- SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
Air handler fan motor control · Modbus register map
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus register map
Updated 17 November 2026
Each supply or extract fan in a SILVER C air handler has its own motor controller with a Modbus RTU slave port. Over it a master can start and stop the fan, give a speed setpoint in percent, reset alarms and read speed, current, power, temperatures, run time and an energy log. Configuration values such as ramp times, I/O module functions and the serial settings are holding registers.
This page lists 106 Modbus registers for the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) — 46 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Swegon
- Model
- SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
- Equipment type
- Air handler fan motor control
- Registers
- 106 (46 writable)
- Transport
- Modbus RTU
- Default unit ID
- 54
- Default serial
- 38400 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F
Integration notes: Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
Set coil 7 (Control) to 0 so speed comes from Modbus, write the speed setpoint in 0.01 % to holding register 0 and switch the motor with coil 0. Poll input registers 3-8 for output, speed, temperature, voltage, current and power, and discrete inputs 0-27 for alarms.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Motor ON/OFF | BIT | Motor on/off | Read/write |
| CO 7 | Control | BIT | Speed source Modbus or 0-10 V | Read/write |
| HR 0 | Setpoint / PrcSet | UINT16 | Speed setpoint 0.01 % | Read/write |
| IR 3 | PrcOut | UINT16 | Actual output % | Read |
| IR 4 | RPMOut | UINT16 | Actual speed | Read |
| IR 8 | Power In | UINT16 | Input power W | Read |
| DI 10 | Internal Stop | BIT | Internal stop alarm | Read |
| CO 1 | Reset Alarms | BIT | Alarm reset | Read/write |
Enable Modbus control & writes
Communication settings are changed with the TBLZ-4-75 hand-held terminal (or the matching holding registers). Coil 7 selects whether speed follows Modbus or the 0-10 V input. Coil 18 can lock the configuration against Modbus writes.
Communication loss & watchdog
Comm. timeout 0-240 s, factory 10 s (holding register 21). What the fan does on timeout is not described.
Byte order & addressing
- Factory slave address is 54 decimal (0x36); the addressing pins on connector A/B select 54-57 so several fan controllers share one bus.
- Coils are written with FC05 using 0xFF00 for ON.
- Factory serial setting is 38400 baud, no parity, 1 stop bit; the alternative factory setting is 115200, even parity.
Network setup
- Connect to terminals Bus A / Bus B / GND or to RJ12 connector A or B; connector C is the master port for external sensors.
- Use the hand-held terminal to change address, baud rate, parity and timeout.
Watch out for
- Do not use RJ12 connector C for the BMS; it is a master port.
- Speed and limit registers change units between EC (rpm) and FC (0.01 Hz) configurations.
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0x0001 | Motor ON/OFF | 1 = motor on. | BIT | Read/write | ||||
| CO | 1doc 0x0002 | Reset Alarms | Write 1 to reset alarms. | BIT | Read/write | ||||
