- HMI-VOLCANO EC controller for VOLCANO air heaters
Thermostat (fan heater controller) · Modbus register map
VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus register map
Updated 17 November 2026
The HMI-VOLCANO EC is the room controller for VTS VOLCANO EC fan heaters, which can run in heating or cooling mode. Over Modbus RTU a BMS can switch it on and off, choose heating or cooling, set the fan output and room setpoint, edit the weekly schedule and read the room temperature, schedule state and output states.
This page lists 49 Modbus registers for the VTS HMI-VOLCANO EC controller for VOLCANO air heaters — 39 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from VTS’s own free documentation (linked below) and checked against it.
- Manufacturer
- VTS
- Model
- HMI-VOLCANO EC controller for VOLCANO air heaters
- Equipment type
- Thermostat (fan heater controller)
- Registers
- 49 (39 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- HMI VOLCANO EC, VOLCANO EC controller
Integration notes: VTS HMI-VOLCANO EC controller for VOLCANO air heaters
Switch the unit with coil 2, select heating/cooling with holding 21, set the room setpoint (0.01 °C) in holding 23 and fan output % in holding 22; read the room temperature from input register 0.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 2 | MB_ADDR_POWER_ON_OFF | BIT | On/off | Read/write |
| HR 21 | MB_ADDR_ZONE_MODE | UINT16 | Heating/cooling | Read/write |
| HR 23 | MB_ADDR_ZONE_TEMPERATURE_TARGET | UINT16 | Room setpoint | Read/write |
| HR 22 | MB_ADDR_ZONE_FAN_SPEED | UINT16 | Fan output % | Read/write |
| IR 0 | MB_ADDR_ZONE_TEMPERATURE_ACTUAL | INT16 | Room temperature | Read |
| IR 1 | MB_ADDR_ZONE_ACTUAL_PROGRAM_STATE | UINT16 | Schedule state | Read |
| HR 19 | MB_ADDR_ZONE_PROGRAM | UINT16 | Continuous or schedule | Read/write |
Enable Modbus control & writes
Modbus RTU is always active on the RS485 terminals (J3 A/B); change baud, parity and address through holding registers 0-2 (the device restarts after each change).
Byte order & addressing
- Setpoints are rounded to 0.5 °C and schedule times to 15 minutes.
- Parity is written as the ASCII code of 'e', 'o' or 'n'; 'n' uses 2 stop bits.
- Writing a setpoint below MIN or above MAX is refused.
Network setup
- RS485 on terminal block J3 (A, B, ground).
- Default 9600 baud, even parity, address 1.
Watch out for
- A sensor fault reads -32768 (shown as 327.68 when treated as unsigned).
VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0 (0x0000) | MB_ADDR_STATE_OUTPUT_1 | Output J1-H1 state; write-locked. | BIT | Read | ||||
| CO | 1doc 1 (0x0001) | MB_ADDR_STATE_OUTPUT_2 | Output J1-H2 state; write-locked. | BIT | Read | ||||
| CO | 2doc 2 (0x0002) | MB_ADDR_POWER_ON_OFF | 1 = on, 0 = off (like the power key). | BIT | Read/write | ||||
| CO | 3doc 3 (0x0003) | MB_ADDR_GO_TO_DEFAULT | Writing it restores default values of the settings. | BIT | Write | ||||
| CO | 4doc 4 (0x0004) | MB_ADDR_LOCK_KEYPAD | 1 = keys locked. | BIT | Read/write | ||||
| DI | 0doc 0 (0x0000) | MB_ADDR_NTC_1_ACTIVE | 1 = built-in temperature sensor active. | BIT | Read | ||||
| DI | 1doc 1 (0x0001) | MB_ADDR_NTC_2_ACTIVE | 1 = external temperature sensor active. | BIT | Read | ||||
| IR | 0doc 0 (0x0000) | MB_ADDR_ZONE_TEMPERATURE_ACTUAL | Room temperature; -32768 means sensor fault. | INT16 | × 0.01 | °C | Read | ||
| IR | 1doc 1 (0x0001) | MB_ADDR_ZONE_ACTUAL_PROGRAM_STATE | Schedule state. | UINT16 | Read | 0 = Continuous (schedule off); 1 = On 1 (first period); 2 = Off 1 (between periods); 3 = On 2 (second period); 4 = Off 2 (after second period) | |||
| HR | 0doc 0 (0x0000) | MB_ADDR_BAUDRATE | Baud rate / 10: 480, 960, 1920 or 3840. Write alone; device resets. | UINT16 | Read/write | 480 = 4800 bps; 960 = 9600 bps; 1920 = 19200 bps; 3840 = 38400 bps | |||
| HR | 1doc 1 (0x0001) | MB_ADDR_PARITY_MODE | ASCII code of the parity letter. Write alone; device resets. | UINT16 | Read/write | 101 = 'e' even parity, 1 stop bit; 110 = 'n' no parity, 2 stop bits; 111 = 'o' odd parity, 1 stop bit | |||
| HR | 2doc 2 (0x0002) | MB_ADDR_SLAVE_ADDR | 1-247. Write alone; device resets. | UINT16 | Read/write | ||||
| HR | 3doc 3 (0x0003) | MB_ADDR_NTC_1_CORRECT | Built-in sensor correction, -8.00 to 8.00 °C. Write alone. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4doc 4 (0x0004) | MB_ADDR_NTC_PERIOD | Time between temperature readings; 0 switches reading off. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 5doc 5 (0x0005) | MB_ADDR_RTC_WEEK_DAY | Set automatically from the date. | UINT16 | Read/write | 0 = Monday; 1 = Tuesday; 2 = Wednesday; 3 = Thursday; 4 = Friday; 5 = Saturday; 6 = Sunday | |||
