Easy Modbus
  1. Home
  2. Modbus register maps
  3. Yaskawa
  4. Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)

Variable frequency drive (HVAC fan / pump) · Modbus register map

Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Z1000 is Yaskawa's HVAC fan and pump drive; its built-in RS-485 port speaks MEMOBUS/Modbus RTU, BACnet, Metasys N2 or APOGEE FLN. Commands are written to hex registers 0001H-000FH, status, fault and alarm words are read from 0020H upward, U monitors from 0040H, and parameters have their own hex addresses. This map covers the command block, status/fault/alarm words, main monitors, fault codes and the b1/H5 setup parameters.

This page lists 53 Modbus registers for the Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yaskawa
Model
Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Equipment type
Variable frequency drive (HVAC fan / pump)
Registers
53 (21 writable)
Transport
Modbus RTU
Default unit ID
31
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump
Source document
YASKAWA AC Drive Z1000 AC Drive for HVAC Fan and Pump Programming Manual · SIEP YAIZ1U 03C
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)

Integration in brief

Set H5-08 = 0 and H5-01..H5-03, power-cycle, set b1-01 = 2 and b1-02 = 2, then write 0001H/0002H with function 10H and poll 0020H-002DH.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Operation commands and multi-function inputsBITMAP16Run/stop and resetRead/write
HR 2Frequency referenceUINT16Frequency referenceRead/write
HR 32Drive status 1BITMAP16Drive status 1Read
HR 33Fault contents 1BITMAP16Fault contents 1Read
HR 36Output frequencyUINT16Output frequencyRead
HR 38Output currentUINT16Output currentRead
HR 44Drive status 2BITMAP16Status 2 incl. comm timeoutRead
HR 128Current fault (U2-01)UINT16Current fault codeRead

Enable Modbus control & writes

H5-08 = 0 selects MEMOBUS/Modbus (1 N2, 2 P1, 3 BACnet). H5-01 address (default 1Fh), H5-02 speed (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 (AUTO mode sources) hand reference and run to serial communications.

Communication loss & watchdog

H5-05 = 1 (default) enables CE detection after H5-09 (default 2.0 s); H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast stop, 3 alarm only (default), 4 run at d1-04. 002CH bit F flags the timeout.

