Variable frequency drive · Modbus register map
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus register map
Updated 17 November 2026
The A510 is TECO-Westinghouse's general-purpose vector inverter with a built-in RS-485 port speaking Modbus RTU or ASCII. Commands, frequency, torque and speed limit are written to 2501H-2504H; status, fault and warning codes and monitors are read from 2520H-252FH. Each parameter nn-mm has its own register, with the group in the high byte and the number in the low byte.
This page lists 16 Modbus registers for the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.
- Manufacturer
- TECO-Westinghouse
- Model
- A510 inverter (Modbus RTU/ASCII)
- Equipment type
- Variable frequency drive
- Registers
- 16 (4 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- TECO A510, A510s
Integration notes: TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
Set the node address and serial parameters and select communication as run/frequency source, then write 2501H and 2502H (0.01 Hz) and poll 2520H-2528H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 9473 | Operation signal | BITMAP16 | Run/stop, direction, reset | Read/write |
| HR 9474 | Frequency command | UINT16 | Frequency command | Read/write |
| HR 9504 | State signal | BITMAP16 | Status bits | Read |
| HR 9505 | Error description | UINT16 | Fault code | Read |
| HR 9508 | Output frequency | UINT16 | Output frequency | Read |
| HR 9511 | Output current | UINT16 | Output current | Read |
| HR 9512 | Alarm description | UINT16 | Warning code | Read |
Enable Modbus control & writes
Set node address and communication settings at the keypad and select communication as run and frequency source (parameter numbers are in the A510 manual). Bit 15 of 2501H with 2503H gives torque control by communication.
Byte order & addressing
- Registers are hex.
- Functions 03H, 06H, 08H and 10H; maximum frame 80 bytes.
- Node addresses 01H-FEH; 00H is broadcast.
- Exception 04 means more than 32 registers were requested.
Network setup
- RS-485 on CN6: S+ / S- per the CN6 pin-out.
- The addendum shows 120 ohm terminators on p. 1-1 but says 220 ohm in Appendix A; up to 31 inverters.
Watch out for
- Exception codes: 01 function, 02 register number, 03 data setting, 04 more than 32 registers.
- Inverter response time is about 10 ms.
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 9473doc 2501H | Operation signal | Run, direction, fault, reset, comm inputs S1-S8, inverter/torque mode. | BITMAP16 | Read/write | bit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault; bit 3 = Fault reset; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 11 = Comm input S6; bit 12 = Comm input S7; bit 13 = Comm input S8; bit 14 = Inverter mode; bit 15 = Torque command set by communication | |||
| HR | 9474doc 2502H | Frequency command | 0.1 Hz instead if max output frequency exceeds 300 Hz. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 9475doc 2503H | Torque command | +/-8192 = +/-100 % of rated torque. | INT16 | × 0.0122070312 | % | Read/write | ||
| HR | 9476doc 2504H | Speed limit | +/-120 = +/-120 %. | INT16 | % | Read/write | |||
| HR | 9504doc 2520H | State signal | BITMAP16 | Read | bit 0 = Running; bit 1 = Reverse; bit 2 = Inverter ready; bit 3 = Fault active; bit 4 = Warning; bit 5 = Zero speed; bit 6 = Is 440 V; bit 7 = Frequency agree; bit 8 = Set frequency agree; bit 9 = Frequency detection 1; bit 10 = Frequency detection 2; bit 11 = Under voltage; bit 12 = Baseblock; bit 13 = Frequency reference not from comm; bit 14 = Sequence not from comm; bit 15 = Over torque | ||||
| HR | 9505doc 2521H | Error description | Active fault code. | UINT16 | Read | 1 = UV; 2 = OC; 3 = OV; 4 = OH1; 5 = OL1; 6 = OL2; 7 = OT; 8 = UT; 9 = SC; 10 = Ground OC; 11 = Fuse broken; 12 = Input phase loss; 13 = Output phase loss; 14 = PG overspeed; 15 = PG open; 16 = PG speed deviation; 17 = External fault 01; 18 = External fault 02; 19 = External fault 03; 20 = External fault 04; 21 = External fault 05; 22 = External fault 06; 23 = External fault 07; 24 = External fault 08; 25 = FB; 26 = OPR; 28 = CE; 29 = STO; 30 = Over torque 2; 38 = CF07; 41 = OLDOP; 47 = SS1; 48 = CF20; 49 = RUN | |||
| HR | 9506doc 2522H | DI state | Terminals S1-S8. | BITMAP16 | Read | bit 0 = Terminal S1; bit 1 = Terminal S2; bit 2 = Terminal S3; bit 3 = Terminal S4; bit 4 = Terminal S5; bit 5 = Terminal S6; bit 6 = Terminal S7; bit 7 = Terminal S8 | |||
| HR | 9507doc 2523H | Frequency command | UINT16 | × 0.01 | Hz | Read | |||
