Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus register map
Updated 17 November 2026
Small Modbus RTU slave that joins a Daikin P1/P2 remote-controller bus and controls up to 16 indoor units as one group. Holding registers carry setpoint, fan, mode, louvre and on/off plus keypad lock modes and limits; input registers return group and per-unit temperatures, faults, filter and defrost state.
This page lists 37 Modbus registers for the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Realtime Control Systems’s own free documentation (linked below) and checked against it.
- Manufacturer
- Realtime Control Systems
- Model
- RTD-NET Modbus interface for Daikin VRV / Sky Air
- Equipment type
- VRF / split AC gateway
- Registers
- 37 (18 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- RTD-NET, RTD-10, Daikin RTD-NET
- Source document
- RTD-NET Installation Instructions · 18870-1.06.03
Integration notes: Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
Set the slave address on SW1, wire DB/DA/GND, then write H0001-H0005 for setpoint, fan, mode, louvre and on/off and poll I0020-I0035 for group status. Use the update registers to decide whether the wall controller stays usable.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 5 | OnOff | UINT16 | Group on/off | Read/write |
| HR 3 | Mode | UINT16 | Mode | Read/write |
| HR 1 | Setpoint | UINT16 | Setpoint | Read/write |
| HR 2 | Fanspeed | UINT16 | Fan speed | Read/write |
| IR 23 | Return Air Average | INT16 | Average return air | Read |
| IR 21 | Is Fault (group) | UINT16 | Any unit faulted | Read |
| IR 22 | Fault Code (group) | UINT16 | Fault code | Read |
| IR 20 | Unit Count | UINT16 | Units found | Read |
Enable Modbus control & writes
No enable step: holding-register writes act on the group straight away. The update registers (H0010-H0015) choose Last Touch (default), Central (locks keypad buttons), Local or On Change behaviour.
Communication loss & watchdog
Optional, set by a SW1 DIP switch: if no holding-register write arrives for 120 s all units are switched on with their current settings, and remote controllers are either unlocked or left as they are depending on the switch.
Byte order & addressing
- Temperatures above 32767 are negative: subtract 65536, then divide by 100.
- In Last Touch mode a master that rewrites the same value every scan overrides the wall controller; use On Change (3) if your master writes cyclically.
- Coil and per-unit thermo readings exist only when the RTD is the P1/P2 MAIN controller.
Network setup
- 9600 baud, no parity, 1 stop bit by default (other rates available on request from the maker).
- Slave address 0..63 on SW1.
- Daisy-chain DB(+), DA(-) and GND; no star or ring wiring; up to 500 m without repeaters.
- Power 15-24 V DC from the indoor unit PCB (X18A/X35A) or a separate supply.
Watch out for
- Infra-red BRC receivers must be set to SUB when the RTD is MAIN.
- If the P1/P2 bus is not found within 1 minute the RTD raises an alarm on its fault output.
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 20doc I0020 | Unit Count | Indoor units found on the P1/P2 bus, 0..16. | UINT16 | Read | ||||
| IR | 21doc I0021 | Is Fault (group) | UINT16 | Read | 0 = No fault; 1 = At least one unit in fault | ||||
| IR | 22doc I0022 | Fault Code (group) | Code of the first faulted unit; two ASCII characters, high byte first. | UINT16 | Read | 0 = Waiting for data; 255 = No fault; 14384 = 80 - group fault, no units found; 14388 = 84 - unit missing | |||
| IR | 23doc I0023 | Return Air Average | Mean of all unit return-air temperatures. | INT16 | × 0.01 | °C | Read | ||
| IR | 24doc I0024 | Filter Alarm (group) | UINT16 | Read | 0 = No alarm; 1 = At least one unit with filter alarm | ||||
| IR | 25doc I0025 | Return Air Min | INT16 | × 0.01 | °C | Read | |||
| IR | 26doc I0026 | Return Air Max | INT16 | × 0.01 | °C | Read | |||
| IR | 30doc I0030 | Thermo On (group) | Summary of what the group is doing. | UINT16 | Read | 0 = Idle/Fan; 1 = Heating; 2 = Cooling; 3 = Heat and Cool | |||
