- Home
- Modbus register maps
- AutomationDirect
- GS2 series AC drive
Variable frequency drive · Modbus register map
AutomationDirect GS2 series AC drive Modbus register map
Updated 17 November 2026
The GS2 is an AutomationDirect AC drive with a built-in RS-485 port running Modbus ASCII or RTU. Drive parameters P0.00-P9.xx map to holding registers (parameter group x 256 + number), and read-only status registers at 2100h report fault code, run state, frequencies, voltages and load. This map covers the status block and the P9 serial control parameters used to run the drive over Modbus.
This page lists 21 Modbus registers for the AutomationDirect GS2 series AC drive — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from AutomationDirect’s own free documentation (linked below) and checked against it.
- Manufacturer
- AutomationDirect
- Model
- GS2 series AC drive
- Equipment type
- Variable frequency drive
- Registers
- 21 (11 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 9600 baud
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-23P0, GS2-25P0, GS2-27P5, GS2-41P0, GS2-42P0, GS2-43P0, GS2-45P0, GS2-47P5
Integration notes: AutomationDirect GS2 series AC drive
Set P9.02 to an RTU mode, P3.00 to serial operation and P4.00 = 5 for serial frequency source, then write speed (P9.26, x10) and run (P9.27). Monitor Status Monitor 1/2 and output frequency at 2100h-2103h.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2330 | P9.26 Serial Comm Speed Reference | UINT16 | Speed reference | Read/write |
| HR 2331 | P9.27 Serial Comm RUN Command | UINT16 | Run/stop | Read/write |
| HR 2332 | P9.28 Serial Comm Direction Command | UINT16 | Direction | Read/write |
| HR 8448 | Status Monitor 1 | UINT16 | Fault code | Read |
| HR 8449 | Status Monitor 2 | BITMAP16 | Run state bits | Read |
| HR 8451 | Output Frequency H | UINT16 | Output frequency | Read |
Enable Modbus control & writes
Set P3.00 (source of operation) to 3 or 4 and P4.00 (source of frequency) to 5 for serial control, as referenced in Status Monitor 2; set P9.00-P9.02 for address, baud and protocol from the keypad.
Communication loss & watchdog
P9.04 enables communication time-out detection, P9.05 sets the time (0.1-60.0 s) and P9.03 selects the reaction (keep running, ramp stop, coast stop).
Byte order & addressing
- Factory protocol is Modbus ASCII, not RTU.
- Speed reference has an implied decimal: write 600 for 60.0 Hz.
- Hex addresses are wire addresses: 091Ah = 2330 decimal = 42331 Modicon.
Network setup
- P9.00 address (default 1), P9.01 baud (default 9600), P9.02 protocol/format.
- Writes to P0-P8 parameters can be grouped through the block transfer parameters P9.11 onward.
Watch out for
- Output current (2104h) and power factor angle (210Ah) have no stated decimal format in this chapter; they are not in this map.
AutomationDirect GS2 series AC drive Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2304doc 0900h (42305) | P9.00 Communication Address | Drive address 1-254. | UINT16 | Read/write | ||||
| HR | 2305doc 0901h (42306) | P9.01 Transmission Speed | UINT16 | Read/write | 0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400 | ||||
| HR | 2306doc 0902h (42307) | P9.02 Communication Protocol | Factory default 0 is Modbus ASCII. | UINT16 | Read/write | 0 = ASCII 7N2; 1 = ASCII 7E1; 2 = ASCII 7O1; 3 = RTU 8N2; 4 = RTU 8E1; 5 = RTU 8O1 | |||
| HR | 2307doc 0903h (42308) | P9.03 Transmission Fault Treatment | UINT16 | Read/write | 0 = Display fault, keep running; 1 = Display fault, ramp to stop; 2 = Display fault, coast to stop; 3 = No fault, keep running | ||||
