Air handler humidifier (steam humidifier controller) · Modbus register map

DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Vapor-logic 5 is the previous-generation DriSteem humidifier controller (electric, GTS gas, XT electrode, STS steam-to-steam and high-pressure systems). Modbus RTU is standard. Its point list is close to Vapor-logic 6 but not identical: input registers for humidity, dew point, demand and output, holding registers for run mode, set points, fieldbus demand and PID, discrete inputs that also report the fill and drain valves, and coils for every alarm and message.

This page lists 107 Modbus registers for the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) — 72 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DriSteem’s own free documentation (linked below) and checked against it.

Manufacturer
DriSteem
Model
Vapor-logic 5 humidifier controller (Modbus RTU)
Equipment type
Air handler humidifier (steam humidifier controller)
Registers
107 (72 writable)
Transport
Modbus RTU
Default unit ID
99
Default serial
9600 baud
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
Vapor-logic version 5
Also known as
Vapor-logic version 5, VL5, Vapor-logic5
Source document
Vapor-logic Version 5 Installation and Operation Manual · VL5-IOM-0914 (Part No. 890000-721 Rev B) · rev. 2014-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)

Integration in brief

Enable Modbus in the Communications setup and poll input registers 0-10 for humidity, demand and output. To command the unit write Run_mode (40001) and a set point (40002) or fieldbus demand (40006).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Space_RHUINT16Space RHRead
IR 8Steam_output_percentUINT16Steam output %Read
IR 4Steam_demand_percentUINT16Steam demand %Read
HR 0Run_modeUINT16Run modeRead/write
HR 1Space_RH_set_pointUINT16Space RH set pointWrite
HR 5Fieldbus_demand_%UINT16Fieldbus demand %Write
CO 2Active_manually_cleared_alarms_existBITManually cleared alarms existRead
CO 3Clear_all_faultsBITClear all faultsRead/write

Enable Modbus control & writes

Setup menu > Communications > Modbus: Modbus enabled = Yes, Modbus address (default 99) and baud rate (default 9600).

