- SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Variable frequency drive · Modbus register map
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00) Modbus register map
Updated 19 November 2026
The SJ-P1 high-function inverter answers Modbus RTU on its RS485 terminals. Coils carry run/stop, direction, reset and the input/output terminals; holding registers carry the dA/db/dC monitors, trip history, RS485 frequency, torque and PID commands and every parameter. This map lists the control set, main monitors, trip monitor 1 and the CF communication parameters.
This page lists 90 Modbus registers for the Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00) — 34 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Hitachi’s own free documentation (linked below) and checked against it.
- Manufacturer
- Hitachi
- Model
- SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
- Equipment type
- Variable frequency drive
- Registers
- 90 (34 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Ver. 2.00 register layout (several register numbers differ in Ver. 1.xx)
- Also known as
- SJ-P1, P1-xxxxx-L, P1-xxxxx-H
Integration notes: Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Set CF-01 to CF-04 for the serial line and CF-08 to Modbus-RTU, then AA101 = 08 and AA111 = 03. Write the signed frequency to 10502/10503, run and stop with coil 1, and poll dA-01, dA-02, dA-40 and the trip monitor.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Operation command | BIT | Run/stop | Read/write |
| CO 3 | Trip reset [RS] | BIT | Trip reset | Read/write |
| HR 10501 | RS485 set frequency | INT32 ABCD | RS485 set frequency | Read/write |
| HR 10000 | Output frequency monitor (dA-01) | UINT16 | Output frequency | Read |
| HR 10001 | Output current monitor (dA-02) | UINT16 | Output current | Read |
| HR 10039 | DC voltage monitor (dA-40) | UINT16 | DC bus voltage | Read |
| HR 1000 | Trip monitor 1 factor | UINT16 | Latest trip factor | Read |
| CO 22 | Inverter operation ready | BIT | Inverter ready | Read |
Enable Modbus control & writes
Select Modbus-RTU with CF-08, then set AA101 = 08 (speed from RS485) and AA111 = 03 (run command from RS485). Coils 1 and 2 only act when AA111 = 03.
Communication loss & watchdog
CF-06 sets the communication timeout (0.00-100.00 s); when it expires error E041 is raised, and CF-05 picks the action (trip, trip after stop, ignore, free-run stop or deceleration stop).
Byte order & addressing
- Wire address is the printed number minus 1.
- Two-register values are high word first.
- Register numbers changed between firmware Ver. 1.xx and 2.00; check the firmware with dC-50 before using this map.
Network setup
- CF-01 baud (03-10 = 2400-115200 bps), CF-02 station 1-247, CF-03 parity, CF-04 stop bits; CF-07 adds a reply delay.
- One request handles at most 32 coils or 16 registers; a coil read of 0 or more than 32 coils returns exception 03h.
Watch out for
- The [NDc] output signal can be assigned to an output terminal to flag a communication loss.
