Pump (electric fire pump controller) · Modbus register map
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus register map
Updated 19 November 2026
The FFL700EP and FFL800EP are Lovato controllers for electric fire pumps built to EN 12845. They speak Modbus RTU, ASCII or TCP on the optical port, the built-in RS-485 and, on FFL800EP, EXP1012T/EXP1013T modules. This map covers the supply voltages, currents, active powers and power factors, frequency and asymmetry, working hours, the alarm words, I/O states, the global status word and the save/reset/command registers.
This page lists 43 Modbus registers for the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lovato Electric
- Model
- FFL700EP / FFL800EP electric fire pump controllers
- Equipment type
- Pump (electric fire pump controller)
- Registers
- 43 (4 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- TCP port
- 1001
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- FFL700EP, FFL800EP, FFL 700 EP, FFL 800 EP
Integration notes: Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
Read the alarm words 2200h-2203h and the global status 2210h for supervision, plus currents, voltages and frequency for motor monitoring. Subtract one from every table address.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 8719 | Device global status | BITMAP16 | Global status (mode, pump running, mains failure) | Read |
| IR 8703 | Alarms A01-A16 | BITMAP16 | Alarms A01-A16 | Read |
| IR 8704 | Alarms A17-A32 | BITMAP16 | Alarms A17-A32 | Read |
| IR 7 | L1 phase current | UINT32 ABCD | L1 current | Read |
| IR 13 | L1-L2 voltage | UINT32 ABCD | L1-L2 voltage | Read |
| IR 57 | Frequency | UINT32 ABCD | Frequency | Read |
Enable Modbus control & writes
In SETUP menu M11 (communication) set P11.n.01 node address, .02 baud rate, .03 data format, .04 stop bits and .05 protocol for port n; port 1 is the built-in RS-485.
Byte order & addressing
- Table addresses are one above the wire address.
- 32-bit values are high word first.
Network setup
- Defaults: node 01, 9600 baud, 8 data bits, no parity, 1 stop bit, Modbus RTU.
- EXP1013T Ethernet module: default IP 192.168.1.1, IP port 1001 (P11.n.06-P11.n.08).
Watch out for
- The document's read example names water temperature at 0F0Ah while Table 2 lists it at 0F0Eh; that register is left out of this map.
- Function 06 writes are accepted only on addresses above 1000h.
Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 1doc 0002h | L1 phase voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 3doc 0004h | L2 phase voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 5doc 0006h | L3 phase voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 7doc 0008h | L1 phase current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 9doc 000Ah | L2 phase current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 11doc 000Ch | L3 phase current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 13doc 000Eh | L1-L2 voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 15doc 0010h | L2-L3 voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 17doc 0012h | L3-L1 voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 19doc 0014h | L1 active power | INT32 | ABCD | × 0.1 | W | Read | ||
| IR | 21doc 0016h | L2 active power | INT32 | ABCD | × 0.1 | W | Read | ||
| IR | 23doc 0018h | L3 active power | INT32 | ABCD | × 0.1 | W | Read | ||
| IR | 37doc 0026h | L1 power factor | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 39doc 0028h | L2 power factor | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 41doc 002Ah | L3 power factor | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 43doc 002Ch | Equivalent phase voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 45doc 002Eh | Equivalent current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 47doc 0030h | Equivalent phase-to-phase voltage | UINT32 | ABCD | × 0.01 | V | Read | ||
| IR | 49doc 0032h | Equivalent active power | INT32 | ABCD | × 0.1 | W | Read | ||
| IR | 51doc 0034h | Equivalent reactive power | INT32 | ABCD | × 0.1 | var | Read | ||