Byte order & addressing

Network setup

Watch out for

Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

53 of 53 shown
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HOperation commands and multi-function inputsBits 0/1 meaning set by H5-12.BITMAP16Read/writebit 0 = H5-12=0: forward run; H5-12=1: run; bit 1 = H5-12=0: reverse run; H5-12=1: reverse direction; bit 2 = External fault (EF0); bit 3 = Fault reset; bit 4 = Multi-function input 1; bit 5 = Multi-function input 2; bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5; bit 9 = Multi-function input 6; bit 10 = Multi-function input 7
HR2doc 0002HFrequency referenceUnits set by o1-03.UINT16Read/write
HR6doc 0006HPI targetSigned, 0.01 % units.INT16× 0.01%Read/write
HR9doc 0009HMulti-function digital output settingsBITMAP16Read/writebit 0 = Contact output 1 (M1-M2); bit 1 = Contact output 2 (M3-M4); bit 2 = Contact output 3 (M5-M6); bit 6 = Enable bit 7; bit 7 = Fault contact output (MA/MB-MC)
HR15doc 000FHControl selection settingBITMAP16Read/writebit 1 = PI setpoint input; bit 4 = PI2 target input from Modbus; bit 12 = Broadcast S5 enable; bit 13 = Broadcast S6 enable; bit 14 = Broadcast S7 enable
HR32doc 0020HDrive status 1BITMAP16Readbit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Output 1 (M1-M2); bit 6 = Output 2 (M3-M4); bit 7 = Output 3 (M5-M6); bit 14 = ComRef status; bit 15 = ComCtrl status
HR33doc 0021HFault contents 1BITMAP16Readbit 0 = oC / GF; bit 1 = ov; bit 2 = oL2; bit 3 = oH1 / oH2; bit 6 = FbL / FbH PI feedback loss; bit 7 = EF to EF7 external fault; bit 8 = CPF hardware fault (incl. oFx); bit 9 = oL1 / oL3 / UL3; bit 11 = Uv main circuit undervoltage; bit 12 = Uv1 / Uv2 / Uv3; bit 13 = LF / PF phase loss; bit 14 = CE / bUS communication error; bit 15 = oPr operator connection fault
HR34doc 0022HData link statusBITMAP16Readbit 0 = Writing data or switching motors; bit 3 = Upper or lower limit error; bit 4 = Data conformity error; bit 5 = Writing to EEPROM
HR35doc 0023HFrequency referenceUnits set by o1-03.UINT16Read
HR36doc 0024HOutput frequencyUnits set by o1-03.UINT16Read
HR38doc 0026HOutput currentUINT16× 0.1ARead
HR41doc 0029HFault contents 2BITMAP16Readbit 1 = GF ground fault; bit 2 = PF input phase loss; bit 3 = LF output phase loss; bit 6 = oH4 motor overheat 2 (PTC)
HR42doc 002AHAlarm contents 1BITMAP16Readbit 2 = EF run command input error; bit 3 = bb drive baseblock; bit 4 = oL3 overtorque 1; bit 5 = oH heatsink overheat; bit 6 = ov overvoltage; bit 7 = Uv undervoltage; bit 8 = FAn cooling fan error; bit 9 = CE Modbus communication error; bit 10 = bUS option communication error; bit 11 = UL3 undertorque 1; bit 12 = oH3 motor overheat; bit 13 = FbL / FbH PI feedback loss; bit 15 = CALL serial transmission error
HR43doc 002BHInput terminal statusBITMAP16Readbit 0 = S1 closed; bit 1 = S2 closed; bit 2 = S3 closed; bit 3 = S4 closed; bit 4 = S5 closed; bit 5 = S6 closed; bit 6 = S7 closed
HR44doc 002CHDrive status 2BITMAP16Readbit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = User speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = During undervoltage; bit 8 = During baseblock; bit 9 = Frequency reference from keypad; bit 10 = Run command from keypad; bit 11 = Over/undertorque 1; bit 12 = Frequency reference loss; bit 13 = During fault restart; bit 14 = Fault; bit 15 = Communication timeout
HR45doc 002DHOutput terminal statusBITMAP16Readbit 0 = Output 1 (M1-M2); bit 1 = Output 2 (M3-M4); bit 2 = Output 3 (M5-M6); bit 7 = Fault contact (MA/MB-MC)
HR49doc 0031HDC bus voltageUINT16VRead
HR56doc 0038HPI feedbackUnsigned, 100 % = max output frequency.UINT16× 0.1%Read
HR57doc 0039HPI inputSigned, 100 % = max output frequency.INT16× 0.1%Read
HR58doc 003AHPI outputSigned, 100 % = max output frequency.INT16× 0.1%Read
HR61doc 003DHCommunications error contentsKept until fault reset.BITMAP16Readbit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout
HR69doc 45Output voltage reference (U1-06)UINT16× 0.1VRead
HR70doc 46DC bus voltage (U1-07)UINT16VRead
HR73doc 49Input terminal status (U1-10)BITMAP16Readbit 0 = S1; bit 1 = S2; bit 2 = S3; bit 3 = S4; bit 4 = S5; bit 5 = S6; bit 6 = S7
HR75doc 004BHDrive status (U1-12)BITMAP16Readbit 0 = During run; bit 1 = During zero speed; bit 2 = During reverse run; bit 3 = Fault reset signal input; bit 4 = Speed agree; bit 5 = Drive ready; bit 6 = Alarm; bit 7 = Fault; bit 8 = Operation error (oPE); bit 9 = Momentary power loss; bit 14 = ComRef / NetRef; bit 15 = ComCtrl / NetCtrl
HR127doc 007FHAlarm codeActive alarm (Table E.4).UINT16Read
