Easy Modbus
  1. Home
  2. Modbus register maps
  3. Intesis (HMS Networks)
  4. INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus register map

Updated 19 November 2026

Short answer

Multi-unit Modbus server on the LG PI485 bus. Each configured indoor unit (AC, ventilation, DX kit or air-to-water) gets a 100-register block with control, temperatures, status and a 32-bit energy counter; registers 0..18 send commands to all units. Modbus RTU and Modbus TCP run together.

This page lists 46 Modbus registers for the Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Equipment type
VRF / split AC gateway
Registers
46 (31 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF
Source document
Intesis Modbus - LG VRF User Manual · User Manual r1.0 EN · rev. 2020-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)

Integration in brief

Add the units in Intesis MAPS, send the project, then poll each IU x 100 block. Write on/off, mode, fan and setpoint (tenths) per unit or use registers 0..18 for building-wide commands.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100IU on/offINT16On/offRead/write
HR 101IU operation modeINT16ModeRead/write
HR 102IU fan speedINT16Fan speedRead/write
HR 104IU temperature setpointINT16Setpoint (x10)Read/write
HR 105IU ambient temperatureINT16Room temperature (x10)Read
HR 108IU unit error codeINT16Error codeRead
HR 128IU communication errorINT16Communication errorRead
HR 129Accumulated power consumptionUINT32 ABCDEnergy counter (UINT32)Read

Enable Modbus control & writes

Units must be configured in MAPS; their index there decides the register block.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

46 of 46 shown
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0On AC/DX/AWHP (all units)INT16Write1 = Switch all on
HR1Off AC/DX/AWHP (all units)INT16Write1 = Switch all off
HR2Auto mode AC/DX/AWHP (all units)INT16Write1 = Set Auto
HR3Heat mode AC/DX/AWHP (all units)INT16Write1 = Set Heat
HR4Dry mode AC/DX/AWHP (all units)INT16Write1 = Set Dry
HR5Fan mode AC/DX/AWHP (all units)INT16Write1 = Set Fan
HR6Cool mode AC/DX/AWHP (all units)INT16Write1 = Set Cool
HR9Normal mode VENT/DX (all units)INT16Write1 = Set normal mode
HR10Heat exchange mode VENT/DX (all units)INT16Write1 = Set heat-exchange mode
HR11Auto mode VENT/DX (all units)INT16Write1 = Set Auto mode
HR12Fan speed Auto (all units)INT16Write1 = Set fan Auto
HR13Fan speed Low (all units)INT16Write1 = Set fan Low
HR14Fan speed Med (all units)INT16Write1 = Set fan Med
HR15Fan speed High (all units)INT16Write1 = Set fan High
HR16Vane swing on (all units)INT16Write1 = Swing on
HR17Vane swing off (all units)INT16Write1 = Swing off
HR18Temperature setpoint (all units)Tenths of a degree °C. Cool 19..30, Heat 17..30.INT16× 0.1°CWrite
HR100doc (IU*100 + 0)IU on/offUnit index 1 shown; see notes.INT16Read/write0 = Off; 1 = On
HR101doc (IU*100 + 1)IU operation modeAC units: all five modes. DX and AWHP units: 0 Auto, 1 Heat, 4 Cool only.INT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR102doc (IU*100 + 2)IU fan speedINT16Read/write0 = Auto; 1 = Low; 2 = Mid; 3 = High
HR103doc (IU*100 + 3)IU vane swingINT16Read/write0 = Swing off; 1 = Swing on
HR104doc (IU*100 + 4)IU temperature setpointTenths of a degree (°C or °F per gateway setting).INT16× 0.1°CRead/write
HR105doc (IU*100 + 5)IU ambient temperatureTenths of a degree; -10..50 °C.INT16× 0.1°CRead
HR106doc (IU*100 + 6)IU remote control lockINT16Read/write0 = Lock disabled; 1 = Lock enabled
HR107doc (IU*100 + 7)IU unit errorINT16Read0 = No error; 1 = Error
HR108doc (IU*100 + 8)IU unit error code0 = no error, other = LG error code.INT16Read
HR109doc (IU*100 + 9)Ventilation on/offINT16Read/write0 = Off; 1 = On
HR110doc (IU*100 + 10)Ventilation operation modeINT16Read/write0 = Normal; 1 = Heat exchange; 4 = Auto
HR111doc (IU*100 + 11)Filter alarmINT16Read0 = Normal; 1 = Alarm
HR112doc (IU*100 + 12)Supply air temperatureTenths of a degree; -10..50 °C.INT16× 0.1°CRead
HR113doc (IU*100 + 13)Outdoor temperatureTenths of a degree; -10..50 °C.INT16× 0.1°CRead
HR114doc (IU*100 + 14)HeaterINT16Read/write0 = Off; 1 = On
HR115doc (IU*100 + 15)Power savingINT16Read/write0 = Off; 1 = On
HR116doc (IU*100 + 16)RapidityINT16Read/write0 = Off; 1 = On
HR118doc (IU*100 + 18)A2W setpoint modeINT16Read0 = Air; 1 = Water
HR119doc (IU*100 + 19)A2W setpointTenths of a degree. Air 18..30 °C, water 6..80 °C.INT16× 0.1°CRead/write
HR120doc (IU*100 + 20)Hot water on/offINT16Read/write0 = Off; 1 = On
HR121doc (IU*100 + 21)Hot water onlyINT16Read0 = Off; 1 = On
HR122doc (IU*100 + 22)Hot water setpointTenths of a degree; 30..80 °C.INT16× 0.1°CRead/write
HR123doc (IU*100 + 23)Water inlet temperatureTenths of a degree.INT16× 0.1°CRead
HR124doc (IU*100 + 24)Water discharge temperatureTenths of a degree.INT16× 0.1°CRead
HR125doc (IU*100 + 25)Water tank temperatureTenths of a degree.INT16× 0.1°CRead
HR126doc (IU*100 + 26)Water solar temperatureTenths of a degree.INT16× 0.1°CRead
HR127doc (IU*100 + 27)Unit typeINT16Read0 = Not defined; 1 = AC; 2 = VENT; 3 = DX; 4 = AWHP
HR128doc (IU*100 + 28)IU communication errorINT16Read0 = No error; 1 = Error
HR129doc (IU*100 + 29)Accumulated power consumption32-bit unsigned, MSB first; 0..9999990 Wh.UINT32ABCDWhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)

What Modbus registers does the Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) have?

This map lists 46 registers: 46 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states formula results are link-layer addresses with the first register at 0. Indoor unit index IU (1..64, from the MAPS Units Configuration tab) uses IU x 100 + offset. This file lists IU = 1 (100..130).

What byte order does the Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)?

Start with HR 100 IU on/off (On/off); HR 101 IU operation mode (Mode); HR 102 IU fan speed (Fan speed); HR 104 IU temperature setpoint (Setpoint (x10)); HR 105 IU ambient temperature (Room temperature (x10)); HR 108 IU unit error code (Error code); HR 128 IU communication error (Communication error); HR 129 Accumulated power consumption (Energy counter (UINT32)).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)?

Units must be configured in MAPS; their index there decides the register block.

Where is the official Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus documentation?

The source is Intesis Modbus - LG VRF User Manual (User Manual r1.0 EN), revision 2020-04, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbslgexxxo000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Intesis Modbus - LG VRF User Manual · User Manual r1.0 EN · rev. 2020-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.