Variable frequency drive (DC drive) · Modbus register map
ABB DCS880 DC drive (embedded Modbus RTU) Modbus register map
Updated 17 November 2026
ABB's thyristor DC drive for armature and field control of DC motors. The control board's XD2D RS-485 port can run Modbus RTU, which puts a control word, two references, a status word and two actual values in the first six holding registers and maps every parameter to a holding register worked out from its group and index. This map covers that cyclic block plus the main armature, field, mains and power signals, the active fault codes and the comm-loss settings, all in 16-bit form.
This page lists 26 Modbus registers for the ABB DCS880 DC drive (embedded Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- DCS880 DC drive (embedded Modbus RTU)
- Equipment type
- Variable frequency drive (DC drive)
- Registers
- 26 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- DCS880-S01, DCS880-S02, DCS880-H, DCS880-R
Integration notes: ABB DCS880 DC drive (embedded Modbus RTU)
Set 58.01 = Modbus RTU plus node, baud and parity, validate with 58.06 = Refresh settings, then set 06.08 Main control word source = EFB, 20.01 Command location = Main control word and the speed reference source to EFB reference 1. Write the control word and REF1 at 400001/400002 and poll the status word and actuals at 400004-400006.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Control word (CW) | BITMAP16 | Control word: on/run/reset | Read/write |
| HR 1 | Reference 1 (REF1) | INT16 | Reference 1 (speed reference) | Read/write |
| HR 3 | Status word (SW) | BITMAP16 | Status word: ready/running/fault | Read |
| HR 4 | Actual value 1 (ACT1) | INT16 | Actual value 1 | Read |
| HR 109 | 01.10 Motor current in A | INT16 | 01.10 Motor current in A | Read |
| HR 120 | 01.21 Armature voltage in V | INT16 | 01.21 Armature voltage, 0.1 V | Read |
| HR 128 | 01.29 M1 field current in A | INT16 | 01.29 Field current, 0.1 A | Read |
| HR 400 | 04.01 Tripping fault | UINT16 | 04.01 Tripping fault code | Read |
Enable Modbus control & writes
58.01 Protocol enable = Modbus RTU (disables the device-to-device link on XD2D). Set 58.03 Node address, 58.04 Baud rate and 58.05 Parity, then 58.06 Communication control = Refresh settings (or reboot). For control set 06.08 Main control word source = EFB, 20.01 Command location = Main control word, and 22.11/22.12 (speed) or 26.11/26.12 (torque) to EFB reference 1 or 2. Save fieldbus parameter writes with 96.16 Parameter save manually = Save.
Communication loss & watchdog
58.14 Communication loss action (No action / Fault / Last speed / Speed reference safe / Fault always / Warning), 58.16 Communication loss time (0-32.5 s, default 0.3 s) and 58.15 Communication loss mode (any message, or only CW/reference writes, resets the timer). Loss gives fault 6681 or warning A7CE.
Byte order & addressing
- The control word is edge-triggered: bit 0 must go 0 to 1 for On and bit 3 must go 0 to 1 for Run.
- Bit 10 Remote command must be 1 or the control word and references are ignored (bits 0-2 still act).
- For holding registers the supported function-code table lists FC 03, FC 06, FC 0x16 (mask write) and FC 0x17 (read/write multiple); FC 16 is not in the list.
- The drive handles 10 registers per 10 ms, so long block reads add response delay (about 22 ms for 20 registers).
Network setup
- RS-485 on terminal XD2D of the control board; see the DCS880 hardware manual 3ADW000462 for termination.
- Defaults: node 1, 19.2 kbit/s, 8 data bits, even parity, 1 stop bit.
- Changes to group 58 take effect after 58.06 = Refresh settings or a reboot.
Watch out for
- Coils mirror the control word bits and discrete inputs the status word bits plus DI states, but both tables number from 00001 without a 0/1-based statement, so they are not listed.
