  3. Intesis (HMS Networks)
  4. IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus) Modbus register map

Updated 19 November 2026

Short answer

Intesis 700 Series gateway that reads Mitsubishi Electric City Multi groups through one or two centralised controllers and serves them as Modbus RTU / TCP. Each group gets a 100-register block with on/off, mode, fan, vane, setpoint (x10), room temperature, run hours, errors, panel permissions and setback / dual setpoints.

This page lists 61 Modbus registers for the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Equipment type
VRF / split AC gateway
Registers
61 (50 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000
Source document
700 Series Air Gateway - IN770AIR***O000, Mitsubishi Electric City Multi to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · User Manual Version 1.0.19 · rev. 2026-03-16
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)

Integration in brief

Pick the Mitsubishi Electric City Multi application and the Modbus interface in Intesis MAPS, discover or add the units, send the project, then read and write each unit's block.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0CC communication errorUINT16Controller communication errorRead
HR 100Group on/offUINT16Group on/offRead/write
HR 101Group operation modeUINT16Group modeRead/write
HR 102Group fan speedUINT16Group fan speedRead/write
HR 104Group temperature setpointUINT16Group setpoint (x10)Read/write
HR 105Group ambient temperatureUINT16Group room temperature (x10)Read
HR 109Group error statusUINT16Group error statusRead
HR 110Group error codeUINT16Group error codeRead

Enable Modbus control & writes

The gateway must be configured with Intesis MAPS (City Multi project, Modbus selected) and the project sent to it; the manual points to the Signals tab of the MAPS configuration guide for the address formulas.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