HR128doc 0080HCurrent fault (U2-01)Fault code (Table E.3).UINT16Read2 = Uv1; 3 = Uv2; 4 = Uv3; 6 = GF; 7 = oC; 8 = ov; 9 = oH; 10 = oH1; 11 = oL1; 12 = oL2; 13 = oL3; 17 = EF3; 18 = EF4; 19 = EF5; 20 = EF6; 21 = EF7; 27 = PF input phase loss; 28 = LF output phase loss; 29 = oH3 motor overheat (PTC); 30 = oPr operator connection; 31 = Err EEPROM write; 32 = oH4 motor overheat (PTC); 33 = CE Modbus communication error; 34 = bUS option communication error; 39 = EF0 option external fault; 40 = FbL PI feedback loss; 41 = UL3 undertorque 1; 43 = oL7 high slip braking overload; 48 = Hardware fault (incl. oFx); 54 = LF2 output current imbalance; 55 = STo pullout detection; 59 = SEr too many speed search restarts; 65 = FbH PI feedback loss; 66 = EF1; 67 = EF2; 70 = CoF current offset; 71 = PE1 PLC detection error 1; 72 = PE2 PLC detection error 2; 77 = voF output voltage detection; 82 = nSE node setup fault; 90 = UL6 motor underload; 131 = CPF02; 132 = CPF03; 135 = CPF06; 136 = CPF07; 137 = CPF08; 140 = CPF11; 141 = CPF12; 142 = CPF13; 143 = CPF14; 145 = CPF16; 146 = CPF17; 147 = CPF18; 148 = CPF19; 149 = CPF20; 150 = CPF21; 151 = CPF22; 152 = CPF23; 153 = CPF24; 154 = CPF25; 155 = CPF26; 156 = CPF27; 157 = CPF28; 158 = CPF29; 159 = CPF30; 160 = CPF31; 161 = CPF32; 162 = CPF33; 163 = CPF34; 164 = CPF35; 169 = CPF40; 170 = CPF41; 171 = CPF42; 172 = CPF43; 173 = CPF44; 174 = CPF45; 257 = oFA00; 258 = oFA01; 262 = oFA05; 263 = oFA06; 1025 = TIM time not set; 1026 = bAT operator battery low; 1027 = TdE time data error; 1028 = TiE time interval error; 1029 = ov2 overvoltage 2; 1031 = Fn1 external fan fault
HR129doc 0081HPrevious fault (U2-02)UINT16Read2 = Uv1; 3 = Uv2; 4 = Uv3; 6 = GF; 7 = oC; 8 = ov; 9 = oH; 10 = oH1; 11 = oL1; 12 = oL2; 13 = oL3; 17 = EF3; 18 = EF4; 19 = EF5; 20 = EF6; 21 = EF7; 27 = PF input phase loss; 28 = LF output phase loss; 29 = oH3 motor overheat (PTC); 30 = oPr operator connection; 31 = Err EEPROM write; 32 = oH4 motor overheat (PTC); 33 = CE Modbus communication error; 34 = bUS option communication error; 39 = EF0 option external fault; 40 = FbL PI feedback loss; 41 = UL3 undertorque 1; 43 = oL7 high slip braking overload; 48 = Hardware fault (incl. oFx); 54 = LF2 output current imbalance; 55 = STo pullout detection; 59 = SEr too many speed search restarts; 65 = FbH PI feedback loss; 66 = EF1; 67 = EF2; 70 = CoF current offset; 71 = PE1 PLC detection error 1; 72 = PE2 PLC detection error 2; 77 = voF output voltage detection; 82 = nSE node setup fault; 90 = UL6 motor underload; 131 = CPF02; 132 = CPF03; 135 = CPF06; 136 = CPF07; 137 = CPF08; 140 = CPF11; 141 = CPF12; 142 = CPF13; 143 = CPF14; 145 = CPF16; 146 = CPF17; 147 = CPF18; 148 = CPF19; 149 = CPF20; 150 = CPF21; 151 = CPF22; 152 = CPF23; 153 = CPF24; 154 = CPF25; 155 = CPF26; 156 = CPF27; 157 = CPF28; 158 = CPF29; 159 = CPF30; 160 = CPF31; 161 = CPF32; 162 = CPF33; 163 = CPF34; 164 = CPF35; 169 = CPF40; 170 = CPF41; 171 = CPF42; 172 = CPF43; 173 = CPF44; 174 = CPF45; 257 = oFA00; 258 = oFA01; 262 = oFA05; 263 = oFA06; 1025 = TIM time not set; 1026 = bAT operator battery low; 1027 = TdE time data error; 1028 = TiE time interval error; 1029 = ov2 overvoltage 2; 1031 = Fn1 external fan fault
HR152doc 0098HAccumulated operation time, high (U4-01)10 h units.UINT16× 10hRead
HR153doc 0099HAccumulated operation time, low (U4-01)1 h units.UINT16hRead
HR191doc 00BFHoPE error numberLast two digits of oPE code.UINT16Read
HR192doc 00C0HFault contents 3BITMAP16Readbit 1 = Uv1; bit 2 = Uv2; bit 3 = Uv3; bit 5 = GF; bit 6 = oC; bit 7 = ov; bit 8 = oH; bit 9 = oH1; bit 10 = oL1; bit 11 = oL2; bit 12 = oL3
HR193doc 00C1HFault contents 4BITMAP16Readbit 0 = EF3; bit 1 = EF4; bit 2 = EF5; bit 3 = EF6; bit 4 = EF7; bit 6 = FAn cooling fan error; bit 10 = PF; bit 11 = LF; bit 12 = oH3; bit 13 = oPr; bit 14 = Err EEPROM write; bit 15 = oH4
HR194doc 00C2HFault contents 5BITMAP16Readbit 0 = CE; bit 1 = bUS; bit 6 = EF0; bit 7 = FbL; bit 8 = UL3; bit 10 = oL7; bit 15 = Hardware fault (incl. oFx)
HR195doc 00C3HFault contents 6BITMAP16Readbit 5 = LF2 current imbalance; bit 6 = STo pullout detection; bit 10 = SEr too many speed search restarts
HR196doc 00C4HFault contents 7BITMAP16Readbit 0 = FbH; bit 1 = EF1; bit 2 = EF2; bit 5 = CoF current offset; bit 12 = voF output voltage detection
HR197doc 00C5HFault contents 8BITMAP16Readbit 1 = nSE node setup fault; bit 9 = UL6 motor underload
HR384doc 180b1-01 Frequency reference selection (AUTO)UINT16Read/write0 = HOA keypad; 1 = Terminals; 2 = Serial communications; 3 = Option card
HR385doc 181b1-02 Run command selection (AUTO)UINT16Read/write1 = Control circuit terminal; 2 = Serial communications; 3 = Option card
HR1061doc 425H5-01 Drive slave addressDefault 1Fh; 0 disables Modbus responses. Power-cycle.UINT16Read/write
HR1062doc 426H5-02 Communication speedPower-cycle after change.UINT16Read/write0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400; 6 = 57600; 7 = 76800; 8 = 115200
HR1063doc 427H5-03 ParityPower-cycle after change.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR1064doc 428H5-04 Stopping method after CEUINT16Read/write0 = Ramp to stop; 1 = Coast to stop; 2 = Fast stop; 3 = Alarm only; 4 = Run at d1-04
HR1065doc 429H5-05 CE detectionUINT16Read/write0 = Disabled; 1 = Enabled
HR1066doc 42AH5-06 Drive transmit wait time5-65 ms.UINT16msRead/write
HR1067doc 42BH5-07 RTS controlUINT16Read/write0 = Disabled; 1 = Enabled
HR1077doc 435H5-09 CE detection time0.0-10.0 s.UINT16× 0.1sRead/write
HR1078doc 436H5-10 Unit for register 0025HUINT16Read/write0 = 0.1 V; 1 = 1 V
HR1084doc 43CH5-11 Enter function selectionUINT16Read/write0 = Enter command required; 1 = No Enter required
HR1085doc 43DH5-12 Run command methodUINT16Read/write0 = FWD/Stop, REV/Stop; 1 = Run/Stop, FWD/REV
HR1581doc 62DH5-08 Protocol selectionUINT16Read/write0 = MEMOBUS/Modbus; 1 = N2 (Metasys); 2 = P1 (APOGEE FLN); 3 = BACnet
HR2304doc 0900HEnter command (EEPROM)Write 0: save to EEPROM and apply.UINT16Write
HR2320doc 0910HEnter command (RAM)Write 0: apply in RAM only.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)

