- MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Air handler (heat recovery ventilation unit) · Modbus register map
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus register map
Updated 19 November 2026
Small Procon protocol converter that plugs into a Mitsubishi Electric Lossnay energy-recovery ventilator and serves Modbus RTU on RS-485 or Modbus TCP. For Lossnay units it gives on/off, ventilation mode (heat recovery / bypass / auto) and fan speed control, plus outdoor and room temperature, filter and maintenance signs, fault code, energy use and actual fan speeds.
This page lists 50 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
- Equipment type
- Air handler (heat recovery ventilation unit)
- Registers
- 50 (7 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- 4.1.1
- Also known as
- A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical
Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Set DIP 7 ON for Modbus RTU, set the node address on DIP 1-5 and DIP 6 ON for 9600 / no parity (or use Modbus TCP on port 502). Check input 9 reads 2, then switch the unit with holding 300, pick the ventilation mode at 302 and fan speed at 303, and poll the temperatures, filter sign and fault code.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 9 | System type detected | UINT16 | Confirms a Lossnay is detected (2) | Read |
| HR 300 | Power on/off | UINT16 | Power on/off | Read/write |
| HR 302 | Ventilation mode | UINT16 | Ventilation mode | Read/write |
| HR 303 | Fan speed | UINT16 | Fan speed (1-4) | Read/write |
| IR 175 | Outdoor temperature (signed) | INT16 | Outdoor temperature (signed, x10) | Read |
| IR 177 | Room temperature | UINT16 | Room temperature (x10) | Read |
| DI 84 | Filter sign | BIT | Filter sign | Read |
| IR 179 | Fault code (hex) | UINT16 | Fault code (0x8000 = none) | Read |
Enable Modbus control & writes
DIP switch 7 ON selects Modbus RTU on RS-485 (OFF = BACnet MS/TP and BACnet IP). The Ethernet port serves Modbus TCP on port 502.
Byte order & addressing
- Fault code 0x8000 (decimal register: 8000) means no fault; 0x6999 / 6999 means the gateway cannot talk to the Lossnay.
- Temperatures read 0x7FFE while the sensor is being detected and 0x7FFF when no thermistor is fitted.
- Write fan speed 1-4 only; Auto (0) is not supported on LGH and VL units.
- Check holding 334 / 335 before writing bypass or auto ventilation mode: they say whether the unit has a bypass damper and auto mode.
Network setup
- RS-485 A, B and GND must all be connected; shielded cable, daisy chain only.
- Factory IP address 192.168.92.114, Modbus TCP port 502.
- Node address 1-30 on DIP 1-5 in binary; each converter on the bus needs its own address.
Watch out for
- The gateway detects ATA, ATW or Lossnay by itself; the Lossnay map applies only when the system type reads 2.
- Outdoor and room temperatures only read correctly when the matching sensor flag (338 / 339) reads 1 (equipped).
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 3doc 00004 | Power on/off | Same as holding 300. | BIT | Read/write | 0 = Off; 1 = On | |||
| DI | 82doc 10083 | Night purge | BIT | Read | 0 = Normal operation; 1 = Night purge running | ||||
| DI | 83doc 10084 | Maintenance sign | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 84doc 10085 | Filter sign | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 85doc 10086 | Actual ventilation mode | BIT | Read | 0 = Lossnay ventilation; 1 = Bypass ventilation | ||||
| DI | 90doc 10091 | Energy consumption data available | BIT | Read | 0 = Not available; 1 = Available | ||||
| DI | 91doc 10092 | Bypass damper available | BIT | Read | 0 = Not available; 1 = Available | ||||
| DI | 92doc 10093 | Auto ventilation mode available | BIT | Read | 0 = Not available; 1 = Available | ||||
| DI | 94doc 10095 | Outdoor temperature sensor | BIT | Read | 0 = Not equipped; 1 = Equipped | ||||
| DI | 95doc 10096 | Return air temperature sensor | BIT | Read | 0 = Not equipped; 1 = Equipped | ||||
| IR | 3doc 30004 | Gateway firmware version | UINT16 | Read | |||||
| IR | 5doc 30006 | Modbus comms counter | Counts valid Modbus commands; wraps to 0 after 65535. | UINT16 | Read | ||||
| IR | 9doc 30010 | System type detected | 2 means a Lossnay is connected. | UINT16 | Read | 0 = Air-To-Air unit; 1 = Air-To-Water system; 2 = Lossnay system; 255 = Undetermined (no unit detected yet) | |||
| IR | 175doc 30176 | Outdoor temperature (signed) | Signed °C x 10 (0xFDD0 = -56.0). 0x7FFE detecting, 0x7FFF no thermistor. | INT16 | × 0.1 | °C | Read | ||
| IR | 176doc 30177 | Outdoor temperature (unsigned) | Unsigned twin of outdoor temperature, °C x 10. 0x7FFE detecting, 0x7FFF no thermistor. | UINT16 | × 0.1 | °C | Read | ||
