Air handler fan motor control · Modbus register map

Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus register map

Updated 17 November 2026

Short answer

Each supply or extract fan in a SILVER C air handler has its own motor controller with a Modbus RTU slave port. Over it a master can start and stop the fan, give a speed setpoint in percent, reset alarms and read speed, current, power, temperatures, run time and an energy log. Configuration values such as ramp times, I/O module functions and the serial settings are holding registers.

This page lists 106 Modbus registers for the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) — 46 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.

Manufacturer
Swegon
Model
SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
Equipment type
Air handler fan motor control
Registers
106 (46 writable)
Transport
Modbus RTU
Default unit ID
54
Default serial
38400 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F
Source document
Modbus RTU SILVER RX, PX, CX, SD, generation E/F · SILVERCModbus.210809
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)

Integration in brief

Set coil 7 (Control) to 0 so speed comes from Modbus, write the speed setpoint in 0.01 % to holding register 0 and switch the motor with coil 0. Poll input registers 3-8 for output, speed, temperature, voltage, current and power, and discrete inputs 0-27 for alarms.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0Motor ON/OFFBITMotor on/offRead/write
CO 7ControlBITSpeed source Modbus or 0-10 VRead/write
HR 0Setpoint / PrcSetUINT16Speed setpoint 0.01 %Read/write
IR 3PrcOutUINT16Actual output %Read
IR 4RPMOutUINT16Actual speedRead
IR 8Power InUINT16Input power WRead
DI 10Internal StopBITInternal stop alarmRead
CO 1Reset AlarmsBITAlarm resetRead/write

Enable Modbus control & writes

Communication settings are changed with the TBLZ-4-75 hand-held terminal (or the matching holding registers). Coil 7 selects whether speed follows Modbus or the 0-10 V input. Coil 18 can lock the configuration against Modbus writes.

Communication loss & watchdog

Comm. timeout 0-240 s, factory 10 s (holding register 21). What the fan does on timeout is not described.

