- CONDUCTOR W3 room controller (air and water, Modbus RTU)
Thermostat / room controller (chilled beam with supply and extract air dampers) · Modbus register map
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus register map
Updated 19 November 2026
CONDUCTOR W3 is the Swegon room controller that handles both the water circuits (cooling/heating) and the supply and extract air dampers of a room, for demand-controlled waterborne climate systems. Over Modbus RTU it exposes alarms, sensor temperatures, outputs and damper positions, plus airflow levels per state, the application-state request and PI tuning. The temperature setpoints are left out because the manual does not give their scaling.
This page lists 122 Modbus registers for the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) — 46 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Swegon
- Model
- CONDUCTOR W3 room controller (air and water, Modbus RTU)
- Registers
- 122 (46 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- 1.38 and later
- Also known as
- CONDUCTOR RE W3, Conductor W3
Integration notes: Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Read 3x0028-3x0030 (temperatures x10), 3x0022 (state) and 3x0055/3x0056 (damper positions); write 4x0002 for state and 4x0036-4x0043 for airflow levels. Temperature setpoints are not in this map because the manual gives no scaling for them.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 27 | Temp sensor regulator | UINT16 | Regulator temperature sensor x10 | Read |
| IR 28 | Temp sensor RU1 | UINT16 | Room unit 1 temperature x10 | Read |
| IR 21 | Application state | UINT16 | Application state | Read |
| HR 1 | Application transition | UINT16 | Application transition | Read/write |
| IR 54 | SA Damper pos. | UINT16 | Supply air damper position | Read |
| IR 55 | EA Damper pos | UINT16 | Extract air damper position | Read |
| DI 5 | Active alarms | BIT | Active alarms | Read |
| HR 35 | Normal flow SA | UINT16 | Normal supply airflow level | Read/write |
Enable Modbus control & writes
Set the BMS address, baud, parity and stop bits in system parameters P_101-P_104 from the room unit (service level).
Byte order & addressing
- Reference numbers use the 0x/1x/3x/4x prefix; subtract 1 inside each table.
- Application transition values 2, 3, 5 and 9 can only be read, not written.
Network setup
- RS-485, Modbus RTU; the controller is a slave on the BMS bus.
- Changes to the BMS parameters are made from the CONDUCTOR room unit.
Watch out for
- Many values only matter in a given application state (manual, economy, boost, night cool); check 3x0022 before writing.
- Register numbering differs between the W1, W3 and W4 tables; use the table for the exact model and software.
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1doc 0x0002 | SA Emergency action | BIT | Read/write | |||||
| CO | 2doc 0x0003 | EA Emergency action | BIT | Read/write | |||||
| CO | 4doc 0x0005 | Economy mode | BIT | Read/write | 0 = Unavailable; 1 = Available | ||||
| CO | 5doc 0x0006 | Timer Function | BIT | Read/write | 0 = Unavailable; 1 = Available | ||||
| CO | 7doc 0x0008 | Restart device | Write 1 to force a software reboot. | BIT | Read/write | ||||
| DI | 0doc 1x0001 | Condensation | BIT | Read | |||||
| DI | 1doc 1x0002 | Relay state | BIT | Read | |||||
| DI | 2doc 1x0003 | Occupancy switch | BIT | Read | |||||
| DI | 3doc 1x0004 | Window switch | BIT | Read | |||||
| DI | 4doc 1x0005 | Motion | BIT | Read | |||||
| DI | 5doc 1x0006 | Active alarms | BIT | Read | 0 = No active alarms; 1 = Active alarms | ||||
| DI | 6doc 1x0007 | No Room Unit 1 | Alarm; clears by itself. | BIT | Read | ||||
| DI | 7doc 1x0008 | No Room Unit 2 | Alarm; clears by itself. | BIT | Read | ||||
| DI | 8doc 1x0009 | No Pressure sensor | Alarm; clears by itself. | BIT | Read | ||||
| DI | 9doc 1x0010 | No Supply Flow sensor | Alarm; clears by itself. | BIT | Read | ||||
| DI | 10doc 1x0011 | No Exhaust Flow sensor | Alarm; clears by itself. | BIT | Read | ||||
| DI | 11doc 1x0012 | Room Unit 1 Temperature | Alarm; clears by itself. | BIT | Read | ||||
| DI | 12doc 1x0013 | Room Unit 2 Temperature | Alarm; clears by itself. | BIT | Read | ||||
| DI | 13doc 1x0014 | Regulator KTY short circuit | Alarm; clears by itself. | BIT | Read | ||||
| DI | 14doc 1x0015 | Regulator KTY open circuit | Alarm; clears by itself. | BIT | Read | ||||
| DI | 15doc 1x0016 | Room Unit Low Battery | Alarm; clears by itself. | BIT | Read | ||||
| DI | 16doc 1x0017 | PI-controller overload | Alarm; clears by itself. | BIT | Read | ||||
| DI | 17doc 1x0018 | Setpoint not reached | Alarm; clears by itself. | BIT | Read | ||||
| DI | 20doc 1x0021 | No device list | Alarm; clears by itself. | BIT | Read | ||||
| DI | 21doc 1x0022 | AC overload | Alarm; clears by itself. | BIT | Read | ||||
| DI | 22doc 1x0023 | System fault | Alarm. | BIT | Read | ||||