| IR | 177doc 30178 | Room temperature | Return-air (room) temperature, °C x 10. Needs the return-air sensor. | UINT16 | × 0.1 | °C | Read | ||
| IR | 179doc 30180 | Fault code (hex) | Lossnay fault code in hex form. | UINT16 | Read | 26985 = No communication with the unit (0x6999); 32768 = No error (0x8000) | |||
| IR | 180doc 30181 | Fault code (decimal) | Same fault code shown as decimal digits. | UINT16 | Read | 6999 = No communication with the unit; 8000 = No error | |||
| IR | 181doc 30182 | Energy consumption | kWh x 10 (0-6553.5 kWh). | UINT16 | × 0.1 | kWh | Read | ||
| IR | 183doc 30184 | Actual supply fan speed | UINT16 | Read | 0 = Stop; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4 | ||||
| IR | 184doc 30185 | Actual extract fan speed | UINT16 | Read | 0 = Stop; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4 | ||||
| IR | 191doc 30192 | Number of fan speeds | 1-4. | UINT16 | Read | ||||
| HR | 4doc 40005 | Modbus slave ID | Used when DIP 1-5 are all ON; 1-247. | UINT16 | Read/write | ||||
| HR | 5doc 40006 | RS-485 baud rate | Used when DIP 6 is OFF. | UINT16 | Read/write | 0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200 | |||
| HR | 6doc 40007 | RS-485 parity | Used when DIP 6 is OFF. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 9doc 40010 | Fault code (hex) | Read-only; other codes are in the Lossnay documentation. | UINT16 | Read | 26985 = No communication with the unit (0x6999); 32768 = No error (0x8000) | |||
| HR | 10doc 40011 | Gateway firmware version | Read-only copy of input register 3. | UINT16 | Read | ||||
| HR | 11doc 40012 | Modbus comms counter | Counts valid Modbus commands; wraps to 0 after 65535. | UINT16 | Read | ||||
| HR | 13doc 40014 | System type detected | Read-only copy of input register 9. | UINT16 | Read | 0 = Air-To-Air unit; 1 = Air-To-Water system; 2 = Lossnay system; 255 = Undetermined (no unit detected yet) | |||
| HR | 300doc 40301 | Power on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 302doc 40303 | Ventilation mode | UINT16 | Read/write | 0 = Lossnay (heat recovery) mode; 1 = Bypass mode; 2 = Auto mode | ||||
| HR | 303doc 40304 | Fan speed | Auto (0) is not supported on LGH or VL units. | UINT16 | Read/write | 0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4 | |||
| HR | 306doc 40307 | Outdoor temperature (signed) | Signed °C x 10 (0xFDD0 = -56.0). 0x7FFE detecting, 0x7FFF no thermistor. | INT16 | × 0.1 | °C | Read | ||
| HR | 307doc 40308 | Outdoor temperature (unsigned) | Unsigned twin of outdoor temperature, °C x 10. 0x7FFE detecting, 0x7FFF no thermistor. | UINT16 | × 0.1 | °C | Read | ||
| HR | 308doc 40309 | Room temperature | Return-air (room) temperature, °C x 10. Needs the return-air sensor. | UINT16 | × 0.1 | °C | Read | ||
| HR | 310doc 40311 | Fault code (hex) | Lossnay fault code in hex form. | UINT16 | Read | 26985 = No communication with the unit (0x6999); 32768 = No error (0x8000) | |||
| HR | 311doc 40312 | Fault code (decimal) | Same fault code shown as decimal digits. | UINT16 | Read | 6999 = No communication with the unit; 8000 = No error | |||
| HR | 313doc 40314 | Energy consumption | kWh x 10 (0-6553.5 kWh). | UINT16 | × 0.1 | kWh | Read | ||
| HR | 316doc 40317 | Night purge | UINT16 | Read | 0 = Normal operation; 1 = Night purge running | ||||
| HR | 317doc 40318 | Maintenance sign | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 318doc 40319 | Filter sign | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 319doc 40320 | Actual ventilation mode | UINT16 | Read | 0 = Lossnay ventilation; 1 = Bypass ventilation | ||||
| HR | 320doc 40321 | Actual supply fan speed | UINT16 | Read | 0 = Stop; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4 | ||||
| HR | 321doc 40322 | Actual extract fan speed | UINT16 | Read | 0 = Stop; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4 | ||||
| HR | 332doc 40333 | Energy consumption data available | UINT16 | Read | 0 = Not available; 1 = Available | ||||
| HR | 333doc 40334 | Number of fan speeds | 1-4. | UINT16 | Read | ||||
| HR | 334doc 40335 | Bypass damper available | UINT16 | Read | 0 = Not available; 1 = Available | ||||
| HR | 335doc 40336 | Auto ventilation mode available | UINT16 | Read | 0 = Not available; 1 = Available | ||||
| HR | 338doc 40339 | Outdoor temperature sensor | UINT16 | Read | 0 = Not equipped; 1 = Equipped | ||||
| HR | 339doc 40340 | Return air temperature sensor | UINT16 | Read | 0 = Not equipped; 1 = Equipped |
Notes on this map
- Only rows the manual ticks for the Lossnay LGH and/or VL series are listed. Every listed row is ticked for both series.
