Air handler humidifier (steam humidifier controller) · Modbus register map
DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus register map
Updated 19 November 2026
Vapor-logic 6 is the DriSteem controller used on its steam humidifiers (electric, GTS gas, XT electrode, STS/LTS steam-to-steam), HPS/LMH high-pressure systems and WM wetted-media units. Modbus RTU is standard on terminal P7. The map gives 16-bit input registers for humidity, dew point, demand, output and temperatures, holding registers for run mode, set points, fieldbus demand and PID, discrete inputs for safety switches, and coils for every alarm and message flag.
This page lists 136 Modbus registers for the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) — 83 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from DriSteem’s own free documentation (linked below) and checked against it.
- Manufacturer
- DriSteem
- Model
- Vapor-logic 6 humidifier controller (Modbus RTU)
- Equipment type
- Air handler humidifier (steam humidifier controller)
- Registers
- 136 (83 writable)
- Transport
- Modbus RTU
- Default unit ID
- 99
- Default serial
- 9600 baud
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- Vapor-logic 6.X.X
- Also known as
- Vapor-logic, Vapor-logic version 6, VL6, DriSteem GTS, DriSteem XT, DriSteem STS, DriSteem LTS, Vaporstream
Integration notes: DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)
Enable Modbus in the Communications setup, wire RS-485 to P7, and poll input registers 0-10 for humidity, demand and output. To command the unit, set Control via Modbus and write RunMode (40001) and either a set point (40002) or fieldbus demand (40006).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | SpaceRH | UINT16 | Space RH | Read |
| IR 8 | SteamOutputPercent | UINT16 | Steam output % | Read |
| IR 4 | SteamDemandPercent | UINT16 | Steam demand % | Read |
| HR 0 | RunMode | UINT16 | Run mode | Read/write |
| HR 1 | SpaceRHSetPoint | UINT16 | Space RH set point | Read/write |
| HR 5 | FieldbusDemandPcnt | UINT16 | Fieldbus demand % | Write |
| CO 2 | ActiveManualClearAlarmsExist | BIT | Manual-clear alarm exists | Read |
| CO 3 | ClearAllActiveAlarms | BIT | Clear all alarms | Read/write |
Enable Modbus control & writes
Setup menu > Communications > Modbus: Modbus enabled = Yes, set address (default 99) and baud rate (default 9600). For demand over Modbus, Setup > Demand signal > Control via Modbus = Yes.
Byte order & addressing
- Printed numbers are Modicon-style (30001, 40001, 10001, coil 1): subtract one for the wire address.
- Units switch between I-P and SI with the unit setting; there are no decimal places.
Network setup
- Connect RS-485 to terminal P7 on the Vapor-logic board (+ to +, - to -).
- Set the Modbus address and baud rate in Setup > Communications, then cycle power.
Watch out for
- Several point numbers mean different things on GTS, XT, HPS, LMH and WM units; check which family you have.
- Numbers are not continuous (no IR 12-22 or 24, no HR 11-13 or 16); DV-65, DV-67, DI-8, DI-9 and DI-15 are on the last table page.
DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc DV-1 / 1 | ProgOutput1StatusNO-1 | Programmable dry contact 1 state (0 open, 1 closed). | BIT | Read | ||||
| CO | 1doc DV-2 / 2 | ProgOutput2StatusNO-2 | Programmable dry contact 2 state. | BIT | Read | ||||
| CO | 2doc DV-3 / 3 | ActiveManualClearAlarmsExist | Set when an alarm needing manual clear exists. | BIT | Read | ||||
| CO | 3doc DV-4 / 4 | ClearAllActiveAlarms | Write 1 to clear all active faults. | BIT | Read/write | ||||
| CO | 4doc DV-5 / 5 | TankTempSensorFailed / WaterTempSensorFailed (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 5doc DV-6 / 6 | TankOvertemp-UnitRebootRequired | Alarm flag. | BIT | Read/write | ||||
| CO | 6doc DV-7 / 7 | SignalAtRHInputOutOfRange | Alarm: RH, dew point or demand signal out of range. | BIT | Read/write | ||||
| CO | 7doc DV-8 / 8 | DuctRHSignalOutOfRange | Alarm flag. | BIT | Read/write | ||||
| CO | 8doc DV-9 / 9 | AuxTempSenseOutOfRange | Alarm flag. | BIT | Read/write | ||||
| CO | 9doc DV-10 / 10 | WaterProbeMiswired | Alarm flag. | BIT | Read/write | ||||
| CO | 10doc DV-11 / 11 | FaultyWaterProbe / VFDFault (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 11doc DV-12 / 12 | ExcessiveFillTime | Alarm flag. | BIT | Read/write | ||||
| CO | 12doc DV-13 / 13 | ExcessiveRefillTime | Alarm flag. | BIT | Read/write | ||||
| CO | 13doc DV-14 / 14 | TankNotDraining / CheckHumidifierFloats (LMH) | Alarm flag. | BIT | Read/write | ||||
| CO | 14doc DV-15 / 15 | ExcessiveBoilTime-UnitRebootRequired | Alarm flag. | BIT | Read/write | ||||
| CO | 15doc DV-16 / 16 | NoSDUAirflow | Alarm: no airflow at the dispersion unit. | BIT | Read/write | ||||
| CO | 16doc DV-17 / 17 | NoPowerVentAirflow (GTS) / XVHeaderFlooded (STS) | Alarm flag. | BIT | Read/write | ||||
| CO | 17doc DV-18 / 18 | NoCombustionAirflow (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 18doc DV-19 / 19 | BlockedFlue (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 19doc DV-20 / 20 | Burner1Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 20doc DV-21 / 21 | Burner2Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 21doc DV-22 / 22 | Burner3Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 22doc DV-23 / 23 | Burner4Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 23doc DV-24 / 24 | IgnitionModule1Fault (GTS) / Stage1EfficiencyBelow50Percent (WM) | Alarm flag. | BIT | Read/write | ||||
| CO | 24doc DV-25 / 25 | IgnitionModule2Fault (GTS) / Stage2EfficiencyBelow50Percent (WM) | Alarm flag. | BIT | Read/write | ||||
| CO | 25doc DV-26 / 26 | IgnitionModule3Fault (GTS) / Stage3EfficiencyBelow50Percent (WM) | Alarm flag. | BIT | Read/write | ||||
| CO | 26doc DV-27 / 27 | IgnitionModule4Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 27doc DV-28 / 28 | Blower1Fault (GTS) / TempSensorStage1Fault (WM) | Alarm flag. | BIT | Read/write | ||||
| CO | 28doc DV-29 / 29 | Blower2Fault (GTS) / TempSensorStage2Fault (WM) | Alarm flag. | BIT | Read/write | ||||
| CO | 29doc DV-30 / 30 | Blower3Fault (GTS) / TempSensorStage3Fault (WM) | Alarm flag. | BIT | Read/write | ||||
