Air handler humidifier (steam humidifier controller) · Modbus register map
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus register map
Updated 19 November 2026
Vapor-logic 5 is the previous-generation DriSteem humidifier controller (electric, GTS gas, XT electrode, STS steam-to-steam and high-pressure systems). Modbus RTU is standard. Its point list is close to Vapor-logic 6 but not identical: input registers for humidity, dew point, demand and output, holding registers for run mode, set points, fieldbus demand and PID, discrete inputs that also report the fill and drain valves, and coils for every alarm and message.
This page lists 107 Modbus registers for the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) — 72 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DriSteem’s own free documentation (linked below) and checked against it.
- Manufacturer
- DriSteem
- Model
- Vapor-logic 5 humidifier controller (Modbus RTU)
- Equipment type
- Air handler humidifier (steam humidifier controller)
- Registers
- 107 (72 writable)
- Transport
- Modbus RTU
- Default unit ID
- 99
- Default serial
- 9600 baud
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- Vapor-logic version 5
- Also known as
- Vapor-logic version 5, VL5, Vapor-logic5
Integration notes: DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)
Enable Modbus in the Communications setup and poll input registers 0-10 for humidity, demand and output. To command the unit write Run_mode (40001) and a set point (40002) or fieldbus demand (40006).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Space_RH | UINT16 | Space RH | Read |
| IR 8 | Steam_output_percent | UINT16 | Steam output % | Read |
| IR 4 | Steam_demand_percent | UINT16 | Steam demand % | Read |
| HR 0 | Run_mode | UINT16 | Run mode | Read/write |
| HR 1 | Space_RH_set_point | UINT16 | Space RH set point | Write |
| HR 5 | Fieldbus_demand_% | UINT16 | Fieldbus demand % | Write |
| CO 2 | Active_manually_cleared_alarms_exist | BIT | Manually cleared alarms exist | Read |
| CO 3 | Clear_all_faults | BIT | Clear all faults | Read/write |
Enable Modbus control & writes
Setup menu > Communications > Modbus: Modbus enabled = Yes, Modbus address (default 99) and baud rate (default 9600).
Byte order & addressing
- Printed numbers are Modicon-style: subtract one for the wire address.
- Units switch between I-P and SI with the unit setting; there are no decimal places.
Network setup
- Wire the RS-485 bus to terminal P7 on the Vapor-logic board (+ to +, - to -), set address and baud in Setup > Communications, then cycle power.
Watch out for
- The map differs from Vapor-logic 6 (e.g. DI-8/DI-9 report fill and drain valves here); use the list matching the controller version.
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc DV-1 / 1 | Active_messages_exist | Reserved. | BIT | Read | ||||
| CO | 1doc DV-2 / 2 | Active_auto_cleared_alarms_exist | Reserved. | BIT | Read | ||||
| CO | 2doc DV-3 / 3 | Active_manually_cleared_alarms_exist | Set when manually cleared alarms exist. | BIT | Read | ||||
| CO | 3doc DV-4 / 4 | Clear_all_faults | Write 1 to clear all active faults. | BIT | Read/write | ||||
| CO | 4doc DV-5 / 5 | Alarm_tank_temp_sensor_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 5doc DV-6 / 6 | Alarm_tank_overtemp | Alarm flag. | BIT | Read/write | ||||
| CO | 6doc DV-7 / 7 | Alarm_RH / dew point / demand signal out of range | Alarm: RH, dew point or demand signal out of range. | BIT | Read/write | ||||
| CO | 7doc DV-8 / 8 | Alarm_duct_RH_sig_out_of_range | Alarm flag. | BIT | Read/write | ||||
