Easy Modbus
  1. Home
  2. Modbus register maps
  3. VTS
  4. HMI-VOLCANO EC controller for VOLCANO air heaters

Thermostat (fan heater controller) · Modbus register map

VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus register map

Updated 17 November 2026

Short answer

The HMI-VOLCANO EC is the room controller for VTS VOLCANO EC fan heaters, which can run in heating or cooling mode. Over Modbus RTU a BMS can switch it on and off, choose heating or cooling, set the fan output and room setpoint, edit the weekly schedule and read the room temperature, schedule state and output states.

This page lists 49 Modbus registers for the VTS HMI-VOLCANO EC controller for VOLCANO air heaters — 39 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from VTS’s own free documentation (linked below) and checked against it.

Manufacturer
VTS
Model
HMI-VOLCANO EC controller for VOLCANO air heaters
Equipment type
Thermostat (fan heater controller)
Registers
49 (39 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
HMI VOLCANO EC, VOLCANO EC controller
Source document
HMI-VOLCANO EC - Device Integration Manual on Modbus RTU Bus · version 1.1
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: VTS HMI-VOLCANO EC controller for VOLCANO air heaters

Integration in brief

Switch the unit with coil 2, select heating/cooling with holding 21, set the room setpoint (0.01 °C) in holding 23 and fan output % in holding 22; read the room temperature from input register 0.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 2MB_ADDR_POWER_ON_OFFBITOn/offRead/write
HR 21MB_ADDR_ZONE_MODEUINT16Heating/coolingRead/write
HR 23MB_ADDR_ZONE_TEMPERATURE_TARGETUINT16Room setpointRead/write
HR 22MB_ADDR_ZONE_FAN_SPEEDUINT16Fan output %Read/write
IR 0MB_ADDR_ZONE_TEMPERATURE_ACTUALINT16Room temperatureRead
IR 1MB_ADDR_ZONE_ACTUAL_PROGRAM_STATEUINT16Schedule stateRead
HR 19MB_ADDR_ZONE_PROGRAMUINT16Continuous or scheduleRead/write

Enable Modbus control & writes

Modbus RTU is always active on the RS485 terminals (J3 A/B); change baud, parity and address through holding registers 0-2 (the device restarts after each change).

