Easy Modbus
  1. Home
  2. Modbus register maps
  3. DriSteem
  4. Vapor-logic 6 humidifier controller (Modbus RTU)

Air handler humidifier (steam humidifier controller) · Modbus register map

DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Vapor-logic 6 is the DriSteem controller used on its steam humidifiers (electric, GTS gas, XT electrode, STS/LTS steam-to-steam), HPS/LMH high-pressure systems and WM wetted-media units. Modbus RTU is standard on terminal P7. The map gives 16-bit input registers for humidity, dew point, demand, output and temperatures, holding registers for run mode, set points, fieldbus demand and PID, discrete inputs for safety switches, and coils for every alarm and message flag.

This page lists 136 Modbus registers for the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) — 83 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DriSteem’s own free documentation (linked below) and checked against it.

Manufacturer
DriSteem
Model
Vapor-logic 6 humidifier controller (Modbus RTU)
Equipment type
Air handler humidifier (steam humidifier controller)
Registers
136 (83 writable)
Transport
Modbus RTU
Default unit ID
99
Default serial
9600 baud
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
Vapor-logic 6.X.X
Also known as
Vapor-logic, Vapor-logic version 6, VL6, DriSteem GTS, DriSteem XT, DriSteem STS, DriSteem LTS, Vaporstream
Source document
Vapor-logic Version 6 Installation, Operation, and Maintenance Manual · VL6-IOM-EN-REVH-0225 (Part No. 890000-741 Rev H) · rev. 2025-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)

Integration in brief

Enable Modbus in the Communications setup, wire RS-485 to P7, and poll input registers 0-10 for humidity, demand and output. To command the unit, set Control via Modbus and write RunMode (40001) and either a set point (40002) or fieldbus demand (40006).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0SpaceRHUINT16Space RHRead
IR 8SteamOutputPercentUINT16Steam output %Read
IR 4SteamDemandPercentUINT16Steam demand %Read
HR 0RunModeUINT16Run modeRead/write
HR 1SpaceRHSetPointUINT16Space RH set pointRead/write
HR 5FieldbusDemandPcntUINT16Fieldbus demand %Write
CO 2ActiveManualClearAlarmsExistBITManual-clear alarm existsRead
CO 3ClearAllActiveAlarmsBITClear all alarmsRead/write

Enable Modbus control & writes

Setup menu > Communications > Modbus: Modbus enabled = Yes, set address (default 99) and baud rate (default 9600). For demand over Modbus, Setup > Demand signal > Control via Modbus = Yes.