| CO | 30doc DV-31 / 31 | Blower4Fault (GTS) / TempSensorFault (WM) | Alarm flag. | BIT | Read/write | ||||
| CO | 31doc DV-32 / 32 | GasValve1Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 32doc DV-33 / 33 | GasValve2Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 33doc DV-34 / 34 | GasValve3Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 34doc DV-35 / 35 | GasValve4Fault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 35doc DV-36 / 36 | LowWaterOrOvertemp (GTS) / OvertempCutoutUnitRebootRequired (Electric, LMH) | Alarm flag. | BIT | Read/write | ||||
| CO | 36doc DV-37 / 37 | ExcessiveFoaming2 (XT) / LowInletPressure (HPS, LMH) / ReplaceIgnitorsNow (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 37doc DV-38 / 38 | ReplaceIgnitorsSoon (GTS) / ReplaceContactors (Electric, LMH) / ReplaceUVLamp (WM) | Message flag. | BIT | Read/write | ||||
| CO | 38doc DV-39 / 39 | ServiceUnit | Message flag. | BIT | Read/write | ||||
| CO | 39doc DV-40 / 40 | DrainPending | Message flag. | BIT | Read/write | ||||
| CO | 40doc DV-41 / 41 | NoAirflow | Message flag. | BIT | Read/write | ||||
| CO | 41doc DV-42 / 42 | InterlockOpen | Message flag. | BIT | Read/write | ||||
| CO | 42doc DV-43 / 43 | FreezeDrain | Message flag. | BIT | Read/write | ||||
| CO | 43doc DV-44 / 44 | EndOfSeasonDrainActive | Message flag. | BIT | Read/write | ||||
| CO | 44doc DV-45 / 45 | TempCompOn | Message: temperature compensation on. | BIT | Read/write | ||||
| CO | 45doc DV-46 / 46 | CleanProbes | Message flag. | BIT | Read/write | ||||
| CO | 46doc DV-47 / 47 | DuctHLTrip | Message: duct high limit tripped. | BIT | Read/write | ||||
| CO | 47doc DV-48 / 48 | DuctHLSpan | Message: within duct high limit span. | BIT | Read/write | ||||
| CO | 48doc DV-49 / 49 | InsufficientWaterFlow | Message flag. | BIT | Read/write | ||||
| CO | 49doc DV-50 / 50 | BoilingTempCalibrated | Message flag. | BIT | Read/write | ||||
| CO | 50doc DV-51 / 51 | CurrentSensorOutOfRange (XT) | Alarm flag. | BIT | Read/write | ||||
| CO | 51doc DV-52 / 52 | CurrentSensorOutOfRange (XT) / ROSensorOutOfRange (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 52doc DV-53 / 53 | Overcurrent (XT) / HighInletPressure (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 53doc DV-54 / 54 | SupplyWaterFailure (XT) / LowInletWaterTemp (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 54doc DV-55 / 55 | ExcessiveFoaming (XT) / HighPumpPressure (HPS) / FoamingFault (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 55doc DV-56 / 56 | CheckCylinderEndOfLife (XT) / LowInletWaterTempMessage (HPS) | Message flag. | BIT | Read/write | ||||
| CO | 56doc DV-57 / 57 | Overcurrent2 (XT) / HighInletWaterTemp (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 57doc DV-58 / 58 | SupplyWater2Failure (XT) / LowPumpPressure (HPS) | Alarm flag. | BIT | Read/write | ||||
| CO | 58doc DV-59 / 59 | CheckCylinder2EndOfLife (XT) | Message flag. | BIT | Read/write | ||||
| CO | 59doc DV-60 / 60 | MainEnableOpen | Message flag. | BIT | Read/write | ||||
| CO | 60doc DV-61 / 61 | LowInletPressure (LMH) | Alarm flag. | BIT | Read/write | ||||