| DI | 23doc 1x0024 | No serial number | Alarm. | BIT | Read | ||||
| DI | 25doc 1x0026 | Short circuit X11 | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 26doc 1x0027 | Short circuit X12 | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 27doc 1x0028 | Short circuit X13 | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 28doc 1x0029 | Short circuit X14 | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 29doc 1x0030 | SPI Flash broken | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 30doc 1x0031 | Radio chip broken | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 31doc 1x0032 | Parameter file revision | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 32doc 1x0033 | Parameter file format | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 33doc 1x0034 | No ModBus ID | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 34doc 1x0035 | No Application | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 35doc 1x0036 | No parameters | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 36doc 1x0037 | Parameter missing | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 37doc 1x0038 | Parameter value error | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 38doc 1x0039 | Parameter file size | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 39doc 1x0040 | Wrong parameter file | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 40doc 1x0041 | Check Duct Group SM | Alarm; clears once the parameters are corrected. | BIT | Read | ||||
| DI | 41doc 1x0042 | Check Duct Group DC | Alarm; clears once the parameters are corrected. | BIT | Read | ||||
| DI | 42doc 1x0043 | Previous parameters are lost | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 43doc 1x0044 | Factory parameters take up | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 46doc 1x0047 | No supply pressure from AHU | Alarm; clears by itself. | BIT | Read | ||||
| DI | 47doc 1x0048 | No exhaust pressure from AHU | Alarm; clears by itself. | BIT | Read | ||||
| DI | 48doc 1x0049 | Supply duct 100% open | Alarm; clears by itself. | BIT | Read | ||||
| DI | 49doc 1x0050 | Exhaust duct 100% open | Alarm; clears by itself. | BIT | Read | ||||
| DI | 50doc 1x0051 | Low voltage detect | Alarm; clears by itself. | BIT | Read | ||||
| DI | 52doc 1x0053 | Duct group member missing | Alarm; clears by itself. | BIT | Read | ||||
| DI | 53doc 1x0054 | Negative pressure | Alarm; clears by itself. | BIT | Read | ||||
| IR | 0doc 3x0001 | Component Name ID | Range 0 to 10. | UINT16 | Read | ||||
| IR | 21doc 3x0022 | Application state | UINT16 | Read | 0 = Init; 1 = Auto Normal; 2 = Auto Economy; 3 = AutoBoost; 4 = Manual; 5 = TimerFunction; 6 = Stand-by; 7 = Emergency; 8 = NightCool | ||||
| IR | 25doc 3x0026 | Time since last boot (Hours) | Range 0 to 8760. | UINT16 | h | Read | |||
| IR | 26doc 3x0027 | Time since last boot (Minutes) | Range 0 to 60. | UINT16 | min | Read | |||
| IR | 27doc 3x0028 | Temp sensor regulator | UINT16 | × 0.1 | °C | Read | |||
| IR | 28doc 3x0029 | Temp sensor RU1 | UINT16 | × 0.1 | °C | Read | |||
| IR | 29doc 3x0030 | Temp sensor RU2 | UINT16 | × 0.1 | °C | Read | |||
| IR | 32doc 3x0033 | Battery level RU | UINT16 | × 0.1 | V | Read | |||
| IR | 36doc 3x0037 | Input Analog 1 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 37doc 3x0038 | Input Analog 2 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 38doc 3x0039 | Input Analog 3 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 39doc 3x0040 | Input Analog 4 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 40doc 3x0041 | Output PWM 1 | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 41doc 3x0042 | Output PWM 2 | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 42doc 3x0043 | Output PWM 3 | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 43doc 3x0044 | Output PWM 4 | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 44doc 3x0045 | Output Analog 1 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 45doc 3x0046 | Output Analog 2 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 46doc 3x0047 | Output Analog 3 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 47doc 3x0048 | Output Analog 4 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 52doc 3x0053 | Cool Water | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 53doc 3x0054 | Warm Water | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 54doc 3x0055 | SA Damper pos. | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 55doc 3x0056 | EA Damper pos | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 62doc 3x0063 | Copy of Input Status 1-16 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read | ||||
| IR | 63doc 3x0064 | Copy of Input Status 17-32 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read | ||||
| IR | 64doc 3x0065 | Copy of Input Status 33-48 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read | ||||
