- RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
Heat pump / chiller Modbus interface · Modbus register map
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus register map
Updated 19 November 2026
Small Modbus RTU slave that joins the P1/P2 bus of Daikin Altherma HT hydroboxes and small inverter chillers. Holding registers set leaving-water and room setpoints, mode, on/off, domestic hot water and quiet mode; input registers return group status, temperatures x100, pump and compressor state, run hours and per-PCB data.
This page lists 37 Modbus registers for the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Realtime Control Systems’s own free documentation (linked below) and checked against it.
- Manufacturer
- Realtime Control Systems
- Model
- RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
- Equipment type
- Heat pump / chiller Modbus interface
- Registers
- 37 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RTD-W, Daikin RTD-W
Integration notes: Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
Set the Modbus address on SW1, wire DB/DA/GND, set H0008 to External or Changeover, then write H0001-H0006 for setpoints, mode and on/off and poll I0020-I0078 for status.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 4 | Space heating/cooling Modbus on/off | INT16 | Space heating/cooling on/off | Read/write |
| HR 3 | Operating mode | INT16 | Heating or cooling | Read/write |
| HR 1 | Leaving water setpoint, heating | INT16 | Heating leaving water setpoint | Read/write |
| HR 8 | Control source for mode and on/off | INT16 | Who may switch the unit | Read/write |
| IR 23 | Group average leaving water temperature | INT16 | Leaving water temperature (x100) | Read |
| IR 21 | Group error | INT16 | Group error | Read |
| IR 22 | Group error code | INT16 | Error code | Read |
| IR 20 | P1P2 PCB count | INT16 | Units found on P1/P2 | Read |
Enable Modbus control & writes
H0008 = 1 (External) or 3 (Changeover, default) lets Modbus switch the unit; 2 (Local) ignores Modbus on/off.
Communication loss & watchdog
If P1/P2 communication is lost for one minute the RTD raises an alarm on the fault relay R2; an RS485 communication timeout is also shown on the LEDs.
Byte order & addressing
- Temperatures in input registers are x100 and signed; setpoints in holding registers are whole °C.
- Read at most 10 registers per request.
Network setup
- RS485 D-Bus: DB(+), DA(-) and common GND, daisy chain only, up to 500 m without repeaters.
- Factory serial settings 9600 baud, no parity, 1 stop bit.
- Power 15..24 V DC, e.g. from X9A on the A3P board.
Watch out for
- The RTD-W works as a SUB controller: a BRC21 must be configured as MAIN on the P1/P2 bus.
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 20doc I0020 | P1P2 PCB count | Units found, 0..16. | INT16 | Read | ||||
| IR | 21doc I0021 | Group error | INT16 | Read | 0 = No error; 1 = Error | ||||
| IR | 22doc I0022 | Group error code | RTD ASCII format. | INT16 | Read | ||||
| IR | 23doc I0023 | Group average leaving water temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 36doc I0036 | Group error sub-code | 0..99. | INT16 | Read | ||||
| IR | 50doc I0050 | Remote controller room temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 70doc I0070 | Space heating/cooling on/off | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 71doc I0071 | Circulation pump running | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 72doc I0072 | Compressor running | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 74doc I0074 | Disinfection operation | INT16 | Read | 0 = Idle; 1 = Busy | ||||
| IR | 75doc I0075 | Setback operation | INT16 | Read | 0 = Idle; 1 = Busy | ||||
| IR | 76doc I0076 | Defrost / start-up mode | INT16 | Read | 0 = Idle; 1 = Busy | ||||
| IR | 77doc I0077 | DHW reheat | INT16 | Read | 0 = Idle; 1 = Busy | ||||
| IR | 78doc I0078 | DHW storage | INT16 | Read | 0 = Idle; 1 = Busy | ||||
| IR | 80doc I0080 / I0081 | Accumulated pump run hours | I0080 high word, I0081 low word. Non-volatile. | UINT32 | ABCD | h | Read | ||