- Rows printed with no tick for either series are left out: operating mode (40302), temperature setpoint (40305), supply air temperature (40306 / 30175), CO2 level (40310 / 30179), thermo on/off, actual operation mode, auto fan speed availability, the 0.5 °C step / heat-cool / auto availability flags, the min/max setpoint limits, the temperature-control-unit flags and the supply-air and CO2 sensor flags.
- All input registers, discrete inputs and the coil are mirrored as read-only holding registers (power on/off is writable on both holding 300 and coil 3).
- Outdoor temperature comes twice: signed (two's complement, down to -56.0 °C) and an unsigned twin for BMSs that cannot handle negative values.
- Fan speed value 0 (Auto) is marked not supported on LGH and VL units.
- The older MelcoBEMS MINI (A1M) manual v1.1.11, section 13 (https://library.mitsubishielectric.co.uk/pdf/download_full/5186, pp. 37-49), prints the same Lossnay table, addresses and ticks; the A1M is RS-485 only (no Modbus TCP).
- DIP switches: 1-5 node address (all OFF = 1, all ON = holding 4), 6 ON = 9600 baud no parity (OFF = holding 5/6), 7 ON = Modbus RTU (OFF = BACnet). Data bits 8 and stop bits 1 are fixed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) have?
This map lists 50 registers: 1 coil, 9 discrete inputs, 12 input registers, 28 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row prints a 0-based 'Addr' next to its Modicon number (40001 = holding 0, 30001 = input 0, 10001 = discrete input 0, 00001 = coil 0). The 0-based Addr is the wire address.
What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)?
Start with IR 9 System type detected (Confirms a Lossnay is detected (2)); HR 300 Power on/off (Power on/off); HR 302 Ventilation mode (Ventilation mode); HR 303 Fan speed (Fan speed (1-4)); IR 175 Outdoor temperature (signed) (Outdoor temperature (signed, x10)); IR 177 Room temperature (Room temperature (x10)); DI 84 Filter sign (Filter sign); IR 179 Fault code (hex) (Fault code (0x8000 = none)).
How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)?
DIP switch 7 ON selects Modbus RTU on RS-485 (OFF = BACnet MS/TP and BACnet IP). The Ethernet port serves Modbus TCP on port 502.
Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series) Modbus documentation?
The source is Procon MelcoBEMS MINI (A1M+) Installation Manual (Manual version 1.0.3), revision 2025-09-18, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5538.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other hvac equipment register maps
- Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Thermostat / temperature and process PID controller
Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)
PAX2C version 2.0 register table (LP0905F, 2017-02-27); the FlexCard (PX2FCA0/PX2FCA1) blocks of the same table are not included.
Also known as: PAX2CHZVR, PAX2C00000, PX2FCA0, PX2FCA1 - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Thermostat (fan heater controller)
VTS HMI-VOLCANO EC controller for VOLCANO air heaters
VTS HMI-VOLCANO EC wall controller with Modbus RTU, device integration manual version 1.1.
Also known as: HMI VOLCANO EC, VOLCANO EC controller - Air curtain controller (Air handler / door heater)
Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
Berner air curtains with the IntelliSwitch Gen 5 control and the AIR BMS package; register document 3.1.0212 (January 2025).
Also known as: IntelliSwitch Gen 5, Berner AIR BMS, AIR BMS Package - Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)
DriSteem humidifiers with the earlier Vapor-logic version 5 controller, per IOM form VL5-IOM-0914.
Also known as: Vapor-logic version 5, VL5, Vapor-logic5
All hvac equipment Modbus register maps →
Source: Procon MelcoBEMS MINI (A1M+) Installation Manual · Manual version 1.0.3 · rev. 2025-09-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.