Byte order & addressing

Network setup

Watch out for

VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

49 of 49 shown
VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0 (0x0000)MB_ADDR_STATE_OUTPUT_1Output J1-H1 state; write-locked.BITRead
CO1doc 1 (0x0001)MB_ADDR_STATE_OUTPUT_2Output J1-H2 state; write-locked.BITRead
CO2doc 2 (0x0002)MB_ADDR_POWER_ON_OFF1 = on, 0 = off (like the power key).BITRead/write
CO3doc 3 (0x0003)MB_ADDR_GO_TO_DEFAULTWriting it restores default values of the settings.BITWrite
CO4doc 4 (0x0004)MB_ADDR_LOCK_KEYPAD1 = keys locked.BITRead/write
DI0doc 0 (0x0000)MB_ADDR_NTC_1_ACTIVE1 = built-in temperature sensor active.BITRead
DI1doc 1 (0x0001)MB_ADDR_NTC_2_ACTIVE1 = external temperature sensor active.BITRead
IR0doc 0 (0x0000)MB_ADDR_ZONE_TEMPERATURE_ACTUALRoom temperature; -32768 means sensor fault.INT16× 0.01°CRead
IR1doc 1 (0x0001)MB_ADDR_ZONE_ACTUAL_PROGRAM_STATESchedule state.UINT16Read0 = Continuous (schedule off); 1 = On 1 (first period); 2 = Off 1 (between periods); 3 = On 2 (second period); 4 = Off 2 (after second period)
HR0doc 0 (0x0000)MB_ADDR_BAUDRATEBaud rate / 10: 480, 960, 1920 or 3840. Write alone; device resets.UINT16Read/write480 = 4800 bps; 960 = 9600 bps; 1920 = 19200 bps; 3840 = 38400 bps
HR1doc 1 (0x0001)MB_ADDR_PARITY_MODEASCII code of the parity letter. Write alone; device resets.UINT16Read/write101 = 'e' even parity, 1 stop bit; 110 = 'n' no parity, 2 stop bits; 111 = 'o' odd parity, 1 stop bit
HR2doc 2 (0x0002)MB_ADDR_SLAVE_ADDR1-247. Write alone; device resets.UINT16Read/write
HR3doc 3 (0x0003)MB_ADDR_NTC_1_CORRECTBuilt-in sensor correction, -8.00 to 8.00 °C. Write alone.INT16× 0.01°CRead/write
HR4doc 4 (0x0004)MB_ADDR_NTC_PERIODTime between temperature readings; 0 switches reading off.UINT16× 0.1sRead/write
HR5doc 5 (0x0005)MB_ADDR_RTC_WEEK_DAYSet automatically from the date.UINT16Read/write0 = Monday; 1 = Tuesday; 2 = Wednesday; 3 = Thursday; 4 = Friday; 5 = Saturday; 6 = Sunday
HR6doc 6 (0x0006)MB_ADDR_RTC_YEAR0-99.UINT16Read/write
HR7doc 7 (0x0007)MB_ADDR_RTC_MONTH1-12.UINT16Read/write
HR8doc 8 (0x0008)MB_ADDR_RTC_DAY1-31.UINT16Read/write
HR9doc 9 (0x0009)MB_ADDR_RTC_HOUR0-23.UINT16Read/write
HR10doc 10 (0x000A)MB_ADDR_RTC_MINUTE0-59.UINT16Read/write
HR11doc 11 (0x000B)MB_ADDR_RTC_SECOND0-59.UINT16Read/write
HR12doc 12 (0x000C)MB_ADDR_FAN_ACTUAL_POWER_VOLTPresent fan analogue output voltage; write-locked.UINT16× 0.01VRead
HR13doc 13 (0x000D)MB_ADDR_FAN_POWER_1_VOLTFan output voltage for speed 1; write-locked.UINT16× 0.01VRead
HR14doc 14 (0x000E)MB_ADDR_FAN_POWER_2_VOLTFan output voltage for speed 2; write-locked.UINT16× 0.01VRead
HR15doc 15 (0x000F)MB_ADDR_FAN_POWER_3_VOLTFan output voltage for speed 3; write-locked.UINT16× 0.01VRead
HR16doc 16 (0x0010)MB_ADDR_FAN_ADDITIONAL_VOLTConstant added to the fan output, 0.00-4.00 V.UINT16× 0.01VRead/write
HR17doc 17 (0x0011)MB_ADDR_ZONE_DISPLAYED_TEMPTemperature shown on the main screen.UINT16Read/write0 = Set (requested) temperature; 1 = Room temperature
HR18doc 18 (0x0012)MB_ADDR_ZONE_AVAILABLE_MODEAllowed operating modes.UINT16Read/write1 = Cooling only; 2 = Heating only; 3 = Cooling and heating
HR19doc 19 (0x0013)MB_ADDR_ZONE_PROGRAMUINT16Read/write0 = Continuous; 1 = Schedule
HR20doc 20 (0x0014)MB_ADDR_ZONE_ECO_FROST_MODEProtection when room drops below the ECO temperature.UINT16Read/write0 = Off; 1 = AntiFrost (valve opens); 2 = ECO (valve opens and fan starts)
HR21doc 21 (0x0015)MB_ADDR_ZONE_MODECurrent operating mode.UINT16Read/write0 = Cooling; 1 = Heating
HR22doc 22 (0x0016)MB_ADDR_ZONE_FAN_SPEEDAir output 0-100 %; 0-14 % is treated as 0.UINT16%Read/write
HR23doc 23 (0x0017)MB_ADDR_ZONE_TEMPERATURE_TARGETRoom setpoint, rounded to 0.5 °C, between MIN and MAX.UINT16× 0.01°CRead/write
HR24doc 24 (0x0018)MB_ADDR_ZONE_TEMPERATURE_ECOFrost/ECO protection temperature, 2-22 °C.UINT16× 0.01°CRead/write
HR25doc 25 (0x0019)MB_ADDR_ZONE_TEMPERATURE_DELTAHysteresis, 0.50-2.00 °C.UINT16× 0.01°CRead/write
HR26doc 26 (0x001A)MB_ADDR_ZONE_TEMPERATURE_MINLowest setpoint allowed.UINT16× 0.01°CRead/write
HR27doc 27 (0x001B)MB_ADDR_ZONE_TEMPERATURE_MAXHighest setpoint allowed (up to 40.00 °C).UINT16× 0.01°CRead/write
HR28doc 28 (0x001C)MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_1_STARTMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR29doc 29 (0x001D)MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_1_STOPMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR30doc 30 (0x001E)MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_2_STARTMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR31doc 31 (0x001F)MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_2_STOPMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR32doc 32 (0x0020)MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_STARTMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR33doc 33 (0x0021)MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_STOPMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR34doc 34 (0x0022)MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_STARTMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR35doc 35 (0x0023)MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_STOPMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR36doc 36 (0x0024)MB_ADDR_ZONE_SCHEDULE_SUN_WORK_1_STARTMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR37doc 37 (0x0025)MB_ADDR_ZONE_SCHEDULE_SUN_WORK_1_STOPMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR38doc 38 (0x0026)MB_ADDR_ZONE_SCHEDULE_SUN_WORK_2_STARTMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write
HR39doc 39 (0x0027)MB_ADDR_ZONE_SCHEDULE_SUN_WORK_2_STOPMinutes after midnight (h x 60 + m), 0-1425, 15-minute steps.UINT16minRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the VTS HMI-VOLCANO EC controller for VOLCANO air heaters