| IR | 122doc I0122 | PCB 01 error code | RTD ASCII format. Per-PCB block; see notes. | INT16 | Read | ||||
| IR | 123doc I0123 | PCB 01 leaving water temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 131doc I0131 | PCB 01 return water temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 132doc I0132 | PCB 01 DHW tank temperature | Signed °C x 100. Only if fitted. | INT16 | × 0.01 | °C | Read | ||
| IR | 133doc I0133 | PCB 01 outdoor temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 136doc I0136 | PCB 01 error sub-code | 0..99. | INT16 | Read | ||||
| IR | 144doc I0144 | PCB 01 system code | ASCII character. | INT16 | Read | ||||
| IR | 145doc I0145 | PCB 01 type code | ASCII character. | INT16 | Read | ||||
| IR | 146doc I0146 | PCB 01 series code | ASCII character. | INT16 | Read | ||||
| IR | 147doc I0147 | PCB 01 capacity code | 0..251. | INT16 | Read | ||||
| HR | 1doc H0001 | Leaving water setpoint, heating | Whole °C: 25..80 HT hydrobox, 25..50 inverter chiller. | INT16 | °C | Read/write | |||
| HR | 2doc H0002 | Leaving water setpoint, cooling | Whole °C: 5..20 HT hydrobox, -10..20 inverter chiller. | INT16 | °C | Read/write | |||
| HR | 3doc H0003 | Operating mode | INT16 | Read/write | 1 = Heating; 2 = Cooling | ||||
| HR | 4doc H0004 | Space heating/cooling Modbus on/off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 5doc H0005 | Room temperature setpoint | Whole °C, 16..32. | INT16 | °C | Read/write | |||
| HR | 6doc H0006 | DHW reheat Modbus on/off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 7doc H0007 | DHW storage start | INT16 | Read/write | 0 = Inactive; 1 = Start | ||||
| HR | 8doc H0008 | Control source for mode and on/off | External = Modbus and S inputs only; Local = remote controller only. | INT16 | Read/write | 1 = External; 2 = Local; 3 = Changeover (default) | |||
| HR | 9doc H0009 | Quiet mode operation | INT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 10doc H0010 | Weather-dependent setpoint operation | INT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 11doc H0011 | Weather-dependent leaving water setpoint offset | -5..+5 °C. | INT16 | °C | Read/write | |||
| HR | 12doc H0012 | Pump run-hour counter reset | Write 55555 to reset (raw value above the signed 16-bit range). | UINT16 | Write | 55555 = Reset |
Notes on this map
- The source is the French edition of the Realtime Control Systems installation instructions, from a Sonepar (distributor) file host. The maker's own site (realtime-controls.co.uk) was offline and no Daikin-hosted copy was found, so the link is marked unofficial.
- All values are 16-bit unless stated. Temperatures marked 'x100' are signed: raw 2150 = 21.50 °C, raw 65036 = -5.00 °C. Holding-register setpoints are printed in whole °C with no x100 marking and are listed at scale 1.
- Fault codes are in the 'RTD ASCII' format described in the RTD-NET instructions (two characters packed high byte / low byte).
- Supported function codes: 03 and 04 (1..10 registers), 06, and 16 (1..10 registers).
- Only PCB 01 of the per-PCB block is listed. For PCB xx add (xx-1) x 100 (PCB 02 leaving water = I0223).
- The pump run-hour counter is 32-bit unsigned: the manual's data-type table says R holds the high word and R+1 the low word.
- Control fields that the connected unit does not support read 32767 and ignore writes.
- Sensor-input mirror registers I10001..I10006 are left out: their printed range (0..1) and values (0 / 100) disagree.
- The Modbus address is 0..63 on SW1.3..SW1.8. Baud and parity can be changed from the defaults if needed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
What Modbus registers does the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers have?
This map lists 37 registers: 25 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states register base 0 and writes H0010 / I0010 for holding / input register 10, so the number after H or I is the wire address. Per-PCB input registers are numbered xx00..xx99 with xx = PCB 01..16; this file lists PCB 01 (I0122..I0147).