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc Coil 1 (0001h) | Operation command | Works when AA111/AA211 = 03. | BIT | Read/write | 0 = Stop; 1 = Run | |||
| CO | 1doc Coil 2 (0002h) | Rotation direction command | Works when AA111/AA211 = 03. | BIT | Read/write | 0 = Normal (forward); 1 = Reverse | |||
| CO | 2doc Coil 3 (0003h) | External trip [EXT] | BIT | Read/write | 0 = Not trip; 1 = Trip | ||||
| CO | 3doc Coil 4 (0004h) | Trip reset [RS] | BIT | Read/write | 0 = Not reset; 1 = Reset | ||||
| CO | 4doc Coil 5 (0005h) | Input terminal 1 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 5doc Coil 6 (0006h) | Input terminal 2 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 6doc Coil 7 (0007h) | Input terminal 3 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 7doc Coil 8 (0008h) | Input terminal 4 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 8doc Coil 9 (0009h) | Input terminal 5 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 9doc Coil 10 (000Ah) | Input terminal 6 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 10doc Coil 11 (000Bh) | Input terminal 7 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 11doc Coil 12 (000Ch) | Input terminal 8 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 12doc Coil 13 (000Dh) | Input terminal 9 | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 13doc Coil 14 (000Eh) | Input terminal A | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 14doc Coil 15 (000Fh) | Input terminal B | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| CO | 20doc Coil 21 (0015h) | Operating status | 1 while rotating forward or reverse (linked with dA-03). | BIT | Read | 0 = Not rotating; 1 = Rotating | |||
| CO | 21doc Coil 22 (0016h) | Rotation direction | BIT | Read | 0 = Normal direction; 1 = Reverse direction | ||||
| CO | 22doc Coil 23 (0017h) | Inverter operation ready | BIT | Read | 0 = Not ready; 1 = Ready | ||||
| CO | 24doc Coil 25 (0019h) | Output terminal 11 | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 25doc Coil 26 (001Ah) | Output terminal 12 | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 26doc Coil 27 (001Bh) | Output terminal 13 | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 27doc Coil 28 (001Ch) | Output terminal 14 | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 28doc Coil 29 (001Dh) | Output terminal 15 | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 29doc Coil 30 (001Eh) | Output terminal 16 | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 30doc Coil 31 (001Fh) | Output terminal AL | BIT | Read | 0 = OFF; 1 = ON | ||||
| CO | 72doc Coil 73 (0049h) | Data being written | BIT | Read | 0 = Normal state; 1 = Being written | ||||
| CO | 73doc Coil 74 (004Ah) | CRC error | BIT | Read | 0 = No error; 1 = With error | ||||
| CO | 74doc Coil 75 (004Bh) | Overrun error | BIT | Read | 0 = No error; 1 = With error | ||||
| CO | 75doc Coil 76 (004Ch) | Framing error | BIT | Read | 0 = No error; 1 = With error | ||||
| CO | 76doc Coil 77 (004Dh) | Parity error | BIT | Read | 0 = No error; 1 = With error | ||||
| CO | 77doc Coil 78 (004Eh) | Sum check error | BIT | Read | 0 = No error; 1 = With error | ||||
| HR | 999doc 1000 (03E8h) | Trip count monitor (dE-01) | UINT16 | times | Read | ||||
| HR | 1000doc 1001 (03E9h) | Trip monitor 1 factor | Trip cause code, 1-255 (e.g. 7 = overvoltage E007). | UINT16 | Read | ||||
| HR | 1001doc 1002 / 1003 (03EAh high, 03EBh low) | Trip monitor 1 output frequency | Signed. | INT32 | ABCD | × 0.01 | Hz | Read | |