| IR | 35doc I0035 | Defrost | Also set during pressure equalisation and hot start. | UINT16 | Read | 0 = No defrost; 1 = At least one unit in defrost | |||
| IR | 50doc I0050 | RC Temperature | Remote controller sensor; only with one indoor unit and RC as MAIN. | INT16 | × 0.01 | °C | Read | ||
| IR | 51doc I0051 | RC Operation Mode | UINT16 | Read | 0 = Idle/Fan; 1 = Heating; 2 = Cooling; 3 = Heat and Cool | ||||
| IR | 120doc 0120 | Unit 1 Unit Exists | Unit n: register n*100+20. | UINT16 | Read | 0 = No unit found; 1 = Unit found | |||
| IR | 121doc 0121 | Unit 1 Is Fault | UINT16 | Read | 0 = No unit fault; 1 = Unit in fault | ||||
| IR | 122doc 0122 | Unit 1 Fault Code | Two ASCII characters, high byte first; 255 = no fault. | UINT16 | Read | 255 = No fault | |||
| IR | 123doc 0123 | Unit 1 Return Air Temperature | INT16 | × 0.01 | °C | Read | |||
| IR | 124doc 0124 | Unit 1 Filter Alarm | UINT16 | Read | 0 = No alarm; 1 = Filter alarm | ||||
| IR | 130doc 0130 | Unit 1 Thermo On | Only when the RTD runs as P1/P2 MAIN. | UINT16 | Read | 0 = Idle/Fan; 1 = Heating; 2 = Cooling | |||
| IR | 131doc 0131 | Unit 1 Coil In Temperature | Only when the RTD runs as P1/P2 MAIN. | INT16 | × 0.01 | °C | Read | ||
| IR | 132doc 0132 | Unit 1 Coil Out Temperature | Only when the RTD runs as P1/P2 MAIN. | INT16 | × 0.01 | °C | Read | ||
| HR | 1doc H0001 | Setpoint | Group setpoint, whole degrees 16..32. | UINT16 | °C | Read/write | |||
| HR | 2doc H0002 | Fanspeed | High2 is HighHigh only where that speed is enabled. | UINT16 | Read/write | 1 = Low; 2 = High1; 3 = High2 | |||
| HR | 3doc H0003 | Mode | UINT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Fan; 3 = Cool; 4 = Dry | ||||
| HR | 4doc H0004 | Louvre | UINT16 | Read/write | 1 = Swing; 2 = 0 degrees; 3 = 20 degrees; 4 = 45 degrees; 5 = 70 degrees; 6 = 90 degrees | ||||
| HR | 5doc H0005 | OnOff | Also switches VAM/VKM ventilation units. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 10doc H0010 | Global Update | Writes the same update mode to all update registers. | UINT16 | Read/write | 0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes) | |||
| HR | 11doc H0011 | Setpoint Update | UINT16 | Read/write | 0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes) | ||||
| HR | 12doc H0012 | Fanspeed Update | UINT16 | Read/write | 0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes) | ||||
| HR | 13doc H0013 | Mode Update | UINT16 | Read/write | 0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes) | ||||
| HR | 14doc H0014 | Louvre Update | UINT16 | Read/write | 0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes) | ||||
| HR | 15doc H0015 | OnOff Update | UINT16 | Read/write | 0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes) | ||||
| HR | 20doc H0020 | Setpoint Min | Lowest setpoint allowed locally, 16..32; 0 = no limit. | UINT16 | °C | Read/write | |||
| HR | 21doc H0021 | Setpoint Max | Highest setpoint allowed locally, 16..32; 0 = no limit. | UINT16 | °C | Read/write | |||
| HR | 22doc H0022 | Fanspeed Inhibit | Sum of inhibit values of speeds to block; 0 = none. See notes. | UINT16 | Read/write | ||||
| HR | 23doc H0023 | Mode Inhibit | Set bits block those modes; 0 = no inhibit. | BITMAP16 | Read/write | bit 0 = Auto (1); bit 1 = Heat (2); bit 2 = Fan (4); bit 3 = Cool (8); bit 4 = Dry (16) | |||
| HR | 24doc H0024 | Louvre Inhibit | Set bits block those louvre settings; 0 = no inhibit. | BITMAP16 | Read/write | bit 1 = Swing (2); bit 2 = 0 degrees (4); bit 3 = 20 degrees (8); bit 4 = 45 degrees (16); bit 5 = 70 degrees (32); bit 6 = 90 degrees (64) | |||
| HR | 30doc H0030 | VAM Damper Control | UINT16 | Read/write | 0 = Auto; 1 = Cross flow / heat recovery; 2 = Bypass | ||||
| HR | 31doc H0031 | VAM Fanspeed | UINT16 | Read/write | 1 = Low; 2 = High |
Notes on this map
- Every register is 16 bits. Temperatures in input registers are signed and multiplied by 100; setpoint and setpoint limits are whole °C (16..32).
