- FR-D700 compact inverter (PU connector, Modbus RTU)
Variable frequency drive · Modbus register map
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU) Modbus register map
Updated 19 November 2026
Mitsubishi Electric's simple compact inverter. The PU connector can run Modbus RTU, giving system variables (control word, operation mode, frequency command) at 40002-40015, a real-time monitor block from 40201, fault history at 40501 and every parameter at 41000 + parameter number. This map covers control, status, monitors, fault codes and the communication parameters.
This page lists 52 Modbus registers for the Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU) — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- FR-D700 compact inverter (PU connector, Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 52 (22 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- FR-D720, FR-D740, FR-D720S, FR-D710W
Integration notes: Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
Set Pr.549 = 1, Pr.117 to 1-247 and Pr.122 to 9999 (or a real interval), reset, then switch to NET mode by writing H0014 to 40010. Write the frequency to 40014 (0.01 Hz) and run bits to 40009; poll 40009, 40201, 40202 and 40501.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8 | Inverter status / control input instruction | BITMAP16 | Run/stop command and inverter status | Read/write |
| HR 9 | Operation mode / inverter setting | UINT16 | Operation mode (write H0014 for NET) | Read/write |
| HR 13 | Running frequency (RAM) | UINT16 | Frequency command (RAM) | Read/write |
| HR 200 | Output frequency / speed | UINT16 | Output frequency | Read |
| HR 201 | Output current | UINT16 | Output current | Read |
| HR 500 | Fault record 1 | UINT16 | Latest fault code | Read/write |
Enable Modbus control & writes
Pr.549 = 1 selects Modbus RTU on the PU connector; set Pr.117 (station), Pr.118 (speed) and Pr.120 (parity) and reset. Operation and frequency commands need NET mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340).
Communication loss & watchdog
Pr.122 is the communication check interval (0.1-999.8 s) with Pr.502 choosing coast or decelerate on E.PUE. Initial value 0 trips E.PUE as soon as the drive enters NET mode, so set 9999 or an interval before switching.
Byte order & addressing
- Request address = register - 40001.
- Station 0 is broadcast and never replies; the initial Pr.117 is 0.
- 40009 means control input when written and inverter status when read.
Network setup
- Pr.118 initial 192 = 19200 bps; Pr.120 initial 2 = even parity, 1 stop bit.
- With Pr.549 = 1 and Pr.118 = 384, the FR-PU04/FR-PU07 parameter unit stops working; use the built-in panel.
- Modbus RTU cannot be used in PU operation mode.
Watch out for
- Pr.122 = 0 (initial) makes the drive trip E.PUE the moment it goes to NET mode.
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 40002 | Inverter reset | Write any value to reset the inverter. | UINT16 | Write | ||||
| HR | 2doc 40003 | Parameter clear | Write H965A. | UINT16 | Write | ||||
| HR | 3doc 40004 | All parameter clear | Write H99AA. | UINT16 | Write | ||||
| HR | 5doc 40006 | Parameter clear (keep comm settings) | Write H5A96; communication parameters are kept. | UINT16 | Write | ||||
| HR | 6doc 40007 | All parameter clear (keep comm settings) | Write HAA99; communication parameters are kept. | UINT16 | Write | ||||
| HR | 8doc 40009 | Inverter status / control input instruction | Write = control input, read = inverter status. | BITMAP16 | Read/write | bit 0 = Write: stop command / Read: RUN (inverter running); bit 1 = Write: forward rotation / Read: during forward rotation; bit 2 = Write: reverse rotation / Read: during reverse rotation; bit 3 = Write: RH (high speed) / Read: up to frequency; bit 4 = Write: RM (middle speed) / Read: overload; bit 5 = Write: RL (low speed); bit 6 = Read: frequency detection; bit 7 = Write: second function selection / Read: ABC (fault); bit 8 = Write: terminal 4 input selection; bit 9 = Read: SO (safety monitor output); bit 10 = Write: output stop; bit 15 = Read: fault occurrence | |||
| HR | 9doc 40010 | Operation mode / inverter setting | Read = current mode; write H0010 EXT, H0011 PU, H0014 NET. | UINT16 | Read/write | 0 = Read: EXT; 1 = Read: PU; 2 = Read: EXT JOG; 3 = Read: PU JOG; 4 = Read: NET; 5 = Read: PU + EXT; 16 = Write: EXT (H0010); 17 = Write: PU (H0011); 20 = Write: NET (H0014) | |||