ABB DCS880 DC drive (embedded Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 400001 | Control word (CW) | ABB Drives profile; default Data I/O 1 (58.101). | BITMAP16 | Read/write | bit 0 = On/Off1: 0->1 = On (to Ready run); 0 = Off1 stop via 21.02; bit 1 = Off2: 1 = normal, 0 = emergency off / coast, to Switch-on inhibited; bit 2 = Off3: 1 = normal, 0 = emergency stop via 21.03; bit 3 = Run: 0->1 = run (firing pulses released); 0 = stop via 21.04; bit 4 = Ramp out zero: 1 = normal, 0 = force ramp output to zero; bit 5 = Ramp halt: 1 = normal, 0 = freeze ramp output; bit 6 = Ramp in zero: 1 = normal, 0 = force ramp input to zero; bit 7 = Reset: 0->1 acknowledges faults; bit 8 = Inching 1 (jog at 22.42); bit 9 = Inching 2 (jog at 22.43); bit 10 = Remote command: 1 = overriding control enabled (must be set); bit 11 = Reserved; bit 12 = Main control 12 (user bit); bit 13 = Main control 13 (user bit); bit 14 = Main control 14 (user bit); bit 15 = Main control 15 (user bit) | |||
| HR | 1doc 400002 | Reference 1 (REF1) | Scaling per 58.26 EFB ref1 type; default Data I/O 2. | INT16 | Read/write | ||||
| HR | 2doc 400003 | Reference 2 (REF2) | Scaling per 58.27 EFB ref2 type; default Data I/O 3. | INT16 | Read/write | ||||
| HR | 3doc 400004 | Status word (SW) | ABB Drives profile; default Data I/O 4 (58.104). | BITMAP16 | Read | bit 0 = Ready on; bit 1 = Ready run (0 = e.g. Off1 active); bit 2 = Ready reference: drive running; bit 3 = Tripped: fault; bit 4 = Off2 inactive; bit 5 = Off3 inactive; bit 6 = Switch-on inhibited; bit 7 = Warning; bit 8 = At setpoint; bit 9 = Remote (0 = local); bit 10 = Above level (selector 06.29); bit 11 = Status control 11 (selector 06.30); bit 12 = Status control 12 (selector 06.31); bit 13 = Status control 13 (selector 06.32); bit 14 = Status control 14 (selector 06.33); bit 15 = Reserved | |||
| HR | 4doc 400005 | Actual value 1 (ACT1) | Type and scaling per 58.28; default Data I/O 5. | INT16 | Read | ||||
| HR | 5doc 400006 | Actual value 2 (ACT2) | Type and scaling per 58.29; default Data I/O 6. | INT16 | Read | ||||
| HR | 106doc 400107 | 01.07 Speed change rate | Positive = accelerating. | INT16 | rpm/s | Read | |||
| HR | 109doc 400110 | 01.10 Motor current in A | Measured motor (armature) current. | INT16 | A | Read | |||
| HR | 119doc 400120 | 01.20 Mains voltage in V | Measured mains voltage, 10 ms filter. | INT16 | × 0.1 | V | Read | ||
| HR | 120doc 400121 | 01.21 Armature voltage in V | Measured armature voltage, 10 ms filter. | INT16 | × 0.1 | V | Read | ||
| HR | 123doc 400124 | 01.24 Output power in kW | Unit follows 96.02 (kW or hp). | INT16 | kW | Read | |||
| HR | 124doc 400125 | 01.25 Output power | Percent of 99.03 motor nominal power. | INT16 | × 0.01 | % | Read | ||
| HR | 125doc 400126 | 01.26 Reactive power | Percent of 99.03 motor nominal power. | INT16 | × 0.01 | % | Read | ||
| HR | 128doc 400129 | 01.29 M1 field current in A | Motor 1 field current, 500 ms filter. | INT16 | × 0.1 | A | Read | ||
| HR | 129doc 400130 | 01.30 M2 field current in A | Motor 2 field current, 500 ms filter. | INT16 | × 0.1 | A | Read | ||
| HR | 139doc 400140 | 01.40 Drive current | Percent of 07.62 drive DC current scaling. | INT16 | × 0.01 | % | Read | ||
| HR | 140doc 400141 | 01.41 Reactive current | Percent of 99.11 motor nominal current. | INT16 | × 0.01 | % | Read | ||