| CO | 3doc 0x0004 | FireMode | 1 = fire mode active. | BIT | Read/write | ||||
| CO | 5doc 0x0006 | Rotation | 1 = clockwise rotation. | BIT | Read/write | ||||
| CO | 6doc 0x0007 | Disable V_Ripple protection | 1 = supply ripple protection disabled. | BIT | Read/write | ||||
| CO | 7doc 0x0008 | Control | Speed command source: 0 = Modbus, 1 = 0-10 V input. | BIT | Read/write | ||||
| CO | 9doc 0x0010 | Autodetect communication | 1 = enabled. | BIT | Read/write | ||||
| CO | 10doc 0x0011 | Analog start signal | 1 = enabled. | BIT | Read/write | ||||
| CO | 11doc 0x0012 | Invert analog speed input | 1 = inverted. | BIT | Read/write | ||||
| CO | 12doc 0x0013 | Allow using Field Weakening | 1 = field weakening allowed. | BIT | Read/write | ||||
| CO | 14doc 0x0015 | Allow using Cooling Fan | 1 = cooling fan allowed. | BIT | Read/write | ||||
| CO | 15doc 0x0016 | 3 x 230V config | 0 = undervoltage value from config file, 1 = fixed value for 3x230 V. | BIT | Read/write | ||||
| CO | 16doc 0x0017 | 1 V start voltage | 0 = start at 2 V, 1 = start at 1 V. | BIT | Read/write | ||||
| CO | 17doc 0x0018 | Very High Switch Frequency | 0 = 8 kHz used as high switching frequency, 1 = 10 kHz. | BIT | Read/write | ||||
| CO | 18doc 0x0019 | Write protect config | 0 = configuration may be changed over Modbus, 1 = locked. | BIT | Read/write | ||||
| CO | 19doc 0x0020 | Clear PowerLog | Write 1 to clear the Wh/kWh/MWh energy log. | BIT | Read/write | ||||
| DI | 0doc 1x0001 | V LO Alarm | 1 = alarm. | BIT | Read | ||||
| DI | 1doc 1x0002 | V HI Alarm | 1 = alarm. | BIT | Read | ||||
| DI | 2doc 1x0003 | I HI Alarm (Motor out short) | 1 = alarm. | BIT | Read | ||||
| DI | 3doc 1x0004 | Temperature High | 1 = warning. | BIT | Read | ||||
| DI | 4doc 1x0005 | Input Phase Error | 1 = error. | BIT | Read | ||||
| DI | 5doc 1x0006 | Rotor Blocked | 1 = error. | BIT | Read | ||||
| DI | 6doc 1x0007 | Limit | 1 = warning. | BIT | Read | ||||
| DI | 7doc 1x0008 | Internal HW Fault | 1 = alarm. | BIT | Read | ||||
| DI | 8doc 1x0009 | Rotor Direction | 1 = alarm. | BIT | Read | ||||
| DI | 9doc 1x0010 | EEPROM Error | 1 = warning. | BIT | Read | ||||
| DI | 10doc 1x0011 | Internal Stop | 1 = alarm (stop). | BIT | Read | ||||
| DI | 13doc 1x0014 | Motor Phase Error | 1 = alarm. | BIT | Read | ||||
| DI | 14doc 1x0015 | Communication error MOC | 1 = alarm. | BIT | Read | ||||
| DI | 15doc 1x0016 | V Ripple | 1 = warning. | BIT | Read | ||||
| DI | 16doc 1x0017 | Digital Input 1 | 1 = input high. | BIT | Read | ||||
| DI | 17doc 1x0018 | Digital Input 2 | 1 = input high. | BIT | Read | ||||
| DI | 18doc 1x0019 | Ext. 24V supply overload | 1 = overload. | BIT | Read | ||||
| DI | 19doc 1x0020 | MOC in bootloader | 1 = alarm. | BIT | Read | ||||
| DI | 20doc 1x0021 | Digital input 3 (IOM) | 1 = input high. | BIT | Read | ||||
| DI | 21doc 1x0022 | Digital input 4 (IOM) | 1 = input high. | BIT | Read | ||||
| DI | 22doc 1x0023 | Communication error (IOM) | 1 = warning. | BIT | Read | ||||
| DI | 23doc 1x0024 | Motor Overheat (IOM) | 1 = alarm. | BIT | Read | ||||
| DI | 24doc 1x0025 | Windmilling | 1 = warning. | BIT | Read | ||||
