Variable frequency drive · Modbus register map

Hitachi SJ700-2 series inverter (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The SJ700-2 is Hitachi's general-purpose sensorless-vector inverter with a built-in RS485 port that speaks Hitachi ASCII or Modbus RTU. Commands and status flags are coils, the frequency reference and monitors are holding registers, and 32-bit values are split into high and low registers. This map covers the run and terminal coils, status coils, frequency command, key d-monitors and accel/decel times.

This page lists 70 Modbus registers for the Hitachi SJ700-2 series inverter (Modbus RTU) — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Hitachi’s own free documentation (linked below) and checked against it.

Manufacturer
Hitachi
Model
SJ700-2 series inverter (Modbus RTU)
Equipment type
Variable frequency drive
Registers
70 (18 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
SJ700, SJ700-2, SJ700 series
Source document
Hitachi Inverter SJ700-2 Series Instruction Manual · NT204DX · rev. 2009-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Hitachi SJ700-2 series inverter (Modbus RTU)

Integration in brief

Set A001 = 03 and A002 = 03, write the frequency to registers 0001h-0002h (wire 0-1, 0.01 Hz) and run with coil 0001h (wire 0). Read output frequency at 1001h-1002h and current at 1003h.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0Operation commandBITRun/stop commandRead/write
CO 1Rotation direction commandBITDirection commandRead/write
HR 0Frequency source setting (F001)UINT32 ABCDFrequency command (F001)Read/write
HR 4096Output frequency (d001)UINT32 ABCDOutput frequencyRead
HR 4098Output current (d002)UINT16Output currentRead
HR 3Inverter status BUINT16Inverter status B (run/trip)Read

Enable Modbus control & writes

Set C079 (communication mode) to Modbus-RTU, C071 speed, C072 node address, C074 parity, C075 stop bits and C078 wait time on the keypad; set A001 = 03 and A002 = 03 to take frequency and run commands over the network.

Communication loss & watchdog

C077 sets the reception timeout (0.00-99.99 s) and C076 picks the action after a timeout (trip, decelerate and trip, ignore, free-run stop, or decelerate and stop); the NDc output (coil 0033h) signals the disconnection.

Byte order & addressing

Network setup

Watch out for

Hitachi SJ700-2 series inverter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

