- Home
- Modbus register maps
- Bonfiglioli
- ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)
Variable frequency drive · Modbus register map
Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
Bonfiglioli's ACTIVE and ACTIVE Cube inverters speak Modbus RTU or ASCII through a CM-232 or CM-485 communication module. As on the Agile, the register address is the parameter number plus the data set number in the top 4 bits, and 32-bit parameters are read as two registers at one parameter address. This map covers the control and status words, RAM references, error and warning readouts and the module's Modbus settings.
This page lists 16 Modbus registers for the Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Bonfiglioli’s own free documentation (linked below) and checked against it.
- Manufacturer
- Bonfiglioli
- Model
- ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)
- Equipment type
- Variable frequency drive
- Registers
- 16 (10 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- 32-bit access with functions 3/16: ACU 5.1.12 or later
- Also known as
- ACTIVE Cube, ACU, ACU 201, ACU 401, ACU 210, ACU 410, ACTIVE, ACT, CM-232, CM-485, CM-MODBUS
Integration notes: Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)
Set 395 = 2 (Modbus RTU), baud 10 and parity 1375, address 1376, reset the inverter, then 412 = 1. Write 484 (2 registers, 0.01 Hz) and step control word 410 through 0x0006, 0x0007, 0x000F; poll 411 and 260.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 410 | Control word | BITMAP16 | Control word | Read/write |
| HR 411 | Status word | BITMAP16 | Status word | Read |
| HR 484 | Reference frequency RAM | INT32 ABCD | Frequency reference, 0.01 Hz (32-bit) | Read/write |
| HR 412 | Local/Remote | UINT16 | Local/Remote: 1 = statemachine | Read/write |
| HR 260 | Actual error | UINT16 | Actual error | Read |
| HR 395 | Protocol | UINT16 | Protocol: 2 = Modbus RTU | Read/write |
| HR 11 | VABus SST error register | UINT16 | Modbus error register | Read |
Enable Modbus control & writes
The CM module ships in VABus (395 = 0): set 395 = 2 (RTU) or 3 (ASCII) with the keypad or VPlus. Baud rate 10 (factory 19200) applies only after a reset (parameter 34 = 123) or mains off/on. For parity 1375 (factory even) the manual contradicts itself (reset needed in 5.2.1, immediate in 5.2.2), so reset after changing it. Address 1376 (factory 1) applies at once. Set 412 = 1 for control-word operation; the hardware release (STOA/STOB on ACU, S1IND on ACT) plus a Start Right/Left input are still needed.
Communication loss & watchdog
413 RS232/RS485 watchdog timer, 0-10000 s (factory 0 = off). When it expires the inverter trips with F2010 Watchdog RS232/RS485.
Byte order & addressing
- Address = parameter number + 0x1000 x data set. Data set 0 writes all four EEPROM sets; data sets 5-9 write RAM only (set + 5). Control word 410 and references 484/524 always use data set 0.
- 32-bit values are high word first and are read as 2 registers at one parameter number.
- Reading or writing a 32-bit parameter with function 3/16 needs ACU firmware 5.1.12 or later; on ACT the manual says this is still in preparation, so use functions 100/101 there.
- Picking the wrong protocol in 395 cuts off the CM port; fix it with the keypad or VPlus.
Network setup
- CM-485 has a termination switch; switch it on only at the two ends of the bus.
- Recommended cable lengths for CM-485: 1200 m at 19200, 300 m at 115200 baud.
Watch out for
- A write error blocks further writes until register 11 is read.
- A baud rate change does nothing until the inverter is reset; reset after a parity change too.
Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 10 | Baud rate | Factory 4 = 19200; active after reset (P34 = 123) or power cycle. | UINT16 | Read/write | 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 57600; 6 = 115200 | |||
| HR | 11 | VABus SST error register | Modbus/VABus error code (0-15); read it to acknowledge write errors. | UINT16 | Read | ||||
| HR | 249 | Active data set | Currently active data set 1-4. | UINT16 | Read | ||||
| HR | 260 | Actual error | Code of the current fault; reachable over the bus only. | UINT16 | Read | ||||
| HR | 270 | Warnings | Bit-coded warnings; several can be set at once. | BITMAP16 | Read | bit 0 = Warning Ixt (set with bit 1 or 2); bit 1 = Short-time Ixt; bit 2 = Long-time Ixt; bit 3 = Heat sink temperature; bit 4 = Inside temperature; bit 5 = Current limit; bit 6 = Init; bit 7 = Motor temperature; bit 8 = Mains phase failure; bit 9 = Motor protective switch; bit 10 = Fmax; bit 11 = Analog input MFI1A; bit 12 = Analog input MFI2A; bit 13 = Systembus slave in fault; bit 14 = DC link voltage (Udc); bit 15 = ACU: application warning (see 274); ACT: V-belt | |||
| HR | 274 | Application warnings | Application warning bits (ACU only). | UINT16 | Read | ||||
| HR | 395 | Protocol | Factory 0 (VABus); takes effect immediately. | UINT16 | Read/write | 0 = VABus; 1 = P-Bus (special applications); 2 = Modbus RTU; 3 = Modbus ASCII | |||
| HR | 410 | Control word | Used when Local/Remote 412 = 1 (statemachine); write in data set 0. | BITMAP16 | Read/write | bit 0 = Switch on; bit 1 = Enable voltage; bit 2 = Quick stop (0 = quick stop); bit 3 = Enable operation; bit 7 = Reset fault (rising edge) | |||
| HR | 411 | Status word | BITMAP16 | Read | bit 0 = Ready to switch on; bit 1 = Switched on; bit 2 = Operation enabled; bit 3 = Error; bit 4 = Voltage enabled (mains present); bit 5 = Quick stop; bit 6 = Switch on disabled; bit 7 = Warning (see 270); bit 9 = Remote; bit 10 = Reference value reached; bit 11 = Limit value reached; bit 15 = Warning 2 (fault switch-off imminent) | ||||
| HR | 412 | Local/Remote | UINT16 | Read/write | 0 = Control via contacts; 1 = Control via statemachine (control word 410); 2 = Control via remote contacts | ||||
| HR | 413 | RS232/RS485 watchdog timer | 0 = off (factory); fault F2010 if no valid exchange in this time. | UINT16 | s | Read/write | |||
| HR | 414 | Data set selection | 0 = digital inputs; 1-4 = set by bus; 5 = switch only when not released. | UINT16 | Read/write | ||||
| HR | 484 | Reference frequency RAM | Long, two decimals: -999.99 to 999.99 Hz. Read/write 2 registers at 484. | INT32 | ABCD | × 0.01 | Hz | Read/write | |
| HR | 524 | Reference percentage RAM | Long, two decimals: -300.00 to 300.00 %. Read/write 2 registers at 524. | INT32 | ABCD | × 0.01 | % | Read/write | |
| HR | 1375 | Modbus parity | Factory 0 = even. | UINT16 | Read/write | 0 = Even; 1 = Odd; 2 = None | |||
| HR | 1376 | Modbus address | 1-247, factory 1. | UINT16 | Read/write |
Notes on this map
- Word order comes from the manual's 32-bit write examples (44.50 Hz to parameter 482 sends 00 00 11 62; an out-of-range value sends 00 03 0D 40): high word first.