| CO | 8doc DV-9 / 9 | Alarm_aux_temp_sens_out_of_range | Alarm flag. | BIT | Read/write | ||||
| CO | 9doc DV-10 / 10 | Alarm_water_probe_miswired | Alarm flag. | BIT | Read/write | ||||
| CO | 10doc DV-11 / 11 | Alarm_water_probe_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 11doc DV-12 / 12 | Alarm_excess_fill_time | Alarm flag. | BIT | Read/write | ||||
| CO | 12doc DV-13 / 13 | Alarm_excess_refill_time | Alarm flag. | BIT | Read/write | ||||
| CO | 13doc DV-14 / 14 | Alarm_tank_not_draining | Alarm flag. | BIT | Read/write | ||||
| CO | 14doc DV-15 / 15 | Alarm_excess_water_no_demand | Alarm flag. | BIT | Read/write | ||||
| CO | 15doc DV-16 / 16 | Alarm_no_SDU_airflow | Alarm flag. | BIT | Read/write | ||||
| CO | 16doc DV-17 / 17 | Alarm_no_power_vent_airflow | Alarm flag. | BIT | Read/write | ||||
| CO | 17doc DV-18 / 18 | Alarm_no_combustion_airflow | Alarm flag. | BIT | Read/write | ||||
| CO | 18doc DV-19 / 19 | Alarm_blocked_flue | Alarm flag. | BIT | Read/write | ||||
| CO | 19doc DV-20 / 20 | Alarm_burner_1_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 20doc DV-21 / 21 | Alarm_burner_2_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 21doc DV-22 / 22 | Alarm_burner_3_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 22doc DV-23 / 23 | Alarm_burner_4_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 23doc DV-24 / 24 | Alarm_ignition_module_1_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 24doc DV-25 / 25 | Alarm_ignition_module_2_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 25doc DV-26 / 26 | Alarm_ignition_module_3_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 26doc DV-27 / 27 | Alarm_ignition_module_4_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 27doc DV-28 / 28 | Alarm_blower_1_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 28doc DV-29 / 29 | Alarm_blower_2_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 29doc DV-30 / 30 | Alarm_blower_3_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 30doc DV-31 / 31 | Alarm_blower_4_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 31doc DV-32 / 32 | Alarm_gas_valve_1_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 32doc DV-33 / 33 | Alarm_gas_valve_2_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 33doc DV-34 / 34 | Alarm_gas_valve_3_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 34doc DV-35 / 35 | Alarm_gas_valve_4_failed | Alarm flag. | BIT | Read/write | ||||
| CO | 35doc DV-36 / 36 | Alarm_low_water (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 36doc DV-37 / 37 | Alarm_foaming_fault_2 (XT) / Alarm_low_inlet_pressure (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 37doc DV-38 / 38 | Message_replace_contactors | Message flag. | BIT | Read/write | ||||
| CO | 38doc DV-39 / 39 | Message_service_unit | Message flag. | BIT | Read/write | ||||
| CO | 39doc DV-40 / 40 | Message_drain_pending | Message flag. | BIT | Read/write | ||||
| CO | 40doc DV-41 / 41 | Message_no_duct_airflow | Message flag. | BIT | Read/write | ||||
| CO | 41doc DV-42 / 42 | Message_interlock_open | Message flag. | BIT | Read/write | ||||
| CO | 42doc DV-43 / 43 | Message_freeze_prevent_draining | Message flag. | BIT | Read/write | ||||
| CO | 43doc DV-44 / 44 | Message_end-of-season_active | Message flag. | BIT | Read/write | ||||
| CO | 44doc DV-45 / 45 | Message_temp_comp_on | Message flag. | BIT | Read/write | ||||
| CO | 45doc DV-46 / 46 | Message_clean_probes | Message flag. | BIT | Read/write | ||||