| HR | 400doc 400401 | 04.01 Tripping fault | Code of the fault that caused the trip (hex). | UINT16 | Read | ||||
| HR | 401doc 400402 | 04.02 Active fault 2 | UINT16 | Read | |||||
| HR | 402doc 400403 | 04.03 Active fault 3 | UINT16 | Read | |||||
| HR | 403doc 400404 | 04.04 Active fault 4 | UINT16 | Read | |||||
| HR | 600doc 400601 | 06.01 Main control word | Read-only view of the control word in use; do not write. | BITMAP16 | Read | bit 0 = On/Off1: 0->1 = On (to Ready run); 0 = Off1 stop via 21.02; bit 1 = Off2: 1 = normal, 0 = emergency off / coast, to Switch-on inhibited; bit 2 = Off3: 1 = normal, 0 = emergency stop via 21.03; bit 3 = Run: 0->1 = run (firing pulses released); 0 = stop via 21.04; bit 4 = Ramp out zero: 1 = normal, 0 = force ramp output to zero; bit 5 = Ramp halt: 1 = normal, 0 = freeze ramp output; bit 6 = Ramp in zero: 1 = normal, 0 = force ramp input to zero; bit 7 = Reset: 0->1 acknowledges faults; bit 8 = Inching 1 (jog at 22.42); bit 9 = Inching 2 (jog at 22.43); bit 10 = Remote command: 1 = overriding control enabled (must be set); bit 11 = Reserved; bit 12 = Main control 12 (user bit); bit 13 = Main control 13 (user bit); bit 14 = Main control 14 (user bit); bit 15 = Main control 15 (user bit) | |||
| HR | 614doc 400615 | 06.15 Main status word | Same bits as the status word at 400004. | BITMAP16 | Read | bit 0 = Ready on; bit 1 = Ready run (0 = e.g. Off1 active); bit 2 = Ready reference: drive running; bit 3 = Tripped: fault; bit 4 = Off2 inactive; bit 5 = Off3 inactive; bit 6 = Switch-on inhibited; bit 7 = Warning; bit 8 = At setpoint; bit 9 = Remote (0 = local); bit 10 = Above level (selector 06.29); bit 11 = Status control 11 (selector 06.30); bit 12 = Status control 12 (selector 06.31); bit 13 = Status control 13 (selector 06.32); bit 14 = Status control 14 (selector 06.33); bit 15 = Reserved | |||
| HR | 5813doc 405814 | 58.14 Communication loss action | UINT16 | Read/write | 0 = No action; 1 = Fault; 2 = Last speed; 3 = Speed reference safe; 4 = Fault always; 5 = Warning | ||||
| HR | 5814doc 405815 | 58.15 Communication loss mode | Which messages reset the loss timer. | UINT16 | Read/write | 1 = Any message; 2 = CW / Ref1 / Ref2 | |||
| HR | 5815doc 405816 | 58.16 Communication loss time | Range 0-32.5 s, default 0.3 s. | UINT16 | × 0.1 | s | Read/write |
Notes on this map
- Source host: ABB lists this manual as 3ADW000474, but its public library returns 'not available' for that number and no other ABB-hosted copy was found; this is a copy of the ABB document hosted by a US distributor.
- Registers 400001-400006 are the defaults of 58.101-58.106 Data I/O 1-6 and can be re-pointed; Data I/O 7-24 (400007-400024) are user-selected and not listed.
- Only 16-bit parameter registers are listed. The manual describes a 32-bit block (420000 + 200 x group + 2 x index, word order set by 58.34, default LO-HI) but prints only 16-bit (FbEq16) scaling, so no 32-bit registers are included.
- Speed and torque signals (01.01-01.06, 01.17, 01.18) use 46.02 / 46.04 scaling, which depends on drive setup, so they are left out. References and actual values in the cyclic block are left unscaled for the same reason.
- The manual's error-code register table is headed 400090-400100 but its rows are numbered 89-94, so those registers are left out.
- 58.14 Communication loss action defaults to No action in the parameter list; the setup table shows Fault as the value to use for fieldbus control.
