Neptronic TSUB Series universal wall-mount controller (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The TSUB is a Neptronic wall-mount room controller with built-in sensing and configurable analog, binary and universal I/O for fan coils and similar terminal HVAC equipment. Over Modbus RTU it exposes room and external temperatures, humidity, CO2 and pressure readings, heating/cooling ramp demands, output states, mode, fan and setpoint control, VFD and 6-way-valve settings, and its configuration registers.

This page lists 157 Modbus registers for the Neptronic TSUB Series universal wall-mount controller (Modbus RTU) — 126 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
TSUB Series universal wall-mount controller (Modbus RTU)
Equipment type
Thermostat / fan coil and unitary controller
Registers
157 (126 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
TSUB Series, TSUB universal wall-mount controller
Source document
TSUB Series Universal Wall-Mount Controller Modbus Communication Module User Guide · TSUB-Modbus Guide-250829 (V1.13) · rev. 2025-08-29
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic TSUB Series universal wall-mount controller (Modbus RTU)

Integration in brief

Read holding registers with function 03 at the wire address shown in the guide's Protocol Address column (Modicon 40001 = address 0). Set the temperature unit for Modbus first, then use the mode, fan and setpoint registers for control.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 11Internal temperature sensor readingINT16Internal (room) temperature x100Read
HR 14Control temperature readingINT16Control temperature x100Read/write
HR 41System mode statusUINT16System modeRead/write
HR 42Fan speed selection by userUINT16Fan speedRead/write
HR 43Temperature setpoint in occupancy or day modeINT16Occupied setpoint x10Read/write
HR 26Actual heating demand of ramp 1UINT16Heating demand ramp 1Read
HR 28Actual cooling demand of ramp 1UINT16Cooling demand ramp 1Read
HR 9System Status 1BITMAP16Status 1Read
HR 10System Status 2BITMAP16Status 2 (alarms)Read
HR 44System option1BITMAP16System option 1 (bit 1 = Modbus temp unit)Read/write

Enable Modbus control & writes

Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.

Byte order & addressing

Network setup

Watch out for

Neptronic TSUB Series universal wall-mount controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