| HR | 13doc 40014 | Running frequency (RAM) | Frequency command, not stored in EEPROM. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 14doc 40015 | Running frequency (EEPROM) | Frequency command, also stored in EEPROM. | UINT16 | × 0.01 | Hz | Write | ||
| HR | 200doc 40201 | Output frequency / speed | 0.01 Hz, or 1 r/min when Pr.37 = 0.01-9998. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 201doc 40202 | Output current | UINT16 | × 0.01 | A | Read | |||
| HR | 202doc 40203 | Output voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 204doc 40205 | Set frequency / speed setting | 0.01 Hz, or 1 r/min when Pr.37 = 0.01-9998. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 207doc 40208 | Converter output voltage | DC bus voltage. | UINT16 | × 0.1 | V | Read | ||
| HR | 208doc 40209 | Regenerative brake duty | UINT16 | × 0.1 | % | Read | |||
| HR | 209doc 40210 | Electronic thermal relay load factor | UINT16 | × 0.1 | % | Read | |||
| HR | 210doc 40211 | Output current peak value | UINT16 | × 0.01 | A | Read | |||
| HR | 211doc 40212 | Converter output voltage peak value | UINT16 | × 0.1 | V | Read | |||
| HR | 213doc 40214 | Output power | UINT16 | × 0.01 | kW | Read | |||
| HR | 214doc 40215 | Input terminal status | 1 = on. | BITMAP16 | Read | bit 0 = STF; bit 1 = STR; bit 4 = RL; bit 5 = RM; bit 6 = RH | |||
| HR | 215doc 40216 | Output terminal status | 1 = on. | BITMAP16 | Read | bit 0 = RUN; bit 5 = ABC; bit 7 = SO | |||
| HR | 219doc 40220 | Cumulative energization time | UINT16 | h | Read | ||||
| HR | 222doc 40223 | Actual operation time | UINT16 | h | Read | ||||
| HR | 223doc 40224 | Motor load factor | Output current as % of rated inverter current. | UINT16 | × 0.1 | % | Read | ||
| HR | 224doc 40225 | Cumulative power | UINT16 | kWh | Read | ||||
| HR | 251doc 40252 | PID set point | UINT16 | × 0.1 | % | Read | |||
| HR | 252doc 40253 | PID measured value | UINT16 | × 0.1 | % | Read | |||
| HR | 260doc 40261 | Motor thermal load factor | UINT16 | × 0.1 | % | Read | |||
| HR | 261doc 40262 | Inverter thermal load factor | UINT16 | × 0.1 | % | Read | |||
| HR | 262doc 40263 | Cumulative power 2 | Only on units built after the version-up noted in the manual. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 263doc 40264 | PTC thermistor resistance | UINT16 | × 0.01 | kΩ | Read | |||
| HR | 500doc 40501 | Fault record 1 | Low byte = fault code (H00xx). Write any value to clear history. | UINT16 | Read/write | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 501doc 40502 | Fault record 2 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 502doc 40503 | Fault record 3 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 503doc 40504 | Fault record 4 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 504doc 40505 | Fault record 5 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 505doc 40506 | Fault record 6 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 506doc 40507 | Fault record 7 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 507doc 40508 | Fault record 8 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 145 = E.PTC; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 192 = E.CPU; 196 = E.CDO; 197 = E.IOH; 199 = E.AIE; 201 = E.SAF; 245 = E.5 | |||
| HR | 1000doc 41001 | Pr.1 Maximum frequency | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1001doc 41002 | Pr.2 Minimum frequency | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1003doc 41004 | Pr.4 Multi-speed setting (high speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1004doc 41005 | Pr.5 Multi-speed setting (middle speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1005doc 41006 | Pr.6 Multi-speed setting (low speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1078doc 41079 | Pr.79 Operation mode selection | UINT16 | Read/write | 0 = External/PU switchover (External at power-on); 1 = Fixed PU operation; 2 = Fixed External operation (NET switchable); 3 = External/PU combined mode 1; 4 = External/PU combined mode 2; 6 = Switchover mode; 7 = External operation (PU interlock) | ||||
| HR | 1116doc 41117 | Pr.117 PU communication station number | 0 = no reply (broadcast only); set 1-247. | UINT16 | Read/write | ||||
| HR | 1117doc 41118 | Pr.118 PU communication speed | Setting x 100 = bps (initial 192 = 19200). | UINT16 | Read/write | ||||
