- SJ700-2 series inverter (Modbus RTU)
Variable frequency drive · Modbus register map
Hitachi SJ700-2 series inverter (Modbus RTU) Modbus register map
Updated 17 November 2026
The SJ700-2 is Hitachi's general-purpose sensorless-vector inverter with a built-in RS485 port that speaks Hitachi ASCII or Modbus RTU. Commands and status flags are coils, the frequency reference and monitors are holding registers, and 32-bit values are split into high and low registers. This map covers the run and terminal coils, status coils, frequency command, key d-monitors and accel/decel times.
This page lists 70 Modbus registers for the Hitachi SJ700-2 series inverter (Modbus RTU) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Hitachi’s own free documentation (linked below) and checked against it.
- Manufacturer
- Hitachi
- Model
- SJ700-2 series inverter (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 70 (18 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- SJ700, SJ700-2, SJ700 series
Integration notes: Hitachi SJ700-2 series inverter (Modbus RTU)
Set A001 = 03 and A002 = 03, write the frequency to registers 0001h-0002h (wire 0-1, 0.01 Hz) and run with coil 0001h (wire 0). Read output frequency at 1001h-1002h and current at 1003h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Operation command | BIT | Run/stop command | Read/write |
| CO 1 | Rotation direction command | BIT | Direction command | Read/write |
| HR 0 | Frequency source setting (F001) | UINT32 ABCD | Frequency command (F001) | Read/write |
| HR 4096 | Output frequency (d001) | UINT32 ABCD | Output frequency | Read |
| HR 4098 | Output current (d002) | UINT16 | Output current | Read |
| HR 3 | Inverter status B | UINT16 | Inverter status B (run/trip) | Read |
Enable Modbus control & writes
Set C079 (communication mode) to Modbus-RTU, C071 speed, C072 node address, C074 parity, C075 stop bits and C078 wait time on the keypad; set A001 = 03 and A002 = 03 to take frequency and run commands over the network.
Communication loss & watchdog
C077 sets the reception timeout (0.00-99.99 s) and C076 picks the action after a timeout (trip, decelerate and trip, ignore, free-run stop, or decelerate and stop); the NDc output (coil 0033h) signals the disconnection.
Byte order & addressing
- Requests use the printed number minus 1.
- 32-bit values are high word first.
Network setup
- RS485 on terminal block TM2 (SP, SN); use RP-SN to enable the terminating resistor.
- 2400-19200 bps, 8 data bits in Modbus-RTU mode, up to 32 inverters.
Watch out for
- The physical intelligent input terminals override the input coils.
- Register writes are lost at power-off unless 1 is written to 0900h to store them in EEPROM.
Hitachi SJ700-2 series inverter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0001h | Operation command | 1 = run, 0 = stop (when A002 = 03). | BIT | Read/write | ||||
| CO | 1doc 0002h | Rotation direction command | 1 = reverse, 0 = forward (when A002 = 03). | BIT | Read/write | ||||
| CO | 2doc 0003h | External trip (EXT) | 1 = trip. | BIT | Read/write | ||||
| CO | 3doc 0004h | Trip reset (RS) | 1 = reset. | BIT | Read/write | ||||
| CO | 6doc 0007h | Intelligent input terminal [1] | Turns the input on over the network; the physical terminal has priority. | BIT | Read/write | ||||
