  3. Mitsubishi Electric
  4. MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)

Air handler (heat recovery ventilation unit) · Modbus register map

Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus register map

Updated 19 November 2026

Short answer

Small Procon protocol converter that plugs into a Mitsubishi Electric Lossnay energy-recovery ventilator and serves Modbus RTU on RS-485 or Modbus TCP. For Lossnay units it gives on/off, ventilation mode (heat recovery / bypass / auto) and fan speed control, plus outdoor and room temperature, filter and maintenance signs, fault code, energy use and actual fan speeds.

This page lists 50 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Equipment type
Air handler (heat recovery ventilation unit)
Registers
50 (7 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
4.1.1
Also known as
A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical
Source document
Procon MelcoBEMS MINI (A1M+) Installation Manual · Manual version 1.0.3 · rev. 2025-09-18
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)

Integration in brief

Set DIP 7 ON for Modbus RTU, set the node address on DIP 1-5 and DIP 6 ON for 9600 / no parity (or use Modbus TCP on port 502). Check input 9 reads 2, then switch the unit with holding 300, pick the ventilation mode at 302 and fan speed at 303, and poll the temperatures, filter sign and fault code.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 9System type detectedUINT16Confirms a Lossnay is detected (2)Read
HR 300Power on/offUINT16Power on/offRead/write
HR 302Ventilation modeUINT16Ventilation modeRead/write
HR 303Fan speedUINT16Fan speed (1-4)Read/write
IR 175Outdoor temperature (signed)INT16Outdoor temperature (signed, x10)Read
IR 177Room temperatureUINT16Room temperature (x10)Read
DI 84Filter signBITFilter signRead
IR 179Fault code (hex)UINT16Fault code (0x8000 = none)Read

Enable Modbus control & writes

DIP switch 7 ON selects Modbus RTU on RS-485 (OFF = BACnet MS/TP and BACnet IP). The Ethernet port serves Modbus TCP on port 502.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

