Easy Modbus
  1. Home
  2. Modbus register maps
  3. Swegon
  4. CONDUCTOR W3 room controller (air and water, Modbus RTU)

Thermostat / room controller (chilled beam with supply and extract air dampers) · Modbus register map

Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

CONDUCTOR W3 is the Swegon room controller that handles both the water circuits (cooling/heating) and the supply and extract air dampers of a room, for demand-controlled waterborne climate systems. Over Modbus RTU it exposes alarms, sensor temperatures, outputs and damper positions, plus airflow levels per state, the application-state request and PI tuning. The temperature setpoints are left out because the manual does not give their scaling.

This page lists 122 Modbus registers for the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) — 46 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.

Manufacturer
Swegon
Model
CONDUCTOR W3 room controller (air and water, Modbus RTU)
Equipment type
Thermostat / room controller (chilled beam with supply and extract air dampers)
Registers
122 (46 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
1.38 and later
Also known as
CONDUCTOR RE W3, Conductor W3
Source document
CONDUCTOR W1, CONDUCTOR W3 Technical Manual · cond_w1w3-sw138-m (SW version 1.38) · rev. 2015-06-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)

Integration in brief

Read 3x0028-3x0030 (temperatures x10), 3x0022 (state) and 3x0055/3x0056 (damper positions); write 4x0002 for state and 4x0036-4x0043 for airflow levels. Temperature setpoints are not in this map because the manual gives no scaling for them.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 27Temp sensor regulatorUINT16Regulator temperature sensor x10Read
IR 28Temp sensor RU1UINT16Room unit 1 temperature x10Read
IR 21Application stateUINT16Application stateRead
HR 1Application transitionUINT16Application transitionRead/write
IR 54SA Damper pos.UINT16Supply air damper positionRead
IR 55EA Damper posUINT16Extract air damper positionRead
DI 5Active alarmsBITActive alarmsRead
HR 35Normal flow SAUINT16Normal supply airflow levelRead/write

Enable Modbus control & writes

Set the BMS address, baud, parity and stop bits in system parameters P_101-P_104 from the room unit (service level).

