Hitachi WJ-C1 series inverter (Modbus RTU) Modbus register map
Updated 19 November 2026
The WJ-C1 compact inverter has an RS485 port that speaks Modbus RTU. Coils give run/stop, direction, reset and the intelligent input and output signals; holding registers give status words, the frequency command, all d-group monitors, trip history and every parameter. This map covers control, the main monitors, the latest trip record and the communication parameters.
This page lists 75 Modbus registers for the Hitachi WJ-C1 series inverter (Modbus RTU) — 26 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Hitachi’s own free documentation (linked below) and checked against it.
- Manufacturer
- Hitachi
- Model
- WJ-C1 series inverter (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 75 (26 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- WJ-C1, WJ-C1 series
- Source document
- WJ-C1 Series Inverter User's Guide · NT361X
Integration notes: Hitachi WJ-C1 series inverter (Modbus RTU)
Set C096 to Modbus-RTU and the C07x serial settings, then set A001 = 03 and A002 = 03 so the frequency and run command come from Modbus. Write the frequency to 0001h/0002h, start and stop with coil 0001h, and poll 0003h-0005h plus the d-group monitors from 1001h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Output frequency setting / monitor [F001] | UINT32 ABCD | Frequency command F001 | Read/write |
| CO 0 | RUN command | BIT | Run/stop | Read/write |
| CO 3 | Reset (RS) | BIT | Fault reset | Read/write |
| HR 2 | Inverter state A | UINT16 | Inverter state A | Read |
| HR 4096 | Output frequency monitor [d001] | UINT32 ABCD | Output frequency | Read |
| HR 4098 | Output current monitor [d002] | UINT16 | Output current | Read |
| HR 17 | Trip monitor 1: trip code [d081] | UINT16 | Latest trip code | Read |
| HR 4133 | DC bus voltage monitor [d102] | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
Set RS485 communication mode [C096] to Modbus-RTU, then A001 = 03 (frequency from Modbus) and A002 = 03 (run command from Modbus). Coils 0001h/0002h only act when A002 = 03.
Communication loss & watchdog
C077 sets a communication timeout (0.00 = off, up to 99.99 s); C076 selects the action on a comm error: trip, trip after deceleration, ignore (default), free run or deceleration stop.
Byte order & addressing
- Wire address is the printed hex number minus 1.
- F001 is a two-register value (0001h high, 0002h low). Reading or writing only the low word 0002h is allowed; accessing only the high word is rejected with exception 27h.
- Byte order of the data field follows [P400]; keep it at 00 Big endian unless the master needs otherwise.
- Parameter writes over Modbus are not stored in EEPROM unless 0900h is written with 1 (or the EEPROM write mode is set).
Network setup
- C071 baud (default 05 = 9600), C072 node address 1-247 (default 1), C074 parity (default none), C075 stop bits (default 1).
- Turn on the built-in 120 ohm termination switch on the inverter at the end of the line.
- Connect SP/SN for the RS485 pair and L as signal ground.
Watch out for
- The intelligent input coils are OR-ed with the physical terminals; the [d005] monitor shows only the physical terminals, not the Modbus-driven state.
- Communication error coils (004Ah-004Eh) latch until an error reset.
