Soft starter (motor control) · Modbus register map
ABB PSTX softstarter (built-in Modbus RTU) Modbus register map
Updated 17 November 2026
ABB's PSTX softstarters have a built-in Modbus RTU slave on their Com3 terminals. Status is read as 16 coils or one status word, ten programmable analog inputs carry measurements such as phase currents, and the motor is started and stopped either through coils or two control words. Parameters are read and written through a 'fieldbus task' handshake register. This map covers every published register.
This page lists 60 Modbus registers for the ABB PSTX softstarter (built-in Modbus RTU) — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- PSTX softstarter (built-in Modbus RTU)
- Equipment type
- Soft starter (motor control)
- Registers
- 60 (32 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250
Integration notes: ABB PSTX softstarter (built-in Modbus RTU)
Set 12.1 Com3 function = Modbus RTU slave and 12.2 FB interface connector = Modbus RTU, then write control word 1 (02FEh) with bit 3 auto mode plus bit 1 stop-permit and bit 0 start, and read the status word (01FFh) and analog inputs 0201h-020Ah with function 04.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 766 | Control word 1 | BITMAP16 | Control word 1: start/stop/reset/auto mode | Read/write |
| IR 511 | Status word | BITMAP16 | Status word: auto mode, event, ready to start | Read |
| IR 513 | Programmable analog input 1 | UINT16 | Analog input 1 (default phase L1 current) | Read |
| IR 514 | Programmable analog input 2 | UINT16 | Analog input 2 (default phase L2 current) | Read |
| CO 1 | Event status | BIT | Event status (fault/warning/protection) | Read |
| HR 768 | FBT Control Word | UINT16 | FBT control word for parameter access | Read/write |
Enable Modbus control & writes
Set 12.2 FB interface connector = Modbus RTU, 12.3 Fieldbus control = On (Off for monitoring only), 12.9 baud (9600-115200), 12.10 parity, 12.11 stop bits, 12.4 Fieldbus address (1-247) and 12.1 Com3 function = Modbus RTU slave. Power-cycle, or set 12.2 to None and back to Modbus RTU, for changes to apply.
Communication loss & watchdog
If no message passes for longer than the fieldbus failure timeout (19.12) the softstarter trips on fieldbus communication failure (P1E00) and by default stops the motor. Set 19.4 Fieldbus failure op = Off if the master does not poll continuously.
Byte order & addressing
- Addresses are hex protocol addresses with the Modicon number alongside; use the hex value on the wire.
- Stop is active-low: bit 1 / coil 0101h must stay set for the motor to keep running.
- Fault reset, FBT toggle, switch to remote and K4-K6 relay commands work even when auto mode is off.
Network setup
- Com3 shares terminals 23 and 24 with the DX111/DX112 expansion I/O module, so both cannot be used at once.
- Supported baud rates: 9600, 19200, 38400, 57600, 76800 and 115200.
Watch out for
- The motor may start unexpectedly when switching between fieldbus and hardwired control, or after Reset all settings, if a start signal is present.
- The local/remote switch on the HMI and the 'Fieldbus disable' digital input also decide whether auto mode (Modbus control) is active.
ABB PSTX softstarter (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0000h (00001) | Auto mode status | 1 = softstarter controlled through Modbus. | BIT | Read | ||||
| CO | 1doc 0001h (00002) | Event status | 1 = active fault, warning or protection. | BIT | Read | ||||
| CO | 2doc 0002h (00003) | Ready to start | 1 = a start will probably not cause a fault. | BIT | Read | ||||
| CO | 3doc 0003h (00004) | FBT Response 0 | Fieldbus task response bit 0. | BIT | Read | ||||
| CO | 4doc 0004h (00005) | FBT Response 1 | Fieldbus task response bit 1. | BIT | Read | ||||
| CO | 5doc 0005h (00006) | FBT Toggle Bit | Toggles to acknowledge a fieldbus task. | BIT | Read | ||||
| CO | 6doc 0006h (00007) | Programmable digital input 1 | Function set by parameter Fieldbus DI 1. | BIT | Read | ||||