| IR | 65doc 3x0066 | Copy of Input Status 49-64 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read | ||||
| HR | 0doc 4x0001 | Relay in Emergency | Default 1. | UINT16 | Read/write | 0 = Close; 1 = Open; 2 = No Action | |||
| HR | 1doc 4x0002 | Application transition | States 2, 3, 5 and 9 are read-only; 1, 4, 6, 7 and 8 can be written. | UINT16 | Read/write | 1 = Auto Normal; 2 = Auto Economy; 3 = Auto boost; 4 = Manual; 5 = Timer function; 6 = Stand-by; 7 = Emergency; 8 = Night cool; 9 = Commissioning | |||
| HR | 2doc 4x0003 | Room number | Default 0. | UINT16 | Read/write | ||||
| HR | 3doc 4x0004 | Valve exercise | Default 48. Range 0 to 72. | UINT16 | h | Read/write | |||
| HR | 4doc 4x0005 | Motion Timer | Default 20. Range 0 to 20. | UINT16 | min | Read/write | |||
| HR | 5doc 4x0006 | General warning time | Default 60. Range 0 to 60. | UINT16 | min | Read/write | |||
| HR | 6doc 4x0007 | PI-overload warning time | Default 120. Range 0 to 60. | UINT16 | min | Read/write | |||
| HR | 7doc 4x0008 | Set-point warning time | Default 60. Range 0 to 60. | UINT16 | min | Read/write | |||
| HR | 8doc 4x0009 | Pressure sensor warning time | Default 15. Range 0 to 60. | UINT16 | min | Read/write | |||
| HR | 13doc 4x0014 | System type | Default 4. | UINT16 | Read/write | 1 = Heat; 2 = Cool; 3 = Change Over; 4 = Heat+Cool | |||
| HR | 14doc 4x0015 | Number of Room units | Default 1. | UINT16 | Read/write | 1 = One room unit; 2 = Two room units | |||
| HR | 15doc 4x0016 | Window switch | Default 0. | UINT16 | Read/write | 0 = Not used; 1 = Normaly Closed; 2 = Normaly Open | |||
| HR | 16doc 4x0017 | Occupancy switch | Default 1. | UINT16 | Read/write | 0 = Not used; 1 = Normaly Closed; 2 = Normaly Open | |||
| HR | 17doc 4x0018 | Actuator Type Cool | Default 1. | UINT16 | Read/write | 1 = NC; 2 = 0-10V; 3 = NO | |||
| HR | 18doc 4x0019 | Actuator Type Heat | Default 1. | UINT16 | Read/write | 1 = NC; 2 = 0-10V; 3 = NO | |||
| HR | 30doc 4x0031 | Room unit's min air flow | Only used in manual state. Default 10. Range 5 to 50. | UINT16 | % | Read/write | |||
| HR | 31doc 4x0032 | Room unit's max air flow | Only used in manual state. Default 100. Range 50 to 100. | UINT16 | % | Read/write | |||
| HR | 34doc 4x0035 | RU back to auto state | Default 480. Range 0 to 1200. | UINT16 | Read/write | ||||
| HR | 35doc 4x0036 | Normal flow SA | Default 50. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 36doc 4x0037 | Normal flow EA | Default 50. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 37doc 4x0038 | Economy flow SA | Default 20. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 38doc 4x0039 | Economy flow EA | Default 20. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 39doc 4x0040 | Night cool flow SA | Default 80. Range 50 to 100. | UINT16 | % | Read/write | |||
| HR | 40doc 4x0041 | Night cool flow EA | Default 80. Range 50 to 100. | UINT16 | % | Read/write | |||
| HR | 41doc 4x0042 | Boost flow SA | Default 90. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 42doc 4x0043 | Boost flow EA | Default 90. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 45doc 4x0046 | Stand-by flow EA | Default 10. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 46doc 4x0047 | Stand-by flow EA | Default 10. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 47doc 4x0048 | P term Heat | Default 5000. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 48doc 4x0049 | I term Heat | Default 10. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 49doc 4x0050 | P term Cool | Default 5000. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 50doc 4x0051 | I term Cool | Default 10. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 51doc 4x0052 | P term Change over | Default 5000. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 52doc 4x0053 | I term Change over | Default 50. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 53doc 4x0054 | SA 0% value | Default 0. Range 0 to 5000. | UINT16 | Read/write | ||||
| HR | 54doc 4x0055 | SA 100% value | Default 10000. Range 5000 to 10000. | UINT16 | Read/write | ||||
| HR | 55doc 4x0056 | EA 0% value | Default 0. Range 0 to 5000. | UINT16 | Read/write | ||||
| HR | 56doc 4x0057 | EA 100% value | Default 10000. Range 5000 to 10000. | UINT16 | Read/write | ||||
| HR | 63doc 4x0064 | Manual SA flow | Only used in manual state. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 64doc 4x0065 | Manual EA flow | Only used in manual state. Range 0 to 100. | UINT16 | % | Read/write | |||
| HR | 68doc 4x0069 | Copy of Coil Status 1-16 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read/write |
Notes on this map
- Addresses are printed in Modicon form (0x coils, 1x discrete inputs, 3x input registers, 4x holding registers); wire address = number - 1 within each table.