| CO | 46doc DV-47 / 47 | Message_duct_HL_trip | Message flag. | BIT | Read/write | ||||
| CO | 47doc DV-48 / 48 | Message_duct_HL_span | Message flag. | BIT | Read/write | ||||
| CO | 48doc DV-49 / 49 | Message_insufficient_water / Insufficient_supply | Message flag. | BIT | Read/write | ||||
| CO | 49doc DV-50 / 50 | Message_boiling_temp_calibrated | Message flag. | BIT | Read/write | ||||
| CO | 50doc DV-51 / 51 | Alarm_Current_Sense1_Out_Of_Range (XT) | Alarm flag. | BIT | Read/write | ||||
| CO | 51doc DV-52 / 52 | Alarm_Current_Sense2_Out_Of_Range (XT) | Alarm flag. | BIT | Read/write | ||||
| CO | 52doc DV-53 / 53 | Alarm_Overcurrent (XT) / Alarm_high_inlet_pressure (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 53doc DV-54 / 54 | Alarm_Supply_Water (XT) / Alarm_supply_water_undertemp (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 54doc DV-55 / 55 | Alarm_Foaming_Fault (XT) / Alarm_high_pump_pressure (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 55doc DV-56 / 56 | Message_Check_Cylinder | Message flag. | BIT | Read/write | ||||
| CO | 56doc DV-57 / 57 | Alarm_Overcurrent_2 (XT) / Alarm_supply_water_overtemp (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 57doc DV-58 / 58 | Alarm_Supply_Water_2 (XT) / Alarm_low_pump_pressure (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 58doc DV-59 / 59 | Message_Check_Cylinder_2 | Message flag. | BIT | Read/write | ||||
| CO | 59doc DV-60 / 60 | Message_master_enable_open | Message flag. | BIT | Read/write | ||||
| DI | 0doc DI-1 / 10001 | Airflow_proving_switch | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 1doc DI-2 / 10002 | Duct_HL_switch | Duct high limit switch. | BIT | Read | 0 = Open; 1 = Closed | |||
| DI | 2doc DI-3 / 10003 | Safety_interlock | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 3doc DI-4 / 10004 | Combustion_air_damper (GTS) / Stage_1 (high-pressure) | GTS: 0 damper closed, 1 open. High-pressure: 0 closed, 1 open. | BIT | Read | ||||
| DI | 4doc DI-5 / 10005 | Flue_pressure_switch (GTS) / Stage_2 (high-pressure) | GTS: 0 open, 1 closed. High-pressure: 0 closed, 1 open. | BIT | Read | ||||
| DI | 5doc DI-6 / 10006 | Power_vent_switch (GTS) / XV_header_status (STS) / Stage_3 (high-pressure) | GTS 0 vent off 1 on; STS 0 not ready 1 ready; high-pressure 0 closed 1 open. | BIT | Read | ||||
| DI | 6doc DI-7 / 10007 | Low_water_sensor (GTS) | BIT | Read | 0 = No water; 1 = Water | ||||
| DI | 7doc DI-8 / 10008 | Fill_valve | BIT | Read | 0 = Closed; 1 = Open | ||||
| DI | 8doc DI-9 / 10009 | Drain_valve | BIT | Read | 0 = Not draining; 1 = Draining | ||||
| DI | 9doc DI-10 / 10010 | MT_active_fault_exists_somewhere | Multi-tank only. | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 10doc DI-11 / 10011 | MT_active_message_exists_somewhere | Multi-tank only. | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 11doc DI-12 / 10012 | High_water_sensor (XT) | XT only. | BIT | Read | 0 = No water; 1 = Water | |||
| DI | 12doc DI-13 / 10013 | High_water_sensor_2 (XT) | Right cylinder, two-cylinder XT only. | BIT | Read | 0 = No water; 1 = Water | |||
| DI | 13doc DI-14 / 10014 | Pump_selected (HPS) | HPS only. | BIT | Read | 0 = Pump 1; 1 = Pump 2 | |||
| DI | 14doc DI-15 / 10015 | VFD_drive_fault (HPS) | HPS only. | BIT | Read | 0 = No fault; 1 = Fault | |||
| IR | 0doc IR-1 / 30001 | Space_RH | Space relative humidity. | UINT16 | % | Read | |||
| IR | 1doc IR-2 / 30002 | Space_dew_point | Space dew point; °F or °C per unit setting. | INT16 | °F / °C | Read | |||
| IR | 2doc IR-3 / 30003 | Duct_RH | Duct relative humidity. | UINT16 | % | Read | |||
