Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus register map

Updated 17 November 2026

Short answer

Small Modbus RTU slave that joins a Daikin P1/P2 remote-controller bus and controls up to 16 indoor units as one group. Holding registers carry setpoint, fan, mode, louvre and on/off plus keypad lock modes and limits; input registers return group and per-unit temperatures, faults, filter and defrost state.

This page lists 37 Modbus registers for the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Realtime Control Systems’s own free documentation (linked below) and checked against it.

Manufacturer
Realtime Control Systems
Model
RTD-NET Modbus interface for Daikin VRV / Sky Air
Equipment type
VRF / split AC gateway
Registers
37 (18 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
RTD-NET, RTD-10, Daikin RTD-NET
Source document
RTD-NET Installation Instructions · 18870-1.06.03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air

Integration in brief

Set the slave address on SW1, wire DB/DA/GND, then write H0001-H0005 for setpoint, fan, mode, louvre and on/off and poll I0020-I0035 for group status. Use the update registers to decide whether the wall controller stays usable.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 5OnOffUINT16Group on/offRead/write
HR 3ModeUINT16ModeRead/write
HR 1SetpointUINT16SetpointRead/write
HR 2FanspeedUINT16Fan speedRead/write
IR 23Return Air AverageINT16Average return airRead
IR 21Is Fault (group)UINT16Any unit faultedRead
IR 22Fault Code (group)UINT16Fault codeRead
IR 20Unit CountUINT16Units foundRead

Enable Modbus control & writes

No enable step: holding-register writes act on the group straight away. The update registers (H0010-H0015) choose Last Touch (default), Central (locks keypad buttons), Local or On Change behaviour.

Communication loss & watchdog

Optional, set by a SW1 DIP switch: if no holding-register write arrives for 120 s all units are switched on with their current settings, and remote controllers are either unlocked or left as they are depending on the switch.