| HR | 1003doc 1004 (03ECh) | Trip monitor 1 output current | UINT16 | × 0.01 | A | Read | |||
| HR | 1004doc 1005 (03EDh) | Trip monitor 1 P-N DC voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 1011doc 1012 / 1013 (03F4h high, 03F5h low) | Trip monitor 1 RUN time | UINT32 | ABCD | h | Read | |||
| HR | 1013doc 1014 / 1015 (03F6h high, 03F7h low) | Trip monitor 1 power-on time | UINT32 | ABCD | h | Read | |||
| HR | 10000doc 10001 (2711h) | Output frequency monitor (dA-01) | 0-590.00 Hz. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 10001doc 10002 (2712h) | Output current monitor (dA-02) | UINT16 | × 0.01 | A | Read | |||
| HR | 10002doc 10003 (2713h) | Operation direction monitor (dA-03) | 0-3. | UINT16 | Read | ||||
| HR | 10003doc 10004 / 10005 (2714h high, 2715h low) | Frequency command after calculation (dA-04) | Signed, Ver. 2.00 layout. | INT32 | ABCD | × 0.01 | Hz | Read | |
| HR | 10007doc 10008 / 10009 (2718h high, 2719h low) | Speed detection value monitor (dA-08) | INT32 | ABCD | × 0.01 | Hz | Read | ||
| HR | 10011doc 10012 / 10013 (271Ch high, 271Dh low) | Output frequency monitor with sign (dA-12) | INT32 | ABCD | × 0.01 | Hz | Read | ||
| HR | 10014doc 10015 (271Fh) | Torque command monitor after calculation (dA-15) | INT16 | × 0.1 | % | Read | |||
| HR | 10016doc 10017 (2721h) | Output torque monitor (dA-17) | INT16 | × 0.1 | % | Read | |||
| HR | 10017doc 10018 (2722h) | Output voltage monitor (dA-18) | UINT16 | × 0.1 | V | Read | |||
| HR | 10031doc 10032 / 10033 (2730h high, 2731h low) | Integrated input power monitor (dA-32) | UINT32 | ABCD | × 0.1 | kWh | Read | ||
| HR | 10035doc 10036 / 10037 (2734h high, 2735h low) | Integrated output power monitor (dA-36) | UINT32 | ABCD | × 0.1 | kWh | Read | ||
| HR | 10037doc 10038 (2736h) | Motor temperature monitor (dA-38) | INT16 | × 0.1 | °C | Read | |||
| HR | 10039doc 10040 (2738h) | DC voltage monitor (dA-40) | UINT16 | × 0.1 | V | Read | |||
| HR | 10040doc 10041 (2739h) | BRD load factor monitor (dA-41) | UINT16 | × 0.01 | % | Read | |||
| HR | 10041doc 10042 (273Ah) | Electronic thermal load factor, motor (dA-42) | UINT16 | × 0.01 | % | Read | |||
| HR | 10042doc 10043 (273Bh) | Electronic thermal load factor, controller (dA-43) | UINT16 | × 0.01 | % | Read | |||
| HR | 10050doc 10051 (2743h) | Input terminal monitor (dA-51) | Packed input terminal states. | BITMAP16 | Read | ||||
| HR | 10053doc 10054 (2746h) | Output terminal monitor (dA-54) | Packed output terminal states. | BITMAP16 | Read | ||||
| HR | 10060doc 10061 (274Dh) | Analog input [Ai1] monitor (dA-61) | UINT16 | × 0.01 | % | Read | |||
| HR | 10061doc 10062 (274Eh) | Analog input [Ai2] monitor (dA-62) | UINT16 | × 0.01 | % | Read | |||
| HR | 10062doc 10063 (274Fh) | Analog input [Ai3] monitor (dA-63) | INT16 | × 0.01 | % | Read | |||
| HR | 10149doc 10150 (27A6h) | PID1 output monitor (db-50) | INT16 | × 0.01 | % | Read | |||
| HR | 10150doc 10151 (27A7h) | PID1 deviation monitor (db-51) | INT16 | × 0.01 | % | Read | |||
| HR | 10201doc 10202 (27DAh) | Rated current monitor (dC-02) | UINT16 | × 0.1 | A | Read | |||
| HR | 10214doc 10215 (27E7h) | Cooling fin temperature monitor (dC-15) | INT16 | × 0.1 | °C | Read | |||
| HR | 10215doc 10216 (27E8h) | Life diagnostic monitor (dC-16) | Packed life warning flags. | BITMAP16 | Read | ||||
| HR | 10219doc 10220 (27ECh) | Total start-up count (dC-20) | UINT16 | Read | |||||
| HR | 10220doc 10221 (27EDh) | Power-on count (dC-21) | UINT16 | Read | |||||
| HR | 10221doc 10222 / 10223 (27EEh high, 27EFh low) | Cumulative operating hours during RUN (dC-22) | UINT32 | ABCD | h | Read | |||