| IR | 3doc IR-4 / 30004 | Steam_demand_mass | Steam demand, lbs/hr or kg/h. | UINT16 | lbs/hr / kg/h | Read | |||
| IR | 4doc IR-5 / 30005 | Steam_demand_percent | Steam demand as % of capacity. | UINT16 | % | Read | |||
| IR | 5doc IR-6 / 30006 | Aux_temp | Auxiliary temperature sensor. | INT16 | °F / °C | Read | |||
| IR | 6doc IR-7 / 30007 | Water_temp | Evaporating-chamber water temperature. | INT16 | °F / °C | Read | |||
| IR | 7doc IR-8 / 30008 | Steam_output_mass | Estimated steam output. | UINT16 | lbs/hr / kg/h | Read | |||
| IR | 8doc IR-9 / 30009 | Steam_output_percent | Estimated output as % of capacity. | UINT16 | % | Read | |||
| IR | 9doc IR-10 / 30010 | Water_until_ADS | Water left before next auto drain sequence; one count = 100 lbs or 100 kg. | UINT16 | × 100 | lbs / kg | Read | ||
| IR | 10doc IR-11 / 30011 | Water_until_service | Water left before next service; one count = 100 lbs or 100 kg. | UINT16 | × 100 | lbs / kg | Read | ||
| IR | 22doc IR-23 / 30023 | MT_sys_output_mass_hr | Multi-tank system steam demand. | UINT16 | lbs/hr / kg/h | Read | |||
| IR | 24doc IR-25 / 30025 | MT_sys_output_pcnt | Multi-tank system steam demand. | UINT16 | % | Read | |||
| IR | 25doc IR-26 / 30026 | Current_1 (XT) | XT operating current. | UINT16 | A | Read | |||
| IR | 26doc IR-27 / 30027 | Current_2 (XT) | XT operating current, right cylinder. | UINT16 | A | Read | |||
| IR | 27doc IR-28 / 30028 | In_Pressure (high-pressure systems) | Supply pressure. | UINT16 | psi / bar | Read | |||
| IR | 28doc IR-29 / 30029 | Out_Pressure (high-pressure systems) | Output pressure. | UINT16 | psi / bar | Read | |||
| HR | 0doc HR-1 / 40001 | Run_mode | Unit mode. Write 1-4; reads can also return 5 or 6. | UINT16 | Read/write | 1 = Auto; 2 = Local standby; 3 = System standby; 4 = Manual drain; 5 = Test outputs (read only); 6 = Test run (read only) | |||
| HR | 1doc HR-2 / 40002 | Space_RH_set_point | Space humidity set point (write). | UINT16 | % | Write | |||
| HR | 2doc HR-3 / 40003 | Space_dew_point_set_point | Space dew point set point (write). | INT16 | °F / °C | Write | |||
| HR | 3doc HR-4 / 40004 | Duct_high_limit_set_point | Duct high limit set point (write). | UINT16 | % | Write | |||
| HR | 4doc HR-5 / 40005 | Fieldbus_demand_mass | Steam demand over the fieldbus; above capacity runs at 100%. | UINT16 | lbs/hr / kg/h | Write | |||
| HR | 5doc HR-6 / 40006 | Fieldbus_demand_% | Steam demand over the fieldbus, % of capacity. | UINT16 | % | Write | |||
| HR | 6doc HR-7 / 40007 | PID_band | UINT16 | % | Read/write | ||||
| HR | 7doc HR-8 / 40008 | PID-Kp | Proportional gain. | UINT16 | Read/write | ||||
| HR | 8doc HR-9 / 40009 | PID-Ki | Integral gain. | UINT16 | Read/write | ||||
| HR | 9doc HR-10 / 40010 | PID-Kd | Derivative gain. | UINT16 | Read/write | ||||
| HR | 13doc HR-14 / 40014 | MT_runmode | Multi-tank run mode. | UINT16 | Read/write | 1 = System standby; 2 = System auto | |||
| HR | 14doc HR-15 / 40015 | MT_steam_req_mass_hr | Multi-tank fieldbus steam request. | UINT16 | lbs/hr / kg/h | Write | |||
| HR | 16doc HR-17 / 40017 | MT_steam_req_sys_pcnt | Multi-tank fieldbus request, % of system capacity. | UINT16 | % | Write | |||
| HR | 17doc HR-18 / 40018 | Pump_1_hours | HPS pump 1 hours since reset. | UINT16 | h | Read/write | |||
| HR | 18doc HR-19 / 40019 | Pump_2_hours | HPS pump 2 hours since reset. | UINT16 | h | Read/write |
Notes on this map
- The PDF sits on the CloudFront host that holds DriSteem public documents (historical-literature folder); the document is the DriSteem IOM.