Byte order & addressing

Network setup

Watch out for

Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

106 of 106 shown
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0x0001Motor ON/OFF1 = motor on.BITRead/write
CO1doc 0x0002Reset AlarmsWrite 1 to reset alarms.BITRead/write
CO3doc 0x0004FireMode1 = fire mode active.BITRead/write
CO5doc 0x0006Rotation1 = clockwise rotation.BITRead/write
CO6doc 0x0007Disable V_Ripple protection1 = supply ripple protection disabled.BITRead/write
CO7doc 0x0008ControlSpeed command source: 0 = Modbus, 1 = 0-10 V input.BITRead/write
CO9doc 0x0010Autodetect communication1 = enabled.BITRead/write
CO10doc 0x0011Analog start signal1 = enabled.BITRead/write
CO11doc 0x0012Invert analog speed input1 = inverted.BITRead/write
CO12doc 0x0013Allow using Field Weakening1 = field weakening allowed.BITRead/write
CO14doc 0x0015Allow using Cooling Fan1 = cooling fan allowed.BITRead/write
CO15doc 0x00163 x 230V config0 = undervoltage value from config file, 1 = fixed value for 3x230 V.BITRead/write
CO16doc 0x00171 V start voltage0 = start at 2 V, 1 = start at 1 V.BITRead/write
CO17doc 0x0018Very High Switch Frequency0 = 8 kHz used as high switching frequency, 1 = 10 kHz.BITRead/write
CO18doc 0x0019Write protect config0 = configuration may be changed over Modbus, 1 = locked.BITRead/write
CO19doc 0x0020Clear PowerLogWrite 1 to clear the Wh/kWh/MWh energy log.BITRead/write
DI0doc 1x0001V LO Alarm1 = alarm.BITRead
DI1doc 1x0002V HI Alarm1 = alarm.BITRead
DI2doc 1x0003I HI Alarm (Motor out short)1 = alarm.BITRead
DI3doc 1x0004Temperature High1 = warning.BITRead
DI4doc 1x0005Input Phase Error1 = error.BITRead
DI5doc 1x0006Rotor Blocked1 = error.BITRead
DI6doc 1x0007Limit1 = warning.BITRead
DI7doc 1x0008Internal HW Fault1 = alarm.BITRead
DI8doc 1x0009Rotor Direction1 = alarm.BITRead
DI9doc 1x0010EEPROM Error1 = warning.BITRead
DI10doc 1x0011Internal Stop1 = alarm (stop).BITRead
DI13doc 1x0014Motor Phase Error1 = alarm.BITRead
DI14doc 1x0015Communication error MOC1 = alarm.BITRead
DI15doc 1x0016V Ripple1 = warning.BITRead
DI16doc 1x0017Digital Input 11 = input high.BITRead
DI17doc 1x0018Digital Input 21 = input high.BITRead
DI18doc 1x0019Ext. 24V supply overload1 = overload.BITRead
DI19doc 1x0020MOC in bootloader1 = alarm.BITRead
DI20doc 1x0021Digital input 3 (IOM)1 = input high.BITRead
DI21doc 1x0022Digital input 4 (IOM)1 = input high.BITRead
DI22doc 1x0023Communication error (IOM)1 = warning.BITRead
DI23doc 1x0024Motor Overheat (IOM)1 = alarm.BITRead
DI24doc 1x0025Windmilling1 = warning.BITRead
DI25doc 1x0026Rotation OK1 = rotation OK.BITRead
DI26doc 0x0027IO Config mismatch1 = warning.BITRead
DI27doc 0x0028Config write attempt1 = attempt detected.BITRead
IR0doc 3x0001Drive TypeUINT16Read
IR1doc 3x0002AOC SW VersionUINT16× 0.01Read
IR2doc 3x0003MOC SW VersionUINT16× 0.01Read
IR3doc 3x0004PrcOutActual output in percent.UINT16× 0.01%Read
IR4doc 3x0005RPMOutActual speed. FC configuration: 0.01 Hz per count instead of rpm.UINT16rpmRead
IR5doc 3x0006Intern TempInternal controller temperature (range -50.00 to 150.00).INT16× 0.01°CRead
IR6doc 3x0007V InSupply voltage.UINT16VRead
IR7doc 3x0008I OutOutput current.UINT16mARead
IR8doc 3x0009Power InInput power.UINT16WRead
IR9doc 3x0010I RippleUINT16mARead
IR10doc 3x0011Operation MinutesMinutes part of the running time (0-1439).UINT16minRead
IR11doc 3x0012Operation DaysDays part of the running time.UINT16daysRead
IR12doc 3x0013V RippleUINT16VRead
IR14doc 3x0015Config. File VersionUINT16× 0.01Read
IR15doc 3x0016ExternSetVoltage on the external setpoint input.UINT16mVRead
IR19doc 3x0020AOC Boot SWUINT16× 0.01Read
IR20doc 3x0021MOC Boot SWUINT16× 0.01Read
IR21doc 3x0022Motor Config. VariantUINT16Read
IR22doc 3x0023Motor Config. VersionUINT16× 0.01Read
IR23doc 3x0024Fan Config. VariantUINT16Read
IR24doc 3x0025Fan Config. VersionUINT16× 0.01Read
IR25doc 3x0026User Data VariantUINT16Read
IR26doc 3x0027User Data VersionUINT16× 0.01Read
IR27doc 3x0028IOM SW versionUINT16× 0.01Read
IR28doc 3x0029V DC Bus (Peak)UINT16VRead
IR29doc 3x0030V Motor (Peak)UINT16VRead
IR30doc 3x0031Power In (unfiltered)UINT16WRead
IR31doc 3x0032Power Consumption WhWh part of the energy log (0-999).UINT16WhRead
IR32doc 3x0033Power Consumption kWhkWh part of the energy log (0-999).UINT16kWhRead
IR33doc 3x0034Power Consumption MWhMWh part of the energy log.UINT16MWhRead
IR1999doc 3x2000Production weekWeek and year coded as WWYY.UINT16Read
IR2000doc 3x2001Production order number LOLow part; order number = LO + HI x 10000.UINT16Read
IR2001doc 3x2002Production order number HIHigh part; the source gives it a resolution of 10000.UINT16× 10000Read
IR2002doc 3x2003Serial number of batchUINT16Read
HR0doc 4x0001Setpoint / PrcSetSpeed setpoint in percent when control source is Modbus.UINT16× 0.01%Read/write
HR1doc 4x0002Min. RPMFC configuration: 0.01 Hz per count.UINT16rpmRead/write
HR2doc 4x0003Max. RPMFC configuration: 0.01 Hz per count.UINT16rpmRead/write
HR3doc 4x0004UpRampTime15-300 s.UINT16sRead/write
HR4doc 4x0005DownRampTime15-300 s.UINT16sRead/write
HR7doc 4x0008Max I OutUINT16mARead/write
HR8doc 4x0009I Out Alarm LimitFC configuration only.UINT16mARead/write
HR10doc 4x0011SwitchModeSwitching frequency.UINT16Read/write0 = Auto; 1 = 4 kHz; 2 = 8 kHz
HR11doc 4x0012U minHzFC configuration only.UINT16VRead/write
HR12doc 4x0013Freq UmaxFC configuration only.UINT16× 0.01HzRead/write
HR13doc 4x0014Auto SF ChangeUINT16× 0.01%Read/write
HR14doc 4x0015ExpSetFC configuration only (0-100).UINT16Read/write
HR15doc 4x0016Drive TypeUINT16Read/write
HR16doc 4x0017Modbus IDSlave address 1-247.UINT16Read/write
HR19doc 4x0020Number of retries-1 to 100.INT16Read/write
HR21doc 4x0022CommTimeoutCommunication timeout 0-240 s.UINT16sRead/write
HR22doc 4x0023CommRateBaud rate.UINT16Read/write0 = 9600; 1 = 19200; 2 = 38400; 3 = 115200
HR23doc 4x0024ParityUINT16Read/write0 = None; 1 = Odd; 2 = Even
HR24doc 4x0025Stop BitsUINT16Read/write1 = 1; 2 = 2
HR25doc 4x0026DigIn1 configUINT16Read/write0 = Disabled; 1 = Start/stop; 2 = Alarm reset; 3 = MB_IDs_2; 4 = Invert 10-0V; 5 = Rotation; 6 = Firemode; 7 = Motor overheat; 8 = Invert 0-10V; 9 = All stop
HR26doc 4x0027DigIn2 configUINT16Read/write0 = Disabled; 1 = TachoOut; 2 = Running; 3 = AlarmOut; 4 = Running spin
HR28doc 4x0029MotorConfigVarUINT16Read/write
HR29doc 4x0030FanConfigVarUINT16Read/write
HR30doc 4x0031DigIn3 config (IOM)UINT16Read/write0 = Disabled; 1 = Start/Stop; 2 = Alarm reset; 3 = Disabled; 4 = Invert 10-0V; 5 = Rotation; 6 = Firemode; 8 = Invert 0-10V; 9 = All stop
HR31doc 4x0032DigIn4 config (IOM)UINT16Read/write0 = Disabled; 1 = Start/Stop; 2 = Alarm reset; 3 = Disabled; 4 = Invert 10-0V; 5 = Rotation; 6 = Firemode; 8 = Invert 0-10V; 9 = All stop
HR34doc 4x0035AnalogOut1 config (IOM)UINT16Read/write0 = Disabled; 1 = ActSpeed
HR35doc 4x0036Thermistor config (IOM)UINT16Read/write0 = Disabled; 1 = Motor Overheat PTC
HR37doc 4x0038Thermistor thresholdUINT16ΩRead/write
HR38doc 4x0039Max Windmilling TimeUINT16sRead/write
HR39doc 4x0040AC motor boost currentUINT16mARead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)

