  3. Berner
  4. Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)

Air curtain controller (Air handler / door heater) · Modbus register map

Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus register map

Updated 17 November 2026

Short answer

Berner's IntelliSwitch Gen 5 air-curtain control exposes a small Modbus map over RS-485 (RTU or ASCII) and Ethernet/Wi-Fi (TCP). Input registers report door temperature, door switch, heater and motor state, E-stop lock and error codes; holding registers set mode (including a BMS mode), fan speed, target temperature, delays and BMS calls for heat and fan.

This page lists 26 Modbus registers for the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Berner’s own free documentation (linked below) and checked against it.

Manufacturer
Berner
Model
Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
Equipment type
Air curtain controller (Air handler / door heater)
Registers
26 (9 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
IntelliSwitch Gen 5, Berner AIR BMS, AIR BMS Package
Source document
Berner AIR BMS Package - Modbus Registers · 3.1.0212 · rev. 2025-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)

Integration in brief

Put the controller in BMS mode (holding 101 = 5), then drive it with call for heat (107) and call for fan (108). Monitor door temperature (input 1), door switch (3), heater and motor state (6, 7) and E-stop (11).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100ModeINT16Mode (5 = BMS)Read/write
HR 106Call for heat (BMS mode)INT16Call for heat in BMS modeRead/write
HR 107Call for fan (BMS mode)INT16Call for fan in BMS modeRead/write
HR 102Target temperature (°C)INT16Target temperature °CRead/write
IR 0Temperature at the door (°C)INT16Door temperature °CRead
IR 2Door switch statusINT16Door switchRead
IR 10E-stop lockedINT16E-stop lockedRead

Enable Modbus control & writes

The document points to the IntelliSwitch Gen 5 Quick Start Guide or the Berner app for Ethernet setup; it does not say where the serial settings are made.

Communication loss & watchdog

The serial settings include a timeout of 1-999 s; the document does not say what it does.

Byte order & addressing

Network setup

Watch out for

Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

26 of 26 shown
Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 1Temperature at the door (°C)INT16× 0.1°CRead
IR1doc 2Temperature at the door (°F)INT16× 0.1°FRead
IR2doc 3Door switch statusINT16Read0 = Closed; 1 = Open
IR3doc 4Door open count since midnightINT16Read
IR4doc 5External thermostat statusINT16Read0 = Off; 1 = On
IR5doc 6Heater statusINT16Read0 = Off; 1 = On
IR6doc 7Motor stateINT16Read0 = Off; 1 = Low; 2 = Default
IR7doc 8Motor speedINT16rpmRead
IR8doc 9Number of available motor speedsINT16Read
IR9doc 10Heating supportedINT16Read0 = No; 1 = Yes
IR10doc 11E-stop lockedWhen 1, marked holding registers reset to 0 and become read-only.INT16Read0 = No; 1 = Yes
IR200doc 201Error code 1INT16Read
IR201doc 202Error code 2INT16Read
IR202doc 203Error code 3INT16Read
IR203doc 204Error code 4INT16Read
IR204doc 205Error code 5INT16Read
IR205doc 206Error code 6INT16Read
HR100doc 101ModeLocked while E-stop is active.INT16Read/write0 = Off; 1 = On; 2 = Auto; 4 = Comfort+; 5 = BMS
HR101doc 102Fan speed1 to N, where N is the number of speeds (1, 2, 3 or 10).INT16Read/write
HR102doc 103Target temperature (°C)INT16× 0.1°CRead/write
HR103doc 104Target temperature (°F)INT16× 0.1°FRead/write
HR104doc 105Time delayINT16sRead/write
HR105doc 106Cool down delayINT16sRead/write
HR106doc 107Call for heat (BMS mode)Locked while E-stop is active.INT16Read/write0 = No; 1 = Yes
HR107doc 108Call for fan (BMS mode)Locked while E-stop is active.INT16Read/write0 = No; 1 = Yes
HR108doc 109Heater disabledINT16Read/write0 = No; 1 = Yes

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)

What Modbus registers does the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) have?

This map lists 26 registers: 17 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Berner lists addresses from 1 and says to send the offset from address 1: address 101 is requested as 100. Input and holding registers use separate address ranges (1-11/201-206 and 101-109).

What are the minimum Modbus registers to integrate the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)?

Start with HR 100 Mode (Mode (5 = BMS)); HR 106 Call for heat (BMS mode) (Call for heat in BMS mode); HR 107 Call for fan (BMS mode) (Call for fan in BMS mode); HR 102 Target temperature (°C) (Target temperature °C); IR 0 Temperature at the door (°C) (Door temperature °C); IR 2 Door switch status (Door switch); IR 10 E-stop locked (E-stop locked).

How do I enable Modbus control of the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)?

The document points to the IntelliSwitch Gen 5 Quick Start Guide or the Berner app for Ethernet setup; it does not say where the serial settings are made.

What happens when the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) loses Modbus communication?

The serial settings include a timeout of 1-999 s; the document does not say what it does.

Where is the official Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus documentation?

The source is Berner AIR BMS Package - Modbus Registers (3.1.0212), revision 2025-01, published free by Berner at https://berner.com/wp-content/uploads/2025/07/Berner-AIR-BMS-Modbus-Registers-3.1.0212.pdf.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Berner AIR BMS Package - Modbus Registers · 3.1.0212 · rev. 2025-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.