| CO | 7doc 0008h | Intelligent input terminal [2] | Turns the input on over the network; the physical terminal has priority. | BIT | Read/write | ||||
| CO | 8doc 0009h | Intelligent input terminal [3] | Turns the input on over the network; the physical terminal has priority. | BIT | Read/write | ||||
| CO | 9doc 000Ah | Intelligent input terminal [4] | Turns the input on over the network; the physical terminal has priority. | BIT | Read/write | ||||
| CO | 10doc 000Bh | Intelligent input terminal [5] | Turns the input on over the network; the physical terminal has priority. | BIT | Read/write | ||||
| CO | 11doc 000Ch | Intelligent input terminal [6] | Turns the input on over the network; the physical terminal has priority. | BIT | Read/write | ||||
| CO | 12doc 000Dh | Intelligent input terminal [7] | Turns the input on over the network; the physical terminal has priority. | BIT | Read/write | ||||
| CO | 13doc 000Eh | Intelligent input terminal [8] | Turns the input on over the network; the physical terminal has priority. | BIT | Read/write | ||||
| CO | 14doc 000Fh | Operation status | 1 = run, 0 = stop. | BIT | Read | ||||
| CO | 15doc 0010h | Rotation direction | 1 = reverse, 0 = forward. | BIT | Read | ||||
| CO | 16doc 0011h | Inverter ready | BIT | Read | |||||
| CO | 19doc 0014h | FA1 constant-speed reached | BIT | Read | |||||
| CO | 20doc 0015h | FA2 set frequency overreached | BIT | Read | |||||
| CO | 21doc 0016h | OL overload notice advance signal 1 | BIT | Read | |||||
| CO | 22doc 0017h | OD output deviation for PID | BIT | Read | |||||
| CO | 23doc 0018h | AL alarm signal | BIT | Read | |||||
| CO | 24doc 0019h | FA3 set frequency reached | BIT | Read | |||||
| CO | 25doc 001Ah | OTQ over-torque | BIT | Read | |||||
| CO | 26doc 001Bh | IP instantaneous power failure | BIT | Read | |||||
| CO | 27doc 001Ch | UV undervoltage | BIT | Read | |||||
| CO | 28doc 001Dh | TRQ torque limited | BIT | Read | |||||
| CO | 29doc 001Eh | RNT operation time over | BIT | Read | |||||
| CO | 30doc 001Fh | ONT plug-in time over | BIT | Read | |||||
| CO | 31doc 0020h | THM thermal alarm signal | BIT | Read | |||||
| CO | 50doc 0033h | NDc communication train disconnection | BIT | Read | |||||
| CO | 57doc 003Ah | WAC capacitor life warning | BIT | Read | |||||
| CO | 58doc 003Bh | WAF cooling-fan speed drop | BIT | Read | |||||
| CO | 60doc 003Dh | OHF heat sink overheat warning | BIT | Read | |||||
| CO | 68doc 0045h | IRDY inverter ready | BIT | Read | |||||
| CO | 69doc 0046h | FWR forward rotation | BIT | Read | |||||
| CO | 70doc 0047h | RVR reverse rotation | BIT | Read | |||||
| CO | 71doc 0048h | MJA major failure | BIT | Read | |||||
| CO | 73doc 004Ah | CRC error | Kept until an error reset. | BIT | Read | ||||
| CO | 74doc 004Bh | Overrun | Kept until an error reset. | BIT | Read | ||||
| CO | 75doc 004Ch | Framing error | Kept until an error reset. | BIT | Read | ||||
| CO | 76doc 004Dh | Parity error | Kept until an error reset. | BIT | Read | ||||
| CO | 77doc 004Eh | Sum check error | Kept until an error reset. | BIT | Read | ||||
| HR | 0doc 0001h-0002h | Frequency source setting (F001) | 0-40000; used when A001 = 03. | UINT32 | ABCD | × 0.01 | Hz | Read/write | |
| HR | 3doc 0004h | Inverter status B | UINT16 | Read | 0 = Stopping; 1 = Running; 2 = Tripping | ||||