- Note 1 of the table states 16-bit input and holding registers and single-bit discrete inputs and coils; its stated ranges (IR1-IR11, HR1-HR10, DI1-DI9, DV1-DV50) are narrower than the rows actually listed, and all listed rows are included.
- No scale is printed, so values are whole numbers in the units shown, except Water_until_ADS / Water_until_service, which the table gives in units of 100 lbs or 100 kg.
- Units follow the controller's I-P or SI setting. Temperatures are typed INT16 because their ranges go below zero; signedness is not stated.
- The set points HR-2 to HR-4 are marked Write in this version (they are RW in Vapor-logic 6).
- The description column prints 'Reserved' beside coils DV-1 / DV-2.
- Several numbers carry different meanings on GTS, XT, STS and high-pressure (HPS) systems; both meanings are given.
- Serial framing (parity, data and stop bits) is not stated in the manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)
What Modbus registers does the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) have?
This map lists 107 registers: 60 coils, 15 discrete inputs, 17 input registers, 15 holding registers. 72 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Points are printed as IR-1 / 30001, HR-1 / 40001, DI-1 / 10001 and coil DV-1 / 1. These are one-based Modicon numbers: subtract one for the wire address (30001 -> input register 0, coil 1 -> coil 0).
What are the minimum Modbus registers to integrate the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)?
Start with IR 0 Space_RH (Space RH); IR 8 Steam_output_percent (Steam output %); IR 4 Steam_demand_percent (Steam demand %); HR 0 Run_mode (Run mode); HR 1 Space_RH_set_point (Space RH set point); HR 5 Fieldbus_demand_% (Fieldbus demand %); CO 2 Active_manually_cleared_alarms_exist (Manually cleared alarms exist); CO 3 Clear_all_faults (Clear all faults).
How do I enable Modbus control of the DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)?
Setup menu > Communications > Modbus: Modbus enabled = Yes, Modbus address (default 99) and baud rate (default 9600).
Where is the official DriSteem Vapor-logic 5 humidifier controller (Modbus RTU) Modbus documentation?
The source is Vapor-logic Version 5 Installation and Operation Manual (VL5-IOM-0914 (Part No. 890000-721 Rev B)), revision 2014-09, published free by DriSteem at https://d2tsmyh31fn7w8.cloudfront.net/public-documents/docs/historical-literature/vl5-iom.pdf.
More DriSteem Modbus register maps
Other hvac equipment register maps
- Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat (shelter HVAC lead/lag controller)
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
Marvair CommStat 4 controllers with protocol version 3 or later and software revision 67 or later, read through the Marvair Modbus Interface Adapter.
Also known as: CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272 - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM
All hvac equipment Modbus register maps →
Source: Vapor-logic Version 5 Installation and Operation Manual · VL5-IOM-0914 (Part No. 890000-721 Rev B) · rev. 2014-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.