| HR | 10223doc 10224 / 10225 (27F0h high, 27F1h low) | Cumulative power-on time (dC-24) | UINT32 | ABCD | h | Read | |||
| HR | 10225doc 10226 / 10227 (27F2h high, 27F3h low) | Cumulative cooling fan operating time (dC-26) | UINT32 | ABCD | h | Read | |||
| HR | 10249doc 10250 (280Ah) | Firmware version monitor (dC-50) | High byte major, low byte minor. | UINT16 | Read | ||||
| HR | 10501doc 10502 / 10503 (2906h high, 2907h low) | RS485 set frequency | Signed frequency command for main and auxiliary speed. | INT32 | ABCD | × 0.01 | Hz | Read/write | |
| HR | 10525doc 10526 (291Eh) | RS485 torque command | INT16 | × 0.1 | % | Read/write | |||
| HR | 10545doc 10546 / 10547 (2932h high, 2933h low) | RS485 PID target value | INT32 | ABCD | × 0.01 | % | Read/write | ||
| HR | 10553doc 10554 / 10555 (293Ah high, 293Bh low) | RS485 PID feedback data | INT32 | ABCD | × 0.01 | % | Read/write | ||
| HR | 11000doc 11001 (2AF9h) | Main speed command (FA-01) | Monitor and setting. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 11009doc 11010 / 11011 (2B02h high, 2B03h low) | Acceleration time (FA-10) | Monitor and setting. | UINT32 | ABCD | × 0.01 | s | Read/write | |
| HR | 11011doc 11012 / 11013 (2B04h high, 2B05h low) | Deceleration time (FA-12) | Monitor and setting. | UINT32 | ABCD | × 0.01 | s | Read/write | |
| HR | 12000doc 12001 (2EE1h) | First main speed command selection (AA101) | Range 1-16; 08 = command from RS485. | UINT16 | Read/write | ||||
| HR | 12010doc 12011 (2EEBh) | First operation command selection (AA111) | Range 0-6; 03 = run command from RS485. | UINT16 | Read/write | ||||
| HR | 12219doc 12220 / 12221 (2FBCh high, 2FBDh low) | First acceleration time 1 (AC120) | UINT32 | ABCD | × 0.01 | s | Read/write | ||
| HR | 12221doc 12222 / 12223 (2FBEh high, 2FBFh low) | First deceleration time 1 (AC122) | UINT32 | ABCD | × 0.01 | s | Read/write | ||
| HR | 14500doc 14501 (38A5h) | Communication baud rate (CF-01) | UINT16 | Read/write | 3 = 2400 bps; 4 = 4800 bps; 5 = 9600 bps; 6 = 19200 bps; 7 = 38400 bps; 8 = 57600 bps; 9 = 76800 bps; 10 = 115200 bps | ||||
| HR | 14501doc 14502 (38A6h) | Communication station number (CF-02) | 1-247. | UINT16 | Read/write | ||||
| HR | 14502doc 14503 (38A7h) | Communication parity (CF-03) | UINT16 | Read/write | 0 = No parity; 1 = Even parity; 2 = Odd parity | ||||
| HR | 14503doc 14504 (38A8h) | Communication stop bits (CF-04) | UINT16 | Read/write | 1 = 1 bit; 2 = 2 bits | ||||
| HR | 14504doc 14505 (38A9h) | Communication error selection (CF-05) | UINT16 | Read/write | 0 = Trip; 1 = Trip after decelerating and stopping; 2 = Ignore; 3 = Free-run stop; 4 = Deceleration stop | ||||
| HR | 14505doc 14506 (38AAh) | Communication timeout time (CF-06) | 0.00-100.00 s; loss longer than this raises E041. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 14506doc 14507 (38ABh) | Communication waiting time (CF-07) | Reply delay. | UINT16 | ms | Read/write | |||
| HR | 16059doc 16060 (3EBCh) | Coil data 0 (coils 0001h-000Fh) | Packed control coils as one word. | BITMAP16 | Read/write | ||||
| HR | 16060doc 16061 (3EBDh) | Coil data 1 (coils 0010h-001Fh) | Packed status coils as one word. | BITMAP16 | Read |
Notes on this map
- Two-register values are printed as (High) then (Low) register; the guide's read example returns 60.00 Hz as 0000h then 1770h, so the high word comes first (ABCD).
- This register layout is for firmware Ver. 2.00. The guide lists items whose register number or range changed from Ver. 1.xx (for example dA-04 was one unsigned register in Ver. 1.xx).