| HR | 4doc 0005h | Inverter status C | UINT16 | Read | 0 = ---; 1 = Stopping; 2 = Decelerating; 3 = Constant-speed operation; 4 = Accelerating; 5 = Forward rotation; 6 = Reverse rotation; 7 = Switching forward to reverse; 8 = Switching reverse to forward; 9 = Starting forward rotation; 10 = Starting reverse rotation | ||||
| HR | 5doc 0006h | PID feedback | 0-10000. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 2303doc 0900h | Writing to EEPROM | UINT16 | Write | 0 = Motor constant recalculation; 1 = Store set data in EEPROM | ||||
| HR | 4096doc 1001h-1002h | Output frequency (d001) | 0-40000. | UINT32 | ABCD | × 0.01 | Hz | Read | |
| HR | 4098doc 1003h | Output current (d002) | 0-9999. | UINT16 | × 0.1 | A | Read | ||
| HR | 4099doc 1004h | Rotation direction (d003) | UINT16 | Read | 0 = Stopping; 1 = Forward rotation; 2 = Reverse rotation | ||||
| HR | 4100doc 1005h-1006h | PV / PID feedback (d004) | 0-9990. | UINT32 | ABCD | × 0.1 | Read | ||
| HR | 4102doc 1007h | Intelligent input terminal status (d005) | BITMAP16 | Read | bit 0 = Terminal 1; bit 1 = Terminal 2; bit 2 = Terminal 3; bit 3 = Terminal 4; bit 4 = Terminal 5; bit 5 = Terminal 6; bit 6 = Terminal 7; bit 7 = Terminal 8 | ||||
| HR | 4103doc 1008h | Intelligent output terminal status (d006) | BITMAP16 | Read | bit 0 = Terminal 11; bit 1 = Terminal 12; bit 2 = Terminal 13; bit 3 = Terminal 14; bit 4 = Terminal 15 | ||||
| HR | 4104doc 1009h-100Ah | Scaled output frequency (d007) | 0-39960. | UINT32 | ABCD | × 0.01 | Read | ||
| HR | 4106doc 100Bh-100Ch | Actual frequency (d008) | -40000 to +40000. | INT32 | ABCD | × 0.01 | Hz | Read | |
| HR | 4108doc 100Dh | Torque command (d009) | -200 to +200. | INT16 | % | Read | |||
| HR | 4109doc 100Eh | Torque bias (d010) | -200 to +200. | INT16 | % | Read | |||
| HR | 4111doc 1010h | Torque (d012) | -200 to +200. | INT16 | % | Read | |||
| HR | 4112doc 1011h | Output voltage (d013) | 0-6000. | UINT16 | × 0.1 | V | Read | ||
| HR | 4113doc 1012h | Power (d014) | 0-9999. | UINT16 | × 0.1 | kW | Read | ||
| HR | 4114doc 1013h-1014h | Cumulative power (d015) | 0-9999999; input power divided by the b079 display gain. | UINT32 | ABCD | × 0.1 | Read | ||
| HR | 4118doc 1017h-1018h | Cumulative power-on time (d017) | 0-999900. | UINT32 | ABCD | h | Read | ||
| HR | 4120doc 1019h | Heat sink temperature (d018) | -200 to 2000. | INT16 | × 0.1 | °C | Read | ||
| HR | 4121doc 101Ah | Motor temperature (d019) | -200 to 2000. | INT16 | × 0.1 | °C | Read | ||
| HR | 4124doc 101Dh | Life-check (d022) | BITMAP16 | Read | bit 0 = Main circuit capacitor; bit 1 = Low cooling-fan speed | ||||
| HR | 4133doc 1026h | DC voltage P-N (d102) | 0-9999. | UINT16 | × 0.1 | V | Read | ||
| HR | 4134doc 1027h | BRD load factor (d103) | 0-1000. | UINT16 | × 0.1 | % | Read | ||
| HR | 4135doc 1028h | Electronic thermal overload (d104) | 0-1000. | UINT16 | × 0.1 | % | Read | ||
| HR | 4354doc 1103h-1104h | Acceleration (1) time (F002) | 1-360000. | UINT32 | ABCD | × 0.01 | s | Read/write | |
| HR | 4356doc 1105h-1106h | Deceleration (1) time (F003) | 1-360000. | UINT32 | ABCD | × 0.01 | s | Read/write | |
| HR | 4358doc 1107h | Keypad Run key routing (F004) | UINT16 | Read/write | 0 = Forward rotation; 1 = Reverse rotation |
Notes on this map
- 32-bit values are two registers labelled (high) then (low), so ABCD.
