Variable frequency drive · Modbus register map

TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus register map

Updated 17 November 2026

Short answer

The A510 is TECO-Westinghouse's general-purpose vector inverter with a built-in RS-485 port speaking Modbus RTU or ASCII. Commands, frequency, torque and speed limit are written to 2501H-2504H; status, fault and warning codes and monitors are read from 2520H-252FH. Each parameter nn-mm has its own register, with the group in the high byte and the number in the low byte.

This page lists 16 Modbus registers for the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from TECO-Westinghouse’s own free documentation (linked below) and checked against it.

Manufacturer
TECO-Westinghouse
Model
A510 inverter (Modbus RTU/ASCII)
Equipment type
Variable frequency drive
Registers
16 (4 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
Also known as
TECO A510, A510s
Source document
A510 Communication Addendum Modbus RTU/ASCII · DOCUMENT-TECO-A510-AC001 Ver01 · rev. 2015-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)

Integration in brief

Set the node address and serial parameters and select communication as run/frequency source, then write 2501H and 2502H (0.01 Hz) and poll 2520H-2528H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 9473Operation signalBITMAP16Run/stop, direction, resetRead/write
HR 9474Frequency commandUINT16Frequency commandRead/write
HR 9504State signalBITMAP16Status bitsRead
HR 9505Error descriptionUINT16Fault codeRead
HR 9508Output frequencyUINT16Output frequencyRead
HR 9511Output currentUINT16Output currentRead
HR 9512Alarm descriptionUINT16Warning codeRead

Enable Modbus control & writes

Set node address and communication settings at the keypad and select communication as run and frequency source (parameter numbers are in the A510 manual). Bit 15 of 2501H with 2503H gives torque control by communication.