70 of 70 shown
Hitachi SJ700-2 series inverter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0001hOperation command1 = run, 0 = stop (when A002 = 03).BITRead/write
CO1doc 0002hRotation direction command1 = reverse, 0 = forward (when A002 = 03).BITRead/write
CO2doc 0003hExternal trip (EXT)1 = trip.BITRead/write
CO3doc 0004hTrip reset (RS)1 = reset.BITRead/write
CO6doc 0007hIntelligent input terminal [1]Turns the input on over the network; the physical terminal has priority.BITRead/write
CO7doc 0008hIntelligent input terminal [2]Turns the input on over the network; the physical terminal has priority.BITRead/write
CO8doc 0009hIntelligent input terminal [3]Turns the input on over the network; the physical terminal has priority.BITRead/write
CO9doc 000AhIntelligent input terminal [4]Turns the input on over the network; the physical terminal has priority.BITRead/write
CO10doc 000BhIntelligent input terminal [5]Turns the input on over the network; the physical terminal has priority.BITRead/write
CO11doc 000ChIntelligent input terminal [6]Turns the input on over the network; the physical terminal has priority.BITRead/write
CO12doc 000DhIntelligent input terminal [7]Turns the input on over the network; the physical terminal has priority.BITRead/write
CO13doc 000EhIntelligent input terminal [8]Turns the input on over the network; the physical terminal has priority.BITRead/write
CO14doc 000FhOperation status1 = run, 0 = stop.BITRead
CO15doc 0010hRotation direction1 = reverse, 0 = forward.BITRead
CO16doc 0011hInverter readyBITRead
CO19doc 0014hFA1 constant-speed reachedBITRead
CO20doc 0015hFA2 set frequency overreachedBITRead
CO21doc 0016hOL overload notice advance signal 1BITRead
CO22doc 0017hOD output deviation for PIDBITRead
CO23doc 0018hAL alarm signalBITRead
CO24doc 0019hFA3 set frequency reachedBITRead
CO25doc 001AhOTQ over-torqueBITRead
CO26doc 001BhIP instantaneous power failureBITRead
CO27doc 001ChUV undervoltageBITRead
CO28doc 001DhTRQ torque limitedBITRead
CO29doc 001EhRNT operation time overBITRead
CO30doc 001FhONT plug-in time overBITRead
CO31doc 0020hTHM thermal alarm signalBITRead
CO50doc 0033hNDc communication train disconnectionBITRead
CO57doc 003AhWAC capacitor life warningBITRead
CO58doc 003BhWAF cooling-fan speed dropBITRead
CO60doc 003DhOHF heat sink overheat warningBITRead
CO68doc 0045hIRDY inverter readyBITRead
CO69doc 0046hFWR forward rotationBITRead
CO70doc 0047hRVR reverse rotationBITRead
CO71doc 0048hMJA major failureBITRead
CO73doc 004AhCRC errorKept until an error reset.BITRead
CO74doc 004BhOverrunKept until an error reset.BITRead
CO75doc 004ChFraming errorKept until an error reset.BITRead
CO76doc 004DhParity errorKept until an error reset.BITRead
CO77doc 004EhSum check errorKept until an error reset.BITRead
HR0doc 0001h-0002hFrequency source setting (F001)0-40000; used when A001 = 03.UINT32ABCD× 0.01HzRead/write
HR3doc 0004hInverter status BUINT16Read0 = Stopping; 1 = Running; 2 = Tripping
HR4doc 0005hInverter status CUINT16Read0 = ---; 1 = Stopping; 2 = Decelerating; 3 = Constant-speed operation; 4 = Accelerating; 5 = Forward rotation; 6 = Reverse rotation; 7 = Switching forward to reverse; 8 = Switching reverse to forward; 9 = Starting forward rotation; 10 = Starting reverse rotation
HR5doc 0006hPID feedback0-10000.UINT16× 0.01%Read/write
HR2303doc 0900hWriting to EEPROMUINT16Write0 = Motor constant recalculation; 1 = Store set data in EEPROM
HR4096doc 1001h-1002hOutput frequency (d001)0-40000.UINT32ABCD× 0.01HzRead
HR4098doc 1003hOutput current (d002)0-9999.UINT16× 0.1ARead
HR4099doc 1004hRotation direction (d003)UINT16Read0 = Stopping; 1 = Forward rotation; 2 = Reverse rotation
HR4100doc 1005h-1006hPV / PID feedback (d004)0-9990.UINT32ABCD× 0.1Read
HR4102doc 1007hIntelligent input terminal status (d005)BITMAP16Readbit 0 = Terminal 1; bit 1 = Terminal 2; bit 2 = Terminal 3; bit 3 = Terminal 4; bit 4 = Terminal 5; bit 5 = Terminal 6; bit 6 = Terminal 7; bit 7 = Terminal 8
HR4103doc 1008hIntelligent output terminal status (d006)BITMAP16Readbit 0 = Terminal 11; bit 1 = Terminal 12; bit 2 = Terminal 13; bit 3 = Terminal 14; bit 4 = Terminal 15
HR4104doc 1009h-100AhScaled output frequency (d007)0-39960.UINT32ABCD× 0.01Read
HR4106doc 100Bh-100ChActual frequency (d008)-40000 to +40000.INT32ABCD× 0.01HzRead
HR4108doc 100DhTorque command (d009)-200 to +200.INT16%Read
HR4109doc 100EhTorque bias (d010)-200 to +200.INT16%Read
HR4111doc 1010hTorque (d012)-200 to +200.INT16%Read
HR4112doc 1011hOutput voltage (d013)0-6000.UINT16× 0.1VRead
HR4113doc 1012hPower (d014)0-9999.UINT16× 0.1kWRead
HR4114doc 1013h-1014hCumulative power (d015)0-9999999; input power divided by the b079 display gain.UINT32ABCD× 0.1Read
HR4118doc 1017h-1018hCumulative power-on time (d017)0-999900.UINT32ABCDhRead
HR4120doc 1019hHeat sink temperature (d018)-200 to 2000.INT16× 0.1°CRead
HR4121doc 101AhMotor temperature (d019)-200 to 2000.INT16× 0.1°CRead
HR4124doc 101DhLife-check (d022)BITMAP16Readbit 0 = Main circuit capacitor; bit 1 = Low cooling-fan speed
HR4133doc 1026hDC voltage P-N (d102)0-9999.UINT16× 0.1VRead
HR4134doc 1027hBRD load factor (d103)0-1000.UINT16× 0.1%Read
HR4135doc 1028hElectronic thermal overload (d104)0-1000.UINT16× 0.1%Read
HR4354doc 1103h-1104hAcceleration (1) time (F002)1-360000.UINT32ABCD× 0.01sRead/write
HR4356doc 1105h-1106hDeceleration (1) time (F003)1-360000.UINT32ABCD× 0.01sRead/write
HR4358doc 1107hKeypad Run key routing (F004)UINT16Read/write0 = Forward rotation; 1 = Reverse rotation

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Hitachi SJ700-2 series inverter (Modbus RTU)

What Modbus registers does the Hitachi SJ700-2 series inverter (Modbus RTU) have?

This map lists 70 registers: 41 coils, 29 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Hitachi SJ700-2 series inverter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Coil and register numbers are printed in hex (0001h). The manual says the starting number in a request is 1 less than the coil or register number, e.g. reading coils from 0007h sends 00 06. So wire address = printed number - 1.

What byte order does the Hitachi SJ700-2 series inverter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Hitachi SJ700-2 series inverter (Modbus RTU)?

Start with CO 0 Operation command (Run/stop command); CO 1 Rotation direction command (Direction command); HR 0 Frequency source setting (F001) (Frequency command (F001)); HR 4096 Output frequency (d001) (Output frequency); HR 4098 Output current (d002) (Output current); HR 3 Inverter status B (Inverter status B (run/trip)).

How do I enable Modbus control of the Hitachi SJ700-2 series inverter (Modbus RTU)?

Set C079 (communication mode) to Modbus-RTU, C071 speed, C072 node address, C074 parity, C075 stop bits and C078 wait time on the keypad; set A001 = 03 and A002 = 03 to take frequency and run commands over the network.

What happens when the Hitachi SJ700-2 series inverter (Modbus RTU) loses Modbus communication?

C077 sets the reception timeout (0.00-99.99 s) and C076 picks the action after a timeout (trip, decelerate and trip, ignore, free-run stop, or decelerate and stop); the NDc output (coil 0033h) signals the disconnection.

Where is the official Hitachi SJ700-2 series inverter (Modbus RTU) Modbus documentation?

The source is Hitachi Inverter SJ700-2 Series Instruction Manual (NT204DX), revision 2009-02, published free by Hitachi at https://www.hitachi-iesa.com/sites/default/files/support/inverter/docs/NT204DX_1.pdf.

More Hitachi Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Hitachi Inverter SJ700-2 Series Instruction Manual · NT204DX · rev. 2009-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.