61 of 61 shown
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc ((CC# - 1) × 30) + 0CC communication errorCentralised controller 1 shown; see notes.UINT16Read0 = OK; 1 = Communication error
HR1doc ((CC# - 1) × 30) + 1Reset errors (all groups)UINT16Write1 = Reset errors
HR2doc ((CC# - 1) × 30) + 2On (all groups)UINT16Write1 = Set groups on
HR3doc ((CC# - 1) × 30) + 3Off (all groups)UINT16Write1 = Set groups off
HR4doc ((CC# - 1) × 30) + 4Mode Auto (all IC groups)UINT16Write1 = Execute
HR5doc ((CC# - 1) × 30) + 5Mode Heat (all IC groups)UINT16Write1 = Execute
HR6doc ((CC# - 1) × 30) + 6Mode Dry (all IC groups)UINT16Write1 = Execute
HR7doc ((CC# - 1) × 30) + 7Mode Fan (all IC groups)UINT16Write1 = Execute
HR8doc ((CC# - 1) × 30) + 8Mode Cool (all IC groups)UINT16Write1 = Execute
HR9doc ((CC# - 1) × 30) + 9Mode Setback (all IC groups)UINT16Write1 = Execute
HR10doc ((CC# - 1) × 30) + 10Mode LC Auto (all Lossnay groups)UINT16Write1 = Execute
HR11doc ((CC# - 1) × 30) + 11Mode Heat Recovery (all Lossnay groups)UINT16Write1 = Execute
HR12doc ((CC# - 1) × 30) + 12Mode Bypass (all Lossnay groups)UINT16Write1 = Execute
HR13doc ((CC# - 1) × 30) + 13Fan Auto (all IC groups)UINT16Write1 = Execute
HR14doc ((CC# - 1) × 30) + 14Fan Low (all IC groups)UINT16Write1 = Execute
HR15doc ((CC# - 1) × 30) + 15Fan Mid-1 (all IC groups)UINT16Write1 = Execute
HR16doc ((CC# - 1) × 30) + 16Fan Mid-2 (all IC groups)UINT16Write1 = Execute
HR17doc ((CC# - 1) × 30) + 17Fan High (all IC groups)UINT16Write1 = Execute
HR18doc ((CC# - 1) × 30) + 18Fan Low (all Lossnay groups)UINT16Write1 = Execute
HR19doc ((CC# - 1) × 30) + 19Fan High (all Lossnay groups)UINT16Write1 = Execute
HR20doc ((CC# - 1) × 30) + 20Vanes Auto (all IC groups)UINT16Write1 = Execute
HR21doc ((CC# - 1) × 30) + 21Vanes Horizontal (all IC groups)UINT16Write1 = Execute
HR22doc ((CC# - 1) × 30) + 22Vanes Position-2 (all IC groups)UINT16Write1 = Execute
HR23doc ((CC# - 1) × 30) + 23Vanes Position-3 (all IC groups)UINT16Write1 = Execute
HR24doc ((CC# - 1) × 30) + 24Vanes Position-4 (all IC groups)UINT16Write1 = Execute
HR25doc ((CC# - 1) × 30) + 25Vanes Vertical (all IC groups)UINT16Write1 = Execute
HR26doc ((CC# - 1) × 30) + 26Vanes Swing (all IC groups)UINT16Write1 = Execute
HR27doc ((CC# - 1) × 30) + 27Setpoint (all groups)Tenths of °C, 5..90.UINT16× 0.1°CWrite
HR28doc ((CC# - 1) × 30) + 28Fan Mid-1 (all Lossnay groups)UINT16Write1 = Execute
HR29doc ((CC# - 1) × 30) + 29Fan Mid-2 (all Lossnay groups)UINT16Write1 = Execute
HR100doc (((CC# - 1) × 50) + Group#) × 100 + 0Group on/offController 1, group 1 shown; see notes.UINT16Read/write0 = Off; 1 = On
HR101doc (((CC# - 1) × 50) + Group#) × 100 + 1Group operation modeIC codes shown; Lossnay and ATW groups use other codes (see notes).UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool; 5 = Auto Heat; 6 = Auto Cool; 7 = Setback; 8 = Setback Heat; 9 = Setback Cool
HR102doc (((CC# - 1) × 50) + Group#) × 100 + 2Group fan speedIC codes shown; Lossnay: 1 Low, 2 Middle 2, 3 Middle 1, 4 High.UINT16Read/write0 = Auto; 1 = Low; 2 = Middle 2; 3 = Middle 1; 4 = High
HR103doc (((CC# - 1) × 50) + Group#) × 100 + 3Group vane positionUINT16Read/write0 = Auto; 1 = Horizontal; 2 = Position 2; 3 = Position 3; 4 = Position 4; 5 = Vertical; 6 = Swing
HR104doc (((CC# - 1) × 50) + Group#) × 100 + 4Group temperature setpointTenths of °C. IC: cool/dry 19..30, heat/auto 17..28; ATW 5..90.UINT16× 0.1°CRead/write
HR105doc (((CC# - 1) × 50) + Group#) × 100 + 5Group ambient temperatureTenths of °C. 0.0..99.9.UINT16× 0.1°CRead
HR106doc (((CC# - 1) × 50) + Group#) × 100 + 6Lossnay / OA operational statusUINT16Read/write0 = Off; 1 = Low; 2 = High
HR107doc (((CC# - 1) × 50) + Group#) × 100 + 7Group operation time, hundreds of hoursRun hours = this x 100 + next register.UINT16× 100hRead
HR108doc (((CC# - 1) × 50) + Group#) × 100 + 8Group operation time, hours remainderRun hours modulo 100.UINT16hRead
HR109doc (((CC# - 1) × 50) + Group#) × 100 + 9Group error statusUINT16Read0 = No error; 1 = Group error
HR110doc (((CC# - 1) × 50) + Group#) × 100 + 10Group error codeMitsubishi Electric 4-digit error code.UINT16Read
HR111doc (((CC# - 1) × 50) + Group#) × 100 + 11Group error resetUINT16Write1 = Reset the error
HR112doc (((CC# - 1) × 50) + Group#) × 100 + 12Group modelModel of units connected to the group.UINT16Read
HR113doc (((CC# - 1) × 50) + Group#) × 100 + 13Allow on/off from local panelUINT16Read/write0 = Allow; 1 = Not allowed
HR114doc (((CC# - 1) × 50) + Group#) × 100 + 14Allow mode from local panelUINT16Read/write0 = Allow; 1 = Not allowed
HR115doc (((CC# - 1) × 50) + Group#) × 100 + 15Allow setpoint from local panelUINT16Read/write0 = Allow; 1 = Not allowed
HR116doc (((CC# - 1) × 50) + Group#) × 100 + 16Allow filter reset from local panelUINT16Read/write0 = Allow; 1 = Not allowed
HR117doc (((CC# - 1) × 50) + Group#) × 100 + 17Allow air direction from local panelUINT16Read/write0 = Allow; 1 = Not allowed
HR118doc (((CC# - 1) × 50) + Group#) × 100 + 18Allow fan speed from local panelUINT16Read/write0 = Allow; 1 = Not allowed
HR119doc (((CC# - 1) × 50) + Group#) × 100 + 19Allow timer from local panelUINT16Read/write0 = Allow; 1 = Not allowed
HR120doc (((CC# - 1) × 50) + Group#) × 100 + 20Setback controlUINT16Read/write0 = Disable; 1 = Enable
HR127doc (((CC# - 1) × 50) + Group#) × 100 + 27Cool/dry/auto upper dual setpoint (ATW: heating setpoint)Tenths of °C. 4.5..90.UINT16× 0.1°CRead/write
HR128doc (((CC# - 1) × 50) + Group#) × 100 + 28Heat/auto lower dual setpoint (ATW: heating eco setpoint)Tenths of °C. 4.5..90.UINT16× 0.1°CRead/write
HR129doc (((CC# - 1) × 50) + Group#) × 100 + 29Auto single setpoint (ATW: hot water setpoint)Tenths of °C. 4.5..90.UINT16× 0.1°CRead/write
HR130doc (((CC# - 1) × 50) + Group#) × 100 + 30Setback upper setpoint (ATW: anti-freeze setpoint)Tenths of °C. 4.5..90.UINT16× 0.1°CRead/write
HR131doc (((CC# - 1) × 50) + Group#) × 100 + 31Setback lower setpoint (ATW: cooling setpoint)Tenths of °C. 4.5..90.UINT16× 0.1°CRead/write
HR132doc (((CC# - 1) × 50) + Group#) × 100 + 32Room humidityUINT16%Read
HR133doc (((CC# - 1) × 50) + Group#) × 100 + 33Brightness statusUINT16Read0 = Dark; 1 = Bright
HR134doc (((CC# - 1) × 50) + Group#) × 100 + 34OccupancyUINT16Read0 = Absence; 1 = Occupancy
HR136doc (((CC# - 1) × 50) + Group#) × 100 + 36Filter statusUINT16Read0 = OK; 1 = Dirty
HR137doc (((CC# - 1) × 50) + Group#) × 100 + 37Dirty filter indication resetUINT16Write1 = Reset the filter