| CO | 7doc 0007h (00008) | Programmable digital input 2 | Function set by parameter Fieldbus DI 2. | BIT | Read | ||||
| CO | 8doc 0008h (00009) | Programmable digital input 3 | Function set by parameter Fieldbus DI 3. | BIT | Read | ||||
| CO | 9doc 0009h (00010) | Programmable digital input 4 | Function set by parameter Fieldbus DI 4. | BIT | Read | ||||
| CO | 10doc 000Ah (00011) | Programmable digital input 5 | Function set by parameter Fieldbus DI 5. | BIT | Read | ||||
| CO | 11doc 000Bh (00012) | Programmable digital input 6 | Function set by parameter Fieldbus DI 6. | BIT | Read | ||||
| CO | 12doc 000Ch (00013) | Programmable digital input 7 | Function set by parameter Fieldbus DI 7. | BIT | Read | ||||
| CO | 13doc 000Dh (00014) | Programmable digital input 8 | Function set by parameter Fieldbus DI 8. | BIT | Read | ||||
| CO | 14doc 000Eh (00015) | Programmable digital input 9 | Function set by parameter Fieldbus DI 9. | BIT | Read | ||||
| CO | 15doc 000Fh (00016) | Programmable digital input 10 | Function set by parameter Fieldbus DI 10. | BIT | Read | ||||
| CO | 256doc 0100h (257) | Start | Starts the motor when set. | BIT | Write | ||||
| CO | 257doc 0101h (258) | Stop | Stops the motor when cleared. | BIT | Write | ||||
| CO | 258doc 0102h (259) | Fault reset | BIT | Write | |||||
| CO | 259doc 0103h (260) | Auto mode | Must be set to control the motor. | BIT | Write | ||||
| CO | 260doc 0104h (261) | Slow speed reverse | BIT | Write | |||||
| CO | 261doc 0105h (262) | Slow speed forward | BIT | Write | |||||
| CO | 263doc 0107h (264) | Start1 | Sequence start motor 1. | BIT | Write | ||||
| CO | 264doc 0108h (265) | Start2 | Sequence start motor 2. | BIT | Write | ||||
| CO | 265doc 0109h (266) | Start3 | Sequence start motor 3. | BIT | Write | ||||
| CO | 266doc 010Ah (267) | Motor heating | BIT | Write | |||||
| CO | 267doc 010Bh (268) | Stand still brake | BIT | Write | |||||
| CO | 268doc 010Ch (269) | Start reverse | BIT | Write | |||||
| CO | 270doc 010Eh (271) | Emergency mode | 1 = enable emergency mode. | BIT | Write | ||||
| CO | 271doc 010Fh (272) | FBT Toggle Bit | Change to execute a fieldbus task. | BIT | Write | ||||
| CO | 272doc 0110h (273) | User defined trip | 1 = trigger the user defined protection. | BIT | Write | ||||
| CO | 273doc 0111h (274) | Switch to remote control | Rising edge switches to remote control. | BIT | Write | ||||
| CO | 274doc 0112h (275) | Pump cleaning automatic | BIT | Write | |||||
| CO | 275doc 0113h (276) | Pump cleaning forward | BIT | Write | |||||
| CO | 276doc 0114h (277) | Pump cleaning reverse | BIT | Write | |||||
| CO | 277doc 0115h (278) | K4 relay command | Needs 10.4 K4 function = Fieldbus. | BIT | Write | ||||
| CO | 278doc 0116h (279) | K5 relay command | Needs 10.5 K5 function = Fieldbus. | BIT | Write | ||||
| CO | 279doc 0117h (280) | K6 relay command | Needs 10.6 K6 function = Fieldbus. | BIT | Write | ||||
| CO | 280doc 0118h (281) | 1DO0 relay command | External relay; needs 11.9 1DO0 function = Fieldbus. | BIT | Write | ||||
| CO | 281doc 0119h (282) | 1DO1 relay command | External relay; needs 11.10 = Fieldbus. | BIT | Write | ||||
| CO | 282doc 011Ah (283) | 2DO2 relay command | External relay; needs 11.11 = Fieldbus. | BIT | Write | ||||
| CO | 283doc 011Bh (284) | 2DO3 relay command | External relay; needs 11.12 = Fieldbus. | BIT | Write | ||||
| CO | 284doc 011Ch (285) | Refresh parameters | Restarts the fieldbus interface to apply new comm settings. | BIT | Write | ||||
| IR | 511doc 01FFh (30512) | Status word | Same bits as the digital input telegram; FC 03 or 04. | BITMAP16 | Read | bit 0 = Auto mode status; bit 1 = Event status; bit 2 = Ready to start; bit 3 = FBT Response 0; bit 4 = FBT Response 1; bit 5 = FBT Toggle Bit; bit 6 = Programmable digital input 1; bit 7 = Programmable digital input 2; bit 8 = Programmable digital input 3; bit 9 = Programmable digital input 4; bit 10 = Programmable digital input 5; bit 11 = Programmable digital input 6; bit 12 = Programmable digital input 7; bit 13 = Programmable digital input 8; bit 14 = Programmable digital input 9; bit 15 = Programmable digital input 10 | |||