| CO | 61doc DV-62 / 62 | HighOutletPressure (LMH) | Alarm flag. | BIT | Read/write | ||||
| CO | 62doc DV-63 / 63 | InletSensorOutOfRange (HPS) / StorageSensorOutOfRange (LMH) / FlueSensorOutOfRange (GTS) | Alarm flag. | BIT | Read/write | ||||
| CO | 63doc DV-64 / 64 | ExcessiveTDSAlarm (LMH) | Alarm flag. | BIT | Read/write | ||||
| CO | 64doc Dv-65 / 65 | ExcessiveTDSDuringFill (LMH) | Message flag. | BIT | Read/write | ||||
| CO | 65doc DV-66 / 66 | PumpStationCannotRun (HPS) | Alarm: HPS redundant system cannot run. | BIT | Read/write | ||||
| CO | 66doc DV-67 / 67 | XVClearingCondensate (XV) | XV is trying to clear condensate from the header. | BIT | Read | ||||
| CO | 67doc DV-68 / 68 | XVCondensateClearingFailure (XV) | Alarm: XV failed to clear header condensate. | BIT | Read/write | ||||
| CO | 68doc DV-69 / 69 | XV2PositionValveFailure (XV) | Alarm: end switch did not close while valve powered. | BIT | Read/write | ||||
| CO | 69doc DV-70 / 70 | PumpSensorOutOfRange (HPS) / InletSensorOutOfRange (LMH) / DrainSensorOutOfRange (GTS) | Alarm flag. | BIT | Read/write | ||||
| DI | 0doc DI-1 / 10001 | AirflowProvingSwitch | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 1doc DI-2 / 10002 | DuctHLSwitch | Duct high limit switch. | BIT | Read | 0 = Open; 1 = Closed | |||
| DI | 2doc DI-3 / 10003 | SafetyInterlock | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 3doc DI-4 / 10004 | CombustionAirDamper (GTS) / Stage1Active (HPS) | GTS: 0 damper closed, 1 open. HPS: stage 1 active. | BIT | Read | ||||
| DI | 4doc DI-5 / 10005 | FluePressureSwitch (GTS) / Stage2Active (HPS) / InletPressureSwitch (LMH) | GTS and LMH: 0 open, 1 closed. HPS: 0 closed, 1 open. | BIT | Read | ||||
| DI | 5doc DI-6 / 10006 | PowerVentSwitch (GTS) / Stage3Active (HPS) / XVHeaderEmptyOrExternalDemand (STS) | GTS 0 off 1 on; HPS 0 closed 1 open; STS 0 not ready 1 ready. | BIT | Read | ||||
| DI | 6doc DI-7 / 10007 | LowWaterSensorOrOvertempLoop (GTS) | BIT | Read | 0 = No water; 1 = Water | ||||
| DI | 7doc DI-8 / 10008 | FillValve | Fill valve state. | BIT | Read | 0 = Closed; 1 = Open | |||
| DI | 8doc DI-9 / 10009 | DrainValve | Drain valve state. | BIT | Read | 0 = Not draining; 1 = Draining | |||
| DI | 9doc DI-10 / 10010 | MTActiveFaultInSystem | Multi-tank only. | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 10doc DI-11 / 10011 | MTActiveMessageInSystem | Multi-tank only. | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 11doc DI-12 / 10012 | HighWaterSensor (XT) | XT systems only. | BIT | Read | 0 = No water; 1 = Water | |||
| DI | 12doc DI-13 / 10013 | HighWaterSensor2 (XT) | Right cylinder, two-cylinder XT only. | BIT | Read | 0 = No water; 1 = Water | |||
| DI | 13doc DI-14 / 10014 | HPASVFDDriveFault (HPS) | HPS systems only. | BIT | Read | 0 = No fault; 1 = Fault | |||
| DI | 14doc DI-15 / 10015 | XV 2 position shutoff valve | XV shutoff valve power state. | BIT | Read | 0 = Valve not powered; 1 = Valve powered | |||
| DI | 15doc DI-16 / 10016 | XV2PositionValveEndSwitch (XV) | XV with Vapor-logic only. | BIT | Read | 0 = Open; 1 = Closed | |||