Hitachi WJ-C1 series inverter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc Coil 0001h | RUN command | Works when [A002] = 03. | BIT | Read/write | 0 = Stop; 1 = Run | |||
| CO | 1doc Coil 0002h | Rotation direction command | Works when [A002] = 03. | BIT | Read/write | 0 = Forward; 1 = Reverse | |||
| CO | 2doc Coil 0003h | External trip (EXT) | BIT | Read/write | 1 = Trip | ||||
| CO | 3doc Coil 0004h | Reset (RS) | BIT | Read/write | 1 = Reset | ||||
| CO | 6doc Coil 0007h | Intelligent input terminal 1 | OR-ed with the physical terminal. | BIT | Read/write | 0 = OFF; 1 = ON | |||
| CO | 7doc Coil 0008h | Intelligent input terminal 2 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 8doc Coil 0009h | Intelligent input terminal 3 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 9doc Coil 000Ah | Intelligent input terminal 4 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 10doc Coil 000Bh | Intelligent input terminal 5 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 11doc Coil 000Ch | Intelligent input terminal 6 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 12doc Coil 000Dh | Intelligent input terminal 7 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 14doc Coil 000Fh | Operation status | BIT | Read | 0 = Stop; 1 = Run | ||||
| CO | 15doc Coil 0010h | Rotation direction | BIT | Read | 0 = Forward; 1 = Reverse | ||||
| CO | 16doc Coil 0011h | Inverter ready | BIT | Read | 0 = Not ready; 1 = Ready | ||||
| CO | 18doc Coil 0013h | RUN (running) | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 19doc Coil 0014h | FA1 constant-frequency reached | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 21doc Coil 0016h | OL overload warning | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 23doc Coil 0018h | AL alarm | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 27doc Coil 001Ch | UV undervoltage | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 31doc Coil 0020h | THM motor electronic thermal alarm | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 50doc Coil 0033h | NDc communication line disconnection | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 57doc Coil 003Ah | WAC capacitor life warning | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 58doc Coil 003Bh | WAF cooling-fan life warning | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 60doc Coil 003Dh | OHF cooling fin overheat warning | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 71doc Coil 0048h | MJA major failure | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 73doc Coil 004Ah | CRC error | Latched until an error reset. | BIT | Read | 0 = No error; 1 = With error | |||
| CO | 83doc Coil 0054h | FREF frequency reference by keypad | BIT | Read | 0 = Other than keypad; 1 = Keypad | ||||
| CO | 84doc Coil 0055h | REF RUN command by keypad | BIT | Read | 0 = Other than keypad; 1 = Keypad | ||||
| HR | 0doc 0001h (High) / 0002h (Low) | Output frequency setting / monitor [F001] | Frequency command; 0.00 to max frequency (or PID % when PID on). | UINT32 | ABCD | × 0.01 | Hz | Read/write | |
| HR | 2doc 0003h | Inverter state A | UINT16 | Read | 0 = Initial state; 2 = Stop; 3 = Running; 4 = Free run stop; 5 = Jogging; 6 = DC braking; 7 = Retry; 8 = Trip; 9 = Undervoltage | ||||
| HR | 3doc 0004h | Inverter status B | UINT16 | Read | 0 = Stop; 1 = Running; 2 = Trip | ||||
| HR | 4doc 0005h | Inverter status C | UINT16 | Read | 0 = ---; 1 = Stop; 2 = Decelerating; 3 = Constant speed; 4 = Accelerating; 5 = Forward; 6 = Reverse; 7 = Forward to reverse; 8 = Reverse to forward; 9 = Forward start; 10 = Reverse start | ||||