| IR | 512doc 0200h (30513) | FBT Return Value | Result or error code of a fieldbus task. | UINT16 | Read | ||||
| IR | 513doc 0201h (30514) | Programmable analog input 1 | Fieldbus AI 1 function (Phase L1 current in the manual's default example). | UINT16 | Read | ||||
| IR | 514doc 0202h (30515) | Programmable analog input 2 | Fieldbus AI 2 function (Phase L2 current in the manual's default example). | UINT16 | Read | ||||
| IR | 515doc 0203h (30516) | Programmable analog input 3 | Function set by parameter Fieldbus AI 3; scaling depends on that function. | UINT16 | Read | ||||
| IR | 516doc 0204h (30517) | Programmable analog input 4 | Function set by parameter Fieldbus AI 4; scaling depends on that function. | UINT16 | Read | ||||
| IR | 517doc 0205h (30518) | Programmable analog input 5 | Function set by parameter Fieldbus AI 5; scaling depends on that function. | UINT16 | Read | ||||
| IR | 518doc 0206h (30519) | Programmable analog input 6 | Function set by parameter Fieldbus AI 6; scaling depends on that function. | UINT16 | Read | ||||
| IR | 519doc 0207h (30520) | Programmable analog input 7 | Function set by parameter Fieldbus AI 7; scaling depends on that function. | UINT16 | Read | ||||
| IR | 520doc 0208h (30521) | Programmable analog input 8 | Function set by parameter Fieldbus AI 8; scaling depends on that function. | UINT16 | Read | ||||
| IR | 521doc 0209h (30522) | Programmable analog input 9 | Function set by parameter Fieldbus AI 9; scaling depends on that function. | UINT16 | Read | ||||
| IR | 522doc 020Ah (30523) | Programmable analog input 10 | Function set by parameter Fieldbus AI 10; scaling depends on that function. | UINT16 | Read | ||||
| HR | 766doc 02FEh (40767) | Control word 1 | Alternative to the digital output coils. | BITMAP16 | Read/write | bit 0 = Start (start when set); bit 1 = Stop (stop when cleared); bit 2 = Fault reset; bit 3 = Auto mode (must be set to control the motor); bit 4 = Slow speed reverse; bit 5 = Slow speed forward; bit 6 = Spare; bit 7 = Start1 (sequence start); bit 8 = Start2 (sequence start); bit 9 = Start3 (sequence start); bit 10 = Motor heating; bit 11 = Stand still brake; bit 12 = Start reverse; bit 13 = Spare; bit 14 = Emergency mode; bit 15 = FBT Toggle Bit | |||
| HR | 767doc 02FFh (40768) | Control word 2 | BITMAP16 | Read/write | bit 0 = User defined trip; bit 1 = Switch to remote control (rising edge); bit 2 = Pump cleaning automatic; bit 3 = Pump cleaning forward; bit 4 = Pump cleaning reverse; bit 5 = K4 relay command (10.4 = Fieldbus); bit 6 = K5 relay command (10.5 = Fieldbus); bit 7 = K6 relay command (10.6 = Fieldbus); bit 8 = 1DO0 relay command (11.9 = Fieldbus); bit 9 = 1DO1 relay command (11.10 = Fieldbus); bit 10 = 2DO2 relay command (11.11 = Fieldbus); bit 11 = 2DO3 relay command (11.12 = Fieldbus); bit 12 = Refresh parameters (restart fieldbus driver); bit 13 = Spare; bit 14 = Spare; bit 15 = Spare | ||||
| HR | 768doc 0300h (40769) | FBT Control Word | Bits 12-14 task ID, bits 0-10 argument 1 (parameter number). | UINT16 | Read/write | ||||
| HR | 769doc 0301h (40770) | Fieldbus AO 1 | FBT argument 2 or internal analog output, per 12.37. | UINT16 | Read/write | ||||
| HR | 770doc 0302h (40771) | Fieldbus AO 2 | FBT argument 3 or external analog output, per 12.38. | UINT16 | Read/write |
Notes on this map
- This map follows Rev F (2021), which includes the external relay coils 0118h-011Bh, the 'Refresh parameters' coil 011Ch and the matching control word 2 bits 8-12. Input data is updated every 20 ms.
- All values are 16-bit; there are no 32-bit registers.
- The digital input telegram (protocol 0000h-000Fh) is read with function 01 (Read Coil Status), so it is listed as read-only coils; the same bits are in the status word at 01FFh. The analog input block (01FFh-020Ah) can be read with function 03 or 04 and is listed as input registers.
