VRF / split AC gateway (IR-to-Modbus controller) · Modbus register map

Cuby Cuby smart AC controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Cuby makes a small controller that drives mini-split air conditioners over infrared and exposes them on Modbus RTU. The registers set power, mode, fan speed, setpoint, vanes and turbo, and report indoor temperature, humidity, occupancy and contact-open time from Cuby sensors. All values are single 16-bit registers.

This page lists 18 Modbus registers for the Cuby Cuby smart AC controller (Modbus RTU) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cuby’s own free documentation (linked below) and checked against it.

Manufacturer
Cuby
Model
Cuby smart AC controller (Modbus RTU)
Equipment type
VRF / split AC gateway (IR-to-Modbus controller)
Registers
18 (13 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
Cuby Smart, Cuby AC controller, Cuby minisplit controller
Source document
MODBUS REGISTERS · rev. 2025
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Cuby Cuby smart AC controller (Modbus RTU)

Integration in brief

Connect RS485 at 9600 8N1 to unit 1. Write power (0), mode (1), fan (2) and setpoint x10 (4); read indoor temperature (13) and humidity (15).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC ON/OFFUINT16Power on/offRead/write
HR 1AC MODEUINT16Operating modeRead/write
HR 4AC Temperature SetpointUINT16Setpoint (x10)Read/write
HR 13Indoor TemperatureINT16Indoor temperature (x10)Read
HR 2FAN SPEEDUINT16Fan speedRead/write

Enable Modbus control & writes

No enable step is described; Modbus RTU is active at fixed address 1.

Byte order & addressing

Network setup

Watch out for

Cuby Cuby smart AC controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

18 of 18 shown
Cuby Cuby smart AC controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0 (PLC 1)AC ON/OFFPower state of the air conditioner.UINT16Read/write0 = Off; 1 = On
HR1doc 1 (PLC 2)AC MODEUINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan only; 4 = Cool
HR2doc 2 (PLC 3)FAN SPEEDUINT16Read/write0 = Auto; 1 = Low; 2 = Med; 3 = High
HR3doc 3 (PLC 4)IR PROTOCOLIR protocol 0-254; other values keep the configured protocol.UINT16Read/write
HR4doc 4 (PLC 5)AC Temperature SetpointSetpoint 16-31 °C, sent as °C x 10.UINT16× 0.1°CRead/write
HR6doc 6 (PLC 7)Command TypeNeeded only for special commands; use 0 (power) otherwise.UINT16Read/write0 = Power; 1 = Temperature; 2 = Mode; 3 = Fan speed; 4 = Display; 5 = Vertical vane; 6 = Horizontal vane; 7 = Turbo; 8 = Units
HR7doc 7 (PLC 8)DisplayOn some units any write toggles the display.UINT16Read/write0 = Off; 1 = On
HR8doc 8 (PLC 9)TurboUINT16Read/write0 = Off; 1 = On
HR9doc 9 (PLC 10)Vertical VaneVertical swing; positions 2-6 are model dependent.UINT16Read/write0 = Off; 1 = Auto; 2 = Top; 3 = Top-Center; 4 = Center; 5 = Bottom-Center; 6 = Bottom
HR10doc 10 (PLC 11)Horizontal VaneHorizontal swing; positions 2-7 are model dependent.UINT16Read/write0 = Off; 1 = Auto; 2 = Left; 3 = Left-Center; 4 = Center; 5 = Right-Center; 6 = Right; 7 = Sides
HR11doc 11 (PLC 12)Temperature UnitsDisplay units on air conditioners that support it.UINT16Read/write0 = Celsius; 1 = Fahrenheit
HR12doc 12 (PLC 13)Command SourceCode 0-31 for who sent the last command (IR remote, app, Modbus, etc.).UINT16Read
HR13doc 13 (PLC 14)Indoor Temperature-50 to 125 °C as °C x 10; -32768 until first reading.INT16× 0.1°CRead
HR15doc 15 (PLC 16)Indoor Relative Humidity0-100 % as % x 10; -32768 until first reading.INT16× 0.1%Read
HR19doc 19 (PLC 20)Occupancy Status-32768 until first reading.INT16Read/write0 = Vacant; 1 = Occupied
HR22doc 22 (PLC 23)Open TimeSeconds any contact sensor has been open (0-32000); resets when all close.INT16sRead
HR40doc 40 (PLC 41)Force IR CommandWrite 1 to send the IR command now; always reads 0.UINT16Read/write
HR48doc 48 (PLC 49)FW VersionFirmware version.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Cuby Cuby smart AC controller (Modbus RTU)

What Modbus registers does the Cuby Cuby smart AC controller (Modbus RTU) have?

This map lists 18 registers: 18 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Cuby Cuby smart AC controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The sheet prints both the protocol address (0-based, e.g. 4 for the setpoint) and the PLC address (1-based, 5). The protocol address goes on the wire. The sheet does not name function codes; the registers are listed here as holding registers because the writable rows can only be holding registers and all rows share one address list.

What are the minimum Modbus registers to integrate the Cuby Cuby smart AC controller (Modbus RTU)?

Start with HR 0 AC ON/OFF (Power on/off); HR 1 AC MODE (Operating mode); HR 4 AC Temperature Setpoint (Setpoint (x10)); HR 13 Indoor Temperature (Indoor temperature (x10)); HR 2 FAN SPEED (Fan speed).

How do I enable Modbus control of the Cuby Cuby smart AC controller (Modbus RTU)?

No enable step is described; Modbus RTU is active at fixed address 1.

Where is the official Cuby Cuby smart AC controller (Modbus RTU) Modbus documentation?

The source is MODBUS REGISTERS, revision 2025, published free by Cuby at https://pages.cuby.mx/hubfs/Fichas%20t%C3%A9cnicas/Modbus-registers.pdf.

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: MODBUS REGISTERS · rev. 2025. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.