| DI | 16doc DI-17 / 10017 | XVFloatSwitch (XV) | XV with Vapor-logic only. | BIT | Read | 0 = Empty, OK to run; 1 = Full | |||
| IR | 0doc IR-1 / 30001 | SpaceRH | Space relative humidity. | UINT16 | % | Read | |||
| IR | 1doc IR-2 / 30002 | SpaceDewPoint | Space dew point; °F or °C per unit setting. | INT16 | °F / °C | Read | |||
| IR | 2doc IR-3 / 30003 | DuctRH | Duct relative humidity. | UINT16 | % | Read | |||
| IR | 3doc IR-4 / 30004 | SteamDemandMass | Steam demand, lbs/hr or kg/h per unit setting. | UINT16 | lbs/hr / kg/h | Read | |||
| IR | 4doc IR-5 / 30005 | SteamDemandPercent | Steam demand as % of total capacity. | UINT16 | % | Read | |||
| IR | 5doc IR-6 / 30006 | AuxTemp | Auxiliary temperature sensor. | INT16 | °F / °C | Read | |||
| IR | 6doc IR-7 / 30007 | TankTemperature / WaterTemperature (HPS) | Evaporating-chamber water temperature; inlet water temperature on HPS. | INT16 | °F / °C | Read | |||
| IR | 7doc IR-8 / 30008 | SteamOutputMass | Estimated steam output, lbs/hr or kg/h. | UINT16 | lbs/hr / kg/h | Read | |||
| IR | 8doc IR-9 / 30009 | SteamOutputPercent | Estimated steam output as % of capacity. | UINT16 | % | Read | |||
| IR | 9doc IR-10 / 30010 | WaterUntilADS | Water left before next auto drain sequence; one count = 100 lbs or 100 kg. | UINT16 | × 100 | lbs / kg | Read | ||
| IR | 10doc IR-11 / 30011 | WaterUntilService | Water left before next service cycle; one count = 100 lbs or 100 kg. | UINT16 | × 100 | lbs / kg | Read | ||
| IR | 22doc IR-23 / 30023 | MTSteamDemandMass | Multi-tank system steam demand. | UINT16 | lbs/hr / kg/h | Read | |||
| IR | 24doc IR-25 / 30025 | MTSteamDemandPercent | Multi-tank system steam demand. | UINT16 | % | Read | |||
| IR | 25doc IR-26 / 30026 | XTBottle1Current (XT) | XT operating current, left cylinder. | UINT16 | A | Read | |||
| IR | 26doc IR-27 / 30027 | XTBottle2Current (XT) | XT operating current, right cylinder. | UINT16 | A | Read | |||
| IR | 27doc IR-28 / 30028 | InPressure (HPS) | Supply water pressure. | UINT16 | psi / bar | Read | |||
| IR | 28doc IR-29 / 30029 | OutPressure (HPS) | Output pressure. | UINT16 | psi / bar | Read | |||
| IR | 29doc IR-30 / 30030 | CurrentTankCOC (WM) | Current tank cycles of concentration. | UINT16 | Read | ||||
| IR | 30doc IR-31 / 30031 | SupplyWaterConductivity (WM) | Supply water conductivity. | UINT16 | µS | Read | |||
| IR | 31doc IR-32 / 30032 | Stage1Temperature (WM) | INT16 | °F / °C | Read | ||||
| IR | 32doc IR-33 / 30033 | Stage2Temperature (WM) | INT16 | °F / °C | Read | ||||
| IR | 33doc IR-34 / 30034 | Stage3Temperature (WM) / FlueTemperature (GTS) | WM stage 3 temperature; GTS flue box temperature. | INT16 | °F / °C | Read | |||
| IR | 34doc IR-35 / 30035 | SupplyAirTemperature (WM) / DrainTemperature (GTS) | WM supply air; GTS drain block water temperature. | INT16 | °F / °C | Read | |||
| IR | 35doc IR-36 / 30036 | Stage1MediaEffectiveness (WM) | UINT16 | % | Read | ||||
| IR | 36doc IR-37 / 30037 | Stage2MediaEffectiveness (WM) | UINT16 | % | Read | ||||
| IR | 37doc IR-38 / 30038 | Stage3MediaEffectiveness (WM) | UINT16 | % | Read | ||||