| HR | 9508doc 2524H | Output frequency | 0.1 Hz instead if max output frequency exceeds 300 Hz. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 9510doc 2526H | DC voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 9511doc 2527H | Output current | UINT16 | × 0.1 | A | Read | |||
| HR | 9512doc 2528H | Alarm description | Active warning code. | UINT16 | Read | 0 = No alarm; 1 = OV; 2 = UV; 3 = OL2; 4 = OH2; 6 = OT; 9 = UT; 10 = OS; 11 = PGO; 12 = DEV; 13 = CE; 14 = CALL; 16 = EF0; 17 = EF1; 18 = EF2; 19 = EF3; 20 = EF4; 21 = EF5; 22 = EF6; 23 = EF7; 24 = EF8; 26 = CLB; 28 = CT; 29 = USP; 30 = RDE; 31 = WRE; 32 = FB; 33 = VRYE; 34 = SE01; 35 = SE02; 36 = SE03; 38 = SE05; 39 = HPERR; 40 = EF; 43 = RDP; 45 = OL1; 46 = HP_ER; 47 = SE10; 49 = BB1; 50 = BB2; 51 = BB3; 52 = BB4; 53 = BB5; 54 = BB6; 55 = BB7; 56 = BB8; 61 = RETRY; 62 = SE07; 63 = SE08; 65 = OH1; 66 = FIRE; 67 = ES; 68 = STP1; 69 = BDERR; 70 = EPERR; 71 = ADCER; 73 = STP0; 74 = ENC; 75 = STP2 | |||
| HR | 9515doc 252BH | AO2 value | 0-1000 = 0.00-10.00 V or 4-20 mA. | UINT16 | Read | ||||
| HR | 9516doc 252CH | AI1 input | UINT16 | × 0.1 | % | Read | |||
| HR | 9517doc 252DH | AI2 input | UINT16 | × 0.1 | % | Read | |||
| HR | 9519doc 252FH | Model check | A510 identification value. | UINT16 | Read |
Notes on this map
- Frequency registers are 0.01 Hz, but the addendum says resolution becomes 0.1 Hz when the motor's maximum output frequency is above 300 Hz.
- The addendum does not name the drive parameters for node address, baud rate, parity or run/frequency source; set those per the A510 manual.
- 2521H (faults) and 2528H (warnings) are code tables, mapped as enums; empty table cells are omitted.
- Left out: 2505H and 252AH AO1 command/readback (raw scale not stated), 2506H AO2 command, 2507H DO and 2529H digital output state (no bit list).
- Parameter 12-00 is 32-bit (2510H high word, 2511H low word) and is not listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)
What Modbus registers does the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) have?
This map lists 16 registers: 16 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged (2520H is sent as 25 20; the 03H example reads 01 23). Parameters map group to the high byte and number to the low byte (11-44 = 0B2CH), except 12-00 which is 32-bit at 2510H (high word) / 2511H (low word).
What are the minimum Modbus registers to integrate the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)?
Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command); HR 9504 State signal (Status bits); HR 9505 Error description (Fault code); HR 9508 Output frequency (Output frequency); HR 9511 Output current (Output current); HR 9512 Alarm description (Warning code).
How do I enable Modbus control of the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)?
Set node address and communication settings at the keypad and select communication as run and frequency source (parameter numbers are in the A510 manual). Bit 15 of 2501H with 2503H gives torque control by communication.
Where is the official TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus documentation?
The source is A510 Communication Addendum Modbus RTU/ASCII (DOCUMENT-TECO-A510-AC001 Ver01), revision 2015-04, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/A510_comm_addendum.pdf.
More TECO-Westinghouse Modbus register maps
- Variable frequency drive
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 Compact (E510N1) inverters with the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510N1-AC002 Ver01 (2017-08).
Also known as: E510N1, E510s, TECO E510 Compact - Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum - Variable frequency drive
TECO-Westinghouse EV micro inverter (Modbus RTU/ASCII)
TECO-Westinghouse EV series micro inverters with the RS-485 option card, per the EV Inverter Series Modbus Communication Manual.
Also known as: TECO EV, EV Inverter Series - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive - Variable frequency drive
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse L510 micro inverters with the RS-485 option card, per communication addendum DOCUMENT-TECO-L510-AC001 Ver01 (2015-06).
Also known as: TECO L510, L510 Communication Addendum
Other variable frequency drives register maps
- Variable frequency drive
Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)
Toshiba TOSVERT VF-nC3 series inverters using the built-in RS-485 port with f829 = 1 (Modbus RTU), per manual E6581657.
Also known as: VF-nC3, VF-nC3M, TOSVERT VF-nC3, VFNC3 - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U
All variable frequency drives Modbus register maps →
Source: A510 Communication Addendum Modbus RTU/ASCII · DOCUMENT-TECO-A510-AC001 Ver01 · rev. 2015-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.