Byte order & addressing

Network setup

Watch out for

Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

122 of 122 shown
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1doc 0x0002SA Emergency actionBITRead/write
CO2doc 0x0003EA Emergency actionBITRead/write
CO4doc 0x0005Economy modeBITRead/write0 = Unavailable; 1 = Available
CO5doc 0x0006Timer FunctionBITRead/write0 = Unavailable; 1 = Available
CO7doc 0x0008Restart deviceWrite 1 to force a software reboot.BITRead/write
DI0doc 1x0001CondensationBITRead
DI1doc 1x0002Relay stateBITRead
DI2doc 1x0003Occupancy switchBITRead
DI3doc 1x0004Window switchBITRead
DI4doc 1x0005MotionBITRead
DI5doc 1x0006Active alarmsBITRead0 = No active alarms; 1 = Active alarms
DI6doc 1x0007No Room Unit 1Alarm; clears by itself.BITRead
DI7doc 1x0008No Room Unit 2Alarm; clears by itself.BITRead
DI8doc 1x0009No Pressure sensorAlarm; clears by itself.BITRead
DI9doc 1x0010No Supply Flow sensorAlarm; clears by itself.BITRead
DI10doc 1x0011No Exhaust Flow sensorAlarm; clears by itself.BITRead
DI11doc 1x0012Room Unit 1 TemperatureAlarm; clears by itself.BITRead
DI12doc 1x0013Room Unit 2 TemperatureAlarm; clears by itself.BITRead
DI13doc 1x0014Regulator KTY short circuitAlarm; clears by itself.BITRead
DI14doc 1x0015Regulator KTY open circuitAlarm; clears by itself.BITRead
DI15doc 1x0016Room Unit Low BatteryAlarm; clears by itself.BITRead
DI16doc 1x0017PI-controller overloadAlarm; clears by itself.BITRead
DI17doc 1x0018Setpoint not reachedAlarm; clears by itself.BITRead
DI20doc 1x0021No device listAlarm; clears by itself.BITRead
DI21doc 1x0022AC overloadAlarm; clears by itself.BITRead
DI22doc 1x0023System faultAlarm.BITRead
DI23doc 1x0024No serial numberAlarm.BITRead
DI25doc 1x0026Short circuit X11Alarm; needs a hardware reset.BITRead
DI26doc 1x0027Short circuit X12Alarm; needs a hardware reset.BITRead
DI27doc 1x0028Short circuit X13Alarm; needs a hardware reset.BITRead
DI28doc 1x0029Short circuit X14Alarm; needs a hardware reset.BITRead
DI29doc 1x0030SPI Flash brokenAlarm; needs a hardware reset.BITRead
DI30doc 1x0031Radio chip brokenAlarm; needs a hardware reset.BITRead
DI31doc 1x0032Parameter file revisionAlarm; needs a hardware reset.BITRead
DI32doc 1x0033Parameter file formatAlarm; needs a hardware reset.BITRead
DI33doc 1x0034No ModBus IDAlarm; needs a hardware reset.BITRead
DI34doc 1x0035No ApplicationAlarm; needs a hardware reset.BITRead
DI35doc 1x0036No parametersAlarm; needs a hardware reset.BITRead
DI36doc 1x0037Parameter missingAlarm; needs a hardware reset.BITRead
DI37doc 1x0038Parameter value errorAlarm; needs a hardware reset.BITRead
DI38doc 1x0039Parameter file sizeAlarm; needs a hardware reset.BITRead
DI39doc 1x0040Wrong parameter fileAlarm; needs a hardware reset.BITRead
DI40doc 1x0041Check Duct Group SMAlarm; clears once the parameters are corrected.BITRead
DI41doc 1x0042Check Duct Group DCAlarm; clears once the parameters are corrected.BITRead
DI42doc 1x0043Previous parameters are lostAlarm; needs a hardware reset.BITRead
DI43doc 1x0044Factory parameters take upAlarm; needs a hardware reset.BITRead
DI46doc 1x0047No supply pressure from AHUAlarm; clears by itself.BITRead
DI47doc 1x0048No exhaust pressure from AHUAlarm; clears by itself.BITRead
DI48doc 1x0049Supply duct 100% openAlarm; clears by itself.BITRead
DI49doc 1x0050Exhaust duct 100% openAlarm; clears by itself.BITRead
DI50doc 1x0051Low voltage detectAlarm; clears by itself.BITRead
DI52doc 1x0053Duct group member missingAlarm; clears by itself.BITRead
DI53doc 1x0054Negative pressureAlarm; clears by itself.BITRead
IR0doc 3x0001Component Name IDRange 0 to 10.UINT16Read
IR21doc 3x0022Application stateUINT16Read0 = Init; 1 = Auto Normal; 2 = Auto Economy; 3 = AutoBoost; 4 = Manual; 5 = TimerFunction; 6 = Stand-by; 7 = Emergency; 8 = NightCool
IR25doc 3x0026Time since last boot (Hours)Range 0 to 8760.UINT16hRead
IR26doc 3x0027Time since last boot (Minutes)Range 0 to 60.UINT16minRead
IR27doc 3x0028Temp sensor regulatorUINT16× 0.1°CRead
IR28doc 3x0029Temp sensor RU1UINT16× 0.1°CRead
IR29doc 3x0030Temp sensor RU2UINT16× 0.1°CRead
IR32doc 3x0033Battery level RUUINT16× 0.1VRead
IR36doc 3x0037Input Analog 1Range 0 to 10000.UINT16mVRead
IR37doc 3x0038Input Analog 2Range 0 to 10000.UINT16mVRead
IR38doc 3x0039Input Analog 3Range 0 to 10000.UINT16mVRead
IR39doc 3x0040Input Analog 4Range 0 to 10000.UINT16mVRead
IR40doc 3x0041Output PWM 1Range 0 to 100.UINT16%Read
IR41doc 3x0042Output PWM 2Range 0 to 100.UINT16%Read
IR42doc 3x0043Output PWM 3Range 0 to 100.UINT16%Read
IR43doc 3x0044Output PWM 4Range 0 to 100.UINT16%Read