| IR | 38doc IR-39 / 30039 | OutputTemperature (WM) | INT16 | °F / °C | Read | ||||
| IR | 39doc IR-40 / 30040 | WetbulbTemperature (WM) | INT16 | °F / °C | Read | ||||
| IR | 40doc IR-41 / 30041 | StoragePressure (LMH) | UINT16 | psi / bar | Read | ||||
| IR | 41doc IR-42 / 30042 | PumpRuntimeHours (HPS, LMH) | UINT16 | h | Read | ||||
| IR | 42doc IR-43 / 30043 | TDS (LMH) | Total dissolved solids reading. | UINT16 | Read | ||||
| IR | 43doc IR-44 / 30044 | HPASActivePumpStationNumber (HPS) | Active pump station, 0-4. | UINT16 | Read | ||||
| HR | 0doc HR-1 / 40001 | RunMode | Unit mode. Write 1-4; reads can also return 5 or 6. | UINT16 | Read/write | 1 = Auto; 2 = Local standby; 3 = System standby; 4 = Manual drain; 5 = Test outputs (read only); 6 = Test run (read only) | |||
| HR | 1doc HR-2 / 40002 | SpaceRHSetPoint | Space humidity set point. | UINT16 | % | Read/write | |||
| HR | 2doc HR-3 / 40003 | SpaceDewPointSetPoint | Space dew point set point. | INT16 | °F / °C | Read/write | |||
| HR | 3doc HR-4 / 40004 | DuctHighLimitSetPoint | Duct high limit set point. | UINT16 | % | Read/write | |||
| HR | 4doc HR-5 / 40005 | FieldbusDemandMass | Steam demand sent over the fieldbus; above capacity runs at 100%. | UINT16 | lbs/hr / kg/h | Write | |||
| HR | 5doc HR-6 / 40006 | FieldbusDemandPcnt | Steam demand over the fieldbus as % of capacity. | UINT16 | % | Write | |||
| HR | 6doc HR-7 / 40007 | PIDBand | PID band. | UINT16 | % | Read/write | |||
| HR | 7doc HR-8 / 40008 | PIDKp | Proportional gain. | UINT16 | Read/write | ||||
| HR | 8doc HR-9 / 40009 | PIDKi | Integral gain. | UINT16 | Read/write | ||||
| HR | 9doc HR-10 / 40010 | PIDKd | Derivative gain. | UINT16 | Read/write | ||||
| HR | 13doc HR-14 / 40014 | MTRunMode | Multi-tank system run mode. | UINT16 | Read/write | 1 = System standby; 2 = System auto | |||
| HR | 14doc HR-15 / 40015 | MTSteamOutputReqMass | Multi-tank fieldbus steam request. | UINT16 | lbs/hr / kg/h | Read/write | |||
| HR | 16doc HR-17 / 40017 | MTSteamOutputReqPcnt | Multi-tank fieldbus steam request, % of system capacity. | UINT16 | % | Read/write | |||
| HR | 17doc HR-18 / 40018 | Pump1RuntimeHours (HPS, LMH) | Pump 1 hours since reset. | UINT16 | h | Read/write | |||
| HR | 18doc HR-19 / 40019 | Pump2RuntimeHours (HPS) | Pump 2 hours since reset. | UINT16 | h | Read/write | |||
| HR | 19doc HR-20 / 40020 | TargetCOC (WM) | Desired cycles of concentration. | UINT16 | Read/write | ||||
| HR | 20doc HR-21 / 40021 | HPASPumpSelected (HPS) | Selected pump, HPS systems. | UINT16 | Read/write | 0 = Pump 1; 1 = Pump 2 |
Notes on this map
- The PDF sits on the CloudFront host that holds DriSteem public documents (path public-documents/docs/iom/vapor-logic); the document itself is the DriSteem IOM (Research Products Corporation copyright).
- Note 1 of the table says all input and holding registers are 16-bit and all discrete inputs and coils single bits; no scale factor is printed, so values are whole numbers in the units shown, except WaterUntilADS / WaterUntilService where the table gives 100 lbs (or kg) per Modbus count.