Byte order & addressing

Network setup

Watch out for

DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

107 of 107 shown
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc DV-1 / 1Active_messages_existReserved.BITRead
CO1doc DV-2 / 2Active_auto_cleared_alarms_existReserved.BITRead
CO2doc DV-3 / 3Active_manually_cleared_alarms_existSet when manually cleared alarms exist.BITRead
CO3doc DV-4 / 4Clear_all_faultsWrite 1 to clear all active faults.BITRead/write
CO4doc DV-5 / 5Alarm_tank_temp_sensor_failedAlarm flag.BITRead/write
CO5doc DV-6 / 6Alarm_tank_overtempAlarm flag.BITRead/write
CO6doc DV-7 / 7Alarm_RH / dew point / demand signal out of rangeAlarm: RH, dew point or demand signal out of range.BITRead/write
CO7doc DV-8 / 8Alarm_duct_RH_sig_out_of_rangeAlarm flag.BITRead/write
CO8doc DV-9 / 9Alarm_aux_temp_sens_out_of_rangeAlarm flag.BITRead/write
CO9doc DV-10 / 10Alarm_water_probe_miswiredAlarm flag.BITRead/write
CO10doc DV-11 / 11Alarm_water_probe_failedAlarm flag.BITRead/write
CO11doc DV-12 / 12Alarm_excess_fill_timeAlarm flag.BITRead/write
CO12doc DV-13 / 13Alarm_excess_refill_timeAlarm flag.BITRead/write
CO13doc DV-14 / 14Alarm_tank_not_drainingAlarm flag.BITRead/write
CO14doc DV-15 / 15Alarm_excess_water_no_demandAlarm flag.BITRead/write
CO15doc DV-16 / 16Alarm_no_SDU_airflowAlarm flag.BITRead/write
CO16doc DV-17 / 17Alarm_no_power_vent_airflowAlarm flag.BITRead/write
CO17doc DV-18 / 18Alarm_no_combustion_airflowAlarm flag.BITRead/write
CO18doc DV-19 / 19Alarm_blocked_flueAlarm flag.BITRead/write
CO19doc DV-20 / 20Alarm_burner_1_failedAlarm flag.BITRead/write
CO20doc DV-21 / 21Alarm_burner_2_failedAlarm flag.BITRead/write
CO21doc DV-22 / 22Alarm_burner_3_failedAlarm flag.BITRead/write
CO22doc DV-23 / 23Alarm_burner_4_failedAlarm flag.BITRead/write
CO23doc DV-24 / 24Alarm_ignition_module_1_failedAlarm flag.BITRead/write
CO24doc DV-25 / 25Alarm_ignition_module_2_failedAlarm flag.BITRead/write
CO25doc DV-26 / 26Alarm_ignition_module_3_failedAlarm flag.BITRead/write
CO26doc DV-27 / 27Alarm_ignition_module_4_failedAlarm flag.BITRead/write
CO27doc DV-28 / 28Alarm_blower_1_failedAlarm flag.BITRead/write
CO28doc DV-29 / 29Alarm_blower_2_failedAlarm flag.BITRead/write
CO29doc DV-30 / 30Alarm_blower_3_failedAlarm flag.BITRead/write
CO30doc DV-31 / 31Alarm_blower_4_failedAlarm flag.BITRead/write
CO31doc DV-32 / 32Alarm_gas_valve_1_failedAlarm flag.BITRead/write
CO32doc DV-33 / 33Alarm_gas_valve_2_failedAlarm flag.BITRead/write
CO33doc DV-34 / 34Alarm_gas_valve_3_failedAlarm flag.BITRead/write
CO34doc DV-35 / 35Alarm_gas_valve_4_failedAlarm flag.BITRead/write
CO35doc DV-36 / 36Alarm_low_water (GTS)Alarm flag.BITRead/write
CO36doc DV-37 / 37Alarm_foaming_fault_2 (XT) / Alarm_low_inlet_pressure (HPS)Alarm flag.BITRead/write
CO37doc DV-38 / 38Message_replace_contactorsMessage flag.BITRead/write
CO38doc DV-39 / 39Message_service_unitMessage flag.BITRead/write
CO39doc DV-40 / 40Message_drain_pendingMessage flag.BITRead/write
CO40doc DV-41 / 41Message_no_duct_airflowMessage flag.BITRead/write
CO41doc DV-42 / 42Message_interlock_openMessage flag.BITRead/write
CO42doc DV-43 / 43Message_freeze_prevent_drainingMessage flag.BITRead/write
CO43doc DV-44 / 44Message_end-of-season_activeMessage flag.BITRead/write
CO44doc DV-45 / 45Message_temp_comp_onMessage flag.BITRead/write
CO45doc DV-46 / 46Message_clean_probesMessage flag.BITRead/write
CO46doc DV-47 / 47Message_duct_HL_tripMessage flag.BITRead/write
CO47doc DV-48 / 48Message_duct_HL_spanMessage flag.BITRead/write
CO48doc DV-49 / 49Message_insufficient_water / Insufficient_supplyMessage flag.BITRead/write
CO49doc DV-50 / 50Message_boiling_temp_calibratedMessage flag.BITRead/write
CO50doc DV-51 / 51Alarm_Current_Sense1_Out_Of_Range (XT)Alarm flag.BITRead/write
CO51doc DV-52 / 52Alarm_Current_Sense2_Out_Of_Range (XT)Alarm flag.BITRead/write
CO52doc DV-53 / 53Alarm_Overcurrent (XT) / Alarm_high_inlet_pressure (HPS)Alarm flag.BITRead/write
CO53doc DV-54 / 54Alarm_Supply_Water (XT) / Alarm_supply_water_undertemp (HPS)Alarm flag.BITRead/write
CO54doc DV-55 / 55Alarm_Foaming_Fault (XT) / Alarm_high_pump_pressure (HPS)Alarm flag.BITRead/write
CO55doc DV-56 / 56Message_Check_CylinderMessage flag.BITRead/write
CO56doc DV-57 / 57Alarm_Overcurrent_2 (XT) / Alarm_supply_water_overtemp (HPS)Alarm flag.BITRead/write
CO57doc DV-58 / 58Alarm_Supply_Water_2 (XT) / Alarm_low_pump_pressure (HPS)Alarm flag.BITRead/write