- A 32-bit parameter occupies one parameter number: request 2 registers starting at that number.
- Values with decimals are sent as integers; the scale for 484 and 524 follows their two-decimal ranges.
- The data set of 410, 484 and 524 is always zero; they are RAM values and are not written to EEPROM.
- Parameters stored in four data sets return error 9 in register 11 when read with data set 0 and the sets differ; register 11 must be read before the next write is accepted.
- In control via remote contacts (412 = 2) the control word bits act as virtual digital inputs (bit 0 = STOA+STOB on ACU, S1IND on ACT); a software-only release is not possible.
- Left out: 282/283 reference bus/ramp frequency (data type not stated) and 392 (selection list not given).
- Application warnings 274 exist on ACU only; on ACT bit 15 of 270 is the V-belt warning instead.
- Function codes 3/16 for 32-bit values need ACU firmware 5.1.12 or later; ACT must use functions 100/101 (same high-word-first layout in the manual's examples).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)
What Modbus registers does the Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII) have?
This map lists 16 registers: 16 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The start address field carries the parameter number (0-1599) in bits 0-11 and the data set (0-9) in bits 12-15, sent as-is: parameter 481 in data set 1 is 0x11E1, in data set 0 it is 0x01E1 (= 481). This map lists data set 0 addresses (parameter number). For another data set add 0x1000 x data set (data set 2 of parameter 372 = 0x2174).
What byte order does the Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)?
Start with HR 410 Control word (Control word); HR 411 Status word (Status word); HR 484 Reference frequency RAM (Frequency reference, 0.01 Hz (32-bit)); HR 412 Local/Remote (Local/Remote: 1 = statemachine); HR 260 Actual error (Actual error); HR 395 Protocol (Protocol: 2 = Modbus RTU); HR 11 VABus SST error register (Modbus error register).
How do I enable Modbus control of the Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)?
The CM module ships in VABus (395 = 0): set 395 = 2 (RTU) or 3 (ASCII) with the keypad or VPlus. Baud rate 10 (factory 19200) applies only after a reset (parameter 34 = 123) or mains off/on. For parity 1375 (factory even) the manual contradicts itself (reset needed in 5.2.1, immediate in 5.2.2), so reset after changing it. Address 1376 (factory 1) applies at once. Set 412 = 1 for control-word operation; the hardware release (STOA/STOB on ACU, S1IND on ACT) plus a Start Right/Left input are still needed.
What happens when the Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII) loses Modbus communication?
413 RS232/RS485 watchdog timer, 0-10000 s (factory 0 = off). When it expires the inverter trips with F2010 Watchdog RS232/RS485.
Where is the official Bonfiglioli ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII) Modbus documentation?
The source is Active Cube - MODBUS Communication Module CM-MODBUS / CM2-MODBUS, Frequency Inverter 230 V / 400 V (VEC 383 R4), revision 2023-04, published free by Bonfiglioli at https://www.bonfiglioli.com/_default_upload_bucket/ACT_ACU_CM232_485_Modbus_VEC383R4.pdf.
More Bonfiglioli Modbus register maps
Other variable frequency drives register maps
- Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Hitachi SJ700-2 series inverter (Modbus RTU)
Hitachi SJ700-2 series inverters using the built-in RS485 port (TM2) in Modbus-RTU mode (C079), per instruction manual NT204DX.
Also known as: SJ700, SJ700-2, SJ700 series - Variable frequency drive
Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)
Invertek Elevator Core lift drives on the RJ45 Modbus RTU port, per the online Elevator Core user guide (support.invertekdrives.com).
Also known as: Elevator Core, Optidrive Elevator Core - Variable frequency drive
INVT Goodrive35 (GD35) closed-loop vector VFD
INVT Goodrive35 closed-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD35 VFD manual V4.0 (communication protocol chapter).
Also known as: GD35, Goodrive35, GD35 vector VFD - Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028
All variable frequency drives Modbus register maps →
Source: Active Cube - MODBUS Communication Module CM-MODBUS / CM2-MODBUS, Frequency Inverter 230 V / 400 V · VEC 383 R4 · rev. 2023-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.