Pump (electric fire pump controller) · Modbus register map

Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus register map

Updated 19 November 2026

Short answer

The FFL700EP and FFL800EP are Lovato controllers for electric fire pumps built to EN 12845. They speak Modbus RTU, ASCII or TCP on the optical port, the built-in RS-485 and, on FFL800EP, EXP1012T/EXP1013T modules. This map covers the supply voltages, currents, active powers and power factors, frequency and asymmetry, working hours, the alarm words, I/O states, the global status word and the save/reset/command registers.

This page lists 43 Modbus registers for the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Lovato Electric
Model
FFL700EP / FFL800EP electric fire pump controllers
Equipment type
Pump (electric fire pump controller)
Registers
43 (4 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
9600 baud, 8N1
TCP port
1001
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP
Source document
FFL700EP - FFL800EP electric fire pump controllers (EN12845) - Modbus protocol · I589 GB I 08 22 · rev. 2022-08-26
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lovato Electric FFL700EP / FFL800EP electric fire pump controllers

Integration in brief

Read the alarm words 2200h-2203h and the global status 2210h for supervision, plus currents, voltages and frequency for motor monitoring. Subtract one from every table address.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 8719Device global statusBITMAP16Global status (mode, pump running, mains failure)Read
IR 8703Alarms A01-A16BITMAP16Alarms A01-A16Read
IR 8704Alarms A17-A32BITMAP16Alarms A17-A32Read
IR 7L1 phase currentUINT32 ABCDL1 currentRead
IR 13L1-L2 voltageUINT32 ABCDL1-L2 voltageRead
IR 57FrequencyUINT32 ABCDFrequencyRead

Enable Modbus control & writes

In SETUP menu M11 (communication) set P11.n.01 node address, .02 baud rate, .03 data format, .04 stop bits and .05 protocol for port n; port 1 is the built-in RS-485.

