1 = DHW primary; 2 = DHW high priority; 3 = Process heat; 4 = Screed drying; 5 = DHW medium priority; 6 = DHW low priority; 7 = Central heating; 8 = Cooling; 9 = Electrical active; 10 = Electrical reactive | |||
| HR | 21026 | SCB 0-10 V / PWM input function (EP014) | 8-bit value in the low byte. | UINT16 | Read/write | 0 = Off; 1 = Temperature control; 2 = Power control | |||
| HR | 21027 | 0-10 V input value (AM028) | 8-bit value in the low byte. | UINT16 | × 0.1 | V | Read/write |
Notes on this map
- UINT8 and ENUM8 values sit in the low byte of a 16-bit register (data-type table p. 8); they are listed as UINT16 here.
- Left out: every UINT32/INT32 register (energy counters 419-451, power 460, zone pump counters 1115/1117, cascade 7151/7160/7162, serial 7228, service starts 516). The manual says 32-bit values take two registers but never says which word comes first.
- Also left out because the manual contradicts itself or gives an impossible scale: 272 system power (1 % in one table, 0.01 % in another), 415 (labelled starts but scaled 0.1 µA), 514/515 (resolution printed as '2 hours'), 7166/7167 (UINT8 at 0.1 % over 0-100 %), 7203/7205 (no unit or scale).
- Zone registers are listed for zone 1. In the manual's per-zone tables most zone registers step by 512 per zone (641, 1153, 1665 ...), but the activity, mode and pump registers jump after zone 6 (zone 7 1107-type at 5121, not 4179); use the manual's zone tables (pp. 16-21) for zones 2-12.
- Cascade member registers 7111-7146 (power output, flow temperature, status, special request per member) are left out: the manual gives their addresses but no data type, scale or coding.
- Register 411 main status uses table 16 of the manual; cascade state 7159 and producer status 7209 use table 47, which has the same codes plus 14 (custom load test). Sub status 412 has a long code list in table 17 of the manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances
What Modbus registers does the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances have?
This map lists 109 registers: 109 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual's read example sends start register 0x0020 and calls it register 32, so the decimal register numbers in the tables go on the wire unchanged.
What are the minimum Modbus registers to integrate the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances?
Start with HR 400 Flow temperature (AM016) (Flow temperature); HR 401 Return temperature (AM018) (Return temperature); HR 409 Primary circuit water pressure (AM019) (Water pressure); HR 411 Appliance main status (AM012) (Main status); HR 531 Current error present (Any error present); HR 258 Algorithm type (Control mode (monitor / power / temperature)); HR 257 System temperature request (Temperature request); HR 259 Heat demand type (Heat demand type).
How do I enable Modbus control of the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances?
Connect the GTW-08 to the appliance L-Bus. Rotary knob 0-F sets the Modbus address 100-115 (default 100). DIP switches 1-2 set the baud rate (9600 default, 19200, 38400, 57600) and switches 3-4 the parity (none default, odd, even).
What happens when the Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances loses Modbus communication?
Registers 21020-21025 define a fallback heat demand (keep, adjust or cancel) used when communication between the gateway and the BMS is lost, with a period in minutes in 21022.
Where is the official Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances Modbus documentation?
The source is GTW-08 Modbus - Configuration manual (multilingual; English section) (7854678 - v.01), revision 2023-09-15, published free by Remeha at https://tools.remeha.nl/wp-content/uploads/sites/11/2024/07/configuratiehandleiding-GTW-08.pdf.
Other ac & vrf gateways register maps
- Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - VRF / split AC gateway (IR-to-Modbus controller)
Cuby Cuby smart AC controller (Modbus RTU)
Cuby smart IR controllers for mini-split air conditioners with the Modbus RTU firmware described in the 2025 'MODBUS REGISTERS' sheet (fixed address 1).
Also known as: Cuby Smart, Cuby AC controller, Cuby minisplit controller - VRF / split AC gateway
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Gree Modbus Gateway (Mini) on CAN-bus multi VRF systems (GMV5, GMV5 C/E/HR/MAX/MINI/SLIM, GMV Water, energy-recovery ventilation); Communication Protocol V2.0, multi VRF part only.
Also known as: ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus
All ac & vrf gateways Modbus register maps →
Source: GTW-08 Modbus - Configuration manual (multilingual; English section) · 7854678 - v.01 · rev. 2023-09-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.