What byte order does the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers?
Start with HR 4 Space heating/cooling Modbus on/off (Space heating/cooling on/off); HR 3 Operating mode (Heating or cooling); HR 1 Leaving water setpoint, heating (Heating leaving water setpoint); HR 8 Control source for mode and on/off (Who may switch the unit); IR 23 Group average leaving water temperature (Leaving water temperature (x100)); IR 21 Group error (Group error); IR 22 Group error code (Error code); IR 20 P1P2 PCB count (Units found on P1/P2).
How do I enable Modbus control of the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers?
H0008 = 1 (External) or 3 (Changeover, default) lets Modbus switch the unit; 2 (Local) ignores Modbus on/off.
What happens when the Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers loses Modbus communication?
If P1/P2 communication is lost for one minute the RTD raises an alarm on the fault relay R2; an RS485 communication timeout is also shown on the LEDs.
Where is the official Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers Modbus documentation?
The source is Instructions pour l'installation de RTD-W (RTD-W Installation Instructions, French) (20670-1.07.12). Realtime Control Systems doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/sonepar-fr/raw/upload/s--ayUiJ1AJ--/v1/documents/121/RTD-W_Installation_Instructions_20670-1.07_FR.pdf. It may be an older revision, so check it against the live unit.
More Realtime Control Systems Modbus register maps
- Heat pump Modbus interface
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
RTD-LT/CA on the P1/P2 bus of Daikin Altherma Split LT CA hydroboxes (heating only and heating/cooling), with an EKRUCAL1 as main controller; all modes except Sequencer. Instructions 22570-2.09.12.
Also known as: RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA - VRF / split AC gateway
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
RTD-NET on the Daikin P1/P2 bus (VRV, Sky Air, VAM/VKM), up to 16 indoor units as one group; RTD-10 with the same firmware uses the same layout.
Also known as: RTD-NET, RTD-10, Daikin RTD-NET - VRF / split AC gateway
Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners
RTD-RA plugged into the S21 port of a Daikin room air conditioner (split) indoor unit, installation instructions 21070-1.07.04.
Also known as: RTD-RA, Daikin RTD-RA
Other pumps register maps
- Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Heat pump
Acond Acond heat pumps (Modbus TCP interface v2.35)
Acond air-to-water and brine heat pumps with the ModbusTCP function activated, interface description version 2.35 dated 01.12.2022.
Also known as: Acond PRO series, Acond ModbusTCP v2.35 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Pump controller (wastewater lift station)
Grundfos Dedicated Controls (CU 361 / CU 362) with CIM 200 / CIM 260 / CIM 500 (Modbus)
Grundfos Dedicated Controls wastewater pit controller (CU 361 / CU 362, up to six pumps and a mixer) with a CIM 200 Modbus RTU, CIM 260 cellular or CIM 500 Modbus TCP module; functional profile 98393520 (2023-03).
Also known as: Dedicated Controls, CU 361, CU 362, CIM 200, CIM 260, CIM 500, 98393520 - Pump (electric fire pump controller)
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
FFL700EP and FFL800EP electric fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800EP), per protocol document I589 GB I 08 22.
Also known as: FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP - Heat pump (air-to-water) Modbus interface
Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
Panasonic CZ-NSMB Modbus PCB fitted inside Panasonic Air-To-Water control boxes; the manual's compatibility list names the A2W M-Series control module WH-CME8 and the Big A2W 20-30 kW outdoor units WH-WXG20/25/30ME8 with control module WH-CME8L (user manual M02412F0). Some registers carry H/J/K/L-series conditions.
Also known as: CZ-NSMB, A2W Modbus PCB, WH-CME8, WH-CME8L, WH-WXG20ME8, WH-WXG25ME8, WH-WXG30ME8, Aquarea M series Modbus, Big A2W Modbus
All pumps Modbus register maps →
Source: Instructions pour l'installation de RTD-W (RTD-W Installation Instructions, French) · 20670-1.07.12 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.