- The ten analog inputs are programmable (parameters Fieldbus AI 1-10) and are left unscaled. Scaling per function from the manual: phase currents, mains voltage, motor current: 1000 = 100 A or 100 V (0.1); active power 1000 = 10 kW (0.01); power factor 100 = 1; mains frequency 1000 = 100 Hz (0.1); motor voltage and percentages 100 = 100 % (1); active energy 1000 = 10 kWh (0.01); 'high range' variants 100 = 100 A/kW (1).
- Start/stop can come from coils 0100h/0101h (with auto mode on coil 0103h) or from bits 0/1 of control word 1 (with auto mode in bit 3). If auto mode is set in both places the device ignores start/stop as a configuration error.
- Parameters are reached only through fieldbus tasks: put the task ID (1 read low word, 2 change value, 3 set clock, 4 read high word) and parameter number in 0300h, any value in 0301h/0302h, then toggle the FBT Toggle Bit; the result is in 0200h once the input toggle bit matches. Error codes: 0 illegal parameter, 1 cannot change, 3 limit violated, 4 invalid argument, 5 no error, 6 invalid task.
- No factory defaults for address, baud or parity are given in this document; they are in the Installation and commissioning manual 1SFC132081M0201.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB PSTX softstarter (built-in Modbus RTU)
What Modbus registers does the ABB PSTX softstarter (built-in Modbus RTU) have?
This map lists 60 registers: 43 coils, 12 input registers, 5 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB PSTX softstarter (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table gives both the protocol address in hex (sent on the wire) and the Modicon address: protocol 01FFh = Modicon 30512, 02FEh = 40767, coil 0100h = 00257. The manual explains the translation itself (Modicon 40002 -> protocol 0001), and its example frames send 0000h, 0100h, 0201h and 0300h directly.
What are the minimum Modbus registers to integrate the ABB PSTX softstarter (built-in Modbus RTU)?
Start with HR 766 Control word 1 (Control word 1: start/stop/reset/auto mode); IR 511 Status word (Status word: auto mode, event, ready to start); IR 513 Programmable analog input 1 (Analog input 1 (default phase L1 current)); IR 514 Programmable analog input 2 (Analog input 2 (default phase L2 current)); CO 1 Event status (Event status (fault/warning/protection)); HR 768 FBT Control Word (FBT control word for parameter access).
How do I enable Modbus control of the ABB PSTX softstarter (built-in Modbus RTU)?
Set 12.2 FB interface connector = Modbus RTU, 12.3 Fieldbus control = On (Off for monitoring only), 12.9 baud (9600-115200), 12.10 parity, 12.11 stop bits, 12.4 Fieldbus address (1-247) and 12.1 Com3 function = Modbus RTU slave. Power-cycle, or set 12.2 to None and back to Modbus RTU, for changes to apply.
What happens when the ABB PSTX softstarter (built-in Modbus RTU) loses Modbus communication?
If no message passes for longer than the fieldbus failure timeout (19.12) the softstarter trips on fieldbus communication failure (P1E00) and by default stops the motor. Set 19.4 Fieldbus failure op = Off if the master does not poll continuously.
Where is the official ABB PSTX softstarter (built-in Modbus RTU) Modbus documentation?
The source is Softstarter type PSTX - Fieldbus communication, Built-in Modbus RTU (1SFC132089M0201 Rev F), revision 2021-05-03, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=1SFC132089M0201&LanguageCode=en&DocumentPartId=&Action=Launch.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other soft starters & protection relays register maps
- Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40 - Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Protection relay
Siemens Reyrolle 7SR11 / 7SR12 Argus overcurrent relays (Modbus RTU)
Reyrolle 7SR11 (non-directional) and 7SR12 (directional) Argus overcurrent relays, default Modbus RTU point list in the 7SR11 & 7SR12 Complete Technical Manual (Chapter 4, Data Communications, 2015).
Also known as: 7SR11 Argus, 7SR12 Argus, Reyrolle 7SR11, Reyrolle 7SR12, 7SR120 - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V - Soft starter
Lovato Electric ADXNP soft starters with CX04 RS-485 module (Modbus RTU)
ADXNP (advanced version) soft starters fitted with the CX04 RS-485 module, per instruction manual I651 GB 02 24.
Also known as: ADXNP, CX04 - Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V
All soft starters & protection relays Modbus register maps →
Source: Softstarter type PSTX - Fieldbus communication, Built-in Modbus RTU · 1SFC132089M0201 Rev F · rev. 2021-05-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.