Soft starter · Modbus register map

Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The Lovato ADXN is a compact soft starter with built-in bypass for pumps, fans, compressors and conveyors. Only the advanced ADXNP version talks Modbus RTU, through the CX04 RS-485 module clipped to its optical port. This map covers voltage, phase currents and powers, frequency, torque, thermal status, thyristor temperature, input and output status, and the start/stop command.

This page lists 19 Modbus registers for the Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Lovato Electric
Model
ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
Equipment type
Soft starter
Registers
19 (1 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
ADXNP, CX04
Source document
ADXN soft starters - instruction manual · I651 GB 02 24 · rev. 2024-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)

Integration in brief

Fit the CX04 module, then read currents (08h-0Dh), total power (3Ah), thermal status (FB0h) and thyristor temperature (FB2h) with function 04, subtracting one from each table address. Start or stop with 1 or 0 written to 1002h.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 7L1 currentUINT32 ABCDL1 currentRead
IR 57Total active powerINT32 ABCDTotal active powerRead
IR 4015Motor thermal statusUINT32 ABCDMotor thermal statusRead
IR 4017Thyristor temperatureINT32 ABCDThyristor temperatureRead
HR 4097Start/stop commandUINT16Start/stop commandWrite

Enable Modbus control & writes

Set the communication menu (M06) on the ADXNP with the LOVATO NFC app or Xpress software while the CX04 is unplugged, then clip the CX04 onto the optical port and wire RS-485 (SG, A, B) plus 24 V AC/DC to the module.

Byte order & addressing

Network setup

Watch out for

Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

19 of 19 shown
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR5doc 06hL3-L1 voltageUINT32ABCD× 0.01VRead
IR7doc 08hL1 currentUINT32ABCD× 0.0001ARead
IR9doc 0AhL2 currentUINT32ABCD× 0.0001ARead
IR11doc 0ChL3 currentUINT32ABCD× 0.0001ARead
IR19doc 14hL1 active powerINT32ABCD× 0.00001kWRead
IR21doc 16hL2 active powerINT32ABCD× 0.00001kWRead
IR23doc 18hL3 active powerINT32ABCD× 0.00001kWRead
IR49doc 32hFrequencyUINT32ABCD× 0.001HzRead
IR57doc 3AhTotal active powerINT32ABCD× 0.00001kWRead
IR117doc 76hMaximum currentUINT32ABCD× 0.0001ARead
IR119doc 78hTorqueUINT32ABCD× 0.1%Read
IR121doc 7AhMaximum instantaneous currentUINT32ABCD× 0.1%Read
IR4015doc FB0hMotor thermal statusUINT32ABCD%Read
IR4017doc FB2hThyristor temperatureINT32ABCD× 0.1°CRead
IR8447doc 2100hST start input statusPrinted as bool (0/1); the document does not say which state is 1.UINT16Read
IR8511doc 2140hOutputs statusGroup word for the outputs (no bit legend printed).UINT16Read
IR8512doc 2141hOutput 1 (11-14) statusPrinted as bool (0/1); the document does not say which state is 1.UINT16Read
IR8513doc 2142hOutput 2 (11-24) statusPrinted as bool (0/1); the document does not say which state is 1.UINT16Read
HR4097doc 1002hStart/stop commandNeeds P04.04 = ON and the ST input closed.UINT16Write0 = Stop motor; 1 = Start motor

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)

What Modbus registers does the Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU) have?

This map lists 19 registers: 18 input registers, 1 holding register. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address table prints hex addresses one above the request address; the manual's example reads thyristor temperature (table 0FB2h) by sending 0F B1, 'decreased by one'. Addresses here are already reduced by one.

What byte order does the Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)?

Start with IR 7 L1 current (L1 current); IR 57 Total active power (Total active power); IR 4015 Motor thermal status (Motor thermal status); IR 4017 Thyristor temperature (Thyristor temperature); HR 4097 Start/stop command (Start/stop command).

How do I enable Modbus control of the Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)?

Set the communication menu (M06) on the ADXNP with the LOVATO NFC app or Xpress software while the CX04 is unplugged, then clip the CX04 onto the optical port and wire RS-485 (SG, A, B) plus 24 V AC/DC to the module.

Where is the official Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU) Modbus documentation?

The source is ADXN soft starters - instruction manual (I651 GB 02 24), revision 2024-02, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/05.%20SOFT%20STARTER/I651GB02_24.pdf.

More Lovato Electric Modbus register maps

Other soft starters & protection relays register maps

All soft starters & protection relays Modbus register maps →

Source: ADXN soft starters - instruction manual · I651 GB 02 24 · rev. 2024-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.