| DI | 25doc 1x0026 | Rotation OK | 1 = rotation OK. | BIT | Read | ||||
| DI | 26doc 0x0027 | IO Config mismatch | 1 = warning. | BIT | Read | ||||
| DI | 27doc 0x0028 | Config write attempt | 1 = attempt detected. | BIT | Read | ||||
| IR | 0doc 3x0001 | Drive Type | UINT16 | Read | |||||
| IR | 1doc 3x0002 | AOC SW Version | UINT16 | × 0.01 | Read | ||||
| IR | 2doc 3x0003 | MOC SW Version | UINT16 | × 0.01 | Read | ||||
| IR | 3doc 3x0004 | PrcOut | Actual output in percent. | UINT16 | × 0.01 | % | Read | ||
| IR | 4doc 3x0005 | RPMOut | Actual speed. FC configuration: 0.01 Hz per count instead of rpm. | UINT16 | rpm | Read | |||
| IR | 5doc 3x0006 | Intern Temp | Internal controller temperature (range -50.00 to 150.00). | INT16 | × 0.01 | °C | Read | ||
| IR | 6doc 3x0007 | V In | Supply voltage. | UINT16 | V | Read | |||
| IR | 7doc 3x0008 | I Out | Output current. | UINT16 | mA | Read | |||
| IR | 8doc 3x0009 | Power In | Input power. | UINT16 | W | Read | |||
| IR | 9doc 3x0010 | I Ripple | UINT16 | mA | Read | ||||
| IR | 10doc 3x0011 | Operation Minutes | Minutes part of the running time (0-1439). | UINT16 | min | Read | |||
| IR | 11doc 3x0012 | Operation Days | Days part of the running time. | UINT16 | days | Read | |||
| IR | 12doc 3x0013 | V Ripple | UINT16 | V | Read | ||||
| IR | 14doc 3x0015 | Config. File Version | UINT16 | × 0.01 | Read | ||||
| IR | 15doc 3x0016 | ExternSet | Voltage on the external setpoint input. | UINT16 | mV | Read | |||
| IR | 19doc 3x0020 | AOC Boot SW | UINT16 | × 0.01 | Read | ||||
| IR | 20doc 3x0021 | MOC Boot SW | UINT16 | × 0.01 | Read | ||||
| IR | 21doc 3x0022 | Motor Config. Variant | UINT16 | Read | |||||
| IR | 22doc 3x0023 | Motor Config. Version | UINT16 | × 0.01 | Read | ||||
| IR | 23doc 3x0024 | Fan Config. Variant | UINT16 | Read | |||||
| IR | 24doc 3x0025 | Fan Config. Version | UINT16 | × 0.01 | Read | ||||
| IR | 25doc 3x0026 | User Data Variant | UINT16 | Read | |||||
| IR | 26doc 3x0027 | User Data Version | UINT16 | × 0.01 | Read | ||||
| IR | 27doc 3x0028 | IOM SW version | UINT16 | × 0.01 | Read | ||||
| IR | 28doc 3x0029 | V DC Bus (Peak) | UINT16 | V | Read | ||||
| IR | 29doc 3x0030 | V Motor (Peak) | UINT16 | V | Read | ||||
| IR | 30doc 3x0031 | Power In (unfiltered) | UINT16 | W | Read | ||||
| IR | 31doc 3x0032 | Power Consumption Wh | Wh part of the energy log (0-999). | UINT16 | Wh | Read | |||
| IR | 32doc 3x0033 | Power Consumption kWh | kWh part of the energy log (0-999). | UINT16 | kWh | Read | |||
| IR | 33doc 3x0034 | Power Consumption MWh | MWh part of the energy log. | UINT16 | MWh | Read | |||
| IR | 1999doc 3x2000 | Production week | Week and year coded as WWYY. | UINT16 | Read | ||||
| IR | 2000doc 3x2001 | Production order number LO | Low part; order number = LO + HI x 10000. | UINT16 | Read | ||||
| IR | 2001doc 3x2002 | Production order number HI | High part; the source gives it a resolution of 10000. | UINT16 | × 10000 | Read | |||
| IR | 2002doc 3x2003 | Serial number of batch | UINT16 | Read | |||||
| HR | 0doc 4x0001 | Setpoint / PrcSet | Speed setpoint in percent when control source is Modbus. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 1doc 4x0002 | Min. RPM | FC configuration: 0.01 Hz per count. | UINT16 | rpm | Read/write | |||