What Modbus registers does the Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU) have?

This map lists 53 registers: 53 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the 03H example reads start address 00 20 (drive status). The parameter list gives each parameter's hex address in brackets (b1-01 = (180), H5-01 = (425), U1-06 = (45)).

What are the minimum Modbus registers to integrate the Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)?

Start with HR 1 Operation commands and multi-function inputs (Run/stop and reset); HR 2 Frequency reference (Frequency reference); HR 32 Drive status 1 (Drive status 1); HR 33 Fault contents 1 (Fault contents 1); HR 36 Output frequency (Output frequency); HR 38 Output current (Output current); HR 44 Drive status 2 (Status 2 incl. comm timeout); HR 128 Current fault (U2-01) (Current fault code).

How do I enable Modbus control of the Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)?

H5-08 = 0 selects MEMOBUS/Modbus (1 N2, 2 P1, 3 BACnet). H5-01 address (default 1Fh), H5-02 speed (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 (AUTO mode sources) hand reference and run to serial communications.

What happens when the Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU) loses Modbus communication?

H5-05 = 1 (default) enables CE detection after H5-09 (default 2.0 s); H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast stop, 3 alarm only (default), 4 run at d1-04. 002CH bit F flags the timeout.

Where is the official Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU) Modbus documentation?

The source is YASKAWA AC Drive Z1000 AC Drive for HVAC Fan and Pump Programming Manual (SIEP YAIZ1U 03C), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIZ1U03&cmd=documents&documentName=SIEPYAIZ1U03.pdf.

More Yaskawa Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: YASKAWA AC Drive Z1000 AC Drive for HVAC Fan and Pump Programming Manual · SIEP YAIZ1U 03C. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.