- 01.24 follows 96.02 Unit selection (kW or hp); the unit shown assumes kW.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB DCS880 DC drive (embedded Modbus RTU)
What Modbus registers does the ABB DCS880 DC drive (embedded Modbus RTU) have?
This map lists 26 registers: 26 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB DCS880 DC drive (embedded Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses 6-digit holding register references 400001-465536, so 400001 is wire address 0. With 58.33 = Mode 0 (default) a 16-bit parameter gg.ii sits at 400000 + 100 x gg + ii, e.g. 01.21 -> 400121 = wire 120. Masters limited to 5 digits can reach 400001-409999 as 40001-49999.
What are the minimum Modbus registers to integrate the ABB DCS880 DC drive (embedded Modbus RTU)?
Start with HR 0 Control word (CW) (Control word: on/run/reset); HR 1 Reference 1 (REF1) (Reference 1 (speed reference)); HR 3 Status word (SW) (Status word: ready/running/fault); HR 4 Actual value 1 (ACT1) (Actual value 1); HR 109 01.10 Motor current in A (01.10 Motor current in A); HR 120 01.21 Armature voltage in V (01.21 Armature voltage, 0.1 V); HR 128 01.29 M1 field current in A (01.29 Field current, 0.1 A); HR 400 04.01 Tripping fault (04.01 Tripping fault code).
How do I enable Modbus control of the ABB DCS880 DC drive (embedded Modbus RTU)?
58.01 Protocol enable = Modbus RTU (disables the device-to-device link on XD2D). Set 58.03 Node address, 58.04 Baud rate and 58.05 Parity, then 58.06 Communication control = Refresh settings (or reboot). For control set 06.08 Main control word source = EFB, 20.01 Command location = Main control word, and 22.11/22.12 (speed) or 26.11/26.12 (torque) to EFB reference 1 or 2. Save fieldbus parameter writes with 96.16 Parameter save manually = Save.
What happens when the ABB DCS880 DC drive (embedded Modbus RTU) loses Modbus communication?
58.14 Communication loss action (No action / Fault / Last speed / Speed reference safe / Fault always / Warning), 58.16 Communication loss time (0-32.5 s, default 0.3 s) and 58.15 Communication loss mode (any message, or only CW/reference writes, resets the timer). Loss gives fault 6681 or warning A7CE.
Where is the official ABB DCS880 DC drive (embedded Modbus RTU) Modbus documentation?
The source is DCS880 drives Firmware manual (3ADW000474R0501 (rev E)). ABB doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2020/12/DCS880-Firmware-Manual.pdf. It may be an older revision, so check it against the live unit.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
ACS800 drives running Standard Control Program 7.x with an RMBA-01 Modbus Adapter in option slot 1 or 2 (Standard Modbus Link, RTU only), ABB Drives communication profile.
Also known as: ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other variable frequency drives register maps
- Variable frequency drive
Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)
Bonfiglioli ACTIVE (ACT) and ACTIVE Cube (ACU 201/401/210/410) inverters with a CM-232 or CM-485 communication module set to Modbus, per manual VEC 383 R4 (04/23).
Also known as: ACTIVE Cube, ACU, ACU 201, ACU 401, ACU 210, ACU 410, ACTIVE, ACT, CM-232, CM-485, CM-MODBUS - Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Hitachi SJ700-2 series inverter (Modbus RTU)
Hitachi SJ700-2 series inverters using the built-in RS485 port (TM2) in Modbus-RTU mode (C079), per instruction manual NT204DX.
Also known as: SJ700, SJ700-2, SJ700 series - Variable frequency drive
Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)
Invertek Elevator Core lift drives on the RJ45 Modbus RTU port, per the online Elevator Core user guide (support.invertekdrives.com).
Also known as: Elevator Core, Optidrive Elevator Core - Variable frequency drive
INVT Goodrive35 (GD35) closed-loop vector VFD
INVT Goodrive35 closed-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD35 VFD manual V4.0 (communication protocol chapter).
Also known as: GD35, Goodrive35, GD35 vector VFD
All variable frequency drives Modbus register maps →
Source: DCS880 drives Firmware manual · 3ADW000474R0501 (rev E) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.