| HR | 5doc 0006h | PID feedback | PID feedback written over Modbus, 0-100.00 %. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 16doc 0011h | Trip count monitor [d080] | Number of trips, 0-65535. | UINT16 | times | Read | |||
| HR | 17doc 0012h | Trip monitor 1: trip code [d081] | Latest trip code E01-E99. | UINT16 | Read | ||||
| HR | 18doc 0013h | Trip monitor 1: inverter status at trip | Status digit n (0-9) shown after the trip code. | UINT16 | Read | ||||
| HR | 19doc 0014h (High) / 0015h (Low) | Trip monitor 1: output frequency at trip | UINT32 | ABCD | × 0.01 | Hz | Read | ||
| HR | 21doc 0016h | Trip monitor 1: output current at trip | UINT16 | × 0.01 | A | Read | |||
| HR | 22doc 0017h | Trip monitor 1: DC bus voltage at trip | UINT16 | × 0.1 | V | Read | |||
| HR | 77doc 004Eh | Warning monitor [d090] | Current warning code. | UINT16 | Read | ||||
| HR | 2303doc 0900h | Write EEPROM | 0 = recalculate motor constants, 1 = store set values in EEPROM. | UINT16 | Write | ||||
| HR | 4096doc 1001h (High) / 1002h (Low) | Output frequency monitor [d001] | 0.00-590.00 Hz. | UINT32 | ABCD | × 0.01 | Hz | Read | |
| HR | 4098doc 1003h | Output current monitor [d002] | 0.00-655.35 A. | UINT16 | × 0.01 | A | Read | ||
| HR | 4099doc 1004h | Rotation direction monitor [d003] | Codes 0-2; guide shows only keypad symbols F / o / r, not the mapping. | UINT16 | Read | ||||
| HR | 4100doc 1005h (High) / 1006h (Low) | PID feedback value monitor [d004] | UINT32 | ABCD | × 0.1 | % | Read | ||
| HR | 4102doc 1007h | Input terminal monitor [d005] | Bit per input terminal 1-8. | BITMAP16 | Read | ||||
| HR | 4103doc 1008h | Output terminal monitor [d006] | Bits for outputs 11, 12 and relay. | BITMAP16 | Read | ||||
| HR | 4106doc 100Bh (High) / 100Ch (Low) | Detect speed monitor [d008] | -590.00 to +590.00 Hz. | INT32 | ABCD | × 0.01 | Hz | Read | |
| HR | 4108doc 100Dh | Torque reference monitor [d009] | INT16 | % | Read | ||||
| HR | 4111doc 1010h | Output torque monitor [d012] | INT16 | % | Read | ||||
| HR | 4112doc 1011h | Output voltage monitor [d013] | UINT16 | × 0.1 | V | Read | |||
| HR | 4113doc 1012h | Input power monitor [d014] | UINT16 | × 0.1 | kW | Read | |||
| HR | 4114doc 1013h (High) / 1014h (Low) | Accumulated input power monitor [d015] | Unit is 1 kWh times the [b079] gain. | UINT32 | ABCD | Read | |||
| HR | 4116doc 1015h (High) / 1016h (Low) | Accumulated RUN time monitor [d016] | UINT32 | ABCD | h | Read | |||
| HR | 4118doc 1017h (High) / 1018h (Low) | Accumulated power-on time monitor [d017] | UINT32 | ABCD | h | Read | |||
| HR | 4120doc 1019h | Cooling fin temperature monitor [d018] | -20.0 to 150.0. | INT16 | × 0.1 | °C | Read | ||
| HR | 4133doc 1026h | DC bus voltage monitor [d102] | UINT16 | × 0.1 | V | Read | |||
| HR | 4134doc 1027h | BRD load ratio monitor [d103] | Braking resistor duty. | UINT16 | × 0.1 | % | Read | ||
| HR | 4135doc 1028h | Electronic thermal load ratio monitor (motor) [d104] | UINT16 | × 0.1 | % | Read | |||
| HR | 4184doc 1059h | Frequency input source monitor [d062] | UINT16 | Read | 0 = Keypad (multi-speed 0); 1 = Multi-speed 1; 2 = Multi-speed 2; 3 = Multi-speed 3; 4 = Multi-speed 4; 5 = Multi-speed 5; 6 = Multi-speed 6; 7 = Multi-speed 7; 8 = Multi-speed 8; 9 = Multi-speed 9; 10 = Multi-speed 10; 11 = Multi-speed 11; 12 = Multi-speed 12; 13 = Multi-speed 13; 14 = Multi-speed 14; 15 = Multi-speed 15; 16 = Jogging; 18 = Modbus communication; 19 = Option; 21 = External POT; 22 = Pulse input; 23 = Calculation function result; 24 = EzSQ; 25 = [Ai1] input; 26 = [Ai2] input; 27 = [Ai1] + [Ai2] input | ||||