- Sensor temperatures and battery voltage carry an explicit 1:10 scaling. Room temperature (3x0060), changeover temperature (3x0061) and the room-unit setpoint/flow readings (3x0031/3x0032) give a unit but no scaling, so they are left out.
- Left out: every temperature setpoint and temperature band in the holding table (frost guard 4x0023, TC1/TH1 normal and TC2/TH2 economy 4x0024-4x0027, night cool 4x0028, room-unit min/max 4x0029-4x0030, boost hysteresis 4x0033-4x0034, manual temperature 4x0063). The table gives °C or nothing and no scaling for them, while the input temperatures are marked 1:10, so the raw format is not settled.
- Also left out: PID Water Out and PID ChangeOver Out (3x0049/3x0050), whose -100 to 100 % range needs a signed format the manual never states.
- Also left out: the 16-register component name (ASCII byte order not given), application ID, serial number, software version and boot-year registers (no format given), and every Not used row.
- BMS port settings are menu parameters P_101 (address 1-247), P_102 (baud 9.6/19.2/38.4 k), P_103 (parity odd/even/none) and P_104 (stop bits).
- The manual prints 4x0046 and 4x0047 both as "Stand-by flow EA"; both are kept with the printed name.
- Input registers 3x0064-3x0066 are printed twice on the last page with identical content.
- The last W3 input-register page (3x0057-3x0066) is headed 'applies to software before 1.38' while every other W3 page says 'after 1.38'; the packed status copies 3x0063-3x0066 are kept because they match the W1 table.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
What Modbus registers does the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) have?
This map lists 122 registers: 5 coils, 48 discrete inputs, 28 input registers, 41 holding registers. 46 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print 0x/1x/3x/4x reference numbers starting at 0001; subtract 1 for the wire address in each table.
What are the minimum Modbus registers to integrate the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)?
Start with IR 27 Temp sensor regulator (Regulator temperature sensor x10); IR 28 Temp sensor RU1 (Room unit 1 temperature x10); IR 21 Application state (Application state); HR 1 Application transition (Application transition); IR 54 SA Damper pos. (Supply air damper position); IR 55 EA Damper pos (Extract air damper position); DI 5 Active alarms (Active alarms); HR 35 Normal flow SA (Normal supply airflow level).
How do I enable Modbus control of the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)?
Set the BMS address, baud, parity and stop bits in system parameters P_101-P_104 from the room unit (service level).
Where is the official Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus documentation?
The source is CONDUCTOR W1, CONDUCTOR W3 Technical Manual (cond_w1w3-sw138-m (SW version 1.38)), revision 2015-06-15, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/waterborne-climate-systems/control-equipment/_en/cond_w1w3-sw138-m.pdf.
More Swegon Modbus register maps
- Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6)
Other hvac equipment register maps
- Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Air handler
Flexit Nordic residential air handling unit (Flexit GO, built-in Modbus)
Flexit NORDIC series residential ventilation units with Flexit GO control and built-in Modbus RTU (cable harness 116405), per the 'Modbus Nordic Basic' register sheet and instruction 117989-01 (2020-01). Not EcoNordic, which has its own register sheet.
Also known as: Nordic S2, Nordic S3, Nordic S4, Nordic CL2, Nordic CL3, Nordic CL4, Flexit GO, Modbus Nordic Basic, 117989 - Thermostat (fan coil)
Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Johnson Controls T7000 series Modbus thermostats listed in the data table: T7600-TF21, T7601-TF20 (ECM fan), T7600-TF20 (relay), T7603-T000 (single-stage heating) and T7600-TB21 (with AI); data table revision 2.4 (2019-12-23).
Also known as: T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603 - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series
All hvac equipment Modbus register maps →
Source: CONDUCTOR W1, CONDUCTOR W3 Technical Manual · cond_w1w3-sw138-m (SW version 1.38) · rev. 2015-06-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.