Byte order & addressing

Network setup

Watch out for

TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

16 of 16 shown
TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR9473doc 2501HOperation signalRun, direction, fault, reset, comm inputs S1-S8, inverter/torque mode.BITMAP16Read/writebit 0 = Run (0 stop); bit 1 = Reverse (0 forward); bit 2 = External fault; bit 3 = Fault reset; bit 6 = Comm input S1; bit 7 = Comm input S2; bit 8 = Comm input S3; bit 9 = Comm input S4; bit 10 = Comm input S5; bit 11 = Comm input S6; bit 12 = Comm input S7; bit 13 = Comm input S8; bit 14 = Inverter mode; bit 15 = Torque command set by communication
HR9474doc 2502HFrequency command0.1 Hz instead if max output frequency exceeds 300 Hz.UINT16× 0.01HzRead/write
HR9475doc 2503HTorque command+/-8192 = +/-100 % of rated torque.INT16× 0.0122070312%Read/write
HR9476doc 2504HSpeed limit+/-120 = +/-120 %.INT16%Read/write
HR9504doc 2520HState signalBITMAP16Readbit 0 = Running; bit 1 = Reverse; bit 2 = Inverter ready; bit 3 = Fault active; bit 4 = Warning; bit 5 = Zero speed; bit 6 = Is 440 V; bit 7 = Frequency agree; bit 8 = Set frequency agree; bit 9 = Frequency detection 1; bit 10 = Frequency detection 2; bit 11 = Under voltage; bit 12 = Baseblock; bit 13 = Frequency reference not from comm; bit 14 = Sequence not from comm; bit 15 = Over torque
HR9505doc 2521HError descriptionActive fault code.UINT16Read1 = UV; 2 = OC; 3 = OV; 4 = OH1; 5 = OL1; 6 = OL2; 7 = OT; 8 = UT; 9 = SC; 10 = Ground OC; 11 = Fuse broken; 12 = Input phase loss; 13 = Output phase loss; 14 = PG overspeed; 15 = PG open; 16 = PG speed deviation; 17 = External fault 01; 18 = External fault 02; 19 = External fault 03; 20 = External fault 04; 21 = External fault 05; 22 = External fault 06; 23 = External fault 07; 24 = External fault 08; 25 = FB; 26 = OPR; 28 = CE; 29 = STO; 30 = Over torque 2; 38 = CF07; 41 = OLDOP; 47 = SS1; 48 = CF20; 49 = RUN
HR9506doc 2522HDI stateTerminals S1-S8.BITMAP16Readbit 0 = Terminal S1; bit 1 = Terminal S2; bit 2 = Terminal S3; bit 3 = Terminal S4; bit 4 = Terminal S5; bit 5 = Terminal S6; bit 6 = Terminal S7; bit 7 = Terminal S8
HR9507doc 2523HFrequency commandUINT16× 0.01HzRead
HR9508doc 2524HOutput frequency0.1 Hz instead if max output frequency exceeds 300 Hz.UINT16× 0.01HzRead
HR9510doc 2526HDC voltageUINT16× 0.1VRead
HR9511doc 2527HOutput currentUINT16× 0.1ARead
HR9512doc 2528HAlarm descriptionActive warning code.UINT16Read0 = No alarm; 1 = OV; 2 = UV; 3 = OL2; 4 = OH2; 6 = OT; 9 = UT; 10 = OS; 11 = PGO; 12 = DEV; 13 = CE; 14 = CALL; 16 = EF0; 17 = EF1; 18 = EF2; 19 = EF3; 20 = EF4; 21 = EF5; 22 = EF6; 23 = EF7; 24 = EF8; 26 = CLB; 28 = CT; 29 = USP; 30 = RDE; 31 = WRE; 32 = FB; 33 = VRYE; 34 = SE01; 35 = SE02; 36 = SE03; 38 = SE05; 39 = HPERR; 40 = EF; 43 = RDP; 45 = OL1; 46 = HP_ER; 47 = SE10; 49 = BB1; 50 = BB2; 51 = BB3; 52 = BB4; 53 = BB5; 54 = BB6; 55 = BB7; 56 = BB8; 61 = RETRY; 62 = SE07; 63 = SE08; 65 = OH1; 66 = FIRE; 67 = ES; 68 = STP1; 69 = BDERR; 70 = EPERR; 71 = ADCER; 73 = STP0; 74 = ENC; 75 = STP2
HR9515doc 252BHAO2 value0-1000 = 0.00-10.00 V or 4-20 mA.UINT16Read
HR9516doc 252CHAI1 inputUINT16× 0.1%Read
HR9517doc 252DHAI2 inputUINT16× 0.1%Read
HR9519doc 252FHModel checkA510 identification value.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)

What Modbus registers does the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) have?

This map lists 16 registers: 16 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged (2520H is sent as 25 20; the 03H example reads 01 23). Parameters map group to the high byte and number to the low byte (11-44 = 0B2CH), except 12-00 which is 32-bit at 2510H (high word) / 2511H (low word).

What are the minimum Modbus registers to integrate the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)?

Start with HR 9473 Operation signal (Run/stop, direction, reset); HR 9474 Frequency command (Frequency command); HR 9504 State signal (Status bits); HR 9505 Error description (Fault code); HR 9508 Output frequency (Output frequency); HR 9511 Output current (Output current); HR 9512 Alarm description (Warning code).

How do I enable Modbus control of the TECO-Westinghouse A510 inverter (Modbus RTU/ASCII)?

Set node address and communication settings at the keypad and select communication as run and frequency source (parameter numbers are in the A510 manual). Bit 15 of 2501H with 2503H gives torque control by communication.

Where is the official TECO-Westinghouse A510 inverter (Modbus RTU/ASCII) Modbus documentation?

The source is A510 Communication Addendum Modbus RTU/ASCII (DOCUMENT-TECO-A510-AC001 Ver01), revision 2015-04, published free by TECO-Westinghouse at https://tecowestinghouse.com/PDF/A510_comm_addendum.pdf.

More TECO-Westinghouse Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: A510 Communication Addendum Modbus RTU/ASCII · DOCUMENT-TECO-A510-AC001 Ver01 · rev. 2015-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.