- Units follow the controller's I-P or SI setting (°F/°C, lbs/hr / kg/h, psi/bar). Temperatures are typed INT16 because the ranges go below zero; the manual does not state signedness.
- Mass values (steam demand/output, up to 100,000) are listed as single 16-bit registers in the source; readings above 65,535 cannot be represented.
- WaterUntilADS and WaterUntilService are input registers but the table marks them RW; input registers cannot be written over Modbus, so they are listed read-only here.
- RunMode (40001) and MTRunMode (40014) have separate read and write meanings; reads of RunMode can also return 5 (Test outputs) and 6 (Test run).
- Many points apply only to one product family, marked in brackets: GTS (gas), XT (electrode), HPS/LMH (high-pressure), WM (wetted media), XV/STS (steam-to-steam). Shared numbers carry different meanings per family.
- Alarm and message coils are marked RW in the source; alarm meanings are in the manual's Alarms menu tables (pp. 49-50) and messages in the Diagnostics menu table (p. 46).
- Serial framing (parity, data and stop bits) is not stated in the manual.
- Note 1 of the table gives DI1-DI7 and DV1-DV69 as the ranges, but the table itself also lists DI-8 to DI-17 and DV-70; those rows are included as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)
What Modbus registers does the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) have?
This map lists 136 registers: 70 coils, 17 discrete inputs, 32 input registers, 17 holding registers. 83 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints each point twice, e.g. IR-1 / 30001, HR-1 / 40001, DI-1 / 10001 and coil DV-1 / 1. These are one-based Modicon numbers: input register 30001 is wire address 0 and coil 1 is wire address 0.
What are the minimum Modbus registers to integrate the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)?
Start with IR 0 SpaceRH (Space RH); IR 8 SteamOutputPercent (Steam output %); IR 4 SteamDemandPercent (Steam demand %); HR 0 RunMode (Run mode); HR 1 SpaceRHSetPoint (Space RH set point); HR 5 FieldbusDemandPcnt (Fieldbus demand %); CO 2 ActiveManualClearAlarmsExist (Manual-clear alarm exists); CO 3 ClearAllActiveAlarms (Clear all alarms).
How do I enable Modbus control of the DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)?
Setup menu > Communications > Modbus: Modbus enabled = Yes, set address (default 99) and baud rate (default 9600). For demand over Modbus, Setup > Demand signal > Control via Modbus = Yes.
Where is the official DriSteem Vapor-logic 6 humidifier controller (Modbus RTU) Modbus documentation?
The source is Vapor-logic Version 6 Installation, Operation, and Maintenance Manual (VL6-IOM-EN-REVH-0225 (Part No. 890000-741 Rev H)), revision 2025-02, published free by DriSteem at https://d2tsmyh31fn7w8.cloudfront.net/public-documents/docs/iom/vapor-logic/VL6-IOM-EN.pdf.
More DriSteem Modbus register maps
Other hvac equipment register maps
- Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523 - Rooftop unit / packaged wall-mount air conditioner
Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU)
Marvair MAH1018A-1060A, MGH1072A, MAH2024A-2060A and MGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: MAH1018A, MAH1024A, MAH1030A, MAH1036A, MAH1042A, MAH1048A, MAH1060A, MGH1072A, MAH2024A, MAH2030A, MAH2036A, MAH2042A, MAH2048A, MAH2060A, MGH2072A, Marvair MAH, Marvair MGH - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Thermostat / temperature and process PID controller
Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
Omega CN2200 and CN2400 series controllers with the Modbus comms option (CN2400 software 1.03-3.05, CN2200 1.00-2.10 per the handbook).
Also known as: CN2204, CN2208, CN2408 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML
All hvac equipment Modbus register maps →
Source: Vapor-logic Version 6 Installation, Operation, and Maintenance Manual · VL6-IOM-EN-REVH-0225 (Part No. 890000-741 Rev H) · rev. 2025-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.