CO58doc DV-59 / 59Message_Check_Cylinder_2Message flag.BITRead/write
CO59doc DV-60 / 60Message_master_enable_openMessage flag.BITRead/write
DI0doc DI-1 / 10001Airflow_proving_switchBITRead0 = Open; 1 = Closed
DI1doc DI-2 / 10002Duct_HL_switchDuct high limit switch.BITRead0 = Open; 1 = Closed
DI2doc DI-3 / 10003Safety_interlockBITRead0 = Open; 1 = Closed
DI3doc DI-4 / 10004Combustion_air_damper (GTS) / Stage_1 (high-pressure)GTS: 0 damper closed, 1 open. High-pressure: 0 closed, 1 open.BITRead
DI4doc DI-5 / 10005Flue_pressure_switch (GTS) / Stage_2 (high-pressure)GTS: 0 open, 1 closed. High-pressure: 0 closed, 1 open.BITRead
DI5doc DI-6 / 10006Power_vent_switch (GTS) / XV_header_status (STS) / Stage_3 (high-pressure)GTS 0 vent off 1 on; STS 0 not ready 1 ready; high-pressure 0 closed 1 open.BITRead
DI6doc DI-7 / 10007Low_water_sensor (GTS)BITRead0 = No water; 1 = Water
DI7doc DI-8 / 10008Fill_valveBITRead0 = Closed; 1 = Open
DI8doc DI-9 / 10009Drain_valveBITRead0 = Not draining; 1 = Draining
DI9doc DI-10 / 10010MT_active_fault_exists_somewhereMulti-tank only.BITRead0 = No; 1 = Yes
DI10doc DI-11 / 10011MT_active_message_exists_somewhereMulti-tank only.BITRead0 = No; 1 = Yes
DI11doc DI-12 / 10012High_water_sensor (XT)XT only.BITRead0 = No water; 1 = Water
DI12doc DI-13 / 10013High_water_sensor_2 (XT)Right cylinder, two-cylinder XT only.BITRead0 = No water; 1 = Water
DI13doc DI-14 / 10014Pump_selected (HPS)HPS only.BITRead0 = Pump 1; 1 = Pump 2
DI14doc DI-15 / 10015VFD_drive_fault (HPS)HPS only.BITRead0 = No fault; 1 = Fault
IR0doc IR-1 / 30001Space_RHSpace relative humidity.UINT16%Read
IR1doc IR-2 / 30002Space_dew_pointSpace dew point; °F or °C per unit setting.INT16°F / °CRead
IR2doc IR-3 / 30003Duct_RHDuct relative humidity.UINT16%Read
IR3doc IR-4 / 30004Steam_demand_massSteam demand, lbs/hr or kg/h.UINT16lbs/hr / kg/hRead
IR4doc IR-5 / 30005Steam_demand_percentSteam demand as % of capacity.UINT16%Read
IR5doc IR-6 / 30006Aux_tempAuxiliary temperature sensor.INT16°F / °CRead
IR6doc IR-7 / 30007Water_tempEvaporating-chamber water temperature.INT16°F / °CRead
IR7doc IR-8 / 30008Steam_output_massEstimated steam output.UINT16lbs/hr / kg/hRead
IR8doc IR-9 / 30009Steam_output_percentEstimated output as % of capacity.UINT16%Read
IR9doc IR-10 / 30010Water_until_ADSWater left before next auto drain sequence; one count = 100 lbs or 100 kg.UINT16× 100lbs / kgRead
IR10doc IR-11 / 30011Water_until_serviceWater left before next service; one count = 100 lbs or 100 kg.UINT16× 100lbs / kgRead
IR22doc IR-23 / 30023MT_sys_output_mass_hrMulti-tank system steam demand.UINT16lbs/hr / kg/hRead
IR24doc IR-25 / 30025MT_sys_output_pcntMulti-tank system steam demand.UINT16%Read
IR25doc IR-26 / 30026Current_1 (XT)XT operating current.UINT16ARead
IR26doc IR-27 / 30027Current_2 (XT)XT operating current, right cylinder.UINT16ARead
IR27doc IR-28 / 30028In_Pressure (high-pressure systems)Supply pressure.UINT16psi / barRead
IR28doc IR-29 / 30029Out_Pressure (high-pressure systems)Output pressure.UINT16psi / barRead
HR0doc HR-1 / 40001Run_modeUnit mode. Write 1-4; reads can also return 5 or 6.UINT16Read/write1 = Auto; 2 = Local standby; 3 = System standby; 4 = Manual drain; 5 = Test outputs (read only); 6 = Test run (read only)
HR1doc HR-2 / 40002Space_RH_set_pointSpace humidity set point (write).UINT16%Write
HR2doc HR-3 / 40003Space_dew_point_set_pointSpace dew point set point (write).INT16°F / °CWrite
HR3doc HR-4 / 40004Duct_high_limit_set_pointDuct high limit set point (write).UINT16%Write
HR4doc HR-5 / 40005Fieldbus_demand_massSteam demand over the fieldbus; above capacity runs at 100%.UINT16lbs/hr / kg/hWrite
HR5doc HR-6 / 40006Fieldbus_demand_%Steam demand over the fieldbus, % of capacity.UINT16%Write
HR6doc HR-7 / 40007PID_bandUINT16%Read/write
HR7doc HR-8 / 40008PID-KpProportional gain.UINT16Read/write
HR8doc HR-9 / 40009PID-KiIntegral gain.UINT16Read/write
HR9doc HR-10 / 40010PID-KdDerivative gain.UINT16Read/write
HR13doc HR-14 / 40014MT_runmodeMulti-tank run mode.UINT16Read/write1 = System standby; 2 = System auto
HR14doc HR-15 / 40015MT_steam_req_mass_hrMulti-tank fieldbus steam request.UINT16lbs/hr / kg/hWrite
HR16doc HR-17 / 40017MT_steam_req_sys_pcntMulti-tank fieldbus request, % of system capacity.UINT16%Write
HR17doc HR-18 / 40018Pump_1_hoursHPS pump 1 hours since reset.UINT16hRead/write
HR18doc HR-19 / 40019Pump_2_hoursHPS pump 2 hours since reset.UINT16hRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)