| HR | 4185doc 105Ah | RUN command input source monitor [d063] | UINT16 | Read | 1 = Control terminal; 2 = Keypad (RUN key); 3 = Modbus communication; 4 = Option | ||||
| HR | 4237doc 108Eh | Analog input [Ai1] monitor [d130] | Raw 0-1023. | UINT16 | Read | ||||
| HR | 4238doc 108Fh | Analog input [Ai2] monitor [d131] | Raw 0-1023. | UINT16 | Read | ||||
| HR | 4354doc 1103h (High) / 1104h (Low) | Acceleration time 1, 1st motor [F002] | 0.00-3600.00 s. | UINT32 | ABCD | × 0.01 | s | Read/write | |
| HR | 4356doc 1105h (High) / 1106h (Low) | Deceleration time 1, 1st motor [F003] | 0.00-3600.00 s. | UINT32 | ABCD | × 0.01 | s | Read/write | |
| HR | 4358doc 1107h | RUN-key rotation direction [F004] | UINT16 | Read/write | 0 = Forward; 1 = Reverse | ||||
| HR | 4608doc 1201h | Frequency input source, 1st motor [A001] | Set 03 to take the frequency from Modbus. | UINT16 | Read/write | 0 = External operator POT; 1 = Control terminal; 2 = Parameter setting; 3 = Modbus communication; 4 = Option; 6 = Pulse input; 7 = Program function (EzSQ); 10 = Calculation function result | |||
| HR | 4609doc 1202h | RUN command source, 1st motor [A002] | Set 03 to run/stop from Modbus. | UINT16 | Read/write | 1 = Control terminal; 2 = Keypad (RUN key); 3 = Modbus communication; 4 = Option | |||
| HR | 5194doc 144Bh | RS485 baud rate [C071] | UINT16 | Read/write | 3 = 2400 bps; 4 = 4800 bps; 5 = 9600 bps; 6 = 19.2 kbps; 7 = 38.4 kbps; 8 = 57.6 kbps; 9 = 76.8 kbps; 10 = 115.2 kbps | ||||
| HR | 5195doc 144Ch | RS485 node address [C072] | 1-247. | UINT16 | Read/write | ||||
| HR | 5197doc 144Eh | RS485 parity [C074] | UINT16 | Read/write | 0 = No parity; 1 = Even parity; 2 = Odd parity | ||||
| HR | 5198doc 144Fh | RS485 stop bits [C075] | UINT16 | Read/write | 1 = 1 bit; 2 = 2 bits | ||||
| HR | 5199doc 1450h | RS485 communication error action [C076] | UINT16 | Read/write | 0 = Trip; 1 = Trip after deceleration stop; 2 = Ignore; 3 = Free run stop; 4 = Deceleration stop | ||||
| HR | 5200doc 1451h | RS485 communication timeout [C077] | 0.00 = disabled, 0.01-99.99 s. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 5201doc 1452h | RS485 communication wait time [C078] | Extra reply delay. | UINT16 | ms | Read/write |
Notes on this map
- Two-register values are printed as (High) then (Low) register. With Endian selection [P400] = 00 Big endian (default) a two-register value 01020304h is sent as 01 02 03 04, which is ABCD. Little endian (01) and special endian (02) change the byte order; trip history registers 0012h-004Eh always read big endian.
- Only a working subset is listed: control coils, status words, main d-group monitors, trip monitor 1, F001-F004, A001/A002 and the C07x communication settings. Trip monitors 2-6 follow at 001Ch, 0026h, 0030h, 003Ah and 0044h with the same layout as trip monitor 1. The full parameter list is in chapter 18.
- Accumulated input power [d015] is in units of 1 kWh multiplied by the [b079] gain, so no fixed unit is given here.
- Inverter state A (0003h) has no code 1 in the source.
- Coils 0010h-0058h can also be read as packed words at 1E01h-1E05h, and coils 0001h-000Fh written via 1F01h; not listed separately.
- The rotation direction monitor [d003] is printed with keypad symbols only (F / o / r for 0-2); the exact code-to-symbol order is not stated, so no value list is given.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Hitachi WJ-C1 series inverter (Modbus RTU)
What Modbus registers does the Hitachi WJ-C1 series inverter (Modbus RTU) have?