| HR | 2doc 4x0003 | Max. RPM | FC configuration: 0.01 Hz per count. | UINT16 | rpm | Read/write | |||
| HR | 3doc 4x0004 | UpRampTime | 15-300 s. | UINT16 | s | Read/write | |||
| HR | 4doc 4x0005 | DownRampTime | 15-300 s. | UINT16 | s | Read/write | |||
| HR | 7doc 4x0008 | Max I Out | UINT16 | mA | Read/write | ||||
| HR | 8doc 4x0009 | I Out Alarm Limit | FC configuration only. | UINT16 | mA | Read/write | |||
| HR | 10doc 4x0011 | SwitchMode | Switching frequency. | UINT16 | Read/write | 0 = Auto; 1 = 4 kHz; 2 = 8 kHz | |||
| HR | 11doc 4x0012 | U minHz | FC configuration only. | UINT16 | V | Read/write | |||
| HR | 12doc 4x0013 | Freq Umax | FC configuration only. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 13doc 4x0014 | Auto SF Change | UINT16 | × 0.01 | % | Read/write | |||
| HR | 14doc 4x0015 | ExpSet | FC configuration only (0-100). | UINT16 | Read/write | ||||
| HR | 15doc 4x0016 | Drive Type | UINT16 | Read/write | |||||
| HR | 16doc 4x0017 | Modbus ID | Slave address 1-247. | UINT16 | Read/write | ||||
| HR | 19doc 4x0020 | Number of retries | -1 to 100. | INT16 | Read/write | ||||
| HR | 21doc 4x0022 | CommTimeout | Communication timeout 0-240 s. | UINT16 | s | Read/write | |||
| HR | 22doc 4x0023 | CommRate | Baud rate. | UINT16 | Read/write | 0 = 9600; 1 = 19200; 2 = 38400; 3 = 115200 | |||
| HR | 23doc 4x0024 | Parity | UINT16 | Read/write | 0 = None; 1 = Odd; 2 = Even | ||||
| HR | 24doc 4x0025 | Stop Bits | UINT16 | Read/write | 1 = 1; 2 = 2 | ||||
| HR | 25doc 4x0026 | DigIn1 config | UINT16 | Read/write | 0 = Disabled; 1 = Start/stop; 2 = Alarm reset; 3 = MB_IDs_2; 4 = Invert 10-0V; 5 = Rotation; 6 = Firemode; 7 = Motor overheat; 8 = Invert 0-10V; 9 = All stop | ||||
| HR | 26doc 4x0027 | DigIn2 config | UINT16 | Read/write | 0 = Disabled; 1 = TachoOut; 2 = Running; 3 = AlarmOut; 4 = Running spin | ||||
| HR | 28doc 4x0029 | MotorConfigVar | UINT16 | Read/write | |||||
| HR | 29doc 4x0030 | FanConfigVar | UINT16 | Read/write | |||||
| HR | 30doc 4x0031 | DigIn3 config (IOM) | UINT16 | Read/write | 0 = Disabled; 1 = Start/Stop; 2 = Alarm reset; 3 = Disabled; 4 = Invert 10-0V; 5 = Rotation; 6 = Firemode; 8 = Invert 0-10V; 9 = All stop | ||||
| HR | 31doc 4x0032 | DigIn4 config (IOM) | UINT16 | Read/write | 0 = Disabled; 1 = Start/Stop; 2 = Alarm reset; 3 = Disabled; 4 = Invert 10-0V; 5 = Rotation; 6 = Firemode; 8 = Invert 0-10V; 9 = All stop | ||||
| HR | 34doc 4x0035 | AnalogOut1 config (IOM) | UINT16 | Read/write | 0 = Disabled; 1 = ActSpeed | ||||
| HR | 35doc 4x0036 | Thermistor config (IOM) | UINT16 | Read/write | 0 = Disabled; 1 = Motor Overheat PTC | ||||
| HR | 37doc 4x0038 | Thermistor threshold | UINT16 | Ω | Read/write | ||||
| HR | 38doc 4x0039 | Max Windmilling Time | UINT16 | s | Read/write | ||||
| HR | 39doc 4x0040 | AC motor boost current | UINT16 | mA | Read/write |
Notes on this map
- Scales and units are for the EC configuration. In the FC configuration speed values (3x0005, 4x0002, 4x0003) are in 0.01 Hz instead of rpm; this is said in the description of those registers.