Byte order & addressing

Network setup

Watch out for

Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

43 of 43 shown
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR1doc 0002hL1 phase voltageUINT32ABCD× 0.01VRead
IR3doc 0004hL2 phase voltageUINT32ABCD× 0.01VRead
IR5doc 0006hL3 phase voltageUINT32ABCD× 0.01VRead
IR7doc 0008hL1 phase currentUINT32ABCD× 0.0001ARead
IR9doc 000AhL2 phase currentUINT32ABCD× 0.0001ARead
IR11doc 000ChL3 phase currentUINT32ABCD× 0.0001ARead
IR13doc 000EhL1-L2 voltageUINT32ABCD× 0.01VRead
IR15doc 0010hL2-L3 voltageUINT32ABCD× 0.01VRead
IR17doc 0012hL3-L1 voltageUINT32ABCD× 0.01VRead
IR19doc 0014hL1 active powerINT32ABCD× 0.1WRead
IR21doc 0016hL2 active powerINT32ABCD× 0.1WRead
IR23doc 0018hL3 active powerINT32ABCD× 0.1WRead
IR37doc 0026hL1 power factorINT32ABCD× 0.0001Read
IR39doc 0028hL2 power factorINT32ABCD× 0.0001Read
IR41doc 002AhL3 power factorINT32ABCD× 0.0001Read
IR43doc 002ChEquivalent phase voltageUINT32ABCD× 0.01VRead
IR45doc 002EhEquivalent currentUINT32ABCD× 0.0001ARead
IR47doc 0030hEquivalent phase-to-phase voltageUINT32ABCD× 0.01VRead
IR49doc 0032hEquivalent active powerINT32ABCD× 0.1WRead
IR51doc 0034hEquivalent reactive powerINT32ABCD× 0.1varRead
IR53doc 0036hEquivalent apparent powerUINT32ABCD× 0.1VARead
IR55doc 0038hEquivalent power factorINT32ABCD× 0.0001Read
IR57doc 003AhFrequencyUINT32ABCD× 0.001HzRead
IR59doc 003ChPhase-to-phase voltage asymmetryUINT32ABCD× 0.1%Read
IR61doc 003EhPhase-to-neutral voltage asymmetryUINT32ABCD× 0.01%Read
IR63doc 0040hCurrent asymmetryUINT32ABCD× 0.01%Read
IR65doc 0042hMax equivalent currentUINT32ABCD× 0.0001ARead
IR3967doc 0F80hTotal working hoursUINT32ABCDhRead
IR3971doc 0F84hPartial working hoursUINT32ABCDhRead
IR8303doc 2070hFront panel keyboard statusBITMAP16Readbit 0 = RIGHT; bit 1 = LEFT; bit 2 = DOWN; bit 3 = UP; bit 4 = STOP; bit 5 = RESET; bit 7 = ENTER; bit 8 = START
IR8447doc 2100hDigital inputs 1-16BITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14; bit 14 = Input 15; bit 15 = Input 16
IR8510doc 213FhDigital inputs 17-25BITMAP16Readbit 0 = Input 17; bit 1 = Input 18; bit 2 = Input 19; bit 3 = Input 20; bit 4 = Input 21; bit 5 = Input 22; bit 6 = Input 23; bit 7 = Input 24; bit 8 = Input 25
IR8511doc 2140hDigital outputs 1-16BITMAP16Readbit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8; bit 8 = Output 9; bit 9 = Output 10; bit 10 = Output 11; bit 11 = Output 12; bit 12 = Output 13; bit 13 = Output 14; bit 14 = Output 15; bit 15 = Output 16
IR8574doc 217FhDigital outputs 17-20BITMAP16Readbit 0 = Output 17; bit 1 = Output 18; bit 2 = Output 19; bit 3 = Output 20
IR8703doc 2200hAlarms A01-A16BITMAP16Readbit 0 = A01 Low mains voltage; bit 1 = A02 High mains voltage; bit 2 = A03 Low mains frequency; bit 3 = A04 High mains frequency; bit 4 = A05 Mains voltage asymmetry; bit 5 = A06 Phase failure; bit 6 = A07 Incorrect phase sequence; bit 7 = A08 Pump starting failure; bit 8 = A09 Rotor blocked; bit 9 = A10 Dry running; bit 10 = A11 Current too low; bit 11 = A12 Current too high; bit 12 = A13 Unbalanced current; bit 13 = A14 Unexpected current; bit 14 = A15 Wrong CT connection; bit 15 = A16 System error
IR8704doc 2201hAlarms A17-A32BITMAP16Readbit 0 = A17 Low temperature in pump room; bit 1 = A18 High temperature in pump room; bit 2 = A19 Water reserve; bit 3 = A20 Low water tank level; bit 4 = A21 Water tank empty; bit 5 = A22 Low level priming tank; bit 6 = A23 System not in automatic mode; bit 7 = A24 Fire pump running; bit 8 = A25 Fire pump not in pressure; bit 9 = A26 Pump in pressure; bit 10 = A27 Maintenance 1 requested; bit 11 = A28 Maintenance 2 requested; bit 12 = A29 Maintenance 3 requested; bit 13 = A30 Suction valve partially opened; bit 14 = A31 Discharge valve partially opened; bit 15 = A32 Sprinkler in pump room activated
IR8705doc 2202hAlarms A33-UA6BITMAP16Readbit 0 = A33 Max number of jockey pump starts; bit 1 = A34 Jockey pump alarm failure; bit 2 = A35 Jockey pump timeout; bit 3 = A36 Drainage pump alarm failure; bit 4 = A37 Communication error; bit 5 = A38 Pressure input test failed; bit 6 = A39 Test valve opened; bit 7 = A40 Power too low; bit 8 = A41 Power too high; bit 9 = A42 Electric fire pump running; bit 10 = UA1 User alarm 1; bit 11 = UA2 User alarm 2; bit 12 = UA3 User alarm 3; bit 13 = UA4 User alarm 4; bit 14 = UA5 User alarm 5; bit 15 = UA6 User alarm 6
IR8706doc 2203hUser alarms UA7-UA12BITMAP16Readbit 0 = UA7 User alarm 7; bit 1 = UA8 User alarm 8; bit 2 = UA9 User alarm 9; bit 3 = UA10 User alarm 10; bit 4 = UA11 User alarm 11; bit 5 = UA12 User alarm 12
IR8719doc 2210hDevice global statusBITMAP16Readbit 0 = Device in OFF mode; bit 1 = Device in MAN mode; bit 2 = Device in AUT mode; bit 3 = Global alarm; bit 4 = Type A alarm; bit 5 = Type B alarm; bit 6 = Siren alarms; bit 7 = Mains failure; bit 8 = Failure to start; bit 9 = Pump running; bit 10 = Starting request; bit 11 = Automatic test in progress; bit 12 = Clock 100 ms; bit 13 = Stop delay enabled
HR12034doc 2F03hSave / rebootUINT16Write1 = Save to EEPROM; 4 = Reboot; 5 = Save and reboot
HR12038doc 2F07hDevice resetUINT16Write0 = Reset device; 1 = Reset device and save FRAM
HR12271doc 2FF0hCommand menu executionUINT16Write0 = C01 Reset maintenance 1; 1 = C02 Reset maintenance 2; 2 = C03 Reset maintenance 3; 3 = C04 Reset partial hour counter; 4 = C05 Reset generic counters CNTx; 5 = C06 Reset limits LIMx; 6 = C07 Reset total hour counter; 7 = C08 Set pump hours; 8 = C09 Reset start counter; 9 = C10 Reset max/min values; 10 = C11 Reset event list; 11 = C12 Setup to default; 12 = C13 Back up setup; 13 = C14 Restore setup; 14 = C15 Forced I/O; 15 = C16 Reset PLC program
HR20223doc 4F00hRemote variable REM1REM2-REM16 follow at 4F01h-4F0Fh.UINT16Write170 = Set to 1 (AAh); 187 = Set to 0 (BBh)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers

What Modbus registers does the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers have?

This map lists 43 registers: 39 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document states that the address in a request is the table address decreased by one (Modbus standard). Addresses here are the table value minus one.

What byte order does the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers?

Start with IR 8719 Device global status (Global status (mode, pump running, mains failure)); IR 8703 Alarms A01-A16 (Alarms A01-A16); IR 8704 Alarms A17-A32 (Alarms A17-A32); IR 7 L1 phase current (L1 current); IR 13 L1-L2 voltage (L1-L2 voltage); IR 57 Frequency (Frequency).

How do I enable Modbus control of the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers?

In SETUP menu M11 (communication) set P11.n.01 node address, .02 baud rate, .03 data format, .04 stop bits and .05 protocol for port n; port 1 is the built-in RS-485.

Where is the official Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus documentation?

The source is FFL700EP - FFL800EP electric fire pump controllers (EN12845) - Modbus protocol (I589 GB I 08 22), revision 2022-08-26, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/33.%20CONTROLLORI%20ANTINCENDIO/I589IGB08_22.pdf.

More Lovato Electric Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: FFL700EP - FFL800EP electric fire pump controllers (EN12845) - Modbus protocol · I589 GB I 08 22 · rev. 2022-08-26. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.