  4. RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers

Heat pump / chiller Modbus interface · Modbus register map

Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus register map

Updated 19 November 2026

Short answer

Small Modbus RTU slave that joins the P1/P2 bus of Daikin Altherma HT hydroboxes and small inverter chillers. Holding registers set leaving-water and room setpoints, mode, on/off, domestic hot water and quiet mode; input registers return group status, temperatures x100, pump and compressor state, run hours and per-PCB data.

This page lists 37 Modbus registers for the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Realtime Control Systems’s own free documentation (linked below) and checked against it.

Manufacturer
Realtime Control Systems
Model
RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
Equipment type
Heat pump / chiller Modbus interface
Registers
37 (12 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
RTD-W, Daikin RTD-W
Source document
Instructions pour l'installation de RTD-W (RTD-W Installation Instructions, French) · 20670-1.07.12 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers

Integration in brief

Set the Modbus address on SW1, wire DB/DA/GND, set H0008 to External or Changeover, then write H0001-H0006 for setpoints, mode and on/off and poll I0020-I0078 for status.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4Space heating/cooling Modbus on/offINT16Space heating/cooling on/offRead/write
HR 3Operating modeINT16Heating or coolingRead/write
HR 1Leaving water setpoint, heatingINT16Heating leaving water setpointRead/write
HR 8Control source for mode and on/offINT16Who may switch the unitRead/write
IR 23Group average leaving water temperatureINT16Leaving water temperature (x100)Read
IR 21Group errorINT16Group errorRead
IR 22Group error codeINT16Error codeRead
IR 20P1P2 PCB countINT16Units found on P1/P2Read

Enable Modbus control & writes

H0008 = 1 (External) or 3 (Changeover, default) lets Modbus switch the unit; 2 (Local) ignores Modbus on/off.

Communication loss & watchdog

If P1/P2 communication is lost for one minute the RTD raises an alarm on the fault relay R2; an RS485 communication timeout is also shown on the LEDs.

Byte order & addressing

Network setup

Watch out for

Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

37 of 37 shown
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR20doc I0020P1P2 PCB countUnits found, 0..16.INT16Read
IR21doc I0021Group errorINT16Read0 = No error; 1 = Error
IR22doc I0022Group error codeRTD ASCII format.INT16Read
IR23doc I0023Group average leaving water temperatureSigned °C x 100.INT16× 0.01°CRead
IR36doc I0036Group error sub-code0..99.INT16Read
IR50doc I0050Remote controller room temperatureSigned °C x 100.INT16× 0.01°CRead
IR70doc I0070Space heating/cooling on/offINT16Read0 = Off; 1 = On
IR71doc I0071Circulation pump runningINT16Read0 = Off; 1 = On
IR72doc I0072Compressor runningINT16Read0 = Off; 1 = On
IR74doc I0074Disinfection operationINT16Read0 = Idle; 1 = Busy
IR75doc I0075Setback operationINT16Read0 = Idle; 1 = Busy
IR76doc I0076Defrost / start-up modeINT16Read0 = Idle; 1 = Busy
IR77doc I0077DHW reheatINT16Read0 = Idle; 1 = Busy
IR78doc I0078DHW storageINT16Read0 = Idle; 1 = Busy
IR80doc I0080 / I0081Accumulated pump run hoursI0080 high word, I0081 low word. Non-volatile.UINT32ABCDhRead
IR122doc I0122PCB 01 error codeRTD ASCII format. Per-PCB block; see notes.INT16Read
IR123doc I0123PCB 01 leaving water temperatureSigned °C x 100.INT16× 0.01°CRead
IR131doc I0131PCB 01 return water temperatureSigned °C x 100.INT16× 0.01°CRead
IR132doc I0132PCB 01 DHW tank temperatureSigned °C x 100. Only if fitted.INT16× 0.01°CRead
IR133doc I0133PCB 01 outdoor temperatureSigned °C x 100.INT16× 0.01°CRead
IR136doc I0136PCB 01 error sub-code0..99.INT16Read
IR144doc I0144PCB 01 system codeASCII character.INT16Read
IR145doc I0145PCB 01 type codeASCII character.INT16Read
IR146doc I0146PCB 01 series codeASCII character.INT16Read
IR147doc I0147PCB 01 capacity code0..251.INT16Read
HR1doc H0001Leaving water setpoint, heatingWhole °C: 25..80 HT hydrobox, 25..50 inverter chiller.INT16°CRead/write
HR2doc H0002Leaving water setpoint, coolingWhole °C: 5..20 HT hydrobox, -10..20 inverter chiller.INT16°CRead/write
HR3doc H0003Operating modeINT16Read/write1 = Heating; 2 = Cooling
HR4doc H0004Space heating/cooling Modbus on/offINT16Read/write0 = Off; 1 = On
HR5doc H0005Room temperature setpointWhole °C, 16..32.INT16°CRead/write
HR6doc H0006DHW reheat Modbus on/offINT16Read/write0 = Off; 1 = On
HR7doc H0007DHW storage startINT16Read/write0 = Inactive; 1 = Start
HR8doc H0008Control source for mode and on/offExternal = Modbus and S inputs only; Local = remote controller only.INT16Read/write1 = External; 2 = Local; 3 = Changeover (default)
HR9doc H0009Quiet mode operationINT16Read/write0 = Disable; 1 = Enable
HR10doc H0010Weather-dependent setpoint operationINT16Read/write0 = Disable; 1 = Enable
HR11doc H0011Weather-dependent leaving water setpoint offset-5..+5 °C.INT16°CRead/write
HR12doc H0012Pump run-hour counter resetWrite 55555 to reset (raw value above the signed 16-bit range).UINT16Write55555 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers

What Modbus registers does the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers have?

This map lists 37 registers: 25 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states register base 0 and writes H0010 / I0010 for holding / input register 10, so the number after H or I is the wire address. Per-PCB input registers are numbered xx00..xx99 with xx = PCB 01..16; this file lists PCB 01 (I0122..I0147).

What byte order does the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers?

Start with HR 4 Space heating/cooling Modbus on/off (Space heating/cooling on/off); HR 3 Operating mode (Heating or cooling); HR 1 Leaving water setpoint, heating (Heating leaving water setpoint); HR 8 Control source for mode and on/off (Who may switch the unit); IR 23 Group average leaving water temperature (Leaving water temperature (x100)); IR 21 Group error (Group error); IR 22 Group error code (Error code); IR 20 P1P2 PCB count (Units found on P1/P2).

How do I enable Modbus control of the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers?

H0008 = 1 (External) or 3 (Changeover, default) lets Modbus switch the unit; 2 (Local) ignores Modbus on/off.

What happens when the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers loses Modbus communication?

If P1/P2 communication is lost for one minute the RTD raises an alarm on the fault relay R2; an RS485 communication timeout is also shown on the LEDs.

Where is the official Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus documentation?

The source is Instructions pour l'installation de RTD-W (RTD-W Installation Instructions, French) (20670-1.07.12). Realtime Control Systems doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/sonepar-fr/raw/upload/s--ayUiJ1AJ--/v1/documents/121/RTD-W_Installation_Instructions_20670-1.07_FR.pdf. It may be an older revision, so check it against the live unit.

More Realtime Control Systems Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Instructions pour l'installation de RTD-W (RTD-W Installation Instructions, French) · 20670-1.07.12 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.