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)

What Modbus registers does the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus) have?

This map lists 61 registers: 61 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual works examples: the first controller signal of controller 1 is address 0 and of controller 2 is 30; on/off of group 1 on controller 1 is 100 and of group 6 on controller 2 is 5600. Printed addresses are wire addresses. This file lists controller 1 (0..29) and its group 1 (100..137).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)?

Start with HR 0 CC communication error (Controller communication error); HR 100 Group on/off (Group on/off); HR 101 Group operation mode (Group mode); HR 102 Group fan speed (Group fan speed); HR 104 Group temperature setpoint (Group setpoint (x10)); HR 105 Group ambient temperature (Group room temperature (x10)); HR 109 Group error status (Group error status); HR 110 Group error code (Group error code).

How do I enable Modbus control of the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)?

The gateway must be configured with Intesis MAPS (City Multi project, Modbus selected) and the project sent to it; the manual points to the Signals tab of the MAPS configuration guide for the address formulas.

Where is the official Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus) Modbus documentation?

The source is 700 Series Air Gateway - IN770AIR***O000, Mitsubishi Electric City Multi to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual (User Manual Version 1.0.19), revision 2026-03-16, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770mitxxxo000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: 700 Series Air Gateway - IN770AIR***O000, Mitsubishi Electric City Multi to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · User Manual Version 1.0.19 · rev. 2026-03-16. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.