| IR | 53doc 0036h | Equivalent apparent power | UINT32 | ABCD | × 0.1 | VA | Read | ||
| IR | 55doc 0038h | Equivalent power factor | INT32 | ABCD | × 0.0001 | Read | |||
| IR | 57doc 003Ah | Frequency | UINT32 | ABCD | × 0.001 | Hz | Read | ||
| IR | 59doc 003Ch | Phase-to-phase voltage asymmetry | UINT32 | ABCD | × 0.1 | % | Read | ||
| IR | 61doc 003Eh | Phase-to-neutral voltage asymmetry | UINT32 | ABCD | × 0.01 | % | Read | ||
| IR | 63doc 0040h | Current asymmetry | UINT32 | ABCD | × 0.01 | % | Read | ||
| IR | 65doc 0042h | Max equivalent current | UINT32 | ABCD | × 0.0001 | A | Read | ||
| IR | 3967doc 0F80h | Total working hours | UINT32 | ABCD | h | Read | |||
| IR | 3971doc 0F84h | Partial working hours | UINT32 | ABCD | h | Read | |||
| IR | 8303doc 2070h | Front panel keyboard status | BITMAP16 | Read | bit 0 = RIGHT; bit 1 = LEFT; bit 2 = DOWN; bit 3 = UP; bit 4 = STOP; bit 5 = RESET; bit 7 = ENTER; bit 8 = START | ||||
| IR | 8447doc 2100h | Digital inputs 1-16 | BITMAP16 | Read | bit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14; bit 14 = Input 15; bit 15 = Input 16 | ||||
| IR | 8510doc 213Fh | Digital inputs 17-25 | BITMAP16 | Read | bit 0 = Input 17; bit 1 = Input 18; bit 2 = Input 19; bit 3 = Input 20; bit 4 = Input 21; bit 5 = Input 22; bit 6 = Input 23; bit 7 = Input 24; bit 8 = Input 25 | ||||
| IR | 8511doc 2140h | Digital outputs 1-16 | BITMAP16 | Read | bit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8; bit 8 = Output 9; bit 9 = Output 10; bit 10 = Output 11; bit 11 = Output 12; bit 12 = Output 13; bit 13 = Output 14; bit 14 = Output 15; bit 15 = Output 16 | ||||
| IR | 8574doc 217Fh | Digital outputs 17-20 | BITMAP16 | Read | bit 0 = Output 17; bit 1 = Output 18; bit 2 = Output 19; bit 3 = Output 20 | ||||
| IR | 8703doc 2200h | Alarms A01-A16 | BITMAP16 | Read | bit 0 = A01 Low mains voltage; bit 1 = A02 High mains voltage; bit 2 = A03 Low mains frequency; bit 3 = A04 High mains frequency; bit 4 = A05 Mains voltage asymmetry; bit 5 = A06 Phase failure; bit 6 = A07 Incorrect phase sequence; bit 7 = A08 Pump starting failure; bit 8 = A09 Rotor blocked; bit 9 = A10 Dry running; bit 10 = A11 Current too low; bit 11 = A12 Current too high; bit 12 = A13 Unbalanced current; bit 13 = A14 Unexpected current; bit 14 = A15 Wrong CT connection; bit 15 = A16 System error | ||||
| IR | 8704doc 2201h | Alarms A17-A32 | BITMAP16 | Read | bit 0 = A17 Low temperature in pump room; bit 1 = A18 High temperature in pump room; bit 2 = A19 Water reserve; bit 3 = A20 Low water tank level; bit 4 = A21 Water tank empty; bit 5 = A22 Low level priming tank; bit 6 = A23 System not in automatic mode; bit 7 = A24 Fire pump running; bit 8 = A25 Fire pump not in pressure; bit 9 = A26 Pump in pressure; bit 10 = A27 Maintenance 1 requested; bit 11 = A28 Maintenance 2 requested; bit 12 = A29 Maintenance 3 requested; bit 13 = A30 Suction valve partially opened; bit 14 = A31 Discharge valve partially opened; bit 15 = A32 Sprinkler in pump room activated | ||||
| IR | 8705doc 2202h | Alarms A33-UA6 | BITMAP16 | Read | bit 0 = A33 Max number of jockey pump starts; bit 1 = A34 Jockey pump alarm failure; bit 2 = A35 Jockey pump timeout; bit 3 = A36 Drainage pump alarm failure; bit 4 = A37 Communication error; bit 5 = A38 Pressure input test failed; bit 6 = A39 Test valve opened; bit 7 = A40 Power too low; bit 8 = A41 Power too high; bit 9 = A42 Electric fire pump running; bit 10 = UA1 User alarm 1; bit 11 = UA2 User alarm 2; bit 12 = UA3 User alarm 3; bit 13 = UA4 User alarm 4; bit 14 = UA5 User alarm 5; bit 15 = UA6 User alarm 6 | ||||
| IR | 8706doc 2203h | User alarms UA7-UA12 | BITMAP16 | Read | bit 0 = UA7 User alarm 7; bit 1 = UA8 User alarm 8; bit 2 = UA9 User alarm 9; bit 3 = UA10 User alarm 10; bit 4 = UA11 User alarm 11; bit 5 = UA12 User alarm 12 | ||||