Byte order & addressing

Network setup

Watch out for

DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

136 of 136 shown
DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc DV-1 / 1ProgOutput1StatusNO-1Programmable dry contact 1 state (0 open, 1 closed).BITRead
CO1doc DV-2 / 2ProgOutput2StatusNO-2Programmable dry contact 2 state.BITRead
CO2doc DV-3 / 3ActiveManualClearAlarmsExistSet when an alarm needing manual clear exists.BITRead
CO3doc DV-4 / 4ClearAllActiveAlarmsWrite 1 to clear all active faults.BITRead/write
CO4doc DV-5 / 5TankTempSensorFailed / WaterTempSensorFailed (HPS)Alarm flag.BITRead/write
CO5doc DV-6 / 6TankOvertemp-UnitRebootRequiredAlarm flag.BITRead/write
CO6doc DV-7 / 7SignalAtRHInputOutOfRangeAlarm: RH, dew point or demand signal out of range.BITRead/write
CO7doc DV-8 / 8DuctRHSignalOutOfRangeAlarm flag.BITRead/write
CO8doc DV-9 / 9AuxTempSenseOutOfRangeAlarm flag.BITRead/write
CO9doc DV-10 / 10WaterProbeMiswiredAlarm flag.BITRead/write
CO10doc DV-11 / 11FaultyWaterProbe / VFDFault (HPS)Alarm flag.BITRead/write
CO11doc DV-12 / 12ExcessiveFillTimeAlarm flag.BITRead/write
CO12doc DV-13 / 13ExcessiveRefillTimeAlarm flag.BITRead/write
CO13doc DV-14 / 14TankNotDraining / CheckHumidifierFloats (LMH)Alarm flag.BITRead/write
CO14doc DV-15 / 15ExcessiveBoilTime-UnitRebootRequiredAlarm flag.BITRead/write
CO15doc DV-16 / 16NoSDUAirflowAlarm: no airflow at the dispersion unit.BITRead/write
CO16doc DV-17 / 17NoPowerVentAirflow (GTS) / XVHeaderFlooded (STS)Alarm flag.BITRead/write
CO17doc DV-18 / 18NoCombustionAirflow (GTS)Alarm flag.BITRead/write
CO18doc DV-19 / 19BlockedFlue (GTS)Alarm flag.BITRead/write
CO19doc DV-20 / 20Burner1Fault (GTS)Alarm flag.BITRead/write
CO20doc DV-21 / 21Burner2Fault (GTS)Alarm flag.BITRead/write
CO21doc DV-22 / 22Burner3Fault (GTS)Alarm flag.BITRead/write
CO22doc DV-23 / 23Burner4Fault (GTS)Alarm flag.BITRead/write
CO23doc DV-24 / 24IgnitionModule1Fault (GTS) / Stage1EfficiencyBelow50Percent (WM)Alarm flag.BITRead/write
CO24doc DV-25 / 25IgnitionModule2Fault (GTS) / Stage2EfficiencyBelow50Percent (WM)Alarm flag.BITRead/write
CO25doc DV-26 / 26IgnitionModule3Fault (GTS) / Stage3EfficiencyBelow50Percent (WM)Alarm flag.BITRead/write
CO26doc DV-27 / 27IgnitionModule4Fault (GTS)Alarm flag.BITRead/write
CO27doc DV-28 / 28Blower1Fault (GTS) / TempSensorStage1Fault (WM)Alarm flag.BITRead/write
CO28doc DV-29 / 29Blower2Fault (GTS) / TempSensorStage2Fault (WM)Alarm flag.BITRead/write
CO29doc DV-30 / 30Blower3Fault (GTS) / TempSensorStage3Fault (WM)Alarm flag.BITRead/write
CO30doc DV-31 / 31Blower4Fault (GTS) / TempSensorFault (WM)Alarm flag.BITRead/write
CO31doc DV-32 / 32GasValve1Fault (GTS)Alarm flag.BITRead/write
CO32doc DV-33 / 33GasValve2Fault (GTS)Alarm flag.BITRead/write
CO33doc DV-34 / 34GasValve3Fault (GTS)Alarm flag.BITRead/write
CO34doc DV-35 / 35GasValve4Fault (GTS)Alarm flag.BITRead/write
CO35doc DV-36 / 36LowWaterOrOvertemp (GTS) / OvertempCutoutUnitRebootRequired (Electric, LMH)Alarm flag.BITRead/write
CO36doc DV-37 / 37ExcessiveFoaming2 (XT) / LowInletPressure (HPS, LMH) / ReplaceIgnitorsNow (GTS)Alarm flag.BITRead/write
CO37doc DV-38 / 38ReplaceIgnitorsSoon (GTS) / ReplaceContactors (Electric, LMH) / ReplaceUVLamp (WM)Message flag.BITRead/write
CO38doc DV-39 / 39ServiceUnitMessage flag.BITRead/write
CO39doc DV-40 / 40DrainPendingMessage flag.BITRead/write
CO40doc DV-41 / 41NoAirflowMessage flag.BITRead/write
CO41doc DV-42 / 42InterlockOpenMessage flag.BITRead/write
CO42doc DV-43 / 43FreezeDrainMessage flag.BITRead/write
CO43doc DV-44 / 44EndOfSeasonDrainActiveMessage flag.BITRead/write
CO44doc DV-45 / 45TempCompOnMessage: temperature compensation on.BITRead/write
CO45doc DV-46 / 46CleanProbesMessage flag.BITRead/write
CO46doc DV-47 / 47DuctHLTripMessage: duct high limit tripped.BITRead/write
CO47doc DV-48 / 48DuctHLSpanMessage: within duct high limit span.BITRead/write
CO48doc DV-49 / 49InsufficientWaterFlowMessage flag.BITRead/write