What Modbus registers does the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) have?

This map lists 107 registers: 60 coils, 15 discrete inputs, 17 input registers, 15 holding registers. 72 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Points are printed as IR-1 / 30001, HR-1 / 40001, DI-1 / 10001 and coil DV-1 / 1. These are one-based Modicon numbers: subtract one for the wire address (30001 -> input register 0, coil 1 -> coil 0).

What are the minimum Modbus registers to integrate the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)?

Start with IR 0 Space_RH (Space RH); IR 8 Steam_output_percent (Steam output %); IR 4 Steam_demand_percent (Steam demand %); HR 0 Run_mode (Run mode); HR 1 Space_RH_set_point (Space RH set point); HR 5 Fieldbus_demand_% (Fieldbus demand %); CO 2 Active_manually_cleared_alarms_exist (Manually cleared alarms exist); CO 3 Clear_all_faults (Clear all faults).

How do I enable Modbus control of the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)?

Setup menu > Communications > Modbus: Modbus enabled = Yes, Modbus address (default 99) and baud rate (default 9600).

Where is the official DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus documentation?

The source is Vapor-logic Version 5 Installation and Operation Manual (VL5-IOM-0914 (Part No. 890000-721 Rev B)), revision 2014-09, published free by DriSteem at https://d2tsmyh31fn7w8.cloudfront.net/public-documents/docs/historical-literature/vl5-iom.pdf.

More DriSteem Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Vapor-logic Version 5 Installation and Operation Manual · VL5-IOM-0914 (Part No. 890000-721 Rev B) · rev. 2014-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.