50 of 50 shown
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO3doc 00004Power on/offSame as holding 300.BITRead/write0 = Off; 1 = On
DI82doc 10083Night purgeBITRead0 = Normal operation; 1 = Night purge running
DI83doc 10084Maintenance signBITRead0 = Inactive; 1 = Active
DI84doc 10085Filter signBITRead0 = Inactive; 1 = Active
DI85doc 10086Actual ventilation modeBITRead0 = Lossnay ventilation; 1 = Bypass ventilation
DI90doc 10091Energy consumption data availableBITRead0 = Not available; 1 = Available
DI91doc 10092Bypass damper availableBITRead0 = Not available; 1 = Available
DI92doc 10093Auto ventilation mode availableBITRead0 = Not available; 1 = Available
DI94doc 10095Outdoor temperature sensorBITRead0 = Not equipped; 1 = Equipped
DI95doc 10096Return air temperature sensorBITRead0 = Not equipped; 1 = Equipped
IR3doc 30004Gateway firmware versionUINT16Read
IR5doc 30006Modbus comms counterCounts valid Modbus commands; wraps to 0 after 65535.UINT16Read
IR9doc 30010System type detected2 means a Lossnay is connected.UINT16Read0 = Air-To-Air unit; 1 = Air-To-Water system; 2 = Lossnay system; 255 = Undetermined (no unit detected yet)
IR175doc 30176Outdoor temperature (signed)Signed °C x 10 (0xFDD0 = -56.0). 0x7FFE detecting, 0x7FFF no thermistor.INT16× 0.1°CRead
IR176doc 30177Outdoor temperature (unsigned)Unsigned twin of outdoor temperature, °C x 10. 0x7FFE detecting, 0x7FFF no thermistor.UINT16× 0.1°CRead
IR177doc 30178Room temperatureReturn-air (room) temperature, °C x 10. Needs the return-air sensor.UINT16× 0.1°CRead
IR179doc 30180Fault code (hex)Lossnay fault code in hex form.UINT16Read26985 = No communication with the unit (0x6999); 32768 = No error (0x8000)
IR180doc 30181Fault code (decimal)Same fault code shown as decimal digits.UINT16Read6999 = No communication with the unit; 8000 = No error
IR181doc 30182Energy consumptionkWh x 10 (0-6553.5 kWh).UINT16× 0.1kWhRead
IR183doc 30184Actual supply fan speedUINT16Read0 = Stop; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4
IR184doc 30185Actual extract fan speedUINT16Read0 = Stop; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4
IR191doc 30192Number of fan speeds1-4.UINT16Read
HR4doc 40005Modbus slave IDUsed when DIP 1-5 are all ON; 1-247.UINT16Read/write
HR5doc 40006RS-485 baud rateUsed when DIP 6 is OFF.UINT16Read/write0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200
HR6doc 40007RS-485 parityUsed when DIP 6 is OFF.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR9doc 40010Fault code (hex)Read-only; other codes are in the Lossnay documentation.UINT16Read26985 = No communication with the unit (0x6999); 32768 = No error (0x8000)
HR10doc 40011Gateway firmware versionRead-only copy of input register 3.UINT16Read
HR11doc 40012Modbus comms counterCounts valid Modbus commands; wraps to 0 after 65535.UINT16Read
HR13doc 40014System type detectedRead-only copy of input register 9.UINT16Read0 = Air-To-Air unit; 1 = Air-To-Water system; 2 = Lossnay system; 255 = Undetermined (no unit detected yet)
HR300doc 40301Power on/offUINT16Read/write0 = Off; 1 = On
HR302doc 40303Ventilation modeUINT16Read/write0 = Lossnay (heat recovery) mode; 1 = Bypass mode; 2 = Auto mode
HR303doc 40304Fan speedAuto (0) is not supported on LGH or VL units.UINT16Read/write0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4
HR306doc 40307Outdoor temperature (signed)Signed °C x 10 (0xFDD0 = -56.0). 0x7FFE detecting, 0x7FFF no thermistor.INT16× 0.1°CRead
HR307doc 40308Outdoor temperature (unsigned)Unsigned twin of outdoor temperature, °C x 10. 0x7FFE detecting, 0x7FFF no thermistor.UINT16× 0.1°CRead
HR308doc 40309Room temperatureReturn-air (room) temperature, °C x 10. Needs the return-air sensor.UINT16× 0.1°CRead
HR310doc 40311Fault code (hex)Lossnay fault code in hex form.UINT16Read26985 = No communication with the unit (0x6999); 32768 = No error (0x8000)
HR311doc 40312Fault code (decimal)Same fault code shown as decimal digits.UINT16Read6999 = No communication with the unit; 8000 = No error
HR313doc 40314Energy consumptionkWh x 10 (0-6553.5 kWh).UINT16× 0.1kWhRead
HR316doc 40317Night purgeUINT16Read0 = Normal operation; 1 = Night purge running
HR317doc 40318Maintenance signUINT16Read0 = Inactive; 1 = Active
HR318doc 40319Filter signUINT16Read0 = Inactive; 1 = Active
HR319doc 40320Actual ventilation modeUINT16Read0 = Lossnay ventilation; 1 = Bypass ventilation
HR320doc 40321Actual supply fan speedUINT16Read0 = Stop; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4
HR321doc 40322Actual extract fan speedUINT16Read0 = Stop; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4
HR332doc 40333Energy consumption data availableUINT16Read0 = Not available; 1 = Available
HR333doc 40334Number of fan speeds1-4.UINT16Read
HR334doc 40335Bypass damper availableUINT16Read0 = Not available; 1 = Available
HR335doc 40336Auto ventilation mode availableUINT16Read0 = Not available; 1 = Available
HR338doc 40339Outdoor temperature sensorUINT16Read0 = Not equipped; 1 = Equipped
HR339doc 40340Return air temperature sensorUINT16Read0 = Not equipped; 1 = Equipped

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)

What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) have?

This map lists 50 registers: 1 coil, 9 discrete inputs, 12 input registers, 28 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row prints a 0-based 'Addr' next to its Modicon number (40001 = holding 0, 30001 = input 0, 10001 = discrete input 0, 00001 = coil 0). The 0-based Addr is the wire address.

What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)?

Start with IR 9 System type detected (Confirms a Lossnay is detected (2)); HR 300 Power on/off (Power on/off); HR 302 Ventilation mode (Ventilation mode); HR 303 Fan speed (Fan speed (1-4)); IR 175 Outdoor temperature (signed) (Outdoor temperature (signed, x10)); IR 177 Room temperature (Room temperature (x10)); DI 84 Filter sign (Filter sign); IR 179 Fault code (hex) (Fault code (0x8000 = none)).

How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)?

DIP switch 7 ON selects Modbus RTU on RS-485 (OFF = BACnet MS/TP and BACnet IP). The Ethernet port serves Modbus TCP on port 502.

Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus documentation?

The source is Procon MelcoBEMS MINI (A1M+) Installation Manual (Manual version 1.0.3), revision 2025-09-18, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5538.

More Mitsubishi Electric Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Procon MelcoBEMS MINI (A1M+) Installation Manual · Manual version 1.0.3 · rev. 2025-09-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.