- The trip-monitoring block 0010h-004Eh (trip counter, six trip records, programming error code) is documented but not included in this map.
- Inverter status A (0003h) is left out because its value list is cut off in the table, and cumulative RUN time (1015h) because its 0.1 resolution has no unit printed.
- Cumulative power (1013h) is listed raw with 0.1 resolution as printed; the manual gives the value as input power divided by the b079 display gain, so no fixed unit is assigned.
- Function-mode parameter registers (1201h and up) are documented in the manual but not listed here.
- Communication error coils 004Ah-004Eh stay set until an error reset.
- Coil 0013h is left out: the table names it RUN (running) but its setting column reads 1 = tripping, 0 = normal.
- Coil 0049h (data writing in progress) is left out: the Enter-command note points to coil 001Ah for that flag, while the coil table puts OTQ at 001Ah and data writing at 0049h.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Hitachi SJ700-2 series inverter (Modbus RTU)
What Modbus registers does the Hitachi SJ700-2 series inverter (Modbus RTU) have?
This map lists 70 registers: 41 coils, 29 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Hitachi SJ700-2 series inverter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Coil and register numbers are printed in hex (0001h). The manual says the starting number in a request is 1 less than the coil or register number, e.g. reading coils from 0007h sends 00 06. So wire address = printed number - 1.
What byte order does the Hitachi SJ700-2 series inverter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Hitachi SJ700-2 series inverter (Modbus RTU)?
Start with CO 0 Operation command (Run/stop command); CO 1 Rotation direction command (Direction command); HR 0 Frequency source setting (F001) (Frequency command (F001)); HR 4096 Output frequency (d001) (Output frequency); HR 4098 Output current (d002) (Output current); HR 3 Inverter status B (Inverter status B (run/trip)).
How do I enable Modbus control of the Hitachi SJ700-2 series inverter (Modbus RTU)?
Set C079 (communication mode) to Modbus-RTU, C071 speed, C072 node address, C074 parity, C075 stop bits and C078 wait time on the keypad; set A001 = 03 and A002 = 03 to take frequency and run commands over the network.
What happens when the Hitachi SJ700-2 series inverter (Modbus RTU) loses Modbus communication?
C077 sets the reception timeout (0.00-99.99 s) and C076 picks the action after a timeout (trip, decelerate and trip, ignore, free-run stop, or decelerate and stop); the NDc output (coil 0033h) signals the disconnection.
Where is the official Hitachi SJ700-2 series inverter (Modbus RTU) Modbus documentation?
The source is Hitachi Inverter SJ700-2 Series Instruction Manual (NT204DX), revision 2009-02, published free by Hitachi at https://www.hitachi-iesa.com/sites/default/files/support/inverter/docs/NT204DX_1.pdf.
More Hitachi Modbus register maps
- Variable frequency drive
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Hitachi SJ-P1 inverters on the built-in RS485 port in Modbus-RTU mode, register layout of firmware Ver. 2.00 (User's Guide NT251BX-2, Rev. 6).
Also known as: SJ-P1, P1-xxxxx-L, P1-xxxxx-H - Variable frequency drive
Hitachi WJ-C1 series inverter (Modbus RTU)
Hitachi WJ-C1 inverters using the built-in RS485 port in Modbus-RTU mode; User's Guide NT361X, chapters 11 and 18.
Also known as: WJ-C1, WJ-C1 series
Other variable frequency drives register maps
- Variable frequency drive
Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)
Invertek Elevator Core lift drives on the RJ45 Modbus RTU port, per the online Elevator Core user guide (support.invertekdrives.com).
Also known as: Elevator Core, Optidrive Elevator Core - Variable frequency drive
INVT Goodrive35 (GD35) closed-loop vector VFD
INVT Goodrive35 closed-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD35 VFD manual V4.0 (communication protocol chapter).
Also known as: GD35, Goodrive35, GD35 vector VFD - Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028 - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX
All variable frequency drives Modbus register maps →
Source: Hitachi Inverter SJ700-2 Series Instruction Manual · NT204DX · rev. 2009-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.