| HR | 2308doc 0904h (42309) | P9.04 Time Out Detection | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 2330doc 091Ah (42331) | P9.26 Serial Comm Speed Reference | 0.0-400.0 Hz with implied decimal (600 = 60.0 Hz). | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 2331doc 091Bh (42332) | P9.27 Serial Comm RUN Command | UINT16 | Read/write | 0 = Stop; 1 = Run | ||||
| HR | 2332doc 091Ch (42333) | P9.28 Serial Comm Direction Command | UINT16 | Read/write | 0 = Forward; 1 = Reverse | ||||
| HR | 2333doc 091Dh (42334) | P9.29 Serial Comm External Fault | UINT16 | Read/write | 0 = No fault; 1 = External fault | ||||
| HR | 2334doc 091Eh (42335) | P9.30 Serial Comm Fault Reset | UINT16 | Read/write | 0 = No action; 1 = Fault reset | ||||
| HR | 2335doc 091Fh (42336) | P9.31 Serial Comm JOG Command | UINT16 | Read/write | 0 = Stop; 1 = Jog | ||||
| HR | 8448doc 2100h (48449) | Status Monitor 1 | Present fault code. | UINT16 | Read | 0 = No fault; 1 = Over-current (oc); 2 = Over-voltage (ov); 3 = Overheat (oH); 4 = Overload (oL); 5 = Overload 1 (oL1); 6 = Overload 2 (oL2); 7 = External fault (EF); 8 = CPU failure 1 (cF1); 9 = CPU failure 2 (cF2); 10 = CPU failure 3 (cF3); 11 = Hardware protection failure (HPF); 12 = Over-current during accel (ocA); 13 = Over-current during decel (ocd); 14 = Over-current at steady state (ocn); 15 = Ground fault or fuse failure (GFF); 16 = Low voltage (Lv); 17 = Input power 3-phase loss (PHL); 18 = External base-block (bb); 19 = Auto adjust accel/decel failure (cFA); 20 = Software protection code (codE) | |||
| HR | 8449doc 2101h (48450) | Status Monitor 2 | Bits 0-1 run state (0 stop..3 run); bits 3-4 direction (0 FWD..3 REV). | BITMAP16 | Read | bit 2 = JOG active; bit 5 = Frequency source = serial comm (P4.00 = 5); bit 6 = Frequency source = AI terminal; bit 7 = Operation source = serial comm (P3.00 = 3 or 4); bit 8 = Parameters locked (P9.07 = 1) | |||
| HR | 8450doc 2102h (48451) | Frequency Command F | Frequency setpoint (XXX.X). | UINT16 | × 0.1 | Hz | Read | ||
| HR | 8451doc 2103h (48452) | Output Frequency H | Output frequency (XXX.X). | UINT16 | × 0.1 | Hz | Read | ||
| HR | 8453doc 2105h (48454) | DC Bus Voltage d | (XXX.X) | UINT16 | × 0.1 | V | Read | ||
| HR | 8454doc 2106h (48455) | Output Voltage U | RMS line-to-line output voltage (XXX.X). | UINT16 | × 0.1 | V | Read | ||
| HR | 8455doc 2107h (48456) | Motor RPM | Estimated motor speed. | UINT16 | rpm | Read | |||
| HR | 8456doc 2108h (48457) | Scale Frequency | Output frequency x P8.01; low word at 2108h, high word at 2109h. | UINT32 | CDAB | Read | |||
| HR | 8459doc 210Bh (48460) | % Load | Output current / drive rated current x 100. | UINT16 | % | Read | |||
| HR | 8464doc 2110h (48465) | Firmware Version | UINT16 | Read |
Notes on this map
- AutomationDirect's own manual chapter (cdn.automationdirect.com).
- Parameter-to-register rule: Px.yy is at hex x*256 + yy (e.g. P9.26 = 091Ah = 42331); the full list is in the chapter's parameter address tables. Only the P9 communication/control parameters are included here.
- Status values marked XXX.X in the manual carry one implied decimal (scale 0.1).
- Scale Frequency is split into low word (2108h) and high word (2109h), so it is listed as a 32-bit value with the low word first (CDAB); its unit depends on P8.01.
- P9.05 (communication time-out, 0.1-60.0 s) is left out because its raw encoding is not stated in this chapter.
- The factory protocol (P9.02 = 0) is Modbus ASCII 7N2; set 3, 4 or 5 for RTU.
- Speed reference scaling: the DirectLOGIC example loads P9.26 'with implied decimal place' (K150 = 15.0 Hz, 600 = 60.0 Hz).