CO49doc DV-50 / 50BoilingTempCalibratedMessage flag.BITRead/write
CO50doc DV-51 / 51CurrentSensorOutOfRange (XT)Alarm flag.BITRead/write
CO51doc DV-52 / 52CurrentSensorOutOfRange (XT) / ROSensorOutOfRange (HPS)Alarm flag.BITRead/write
CO52doc DV-53 / 53Overcurrent (XT) / HighInletPressure (HPS)Alarm flag.BITRead/write
CO53doc DV-54 / 54SupplyWaterFailure (XT) / LowInletWaterTemp (HPS)Alarm flag.BITRead/write
CO54doc DV-55 / 55ExcessiveFoaming (XT) / HighPumpPressure (HPS) / FoamingFault (GTS)Alarm flag.BITRead/write
CO55doc DV-56 / 56CheckCylinderEndOfLife (XT) / LowInletWaterTempMessage (HPS)Message flag.BITRead/write
CO56doc DV-57 / 57Overcurrent2 (XT) / HighInletWaterTemp (HPS)Alarm flag.BITRead/write
CO57doc DV-58 / 58SupplyWater2Failure (XT) / LowPumpPressure (HPS)Alarm flag.BITRead/write
CO58doc DV-59 / 59CheckCylinder2EndOfLife (XT)Message flag.BITRead/write
CO59doc DV-60 / 60MainEnableOpenMessage flag.BITRead/write
CO60doc DV-61 / 61LowInletPressure (LMH)Alarm flag.BITRead/write
CO61doc DV-62 / 62HighOutletPressure (LMH)Alarm flag.BITRead/write
CO62doc DV-63 / 63InletSensorOutOfRange (HPS) / StorageSensorOutOfRange (LMH) / FlueSensorOutOfRange (GTS)Alarm flag.BITRead/write
CO63doc DV-64 / 64ExcessiveTDSAlarm (LMH)Alarm flag.BITRead/write
CO64doc Dv-65 / 65ExcessiveTDSDuringFill (LMH)Message flag.BITRead/write
CO65doc DV-66 / 66PumpStationCannotRun (HPS)Alarm: HPS redundant system cannot run.BITRead/write
CO66doc DV-67 / 67XVClearingCondensate (XV)XV is trying to clear condensate from the header.BITRead
CO67doc DV-68 / 68XVCondensateClearingFailure (XV)Alarm: XV failed to clear header condensate.BITRead/write
CO68doc DV-69 / 69XV2PositionValveFailure (XV)Alarm: end switch did not close while valve powered.BITRead/write
CO69doc DV-70 / 70PumpSensorOutOfRange (HPS) / InletSensorOutOfRange (LMH) / DrainSensorOutOfRange (GTS)Alarm flag.BITRead/write
DI0doc DI-1 / 10001AirflowProvingSwitchBITRead0 = Open; 1 = Closed
DI1doc DI-2 / 10002DuctHLSwitchDuct high limit switch.BITRead0 = Open; 1 = Closed
DI2doc DI-3 / 10003SafetyInterlockBITRead0 = Open; 1 = Closed
DI3doc DI-4 / 10004CombustionAirDamper (GTS) / Stage1Active (HPS)GTS: 0 damper closed, 1 open. HPS: stage 1 active.BITRead
DI4doc DI-5 / 10005FluePressureSwitch (GTS) / Stage2Active (HPS) / InletPressureSwitch (LMH)GTS and LMH: 0 open, 1 closed. HPS: 0 closed, 1 open.BITRead
DI5doc DI-6 / 10006PowerVentSwitch (GTS) / Stage3Active (HPS) / XVHeaderEmptyOrExternalDemand (STS)GTS 0 off 1 on; HPS 0 closed 1 open; STS 0 not ready 1 ready.BITRead
DI6doc DI-7 / 10007LowWaterSensorOrOvertempLoop (GTS)BITRead0 = No water; 1 = Water
DI7doc DI-8 / 10008FillValveFill valve state.BITRead0 = Closed; 1 = Open
DI8doc DI-9 / 10009DrainValveDrain valve state.BITRead0 = Not draining; 1 = Draining
DI9doc DI-10 / 10010MTActiveFaultInSystemMulti-tank only.BITRead0 = No; 1 = Yes
DI10doc DI-11 / 10011MTActiveMessageInSystemMulti-tank only.BITRead0 = No; 1 = Yes
DI11doc DI-12 / 10012HighWaterSensor (XT)XT systems only.BITRead0 = No water; 1 = Water
DI12doc DI-13 / 10013HighWaterSensor2 (XT)Right cylinder, two-cylinder XT only.BITRead0 = No water; 1 = Water
DI13doc DI-14 / 10014HPASVFDDriveFault (HPS)HPS systems only.BITRead0 = No fault; 1 = Fault
DI14doc DI-15 / 10015XV 2 position shutoff valveXV shutoff valve power state.BITRead0 = Valve not powered; 1 = Valve powered
DI15doc DI-16 / 10016XV2PositionValveEndSwitch (XV)XV with Vapor-logic only.BITRead0 = Open; 1 = Closed
DI16doc DI-17 / 10017XVFloatSwitch (XV)XV with Vapor-logic only.BITRead0 = Empty, OK to run; 1 = Full
IR0doc IR-1 / 30001SpaceRHSpace relative humidity.UINT16%Read
IR1doc IR-2 / 30002SpaceDewPointSpace dew point; °F or °C per unit setting.INT16°F / °CRead
IR2doc IR-3 / 30003DuctRHDuct relative humidity.UINT16%Read
IR3doc IR-4 / 30004SteamDemandMassSteam demand, lbs/hr or kg/h per unit setting.UINT16lbs/hr / kg/hRead
IR4doc IR-5 / 30005SteamDemandPercentSteam demand as % of total capacity.UINT16%Read