| IR | 8719doc 2210h | Device global status | BITMAP16 | Read | bit 0 = Device in OFF mode; bit 1 = Device in MAN mode; bit 2 = Device in AUT mode; bit 3 = Global alarm; bit 4 = Type A alarm; bit 5 = Type B alarm; bit 6 = Siren alarms; bit 7 = Mains failure; bit 8 = Failure to start; bit 9 = Pump running; bit 10 = Starting request; bit 11 = Automatic test in progress; bit 12 = Clock 100 ms; bit 13 = Stop delay enabled | ||||
| HR | 12034doc 2F03h | Save / reboot | UINT16 | Write | 1 = Save to EEPROM; 4 = Reboot; 5 = Save and reboot | ||||
| HR | 12038doc 2F07h | Device reset | UINT16 | Write | 0 = Reset device; 1 = Reset device and save FRAM | ||||
| HR | 12271doc 2FF0h | Command menu execution | UINT16 | Write | 0 = C01 Reset maintenance 1; 1 = C02 Reset maintenance 2; 2 = C03 Reset maintenance 3; 3 = C04 Reset partial hour counter; 4 = C05 Reset generic counters CNTx; 5 = C06 Reset limits LIMx; 6 = C07 Reset total hour counter; 7 = C08 Set pump hours; 8 = C09 Reset start counter; 9 = C10 Reset max/min values; 10 = C11 Reset event list; 11 = C12 Setup to default; 12 = C13 Back up setup; 13 = C14 Restore setup; 14 = C15 Forced I/O; 15 = C16 Reset PLC program | ||||
| HR | 20223doc 4F00h | Remote variable REM1 | REM2-REM16 follow at 4F01h-4F0Fh. | UINT16 | Write | 170 = Set to 1 (AAh); 187 = Set to 0 (BBh) |
Notes on this map
- Measures and status words are read with function 03 or 04 (same data) and are listed as input registers. Commands use function 06.
- Word order: the example answer 00 00 09 EC decodes to 2540 = 25.40 °C, so 32-bit values are high word first (ABCD).
- The example says it reads water temperature with start address 0F 09 (table 0F0Ah), but Table 2 lists water temperature at 0F0Eh. Because of that mismatch the water temperature register is left out; the minus-one rule itself is stated in the text.
- Scales are the divisors printed in the unit column (V/100, A/10000, W/10, var/10, VA/10, PF/10000, Hz/1000). Phase-to-phase asymmetry is printed %/10 while the other asymmetries are %/100.
- Left out: L1-L3 reactive and apparent powers (same pattern at 001Ah-0024h), max/min equivalent phase-to-phase voltage, LIM1-8 words, CNT1-8 counters, analog inputs/outputs (no units printed) and the key simulation at 2F0Ah.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers
What Modbus registers does the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers have?
This map lists 43 registers: 39 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document states that the address in a request is the table address decreased by one (Modbus standard). Addresses here are the table value minus one.
What byte order does the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers?
Start with IR 8719 Device global status (Global status (mode, pump running, mains failure)); IR 8703 Alarms A01-A16 (Alarms A01-A16); IR 8704 Alarms A17-A32 (Alarms A17-A32); IR 7 L1 phase current (L1 current); IR 13 L1-L2 voltage (L1-L2 voltage); IR 57 Frequency (Frequency).
How do I enable Modbus control of the Lovato Electric FFL700EP / FFL800EP electric fire pump controllers?
In SETUP menu M11 (communication) set P11.n.01 node address, .02 baud rate, .03 data format, .04 stop bits and .05 protocol for port n; port 1 is the built-in RS-485.
Where is the official Lovato Electric FFL700EP / FFL800EP electric fire pump controllers Modbus documentation?
The source is FFL700EP - FFL800EP electric fire pump controllers (EN12845) - Modbus protocol (I589 GB I 08 22), revision 2022-08-26, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/33.%20CONTROLLORI%20ANTINCENDIO/I589IGB08_22.pdf.
More Lovato Electric Modbus register maps
- Soft starter
Lovato Electric ADXL soft starters (Modbus RTU / ASCII / TCP)
ADXL soft starters fitted with the EXC1042 RS-485 board, per Lovato protocol addendum I454IGB03_22.
Also known as: ADXL, ADXL0030600, ADXL0045600, ADXL0060600, ADXL0075600, ADXL0085600, ADXL0115600, ADXL0135600, ADXL0162600, ADXL0195600, ADXL0250600, ADXL0320600, EXC1042 - Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Transfer switch
Lovato Electric ATL610 automatic transfer switch controller
ATL610 ATS controller via the optical port or an EXP1010/1011/1012/1013 communication module, per protocol document I428 GB I 09 22.