| HR | 6doc 6 (0x0006) | MB_ADDR_RTC_YEAR | 0-99. | UINT16 | Read/write | ||||
| HR | 7doc 7 (0x0007) | MB_ADDR_RTC_MONTH | 1-12. | UINT16 | Read/write | ||||
| HR | 8doc 8 (0x0008) | MB_ADDR_RTC_DAY | 1-31. | UINT16 | Read/write | ||||
| HR | 9doc 9 (0x0009) | MB_ADDR_RTC_HOUR | 0-23. | UINT16 | Read/write | ||||
| HR | 10doc 10 (0x000A) | MB_ADDR_RTC_MINUTE | 0-59. | UINT16 | Read/write | ||||
| HR | 11doc 11 (0x000B) | MB_ADDR_RTC_SECOND | 0-59. | UINT16 | Read/write | ||||
| HR | 12doc 12 (0x000C) | MB_ADDR_FAN_ACTUAL_POWER_VOLT | Present fan analogue output voltage; write-locked. | UINT16 | × 0.01 | V | Read | ||
| HR | 13doc 13 (0x000D) | MB_ADDR_FAN_POWER_1_VOLT | Fan output voltage for speed 1; write-locked. | UINT16 | × 0.01 | V | Read | ||
| HR | 14doc 14 (0x000E) | MB_ADDR_FAN_POWER_2_VOLT | Fan output voltage for speed 2; write-locked. | UINT16 | × 0.01 | V | Read | ||
| HR | 15doc 15 (0x000F) | MB_ADDR_FAN_POWER_3_VOLT | Fan output voltage for speed 3; write-locked. | UINT16 | × 0.01 | V | Read | ||
| HR | 16doc 16 (0x0010) | MB_ADDR_FAN_ADDITIONAL_VOLT | Constant added to the fan output, 0.00-4.00 V. | UINT16 | × 0.01 | V | Read/write | ||
| HR | 17doc 17 (0x0011) | MB_ADDR_ZONE_DISPLAYED_TEMP | Temperature shown on the main screen. | UINT16 | Read/write | 0 = Set (requested) temperature; 1 = Room temperature | |||
| HR | 18doc 18 (0x0012) | MB_ADDR_ZONE_AVAILABLE_MODE | Allowed operating modes. | UINT16 | Read/write | 1 = Cooling only; 2 = Heating only; 3 = Cooling and heating | |||
| HR | 19doc 19 (0x0013) | MB_ADDR_ZONE_PROGRAM | UINT16 | Read/write | 0 = Continuous; 1 = Schedule | ||||
| HR | 20doc 20 (0x0014) | MB_ADDR_ZONE_ECO_FROST_MODE | Protection when room drops below the ECO temperature. | UINT16 | Read/write | 0 = Off; 1 = AntiFrost (valve opens); 2 = ECO (valve opens and fan starts) | |||
| HR | 21doc 21 (0x0015) | MB_ADDR_ZONE_MODE | Current operating mode. | UINT16 | Read/write | 0 = Cooling; 1 = Heating | |||
| HR | 22doc 22 (0x0016) | MB_ADDR_ZONE_FAN_SPEED | Air output 0-100 %; 0-14 % is treated as 0. | UINT16 | % | Read/write | |||
| HR | 23doc 23 (0x0017) | MB_ADDR_ZONE_TEMPERATURE_TARGET | Room setpoint, rounded to 0.5 °C, between MIN and MAX. | UINT16 | × 0.01 | °C | Read/write | ||
| HR | 24doc 24 (0x0018) | MB_ADDR_ZONE_TEMPERATURE_ECO | Frost/ECO protection temperature, 2-22 °C. | UINT16 | × 0.01 | °C | Read/write | ||
| HR | 25doc 25 (0x0019) | MB_ADDR_ZONE_TEMPERATURE_DELTA | Hysteresis, 0.50-2.00 °C. | UINT16 | × 0.01 | °C | Read/write | ||
| HR | 26doc 26 (0x001A) | MB_ADDR_ZONE_TEMPERATURE_MIN | Lowest setpoint allowed. | UINT16 | × 0.01 | °C | Read/write | ||
| HR | 27doc 27 (0x001B) | MB_ADDR_ZONE_TEMPERATURE_MAX | Highest setpoint allowed (up to 40.00 °C). | UINT16 | × 0.01 | °C | Read/write | ||
| HR | 28doc 28 (0x001C) | MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_1_START | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 29doc 29 (0x001D) | MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_1_STOP | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 30doc 30 (0x001E) | MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_2_START | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 31doc 31 (0x001F) | MB_ADDR_ZONE_SCHEDULE_MON_FRI_WORK_2_STOP | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 32doc 32 (0x0020) | MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_START | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 33doc 33 (0x0021) | MB_ADDR_ZONE_SCHEDULE_SAT_WORK_1_STOP | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 34doc 34 (0x0022) | MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_START | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 35doc 35 (0x0023) | MB_ADDR_ZONE_SCHEDULE_SAT_WORK_2_STOP | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 36doc 36 (0x0024) | MB_ADDR_ZONE_SCHEDULE_SUN_WORK_1_START | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 37doc 37 (0x0025) | MB_ADDR_ZONE_SCHEDULE_SUN_WORK_1_STOP | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 38doc 38 (0x0026) | MB_ADDR_ZONE_SCHEDULE_SUN_WORK_2_START | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write | |||
| HR | 39doc 39 (0x0027) | MB_ADDR_ZONE_SCHEDULE_SUN_WORK_2_STOP | Minutes after midnight (h x 60 + m), 0-1425, 15-minute steps. | UINT16 | min | Read/write |
Notes on this map
- Holding registers 0-3 (baud, parity, address, sensor correction) must be written one per message; a multi-register write that includes them is refused.