This map lists 75 registers: 28 coils, 47 holding registers. 26 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Hitachi WJ-C1 series inverter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints coil and register numbers in hex starting at 0001h and says the start number in the frame is the register number minus 1 (its coil read example asks for coil 0007h with 0006h). So wire address = printed number - 1: register 1001h is wire 0x1000.
What byte order does the Hitachi WJ-C1 series inverter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Hitachi WJ-C1 series inverter (Modbus RTU)?
Start with HR 0 Output frequency setting / monitor [F001] (Frequency command F001); CO 0 RUN command (Run/stop); CO 3 Reset (RS) (Fault reset); HR 2 Inverter state A (Inverter state A); HR 4096 Output frequency monitor [d001] (Output frequency); HR 4098 Output current monitor [d002] (Output current); HR 17 Trip monitor 1: trip code [d081] (Latest trip code); HR 4133 DC bus voltage monitor [d102] (DC bus voltage).
How do I enable Modbus control of the Hitachi WJ-C1 series inverter (Modbus RTU)?
Set RS485 communication mode [C096] to Modbus-RTU, then A001 = 03 (frequency from Modbus) and A002 = 03 (run command from Modbus). Coils 0001h/0002h only act when A002 = 03.
What happens when the Hitachi WJ-C1 series inverter (Modbus RTU) loses Modbus communication?
C077 sets a communication timeout (0.00 = off, up to 99.99 s); C076 selects the action on a comm error: trip, trip after deceleration, ignore (default), free run or deceleration stop.
Where is the official Hitachi WJ-C1 series inverter (Modbus RTU) Modbus documentation?
The source is WJ-C1 Series Inverter User's Guide (NT361X), published free by Hitachi at https://www.hitachi-iesa.com/sites/default/files/supportingdocs/WJ-C1_UsersGuide_NT361X.pdf.
More Hitachi Modbus register maps
- Variable frequency drive
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Hitachi SJ-P1 inverters on the built-in RS485 port in Modbus-RTU mode, register layout of firmware Ver. 2.00 (User's Guide NT251BX-2, Rev. 6).
Also known as: SJ-P1, P1-xxxxx-L, P1-xxxxx-H - Variable frequency drive
Hitachi SJ700-2 series inverter (Modbus RTU)
Hitachi SJ700-2 series inverters using the built-in RS485 port (TM2) in Modbus-RTU mode (C079), per instruction manual NT204DX.
Also known as: SJ700, SJ700-2, SJ700 series
Other variable frequency drives register maps
- Variable frequency drive
Invertek Drives Optidrive P2 (built-in Modbus RTU)
Invertek Optidrive P2 drives (0.75-250 kW) using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-P2MAN-IN V3.10.
Also known as: ODP-2, Optidrive P2 IP20, Optidrive P2 IP55, Optidrive P2 IP66 - Variable frequency drive
INVT Goodrive350 (GD350) high-performance multifunction VFD
INVT Goodrive350 drives (not GD350A) using the built-in RS-485 Modbus RTU port, per the GD350 manual V1.1 (communication chapter).
Also known as: GD350, Goodrive350, GD350 series - Variable frequency drive
Lenze SMVector drive with ESVZAR0 RS-485 Modbus module
Lenze AC Tech SMVector drives up to 10 HP with the ESVZAR0 RS-485 Modbus module, module software 1.01 / 1.10 / 1.30 (guide CMVMB401C).
Also known as: SMVector, SMV, ESVZAR0, Lenze AC Tech SMV, CMVMB401C - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D - Variable frequency drive
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse A510 inverters using the built-in RS-485 port (CN6), per communication addendum DOCUMENT-TECO-A510-AC001 Ver01 (2015-04).
Also known as: TECO A510, A510s
All variable frequency drives Modbus register maps →
Source: WJ-C1 Series Inverter User's Guide · NT361X. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.