- Only unit 1 of the per-unit block is listed. For unit n add (n-1) x 100 to each address (e.g. unit 2 return air = 223).
- Fanspeed inhibit (H0022) is listed without bit meanings: the manual's fan inhibit table (Low 2, High 13) does not follow the powers-of-two pattern of the mode and louvre tables, so it is not decoded here.
- Fault codes are two ASCII characters packed high byte / low byte (e.g. 16697 = 'A9'). The full Daikin code table is published by Realtime Controls separately.
- Function codes 03, 04, 06 and 16 are supported, 1..10 registers per request.
- The Modbus slave address is set 0..63 on DIP switch SW1.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
What Modbus registers does the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air have?
This map lists 37 registers: 19 input registers, 18 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states register base 0 and writes registers as H0010 / I0010 meaning wire address 10. Per-unit input registers are numbered unit x 100 + offset (unit 1 = 0120..0132, unit 16 = 1620..1632).
What are the minimum Modbus registers to integrate the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air?
Start with HR 5 OnOff (Group on/off); HR 3 Mode (Mode); HR 1 Setpoint (Setpoint); HR 2 Fanspeed (Fan speed); IR 23 Return Air Average (Average return air); IR 21 Is Fault (group) (Any unit faulted); IR 22 Fault Code (group) (Fault code); IR 20 Unit Count (Units found).
How do I enable Modbus control of the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air?
No enable step: holding-register writes act on the group straight away. The update registers (H0010-H0015) choose Last Touch (default), Central (locks keypad buttons), Local or On Change behaviour.
What happens when the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air loses Modbus communication?
Optional, set by a SW1 DIP switch: if no holding-register write arrives for 120 s all units are switched on with their current settings, and remote controllers are either unlocked or left as they are depending on the switch.
Where is the official Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus documentation?
The source is RTD-NET Installation Instructions (18870-1.06.03), published free by Realtime Control Systems at https://www.daikin.eu/content/dam/document-library/installation-manuals/ctrl/RTD-NET%20installation%20instructions_18870-1.06%20EN_Installation%20manuals_English.pdf.
More Realtime Control Systems Modbus register maps
- Heat pump Modbus interface
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
RTD-LT/CA on the P1/P2 bus of Daikin Altherma Split LT CA hydroboxes (heating only and heating/cooling), with an EKRUCAL1 as main controller; all modes except Sequencer. Instructions 22570-2.09.12.
Also known as: RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA - VRF / split AC gateway
Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners
RTD-RA plugged into the S21 port of a Daikin room air conditioner (split) indoor unit, installation instructions 21070-1.07.04.
Also known as: RTD-RA, Daikin RTD-RA - Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W
Other ac & vrf gateways register maps
- Heat pump (via ISG Modbus TCP gateway)
Stiebel Eltron Heat pumps with WPM controller via ISG Modbus TCP/IP (WPMsystem, WPM 3, WPM 3i)
Stiebel Eltron heat pumps run by a WPMsystem, WPM 3 or WPM 3i manager, reached through an ISG web (229336) or ISG plus (233493) with the Modbus TCP/IP software extension.
Also known as: ISG web Modbus TCP/IP, ISG plus Modbus TCP/IP, WPMsystem, WPM 3, WPM 3i - VRF / split AC gateway
Airzone Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners
Airzone Aidoo Pro units configured for Modbus output and connected to a direct-expansion AC unit; register table 'Registers for Direct Expansion units' of the Aidoo - Modbus integration manual (v. 201). The air-to-water table in the same manual is not covered.
Also known as: Aidoo Pro, Aidoo Pro Modbus, Airzone Aidoo Modbus - VRF / split AC gateway
Fujitsu General UTY-VMSX Modbus converter (one indoor unit)
Fujitsu General UTY-VMSX Modbus RTU converter, one per indoor unit, per interface specification part no. 9708438047-05.
Also known as: UTY-VMSX - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi
All ac & vrf gateways Modbus register maps →
Source: RTD-NET Installation Instructions · 18870-1.06.03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.