Byte order & addressing

Network setup

Watch out for

Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

37 of 37 shown
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR20doc I0020Unit CountIndoor units found on the P1/P2 bus, 0..16.UINT16Read
IR21doc I0021Is Fault (group)UINT16Read0 = No fault; 1 = At least one unit in fault
IR22doc I0022Fault Code (group)Code of the first faulted unit; two ASCII characters, high byte first.UINT16Read0 = Waiting for data; 255 = No fault; 14384 = 80 - group fault, no units found; 14388 = 84 - unit missing
IR23doc I0023Return Air AverageMean of all unit return-air temperatures.INT16× 0.01°CRead
IR24doc I0024Filter Alarm (group)UINT16Read0 = No alarm; 1 = At least one unit with filter alarm
IR25doc I0025Return Air MinINT16× 0.01°CRead
IR26doc I0026Return Air MaxINT16× 0.01°CRead
IR30doc I0030Thermo On (group)Summary of what the group is doing.UINT16Read0 = Idle/Fan; 1 = Heating; 2 = Cooling; 3 = Heat and Cool
IR35doc I0035DefrostAlso set during pressure equalisation and hot start.UINT16Read0 = No defrost; 1 = At least one unit in defrost
IR50doc I0050RC TemperatureRemote controller sensor; only with one indoor unit and RC as MAIN.INT16× 0.01°CRead
IR51doc I0051RC Operation ModeUINT16Read0 = Idle/Fan; 1 = Heating; 2 = Cooling; 3 = Heat and Cool
IR120doc 0120Unit 1 Unit ExistsUnit n: register n*100+20.UINT16Read0 = No unit found; 1 = Unit found
IR121doc 0121Unit 1 Is FaultUINT16Read0 = No unit fault; 1 = Unit in fault
IR122doc 0122Unit 1 Fault CodeTwo ASCII characters, high byte first; 255 = no fault.UINT16Read255 = No fault
IR123doc 0123Unit 1 Return Air TemperatureINT16× 0.01°CRead
IR124doc 0124Unit 1 Filter AlarmUINT16Read0 = No alarm; 1 = Filter alarm
IR130doc 0130Unit 1 Thermo OnOnly when the RTD runs as P1/P2 MAIN.UINT16Read0 = Idle/Fan; 1 = Heating; 2 = Cooling
IR131doc 0131Unit 1 Coil In TemperatureOnly when the RTD runs as P1/P2 MAIN.INT16× 0.01°CRead
IR132doc 0132Unit 1 Coil Out TemperatureOnly when the RTD runs as P1/P2 MAIN.INT16× 0.01°CRead
HR1doc H0001SetpointGroup setpoint, whole degrees 16..32.UINT16°CRead/write
HR2doc H0002FanspeedHigh2 is HighHigh only where that speed is enabled.UINT16Read/write1 = Low; 2 = High1; 3 = High2
HR3doc H0003ModeUINT16Read/write0 = Auto; 1 = Heat; 2 = Fan; 3 = Cool; 4 = Dry
HR4doc H0004LouvreUINT16Read/write1 = Swing; 2 = 0 degrees; 3 = 20 degrees; 4 = 45 degrees; 5 = 70 degrees; 6 = 90 degrees
HR5doc H0005OnOffAlso switches VAM/VKM ventilation units.UINT16Read/write0 = Off; 1 = On
HR10doc H0010Global UpdateWrites the same update mode to all update registers.UINT16Read/write0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes)
HR11doc H0011Setpoint UpdateUINT16Read/write0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes)
HR12doc H0012Fanspeed UpdateUINT16Read/write0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes)
HR13doc H0013Mode UpdateUINT16Read/write0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes)
HR14doc H0014Louvre UpdateUINT16Read/write0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes)
HR15doc H0015OnOff UpdateUINT16Read/write0 = Last Touch (keypad unlocked); 1 = Central (keypad locked, value re-sent); 2 = Local (keypad unlocked, writes not sent); 3 = On Change (sent only when value changes)
HR20doc H0020Setpoint MinLowest setpoint allowed locally, 16..32; 0 = no limit.UINT16°CRead/write
HR21doc H0021Setpoint MaxHighest setpoint allowed locally, 16..32; 0 = no limit.UINT16°CRead/write
HR22doc H0022Fanspeed InhibitSum of inhibit values of speeds to block; 0 = none. See notes.UINT16Read/write
HR23doc H0023Mode InhibitSet bits block those modes; 0 = no inhibit.BITMAP16Read/writebit 0 = Auto (1); bit 1 = Heat (2); bit 2 = Fan (4); bit 3 = Cool (8); bit 4 = Dry (16)
HR24doc H0024Louvre InhibitSet bits block those louvre settings; 0 = no inhibit.BITMAP16Read/writebit 1 = Swing (2); bit 2 = 0 degrees (4); bit 3 = 20 degrees (8); bit 4 = 45 degrees (16); bit 5 = 70 degrees (32); bit 6 = 90 degrees (64)
HR30doc H0030VAM Damper ControlUINT16Read/write0 = Auto; 1 = Cross flow / heat recovery; 2 = Bypass
HR31doc H0031VAM FanspeedUINT16Read/write1 = Low; 2 = High

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air

What Modbus registers does the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air have?

This map lists 37 registers: 19 input registers, 18 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states register base 0 and writes registers as H0010 / I0010 meaning wire address 10. Per-unit input registers are numbered unit x 100 + offset (unit 1 = 0120..0132, unit 16 = 1620..1632).

What are the minimum Modbus registers to integrate the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air?

Start with HR 5 OnOff (Group on/off); HR 3 Mode (Mode); HR 1 Setpoint (Setpoint); HR 2 Fanspeed (Fan speed); IR 23 Return Air Average (Average return air); IR 21 Is Fault (group) (Any unit faulted); IR 22 Fault Code (group) (Fault code); IR 20 Unit Count (Units found).

How do I enable Modbus control of the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air?

No enable step: holding-register writes act on the group straight away. The update registers (H0010-H0015) choose Last Touch (default), Central (locks keypad buttons), Local or On Change behaviour.

What happens when the Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air loses Modbus communication?

Optional, set by a SW1 DIP switch: if no holding-register write arrives for 120 s all units are switched on with their current settings, and remote controllers are either unlocked or left as they are depending on the switch.

Where is the official Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air Modbus documentation?

The source is RTD-NET Installation Instructions (18870-1.06.03), published free by Realtime Control Systems at https://www.daikin.eu/content/dam/document-library/installation-manuals/ctrl/RTD-NET%20installation%20instructions_18870-1.06%20EN_Installation%20manuals_English.pdf.

More Realtime Control Systems Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: RTD-NET Installation Instructions · 18870-1.06.03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.