IR5doc IR-6 / 30006AuxTempAuxiliary temperature sensor.INT16°F / °CRead
IR6doc IR-7 / 30007TankTemperature / WaterTemperature (HPS)Evaporating-chamber water temperature; inlet water temperature on HPS.INT16°F / °CRead
IR7doc IR-8 / 30008SteamOutputMassEstimated steam output, lbs/hr or kg/h.UINT16lbs/hr / kg/hRead
IR8doc IR-9 / 30009SteamOutputPercentEstimated steam output as % of capacity.UINT16%Read
IR9doc IR-10 / 30010WaterUntilADSWater left before next auto drain sequence; one count = 100 lbs or 100 kg.UINT16× 100lbs / kgRead
IR10doc IR-11 / 30011WaterUntilServiceWater left before next service cycle; one count = 100 lbs or 100 kg.UINT16× 100lbs / kgRead
IR22doc IR-23 / 30023MTSteamDemandMassMulti-tank system steam demand.UINT16lbs/hr / kg/hRead
IR24doc IR-25 / 30025MTSteamDemandPercentMulti-tank system steam demand.UINT16%Read
IR25doc IR-26 / 30026XTBottle1Current (XT)XT operating current, left cylinder.UINT16ARead
IR26doc IR-27 / 30027XTBottle2Current (XT)XT operating current, right cylinder.UINT16ARead
IR27doc IR-28 / 30028InPressure (HPS)Supply water pressure.UINT16psi / barRead
IR28doc IR-29 / 30029OutPressure (HPS)Output pressure.UINT16psi / barRead
IR29doc IR-30 / 30030CurrentTankCOC (WM)Current tank cycles of concentration.UINT16Read
IR30doc IR-31 / 30031SupplyWaterConductivity (WM)Supply water conductivity.UINT16µSRead
IR31doc IR-32 / 30032Stage1Temperature (WM)INT16°F / °CRead
IR32doc IR-33 / 30033Stage2Temperature (WM)INT16°F / °CRead
IR33doc IR-34 / 30034Stage3Temperature (WM) / FlueTemperature (GTS)WM stage 3 temperature; GTS flue box temperature.INT16°F / °CRead
IR34doc IR-35 / 30035SupplyAirTemperature (WM) / DrainTemperature (GTS)WM supply air; GTS drain block water temperature.INT16°F / °CRead
IR35doc IR-36 / 30036Stage1MediaEffectiveness (WM)UINT16%Read
IR36doc IR-37 / 30037Stage2MediaEffectiveness (WM)UINT16%Read
IR37doc IR-38 / 30038Stage3MediaEffectiveness (WM)UINT16%Read
IR38doc IR-39 / 30039OutputTemperature (WM)INT16°F / °CRead
IR39doc IR-40 / 30040WetbulbTemperature (WM)INT16°F / °CRead
IR40doc IR-41 / 30041StoragePressure (LMH)UINT16psi / barRead
IR41doc IR-42 / 30042PumpRuntimeHours (HPS, LMH)UINT16hRead
IR42doc IR-43 / 30043TDS (LMH)Total dissolved solids reading.UINT16Read
IR43doc IR-44 / 30044HPASActivePumpStationNumber (HPS)Active pump station, 0-4.UINT16Read
HR0doc HR-1 / 40001RunModeUnit mode. Write 1-4; reads can also return 5 or 6.UINT16Read/write1 = Auto; 2 = Local standby; 3 = System standby; 4 = Manual drain; 5 = Test outputs (read only); 6 = Test run (read only)
HR1doc HR-2 / 40002SpaceRHSetPointSpace humidity set point.UINT16%Read/write
HR2doc HR-3 / 40003SpaceDewPointSetPointSpace dew point set point.INT16°F / °CRead/write
HR3doc HR-4 / 40004DuctHighLimitSetPointDuct high limit set point.UINT16%Read/write
HR4doc HR-5 / 40005FieldbusDemandMassSteam demand sent over the fieldbus; above capacity runs at 100%.UINT16lbs/hr / kg/hWrite
HR5doc HR-6 / 40006FieldbusDemandPcntSteam demand over the fieldbus as % of capacity.UINT16%Write
HR6doc HR-7 / 40007PIDBandPID band.UINT16%Read/write
HR7doc HR-8 / 40008PIDKpProportional gain.UINT16Read/write
HR8doc HR-9 / 40009PIDKiIntegral gain.UINT16Read/write
HR9doc HR-10 / 40010PIDKdDerivative gain.UINT16Read/write
HR13doc HR-14 / 40014MTRunModeMulti-tank system run mode.UINT16Read/write1 = System standby; 2 = System auto
HR14doc HR-15 / 40015MTSteamOutputReqMassMulti-tank fieldbus steam request.UINT16lbs/hr / kg/hRead/write
HR16doc HR-17 / 40017MTSteamOutputReqPcntMulti-tank fieldbus steam request, % of system capacity.UINT16%Read/write
HR17doc HR-18 / 40018Pump1RuntimeHours (HPS, LMH)Pump 1 hours since reset.UINT16hRead/write
HR18doc HR-19 / 40019Pump2RuntimeHours (HPS)Pump 2 hours since reset.UINT16hRead/write
HR19doc HR-20 / 40020TargetCOC (WM)Desired cycles of concentration.UINT16Read/write
HR20doc HR-21 / 40021HPASPumpSelected (HPS)Selected pump, HPS systems.UINT16Read/write0 = Pump 1; 1 = Pump 2

