- Home
- Modbus register maps
- Berner
- Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
Air curtain controller (Air handler / door heater) · Modbus register map
Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus register map
Updated 17 November 2026
Berner's IntelliSwitch Gen 5 air-curtain control exposes a small Modbus map over RS-485 (RTU or ASCII) and Ethernet/Wi-Fi (TCP). Input registers report door temperature, door switch, heater and motor state, E-stop lock and error codes; holding registers set mode (including a BMS mode), fan speed, target temperature, delays and BMS calls for heat and fan.
This page lists 26 Modbus registers for the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Berner’s own free documentation (linked below) and checked against it.
- Manufacturer
- Berner
- Model
- Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
- Equipment type
- Air curtain controller (Air handler / door heater)
- Registers
- 26 (9 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- IntelliSwitch Gen 5, Berner AIR BMS, AIR BMS Package
Integration notes: Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
Put the controller in BMS mode (holding 101 = 5), then drive it with call for heat (107) and call for fan (108). Monitor door temperature (input 1), door switch (3), heater and motor state (6, 7) and E-stop (11).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | Mode | INT16 | Mode (5 = BMS) | Read/write |
| HR 106 | Call for heat (BMS mode) | INT16 | Call for heat in BMS mode | Read/write |
| HR 107 | Call for fan (BMS mode) | INT16 | Call for fan in BMS mode | Read/write |
| HR 102 | Target temperature (°C) | INT16 | Target temperature °C | Read/write |
| IR 0 | Temperature at the door (°C) | INT16 | Door temperature °C | Read |
| IR 2 | Door switch status | INT16 | Door switch | Read |
| IR 10 | E-stop locked | INT16 | E-stop locked | Read |
Enable Modbus control & writes
The document points to the IntelliSwitch Gen 5 Quick Start Guide or the Berner app for Ethernet setup; it does not say where the serial settings are made.
Communication loss & watchdog
The serial settings include a timeout of 1-999 s; the document does not say what it does.
Byte order & addressing
- Input and holding registers do not share addresses, by design.
- Temperatures exist in both °C and °F registers.
Network setup
- RS-485 for RTU/ASCII; Ethernet or Wi-Fi for TCP (DHCP by default).
Watch out for
- While E-stop locked (input 11) is 1, mode and the BMS call registers are forced to 0 and read-only.
Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 1 | Temperature at the door (°C) | INT16 | × 0.1 | °C | Read | |||
| IR | 1doc 2 | Temperature at the door (°F) | INT16 | × 0.1 | °F | Read | |||
| IR | 2doc 3 | Door switch status | INT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 3doc 4 | Door open count since midnight | INT16 | Read | |||||
| IR | 4doc 5 | External thermostat status | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 5doc 6 | Heater status | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 6doc 7 | Motor state | INT16 | Read | 0 = Off; 1 = Low; 2 = Default | ||||
| IR | 7doc 8 | Motor speed | INT16 | rpm | Read | ||||
| IR | 8doc 9 | Number of available motor speeds | INT16 | Read | |||||
| IR | 9doc 10 | Heating supported | INT16 | Read | 0 = No; 1 = Yes | ||||
| IR | 10doc 11 | E-stop locked | When 1, marked holding registers reset to 0 and become read-only. | INT16 | Read | 0 = No; 1 = Yes | |||
| IR | 200doc 201 | Error code 1 | INT16 | Read | |||||
| IR | 201doc 202 | Error code 2 | INT16 | Read | |||||
| IR | 202doc 203 | Error code 3 | INT16 | Read | |||||
| IR | 203doc 204 | Error code 4 | INT16 | Read | |||||
| IR | 204doc 205 | Error code 5 | INT16 | Read | |||||
| IR | 205doc 206 | Error code 6 | INT16 | Read | |||||
| HR | 100doc 101 | Mode | Locked while E-stop is active. | INT16 | Read/write | 0 = Off; 1 = On; 2 = Auto; 4 = Comfort+; 5 = BMS | |||
| HR | 101doc 102 | Fan speed | 1 to N, where N is the number of speeds (1, 2, 3 or 10). | INT16 | Read/write | ||||
| HR | 102doc 103 | Target temperature (°C) | INT16 | × 0.1 | °C | Read/write | |||
| HR | 103doc 104 | Target temperature (°F) | INT16 | × 0.1 | °F | Read/write | |||
| HR | 104doc 105 | Time delay | INT16 | s | Read/write | ||||
| HR | 105doc 106 | Cool down delay | INT16 | s | Read/write | ||||
| HR | 106doc 107 | Call for heat (BMS mode) | Locked while E-stop is active. | INT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 107doc 108 | Call for fan (BMS mode) | Locked while E-stop is active. | INT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 108doc 109 | Heater disabled | INT16 | Read/write | 0 = No; 1 = Yes |
Notes on this map
- All registers are signed 16-bit (INT16); temperatures are x10 (215 = 21.5 °C).
- Serial settings are configurable (300-115200 bps, 5-8 data bits, 1-2 stop bits, none/odd/even/space/mark parity, ID 1-247, timeout 1-999 s with no stated purpose); the document does not state factory defaults. TCP defaults to DHCP and port 502.
- Error code registers 201-206 hold codes without a code list in this document.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)
What Modbus registers does the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) have?
This map lists 26 registers: 17 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Berner lists addresses from 1 and says to send the offset from address 1: address 101 is requested as 100. Input and holding registers use separate address ranges (1-11/201-206 and 101-109).
What are the minimum Modbus registers to integrate the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)?
Start with HR 100 Mode (Mode (5 = BMS)); HR 106 Call for heat (BMS mode) (Call for heat in BMS mode); HR 107 Call for fan (BMS mode) (Call for fan in BMS mode); HR 102 Target temperature (°C) (Target temperature °C); IR 0 Temperature at the door (°C) (Door temperature °C); IR 2 Door switch status (Door switch); IR 10 E-stop locked (E-stop locked).
How do I enable Modbus control of the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)?
The document points to the IntelliSwitch Gen 5 Quick Start Guide or the Berner app for Ethernet setup; it does not say where the serial settings are made.
What happens when the Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) loses Modbus communication?
The serial settings include a timeout of 1-999 s; the document does not say what it does.
Where is the official Berner Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package) Modbus documentation?
The source is Berner AIR BMS Package - Modbus Registers (3.1.0212), revision 2025-01, published free by Berner at https://berner.com/wp-content/uploads/2025/07/Berner-AIR-BMS-Modbus-Registers-3.1.0212.pdf.
Other hvac equipment register maps
- Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 5 humidifier controller (Modbus RTU)
DriSteem humidifiers with the earlier Vapor-logic version 5 controller, per IOM form VL5-IOM-0914.
Also known as: Vapor-logic version 5, VL5, Vapor-logic5 - Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat (shelter HVAC lead/lag controller)
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
Marvair CommStat 4 controllers with protocol version 3 or later and software revision 67 or later, read through the Marvair Modbus Interface Adapter.
Also known as: CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272 - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3
All hvac equipment Modbus register maps →
Source: Berner AIR BMS Package - Modbus Registers · 3.1.0212 · rev. 2025-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.