Also known as: ATL610, ATL 610, EXP1012, EXP1013 - Transfer switch
Lovato Electric ATL800 / ATL900 automatic transfer switch controllers
ATL800 and ATL900 ATS controllers (document I463 GB I 11 21); LINE3, BRK3 and TB2 items are ATL900 only.
Also known as: ATL800, ATL900, ATL 800, ATL 900 - Power meter (power factor controller)
Lovato Electric DCRL3 / DCRL5 / DCRL8 power factor controllers
DCRL3, DCRL5 and DCRL8 automatic power factor controllers with optical port or EXP10xx modules (Modbus TCP on DCRL8 only), per protocol document I427 GB 05 20.
Also known as: DCRL3, DCRL5, DCRL8, DCRL 3, DCRL 5, DCRL 8 - Power meter (power analyzer)
Lovato Electric DMG7000 / DMG7500 / DMG8000 / DMG9000 power analyzers
Lovato DMG7000, DMG7500, DMG8000 and DMG9000 panel power analyzers on any Modbus port (RTU, ASCII or TCP); DMG9000-only rows are marked.
Also known as: DMG7000, DMG7500, DMG8000, DMG9000, DMG 7000, DMG 8000, DMG 9000, Lovato DMG - Pump (diesel fire pump controller)
Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers
FFL700DP and FFL800DP diesel engine fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800DP), per protocol document I557 GB I 11 17.
Also known as: FFL700DP, FFL800DP, FFL 700 DP, FFL 800 DP - Generator controller
Lovato Electric RGK610 genset controller
RGK610, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 610 - Generator controller
Lovato Electric RGK700 AMF genset controller
RGK700, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700, RGK700 AMF - Generator controller
Lovato Electric RGK700SA stand-alone genset controller
RGK700SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 700SA, RGK700 SA - Generator controller
Lovato Electric RGK750 genset controller
RGK750, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 750 - Generator controller
Lovato Electric RGK800 AMF genset controller
RGK800, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800, RGK800 AMF - Generator controller
Lovato Electric RGK800SA stand-alone genset controller
RGK800SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 800SA, RGK800 SA - Generator controller
Lovato Electric RGK900 genset paralleling controller
RGK900, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900 - Generator controller
Lovato Electric RGK900MC mains/master controller
RGK900MC, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900MC, RGK900 MC - Generator controller
Lovato Electric RGK900SA genset paralleling controller (stand-alone)
RGK900SA, as marked in the per-model columns of the RGK series Modbus protocol document I375 I GB 08 22.
Also known as: RGK 900SA, RGK900 SA - Variable frequency drive
Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)
Lovato VT1 series drives on the built-in RS-485 port, per communication manual I646 GB I 02 21 (Modbus part).
Also known as: VT1, Lovato VT1, VT1 series
Other pumps register maps
- Heat pump (air-to-water) Modbus interface
Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
Panasonic CZ-NSMB Modbus PCB fitted inside Panasonic Air-To-Water control boxes; the manual's compatibility list names the A2W M-Series control module WH-CME8 and the Big A2W 20-30 kW outdoor units WH-WXG20/25/30ME8 with control module WH-CME8L (user manual M02412F0). Some registers carry H/J/K/L-series conditions.
Also known as: CZ-NSMB, A2W Modbus PCB, WH-CME8, WH-CME8L, WH-WXG20ME8, WH-WXG25ME8, WH-WXG30ME8, Aquarea M series Modbus, Big A2W Modbus - Pump (multistage pressure-boosting pump)
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
Wilo Helix2.0-VE pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Helix2.0-VE, Medana CH3-LE, Wilo-Medana CH3-LE - Pump controller (switchgear)
Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
Wilo-Control EC-WP for one or two fixed-speed pumps, hardware HW2, software SW102x (instructions Ed.01/2024-08, 2552567).
Also known as: Control EC-WP, Wilo Control EC WP, EC-WP - Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface - Heat pump (air-to-water)
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Gree Versati air-to-water heat pumps through the BMS port of the wired controller, per 'Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater'. The document itself does not name a generation or refrigerant; the distributor files it as the R32 Versati III protocol.
Also known as: Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5 - Heat pump (air-to-water)
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
LG THERMA V R32 Monobloc air-to-water heat pumps covered by installation manual MFL68026615 Rev.02 (North American models ZHBW041GA0 / ZHBW048GA0 / ZHBW055GA0), using the indoor PCB's own Modbus RTU slave port.
Also known as: ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615
All pumps Modbus register maps →
Source: FFL700EP - FFL800EP electric fire pump controllers (EN12845) - Modbus protocol · I589 GB I 08 22 · rev. 2022-08-26. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.