IR44doc 3x0045Output Analog 1Range 0 to 10000.UINT16mVRead
IR45doc 3x0046Output Analog 2Range 0 to 10000.UINT16mVRead
IR46doc 3x0047Output Analog 3Range 0 to 10000.UINT16mVRead
IR47doc 3x0048Output Analog 4Range 0 to 10000.UINT16mVRead
IR52doc 3x0053Cool WaterRange 0 to 100.UINT16%Read
IR53doc 3x0054Warm WaterRange 0 to 100.UINT16%Read
IR54doc 3x0055SA Damper pos.Range 0 to 100.UINT16%Read
IR55doc 3x0056EA Damper posRange 0 to 100.UINT16%Read
IR62doc 3x0063Copy of Input Status 1-16Same flags as the bit table, packed 16 per register (bit 0 = first item).BITMAP16Read
IR63doc 3x0064Copy of Input Status 17-32Same flags as the bit table, packed 16 per register (bit 0 = first item).BITMAP16Read
IR64doc 3x0065Copy of Input Status 33-48Same flags as the bit table, packed 16 per register (bit 0 = first item).BITMAP16Read
IR65doc 3x0066Copy of Input Status 49-64Same flags as the bit table, packed 16 per register (bit 0 = first item).BITMAP16Read
HR0doc 4x0001Relay in EmergencyDefault 1.UINT16Read/write0 = Close; 1 = Open; 2 = No Action
HR1doc 4x0002Application transitionStates 2, 3, 5 and 9 are read-only; 1, 4, 6, 7 and 8 can be written.UINT16Read/write1 = Auto Normal; 2 = Auto Economy; 3 = Auto boost; 4 = Manual; 5 = Timer function; 6 = Stand-by; 7 = Emergency; 8 = Night cool; 9 = Commissioning
HR2doc 4x0003Room numberDefault 0.UINT16Read/write
HR3doc 4x0004Valve exerciseDefault 48. Range 0 to 72.UINT16hRead/write
HR4doc 4x0005Motion TimerDefault 20. Range 0 to 20.UINT16minRead/write
HR5doc 4x0006General warning timeDefault 60. Range 0 to 60.UINT16minRead/write
HR6doc 4x0007PI-overload warning timeDefault 120. Range 0 to 60.UINT16minRead/write
HR7doc 4x0008Set-point warning timeDefault 60. Range 0 to 60.UINT16minRead/write
HR8doc 4x0009Pressure sensor warning timeDefault 15. Range 0 to 60.UINT16minRead/write
HR13doc 4x0014System typeDefault 4.UINT16Read/write1 = Heat; 2 = Cool; 3 = Change Over; 4 = Heat+Cool
HR14doc 4x0015Number of Room unitsDefault 1.UINT16Read/write1 = One room unit; 2 = Two room units
HR15doc 4x0016Window switchDefault 0.UINT16Read/write0 = Not used; 1 = Normaly Closed; 2 = Normaly Open
HR16doc 4x0017Occupancy switchDefault 1.UINT16Read/write0 = Not used; 1 = Normaly Closed; 2 = Normaly Open
HR17doc 4x0018Actuator Type CoolDefault 1.UINT16Read/write1 = NC; 2 = 0-10V; 3 = NO
HR18doc 4x0019Actuator Type HeatDefault 1.UINT16Read/write1 = NC; 2 = 0-10V; 3 = NO
HR30doc 4x0031Room unit's min air flowOnly used in manual state. Default 10. Range 5 to 50.UINT16%Read/write
HR31doc 4x0032Room unit's max air flowOnly used in manual state. Default 100. Range 50 to 100.UINT16%Read/write
HR34doc 4x0035RU back to auto stateDefault 480. Range 0 to 1200.UINT16Read/write
HR35doc 4x0036Normal flow SADefault 50. Range 0 to 100.UINT16%Read/write
HR36doc 4x0037Normal flow EADefault 50. Range 0 to 100.UINT16%Read/write
HR37doc 4x0038Economy flow SADefault 20. Range 0 to 100.UINT16%Read/write
HR38doc 4x0039Economy flow EADefault 20. Range 0 to 100.UINT16%Read/write
HR39doc 4x0040Night cool flow SADefault 80. Range 50 to 100.UINT16%Read/write
HR40doc 4x0041Night cool flow EADefault 80. Range 50 to 100.UINT16%Read/write
HR41doc 4x0042Boost flow SADefault 90. Range 0 to 100.UINT16%Read/write
HR42doc 4x0043Boost flow EADefault 90. Range 0 to 100.UINT16%Read/write
HR45doc 4x0046Stand-by flow EADefault 10. Range 0 to 100.UINT16%Read/write
HR46doc 4x0047Stand-by flow EADefault 10. Range 0 to 100.UINT16%Read/write
HR47doc 4x0048P term HeatDefault 5000. Range 10 to 10000.UINT16× 0.01Read/write
HR48doc 4x0049I term HeatDefault 10. Range 10 to 10000.UINT16× 0.01Read/write
HR49doc 4x0050P term CoolDefault 5000. Range 10 to 10000.UINT16× 0.01Read/write
HR50doc 4x0051I term CoolDefault 10. Range 10 to 10000.UINT16× 0.01Read/write
HR51doc 4x0052P term Change overDefault 5000. Range 10 to 10000.UINT16× 0.01Read/write
HR52doc 4x0053I term Change overDefault 50. Range 10 to 10000.UINT16× 0.01Read/write
HR53doc 4x0054SA 0% valueDefault 0. Range 0 to 5000.UINT16Read/write
HR54doc 4x0055SA 100% valueDefault 10000. Range 5000 to 10000.UINT16Read/write
HR55doc 4x0056EA 0% valueDefault 0. Range 0 to 5000.UINT16Read/write
HR56doc 4x0057EA 100% valueDefault 10000. Range 5000 to 10000.UINT16Read/write
HR63doc 4x0064Manual SA flowOnly used in manual state. Range 0 to 100.UINT16%Read/write
HR64doc 4x0065Manual EA flowOnly used in manual state. Range 0 to 100.UINT16%Read/write
HR68doc 4x0069Copy of Coil Status 1-16Same flags as the bit table, packed 16 per register (bit 0 = first item).BITMAP16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)