- Discrete inputs 26 and 27 are printed with a 0x prefix (0x0027, 0x0028) inside the discrete-input table; they are kept as discrete inputs at the printed addresses.
- Left out: 3x0014 config file variant (two ASCII characters), 3x0019 AOC SW variant (no range or unit), the product name characters 3x2004-3x2012 (the address column switches between decimal and hex there), 4x0033/4x0034 relay configuration and 4x0037 analog input 2 (option tables mostly TBD / N/A).
- Run time is split into minutes (0-1439) and days; energy is split into Wh, kWh and MWh parts. Add the parts yourself.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
What Modbus registers does the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) have?
This map lists 106 registers: 16 coils, 26 discrete inputs, 34 input registers, 30 holding registers. 46 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table prints the reference (0x0001, 1x0001, 3x0001, 4x0001) and the protocol address next to it; the address column is the reference number minus 1 (4x0001 = address 0). The address column is used here.
What are the minimum Modbus registers to integrate the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)?
Start with CO 0 Motor ON/OFF (Motor on/off); CO 7 Control (Speed source Modbus or 0-10 V); HR 0 Setpoint / PrcSet (Speed setpoint 0.01 %); IR 3 PrcOut (Actual output %); IR 4 RPMOut (Actual speed); IR 8 Power In (Input power W); DI 10 Internal Stop (Internal stop alarm); CO 1 Reset Alarms (Alarm reset).
How do I enable Modbus control of the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)?
Communication settings are changed with the TBLZ-4-75 hand-held terminal (or the matching holding registers). Coil 7 selects whether speed follows Modbus or the 0-10 V input. Coil 18 can lock the configuration against Modbus writes.
What happens when the Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) loses Modbus communication?
Comm. timeout 0-240 s, factory 10 s (holding register 21). What the fan does on timeout is not described.
Where is the official Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F) Modbus documentation?
The source is Modbus RTU SILVER RX, PX, CX, SD, generation E/F (SILVERCModbus.210809), published free by Swegon at https://www.swegon.com/globalassets/digizuite/12063-en-silverc_modbus_other_en.pdf.
More Swegon Modbus register maps
- Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6)
Other hvac equipment register maps
- Thermostat (fan heater controller)
VTS HMI-VOLCANO EC controller for VOLCANO air heaters
VTS HMI-VOLCANO EC wall controller with Modbus RTU, device integration manual version 1.1.
Also known as: HMI VOLCANO EC, VOLCANO EC controller - Air curtain controller (Air handler / door heater)
Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
Berner air curtains with the IntelliSwitch Gen 5 control and the AIR BMS package; register document 3.1.0212 (January 2025).
Also known as: IntelliSwitch Gen 5, Berner AIR BMS, AIR BMS Package - Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)
DriSteem humidifiers with the earlier Vapor-logic version 5 controller, per IOM form VL5-IOM-0914.
Also known as: Vapor-logic version 5, VL5, Vapor-logic5 - Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat (shelter HVAC lead/lag controller)
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
Marvair CommStat 4 controllers with protocol version 3 or later and software revision 67 or later, read through the Marvair Modbus Interface Adapter.
Also known as: CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272 - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1
All hvac equipment Modbus register maps →
Source: Modbus RTU SILVER RX, PX, CX, SD, generation E/F · SILVERCModbus.210809. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.