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)

What Modbus registers does the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) have?

This map lists 136 registers: 70 coils, 17 discrete inputs, 32 input registers, 17 holding registers. 83 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints each point twice, e.g. IR-1 / 30001, HR-1 / 40001, DI-1 / 10001 and coil DV-1 / 1. These are one-based Modicon numbers: input register 30001 is wire address 0 and coil 1 is wire address 0.

What are the minimum Modbus registers to integrate the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)?

Start with IR 0 SpaceRH (Space RH); IR 8 SteamOutputPercent (Steam output %); IR 4 SteamDemandPercent (Steam demand %); HR 0 RunMode (Run mode); HR 1 SpaceRHSetPoint (Space RH set point); HR 5 FieldbusDemandPcnt (Fieldbus demand %); CO 2 ActiveManualClearAlarmsExist (Manual-clear alarm exists); CO 3 ClearAllActiveAlarms (Clear all alarms).

How do I enable Modbus control of the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)?

Setup menu > Communications > Modbus: Modbus enabled = Yes, set address (default 99) and baud rate (default 9600). For demand over Modbus, Setup > Demand signal > Control via Modbus = Yes.

Where is the official DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus documentation?

The source is Vapor-logic Version 6 Installation, Operation, and Maintenance Manual (VL6-IOM-EN-REVH-0225 (Part No. 890000-741 Rev H)), revision 2025-02, published free by DriSteem at https://d2tsmyh31fn7w8.cloudfront.net/public-documents/docs/iom/vapor-logic/VL6-IOM-EN.pdf.

More DriSteem Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Vapor-logic Version 6 Installation, Operation, and Maintenance Manual · VL6-IOM-EN-REVH-0225 (Part No. 890000-741 Rev H) · rev. 2025-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.