What Modbus registers does the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) have?

This map lists 122 registers: 5 coils, 48 discrete inputs, 28 input registers, 41 holding registers. 46 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print 0x/1x/3x/4x reference numbers starting at 0001; subtract 1 for the wire address in each table.

What are the minimum Modbus registers to integrate the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)?

Start with IR 27 Temp sensor regulator (Regulator temperature sensor x10); IR 28 Temp sensor RU1 (Room unit 1 temperature x10); IR 21 Application state (Application state); HR 1 Application transition (Application transition); IR 54 SA Damper pos. (Supply air damper position); IR 55 EA Damper pos (Extract air damper position); DI 5 Active alarms (Active alarms); HR 35 Normal flow SA (Normal supply airflow level).

How do I enable Modbus control of the Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)?

Set the BMS address, baud, parity and stop bits in system parameters P_101-P_104 from the room unit (service level).

Where is the official Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU) Modbus documentation?

The source is CONDUCTOR W1, CONDUCTOR W3 Technical Manual (cond_w1w3-sw138-m (SW version 1.38)), revision 2015-06-15, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/waterborne-climate-systems/control-equipment/_en/cond_w1w3-sw138-m.pdf.

More Swegon Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: CONDUCTOR W1, CONDUCTOR W3 Technical Manual · cond_w1w3-sw138-m (SW version 1.38) · rev. 2015-06-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.