VRF / split AC gateway (IR-to-Modbus controller) · Modbus register map
Cuby Cuby smart AC controller (Modbus RTU) Modbus register map
Updated 17 November 2026
Cuby makes a small controller that drives mini-split air conditioners over infrared and exposes them on Modbus RTU. The registers set power, mode, fan speed, setpoint, vanes and turbo, and report indoor temperature, humidity, occupancy and contact-open time from Cuby sensors. All values are single 16-bit registers.
This page lists 18 Modbus registers for the Cuby Cuby smart AC controller (Modbus RTU) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cuby’s own free documentation (linked below) and checked against it.
- Manufacturer
- Cuby
- Model
- Cuby smart AC controller (Modbus RTU)
- Equipment type
- VRF / split AC gateway (IR-to-Modbus controller)
- Registers
- 18 (13 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- Cuby Smart, Cuby AC controller, Cuby minisplit controller
- Source document
- MODBUS REGISTERS · rev. 2025
Integration notes: Cuby Cuby smart AC controller (Modbus RTU)
Connect RS485 at 9600 8N1 to unit 1. Write power (0), mode (1), fan (2) and setpoint x10 (4); read indoor temperature (13) and humidity (15).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | AC ON/OFF | UINT16 | Power on/off | Read/write |
| HR 1 | AC MODE | UINT16 | Operating mode | Read/write |
| HR 4 | AC Temperature Setpoint | UINT16 | Setpoint (x10) | Read/write |
| HR 13 | Indoor Temperature | INT16 | Indoor temperature (x10) | Read |
| HR 2 | FAN SPEED | UINT16 | Fan speed | Read/write |
Enable Modbus control & writes
No enable step is described; Modbus RTU is active at fixed address 1.
Byte order & addressing
- Setpoint and temperatures are x10 (225 = 22.5 °C).
- Special commands (display, turbo, swing, units) may need Command Type (6) set first.
- Display is a toggle on some air conditioners.
Network setup
- Fixed address 1, 9600 baud, 8 data bits, no parity, 1 stop bit.
Watch out for
- Command Source (12) shows who sent the last command (IR remote, app, Modbus, rules, HTTP API, BACnet and others).
- If reads of the read-only rows fail with function 03, the sheet does not name function codes; try function 04.
Cuby Cuby smart AC controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0 (PLC 1) | AC ON/OFF | Power state of the air conditioner. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 1doc 1 (PLC 2) | AC MODE | UINT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan only; 4 = Cool | ||||
| HR | 2doc 2 (PLC 3) | FAN SPEED | UINT16 | Read/write | 0 = Auto; 1 = Low; 2 = Med; 3 = High | ||||
| HR | 3doc 3 (PLC 4) | IR PROTOCOL | IR protocol 0-254; other values keep the configured protocol. | UINT16 | Read/write | ||||
| HR | 4doc 4 (PLC 5) | AC Temperature Setpoint | Setpoint 16-31 °C, sent as °C x 10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 6doc 6 (PLC 7) | Command Type | Needed only for special commands; use 0 (power) otherwise. | UINT16 | Read/write | 0 = Power; 1 = Temperature; 2 = Mode; 3 = Fan speed; 4 = Display; 5 = Vertical vane; 6 = Horizontal vane; 7 = Turbo; 8 = Units | |||
| HR | 7doc 7 (PLC 8) | Display | On some units any write toggles the display. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 8doc 8 (PLC 9) | Turbo | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 9doc 9 (PLC 10) | Vertical Vane | Vertical swing; positions 2-6 are model dependent. | UINT16 | Read/write | 0 = Off; 1 = Auto; 2 = Top; 3 = Top-Center; 4 = Center; 5 = Bottom-Center; 6 = Bottom | |||
| HR | 10doc 10 (PLC 11) | Horizontal Vane | Horizontal swing; positions 2-7 are model dependent. | UINT16 | Read/write | 0 = Off; 1 = Auto; 2 = Left; 3 = Left-Center; 4 = Center; 5 = Right-Center; 6 = Right; 7 = Sides | |||
| HR | 11doc 11 (PLC 12) | Temperature Units | Display units on air conditioners that support it. | UINT16 | Read/write | 0 = Celsius; 1 = Fahrenheit | |||
| HR | 12doc 12 (PLC 13) | Command Source | Code 0-31 for who sent the last command (IR remote, app, Modbus, etc.). | UINT16 | Read | ||||
| HR | 13doc 13 (PLC 14) | Indoor Temperature | -50 to 125 °C as °C x 10; -32768 until first reading. | INT16 | × 0.1 | °C | Read | ||
| HR | 15doc 15 (PLC 16) | Indoor Relative Humidity | 0-100 % as % x 10; -32768 until first reading. | INT16 | × 0.1 | % | Read | ||
| HR | 19doc 19 (PLC 20) | Occupancy Status | -32768 until first reading. | INT16 | Read/write | 0 = Vacant; 1 = Occupied | |||
| HR | 22doc 22 (PLC 23) | Open Time | Seconds any contact sensor has been open (0-32000); resets when all close. | INT16 | s | Read | |||
| HR | 40doc 40 (PLC 41) | Force IR Command | Write 1 to send the IR command now; always reads 0. | UINT16 | Read/write | ||||
| HR | 48doc 48 (PLC 49) | FW Version | Firmware version. | UINT16 | Read |
Notes on this map
- Hosted on Cuby's own HubSpot file storage (pages.cuby.mx).
- The unit address is fixed at 1 and the serial setting is 9600 8N1 in this firmware; the sheet says later firmware will make them configurable.
- Indoor temperature, humidity, occupancy and open time read -32768 until a value is available; signed 16-bit is assumed for those rows because of that initial value.
- Address 5 and other gaps are not listed in the source.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Cuby Cuby smart AC controller (Modbus RTU)
What Modbus registers does the Cuby Cuby smart AC controller (Modbus RTU) have?
This map lists 18 registers: 18 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Cuby Cuby smart AC controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The sheet prints both the protocol address (0-based, e.g. 4 for the setpoint) and the PLC address (1-based, 5). The protocol address goes on the wire. The sheet does not name function codes; the registers are listed here as holding registers because the writable rows can only be holding registers and all rows share one address list.
What are the minimum Modbus registers to integrate the Cuby Cuby smart AC controller (Modbus RTU)?
Start with HR 0 AC ON/OFF (Power on/off); HR 1 AC MODE (Operating mode); HR 4 AC Temperature Setpoint (Setpoint (x10)); HR 13 Indoor Temperature (Indoor temperature (x10)); HR 2 FAN SPEED (Fan speed).
How do I enable Modbus control of the Cuby Cuby smart AC controller (Modbus RTU)?
No enable step is described; Modbus RTU is active at fixed address 1.
Where is the official Cuby Cuby smart AC controller (Modbus RTU) Modbus documentation?
The source is MODBUS REGISTERS, revision 2025, published free by Cuby at https://pages.cuby.mx/hubfs/Fichas%20t%C3%A9cnicas/Modbus-registers.pdf.
Other ac & vrf gateways register maps
- VRF / split AC gateway
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Gree Modbus Gateway (Mini) on CAN-bus multi VRF systems (GMV5, GMV5 C/E/HR/MAX/MINI/SLIM, GMV Water, energy-recovery ventilation); Communication Protocol V2.0, multi VRF part only.
Also known as: ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64
All ac & vrf gateways Modbus register maps →
Source: MODBUS REGISTERS · rev. 2025. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.