| HR | 1119doc 41120 | Pr.120 PU communication parity check | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit | ||||
| HR | 1121doc 41122 | Pr.122 PU communication check time interval | 0 = E.PUE as soon as NET mode is entered; 9999 = no check. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1342doc 41343 | Pr.343 Communication error count | Modbus RTU error count (RAM, cleared at reset). | UINT16 | Read | ||||
| HR | 1501doc 41502 | Pr.502 Stop mode selection at communication error | UINT16 | Read/write | 0 = Coast to stop, E.PUE; 1 = Decelerate, E.PUE after stop; 2 = Decelerate, E.PUE after stop, automatic restart on removal | ||||
| HR | 1548doc 41549 | Pr.549 Protocol selection | UINT16 | Read/write | 0 = Mitsubishi inverter protocol (computer link); 1 = MODBUS RTU |
Notes on this map
- All registers are single 16-bit words.
- Modbus RTU runs on the PU connector (RJ45-type RS-485 port), configured with the PU communication parameters Pr.117-Pr.122, not on separate terminals.
- Frequency registers use 0.01 Hz; with Pr.37 (speed display) set they switch to 1 r/min. The 0.01 Hz unit for 40014/40015 is from the same manual's computer-link set-frequency description (H0000-HFFFF in 0.01 Hz increments).
- Fault history registers hold the fault code in the low byte; the values listed are the manual's fault code list.
- Parameters with a 9999 (function off) setting, such as the communication check interval, are listed with their normal increment; the manual does not say how the 9999 setting itself is encoded on the wire, so read the parameter back after setting it from the panel.
- Parameters 0-999 sit at 41000 + Pr. number; calibration parameters C2-C25 have their own registers and are not listed. Pr.7/Pr.8 are left out (increment depends on Pr.21 / capacity).
- Left out because the sign is not stated: PID deviation 40254.
- Several status bits and real-time monitors depend on the unit's manufacturing date (marked Ver.UP in the manual); older units may read 0 there.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
What Modbus registers does the Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU) have?
This map lists 52 registers: 52 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modicon-style register numbers (40002, 41004) and states: starting address = register number - 40001. Its example reads 41004 (Pr.4) with start address H03EB (1003).
What are the minimum Modbus registers to integrate the Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)?
Start with HR 8 Inverter status / control input instruction (Run/stop command and inverter status); HR 9 Operation mode / inverter setting (Operation mode (write H0014 for NET)); HR 13 Running frequency (RAM) (Frequency command (RAM)); HR 200 Output frequency / speed (Output frequency); HR 201 Output current (Output current); HR 500 Fault record 1 (Latest fault code).
How do I enable Modbus control of the Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)?
Pr.549 = 1 selects Modbus RTU on the PU connector; set Pr.117 (station), Pr.118 (speed) and Pr.120 (parity) and reset. Operation and frequency commands need NET mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340).
What happens when the Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU) loses Modbus communication?
Pr.122 is the communication check interval (0.1-999.8 s) with Pr.502 choosing coast or decelerate on E.PUE. Initial value 0 trips E.PUE as soon as the drive enters NET mode, so set 9999 or an interval before switching.
Where is the official Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU) Modbus documentation?
The source is FR-D700 Instruction Manual (Applied) (IB(NA)-0600366ENG-H), revision 2018-06, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600366eng/ib0600366engh.pdf.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other variable frequency drives register maps
- Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Variable frequency drive
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse L510 micro inverters with the RS-485 option card, per communication addendum DOCUMENT-TECO-L510-AC001 Ver01 (2015-06).
Also known as: TECO L510, L510 Communication Addendum - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive
All variable frequency drives Modbus register maps →
Source: FR-D700 Instruction Manual (Applied) · IB(NA)-0600366ENG-H · rev. 2018-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.