- Only a working subset is listed. Later trip monitors repeat the trip monitor 1 block every 20 registers (trip monitor 2 at 1021, 3 at 1041 ...). The full parameter list is in chapter 14.6.
- AA101/AA111 are listed without full value tables; the guide states 08 = RS485 for AA101 and 03 = RS485 for AA111. CF-08 (communication method) is left out because its printed codes (00-02) and register range (1-3) disagree.
- Monitor and setting ranges assume CF-11 register data selection = 00 (A, V). With 01 (%), current and voltage items read as % of rating.
- The single-register input/output power monitors (dA-30, dA-34) are left out: their printed resolution changes with drive size and is given in kWh for a power value.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
What Modbus registers does the Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00) have?
This map lists 90 registers: 31 coils, 59 holding registers. 34 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints register and coil numbers in decimal and hex and says the start number in the frame is the number minus 1; its examples read trip monitor 1 (register 03E9h) with start 03E8h and write coil 1 with start 0000h. So wire address = printed number - 1.
What byte order does the Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)?
Start with CO 0 Operation command (Run/stop); CO 3 Trip reset [RS] (Trip reset); HR 10501 RS485 set frequency (RS485 set frequency); HR 10000 Output frequency monitor (dA-01) (Output frequency); HR 10001 Output current monitor (dA-02) (Output current); HR 10039 DC voltage monitor (dA-40) (DC bus voltage); HR 1000 Trip monitor 1 factor (Latest trip factor); CO 22 Inverter operation ready (Inverter ready).
How do I enable Modbus control of the Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)?
Select Modbus-RTU with CF-08, then set AA101 = 08 (speed from RS485) and AA111 = 03 (run command from RS485). Coils 1 and 2 only act when AA111 = 03.
What happens when the Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00) loses Modbus communication?
CF-06 sets the communication timeout (0.00-100.00 s); when it expires error E041 is raised, and CF-05 picks the action (trip, trip after stop, ignore, free-run stop or deceleration stop).
Where is the official Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00) Modbus documentation?
The source is SJ-P1 Series Inverter User's Guide (chapters 1-20) (NT251BX-2 Rev. 6), published free by Hitachi at https://www.hitachi-iesa.com/sites/default/files/supportdocs/SJ-P1_Users_guide_chapter1-20_Rev06_NT251BX-2.pdf.
More Hitachi Modbus register maps
- Variable frequency drive
Hitachi SJ700-2 series inverter (Modbus RTU)
Hitachi SJ700-2 series inverters using the built-in RS485 port (TM2) in Modbus-RTU mode (C079), per instruction manual NT204DX.
Also known as: SJ700, SJ700-2, SJ700 series - Variable frequency drive
Hitachi WJ-C1 series inverter (Modbus RTU)
Hitachi WJ-C1 inverters using the built-in RS485 port in Modbus-RTU mode; User's Guide NT361X, chapters 11 and 18.
Also known as: WJ-C1, WJ-C1 series
Other variable frequency drives register maps
- Variable frequency drive
Invertek Drives Optidrive Eco (built-in Modbus RTU)
Invertek Optidrive Eco drives using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-HEMAN-IN V3.13.
Also known as: ODV-3, Optidrive Eco HVAC, Optidrive Eco IP20, Optidrive Eco IP55, Optidrive Eco IP66 - Variable frequency drive
INVT Goodrive300 (GD300) vector VFD
INVT Goodrive300 open-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD300 VFD manual V3.6 (chapter 10).
Also known as: GD300, Goodrive300, GD300 vector VFD - Variable frequency drive
Lenze MCH Series HVAC drive (Modbus RTU)
Lenze AC Tech MCH Series drives, software 213-070 rev 00 (parameter configuration 148); reference guide RG-MHMOD.
Also known as: MCH, Lenze AC Tech MCH, RG-MHMOD - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE
All variable frequency drives Modbus register maps →
Source: SJ-P1 Series Inverter User's Guide (chapters 1-20) · NT251BX-2 Rev. 6. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.