What Modbus registers does the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) have?

This map lists 106 registers: 16 coils, 26 discrete inputs, 34 input registers, 30 holding registers. 46 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table prints the reference (0x0001, 1x0001, 3x0001, 4x0001) and the protocol address next to it; the address column is the reference number minus 1 (4x0001 = address 0). The address column is used here.

What are the minimum Modbus registers to integrate the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)?

Start with CO 0 Motor ON/OFF (Motor on/off); CO 7 Control (Speed source Modbus or 0-10 V); HR 0 Setpoint / PrcSet (Speed setpoint 0.01 %); IR 3 PrcOut (Actual output %); IR 4 RPMOut (Actual speed); IR 8 Power In (Input power W); DI 10 Internal Stop (Internal stop alarm); CO 1 Reset Alarms (Alarm reset).

How do I enable Modbus control of the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)?

Communication settings are changed with the TBLZ-4-75 hand-held terminal (or the matching holding registers). Coil 7 selects whether speed follows Modbus or the 0-10 V input. Coil 18 can lock the configuration against Modbus writes.

What happens when the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) loses Modbus communication?

Comm. timeout 0-240 s, factory 10 s (holding register 21). What the fan does on timeout is not described.

Where is the official Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus documentation?

The source is Modbus RTU SILVER RX, PX, CX, SD, generation E/F (SILVERCModbus.210809), published free by Swegon at https://www.swegon.com/globalassets/digizuite/12063-en-silverc_modbus_other_en.pdf.

More Swegon Modbus register maps

Other hvac equipment register maps