- Temperatures are in 0.01 °C (value / 100). When the controller is set to °F, temperature registers are in °F with the same scale.
- Left out: coils 5 and 6 (temperature unit and clock format) and holding register 40 (fan regulation mode), which appear only in the default-value table and not in the register tables.
- Defaults per the default-value table: 9600 baud (960), even parity, address 1, setpoint 22.00 °C, ECO 18.00 °C.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the VTS HMI-VOLCANO EC controller for VOLCANO air heaters
What Modbus registers does the VTS HMI-VOLCANO EC controller for VOLCANO air heaters have?
This map lists 49 registers: 5 coils, 2 discrete inputs, 2 input registers, 40 holding registers. 39 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table gives the address 'for PDU' in decimal and hex (first register 0 = 0x0000), so that address goes on the wire unchanged. The function-code examples count registers from 1 instead (register 108 is requested as 0x006B = 107), which matches: PDU address = register number - 1. This map uses the 'for PDU' column.
What are the minimum Modbus registers to integrate the VTS HMI-VOLCANO EC controller for VOLCANO air heaters?
Start with CO 2 MB_ADDR_POWER_ON_OFF (On/off); HR 21 MB_ADDR_ZONE_MODE (Heating/cooling); HR 23 MB_ADDR_ZONE_TEMPERATURE_TARGET (Room setpoint); HR 22 MB_ADDR_ZONE_FAN_SPEED (Fan output %); IR 0 MB_ADDR_ZONE_TEMPERATURE_ACTUAL (Room temperature); IR 1 MB_ADDR_ZONE_ACTUAL_PROGRAM_STATE (Schedule state); HR 19 MB_ADDR_ZONE_PROGRAM (Continuous or schedule).
How do I enable Modbus control of the VTS HMI-VOLCANO EC controller for VOLCANO air heaters?
Modbus RTU is always active on the RS485 terminals (J3 A/B); change baud, parity and address through holding registers 0-2 (the device restarts after each change).
Where is the official VTS HMI-VOLCANO EC controller for VOLCANO air heaters Modbus documentation?
The source is HMI-VOLCANO EC - Device Integration Manual on Modbus RTU Bus (version 1.1), published free by VTS at https://www.vtsgroup.com/files/document-files/86/Modbus_RTU_Manual.pdf.
More VTS Modbus register maps
- Sensor
VTS CO2-SENS-D-MODRTU
VTS CO2-SENS-D-MODRTU duct CO2 transducer (MH-Z19B sensing module), manual ver. 2.0 (11.2021).
Also known as: CO2 transducer CO2-SENS-D-MODRTU, VTS duct CO2 sensor - Sensor
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer
VTS RH+T-SENS-D-MODRTU duct humidity and temperature transducer (Sensirion SHT31-DIS-B), manual ver. 2.0 (11.2021).
Also known as: RH&T-SENS-D-MODRTU, VTS duct humidity sensor
Other hvac equipment register maps
- Air curtain controller (Air handler / door heater)
Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
Berner air curtains with the IntelliSwitch Gen 5 control and the AIR BMS package; register document 3.1.0212 (January 2025).
Also known as: IntelliSwitch Gen 5, Berner AIR BMS, AIR BMS Package - Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)
DriSteem humidifiers with the earlier Vapor-logic version 5 controller, per IOM form VL5-IOM-0914.
Also known as: Vapor-logic version 5, VL5, Vapor-logic5 - Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat (shelter HVAC lead/lag controller)
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
Marvair CommStat 4 controllers with protocol version 3 or later and software revision 67 or later, read through the Marvair Modbus Interface Adapter.
Also known as: CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272 - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller
All hvac equipment Modbus register maps →
Source: HMI-VOLCANO EC - Device Integration Manual on Modbus RTU Bus · version 1.1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.