Swegon Modbus register maps

Updated 19 November 2026

9 Swegon models, 731 registers in all, each re-typed from Swegon’s own free documentation and checked against it.

9 of 9 shown

Swegon: default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)RTUNot stated-16-bit onlyModicon98
CONDUCTOR W3 room controller (air and water, Modbus RTU)RTUNot stated-16-bit onlyModicon122
CONDUCTOR W4 room controller (airflow and water, Modbus RTU)RTUNot stated-16-bit onlyModicon119
REACT damper / VAV actuator (Modbus RTU, 2018 sheet)RTUNot stated-16-bit only0-based18
REACT Parasol Zenith with Belimo actuator (Modbus RTU)RTUNot stated19200 baud, 8E1CDAB0-based27
SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)RTU7938400 baud, 8N116-bit only0-based57
SILVER C fan motor control (RX/PX/CX/SD, generation E/F)RTU5438400 baud, 8N116-bit only1-based106
TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)RTU/TCP19600 baud, 8N1CDABModicon91
TAC6 controller (Global units)TCP1-CDABModicon93