What Modbus registers does the VTS HMI-VOLCANO EC controller for VOLCANO air heaters have?

This map lists 49 registers: 5 coils, 2 discrete inputs, 2 input registers, 40 holding registers. 39 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table gives the address 'for PDU' in decimal and hex (first register 0 = 0x0000), so that address goes on the wire unchanged. The function-code examples count registers from 1 instead (register 108 is requested as 0x006B = 107), which matches: PDU address = register number - 1. This map uses the 'for PDU' column.

What are the minimum Modbus registers to integrate the VTS HMI-VOLCANO EC controller for VOLCANO air heaters?

Start with CO 2 MB_ADDR_POWER_ON_OFF (On/off); HR 21 MB_ADDR_ZONE_MODE (Heating/cooling); HR 23 MB_ADDR_ZONE_TEMPERATURE_TARGET (Room setpoint); HR 22 MB_ADDR_ZONE_FAN_SPEED (Fan output %); IR 0 MB_ADDR_ZONE_TEMPERATURE_ACTUAL (Room temperature); IR 1 MB_ADDR_ZONE_ACTUAL_PROGRAM_STATE (Schedule state); HR 19 MB_ADDR_ZONE_PROGRAM (Continuous or schedule).

How do I enable Modbus control of the VTS HMI-VOLCANO EC controller for VOLCANO air heaters?

Modbus RTU is always active on the RS485 terminals (J3 A/B); change baud, parity and address through holding registers 0-2 (the device restarts after each change).

Where is the official VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus documentation?

The source is HMI-VOLCANO EC - Device Integration Manual on Modbus RTU Bus (version 1.1), published free by VTS at https://www.vtsgroup.com/files/document-files/86/Modbus_RTU_Manual.pdf.

More VTS Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: HMI-VOLCANO EC - Device Integration Manual on Modbus RTU Bus · version 1.1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.