- Left out: Output Current (2104h) and Power Factor Angle (210Ah) because the GS2 chapter gives no decimal format for them.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the AutomationDirect GS2 series AC drive
What Modbus registers does the AutomationDirect GS2 series AC drive have?
This map lists 21 registers: 21 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the AutomationDirect GS2 series AC drive Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists each register in hex and as a Modicon number: hex 0000h = 40001, 2100h = 48449. The hex value is the wire address.
What byte order does the AutomationDirect GS2 series AC drive use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the AutomationDirect GS2 series AC drive?
Start with HR 2330 P9.26 Serial Comm Speed Reference (Speed reference); HR 2331 P9.27 Serial Comm RUN Command (Run/stop); HR 2332 P9.28 Serial Comm Direction Command (Direction); HR 8448 Status Monitor 1 (Fault code); HR 8449 Status Monitor 2 (Run state bits); HR 8451 Output Frequency H (Output frequency).
How do I enable Modbus control of the AutomationDirect GS2 series AC drive?
Set P3.00 (source of operation) to 3 or 4 and P4.00 (source of frequency) to 5 for serial control, as referenced in Status Monitor 2; set P9.00-P9.02 for address, baud and protocol from the keypad.
What happens when the AutomationDirect GS2 series AC drive loses Modbus communication?
P9.04 enables communication time-out detection, P9.05 sets the time (0.1-60.0 s) and P9.03 selects the reaction (keep running, ramp stop, coast stop).
Where is the official AutomationDirect GS2 series AC drive Modbus documentation?
The source is GS2 Series AC Drive User Manual - Chapter 5: GS2 Modbus Communications (GS2-M 1st Ed. Rev. C 12/2006 (chapter 5)), published free by AutomationDirect at https://cdn.automationdirect.com/static/manuals/gs2m/ch5.pdf.
More AutomationDirect Modbus register maps
- Variable frequency drive
AutomationDirect DURApulse GS10 AC drive
GS10 drives (built-in RS-485 port) per the GS10 user manual, 1st edition rev. C, chapter 5.
Also known as: DURApulse GS10, GS10 micro drive - Variable frequency drive
AutomationDirect DURApulse GS20 / GS20X AC drive
GS20 and GS20X drives (built-in RS-485 port) per the GS20 & GS20X user manual, 1st edition rev. F, chapter 5.
Also known as: GS20X, DURApulse GS20, GS21-11P0 - Variable frequency drive
AutomationDirect DURApulse GS3 AC drive
All GS3 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: DURApulse GS3, GS3-21P0, GS3-22P0, GS3-23P0, GS3-25P0, GS3-27P5, GS3-2010, GS3-2015, GS3-2020, GS3-2025 - Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0
Other variable frequency drives register maps
- Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Hitachi SJ-P1 inverters on the built-in RS485 port in Modbus-RTU mode, register layout of firmware Ver. 2.00 (User's Guide NT251BX-2, Rev. 6).
Also known as: SJ-P1, P1-xxxxx-L, P1-xxxxx-H - Variable frequency drive
Invertek Drives Optidrive Eco (built-in Modbus RTU)
Invertek Optidrive Eco drives using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-HEMAN-IN V3.13.
Also known as: ODV-3, Optidrive Eco HVAC, Optidrive Eco IP20, Optidrive Eco IP55, Optidrive Eco IP66 - Variable frequency drive
INVT Goodrive300 (GD300) vector VFD
INVT Goodrive300 open-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD300 VFD manual V3.6 (chapter 10).
Also known as: GD300, Goodrive300, GD300 vector VFD - Variable frequency drive
Lenze MCH Series HVAC drive (Modbus RTU)
Lenze AC Tech MCH Series drives, software 213-070 rev 00 (parameter configuration 148); reference guide RG-MHMOD.
Also known as: MCH, Lenze AC Tech MCH, RG-MHMOD
All variable frequency drives Modbus register maps →
Source: GS2 Series AC Drive User Manual - Chapter 5: GS2 Modbus Communications · GS2-M 1st Ed. Rev. C 12/2006 (chapter 5). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.