157 of 157 shown
Neptronic TSUB Series universal wall-mount controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Address - Neptronic ID and Modbus address of current deviceUINT16Read/write
HR1doc 40002Baud rate (baud / 100)0 = automatic detection.UINT16× 100Read/write
HR2doc 40003Communication port configurationUINT16Read/write1 = No parity, 2 Stop bits; 2 = Even parity, 1 stop bit; 3 = Odd parity, 1 stop bit
HR7doc 40008Controller Product_Version, actual firmware versionUINT16Read
HR8doc 40009Controller parameters versionUINT16Read
HR9doc 40010System Status 1BITMAP16Readbit 0 = System operation (0 = Normal, 1 = Fault); bit 2 = System override by NSB or OCC (0 = Normal, 1 = OFF); bit 3 = ChangeOverMode (0 = Cooling, 1 = Heating); bit 4 = AL_FlowSwitch (0 = No alarm, 1 = Alarm activated); bit 6 = AL_DirtyFilter (0 = No alarm, 1 = Alarm activated)
HR10doc 40011System Status 2BITMAP16Readbit 0 = Selector Switch Status (0 = Remote Mode, 1 = Local Mode); bit 2 = CO2 Alarm (0 = Normal, 1 = Alarm); bit 7 = AL_Override (0 = Off, 1 = On); bit 8 = AL_WindowOpened (0 = Off, 1 = On); bit 9 = AL_DoorOpened (0 = Off, 1 = On); bit 10 = AL_UI1 (0 = Off, 1 = On); bit 11 = AL_UI2 (0 = Off, 1 = On); bit 15 = AL_OverHeat (0 = Off, 1 = On)
HR11doc 40012Internal temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead
HR12doc 40013External temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead
HR13doc 40014Changeover temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead
HR14doc 40015Control temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR15doc 40016Internal humidity sensor reading.Not on every model.UINT16× 0.1%RHRead
HR16doc 40017External humidity sensor readingUINT16× 0.1%RHRead
HR17doc 40018Analog input 1 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR18doc 40019Analog input 2 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR21doc 40022External CO2 sensor value in ppmINT16ppmRead
HR23doc 40024CO2 control value in ppmINT16ppmRead
HR24doc 40025Actual system occupancy stateUINT16Read1 = NoOccupancy; 2 = Occupancy; 3 = Override
HR25doc 40026Actual night setback state of the systemUINT16Read1 = Day; 2 = Night; 3 = Override
HR26doc 40027Actual heating demand of ramp 1UINT16× 0.1%Read
HR27doc 40028Actual heating demand of ramp 2UINT16× 0.1%Read
HR28doc 40029Actual cooling demand of ramp 1UINT16× 0.1%Read
HR29doc 40030Actual cooling demand of ramp 2UINT16× 0.1%Read
HR30doc 40031Actual changeover demandUINT16× 0.1%Read
HR31doc 40032Actual fan demandUINT16× 0.1%Read
HR32doc 40033Actual dehumidification demandUINT16× 0.1%Read
HR33doc 40034Actual humidification demandUINT16× 0.1%Read
HR34doc 40035Cooling/heating switch timer countdownUINT16sRead
HR36doc 40037Analog output 2 valuePercent of control or electrical range, per system option 4 bit 12.UINT16× 0.1%Read/write
HR37doc 40038Analog output 3 valuePercent of control or electrical range, per system option 4 bit 12.UINT16× 0.1%Read/write
HR39doc 40040Binary output - 6 relays output statusBITMAP16Read/writebit 2 = Binary Output 3 (0 = Open, 1 = Close); bit 3 = Binary Output 4 (0 = Open, 1 = Close); bit 4 = Binary Output 5 (0 = Open, 1 = Close); bit 5 = Binary Output 6 (0 = Open, 1 = Close); bit 6 = Binary Output 7 (0 = Open, 1 =Close)
HR40doc 40041System commandBITMAP16Read/writebit 0 = Cfg_ServiceDisplayAddress (0 = Normal, 1 = Display address on LCD); bit 1 = Cfg_CoolingRampLock (0 = Off, 1 = On); bit 3 = Cfg_HeatingRamp1Lock (0 = Off, 1 = On); bit 4 = Cfg_HeatingRamp2Lock (0 = Off, 1 = On); bit 5 = Cfg_ChangeOverRampLock (0 = Off, 1 = On); bit 7 = Cfg_HumidifyRampLock (0 = Off, 1 = On); bit 8 = Cfg_DehumidifyRampLock (0 = Off, 1 = On)
HR41doc 40042System mode statusEach mode is only accepted when the system control mode and option bits allow it.UINT16Read/write1 = Auto; 2 = Heating; 3 = Emergency heat (EMH); 4 = Cooling; 5 = Fan; 6 = Off
HR42doc 40043Fan speed selection by userUINT16Read/write1 = Auto; 2 = Low; 3 = Med; 4 = High
HR43doc 40044Temperature setpoint in occupancy or day modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR44doc 40045System option1BITMAP16Read/writebit 0 = Cfg_TempUnitTstat (0 = °C, 1 = °F); bit 1 = Cfg_TempUnitModbus (0 = °C, 1 = °F); bit 2 = Cfg_TempSetPointLock (0 = Off, 1 = On); bit 3 = Cfg_HumSetPointLock (0 = Off, 1 = On); bit 4 = Cfg_ProgramModeLock (0 = Off, 1 = On); bit 5 = AL_FreezeProtection (0 = Off, 1 = On); bit 6 = Cfg_UserSysOffModes (0 = Enable, 1 = Disable); bit 7 = Cfg_KeyPadBottomLeftLock (0 = Off, 1 = On); bit 8 = Cfg_KeyPadUpperLeftLock (0 = Off, 1 = On); bit 9 = Cfg_KeyPadArrowsLock (0 = Off, 1 = On); bit 10 = Cfg_UserFanAutoMode (0 = Enable, 1 = Disable); bit 11 = Cfg_ NightOrNoOccMode (0 = Setpoint, 1 = OFF); bit 12 = Cfg_HumControlSource (0 = Intern Sensor, 1 = Extern Sensor Not available on all models.); bit 13 = Time Mode (0 = 24h, 1 = 12h); bit 14 = Cfg_WindowOpenedMode (0 = Setpoint, 1 = OFF); bit 15 = Cfg_DoorOpenedMode (0 = Setpoint, 1 = OFF)
HR45doc 40046System option2BITMAP16Read/writebit 0 = Baud Rate (0 = Auto, 1 = Manual); bit 1 = Cfg_ActivateSchedule (0 = Off, 1 = On); bit 3 = Cfg_AnalogOutput2Direction (0 = Direct, 1 = Reverse); bit 4 = Cfg_AnalogOutput3Direction (0 = Direct, 1 = Reverse); bit 8 = Cfg_BinaryOutput3Direction (0 = Direct, 1 = Reverse); bit 9 = Cfg_BinaryOutput4Direction (0 = Direct, 1 = Reverse); bit 10 = Cfg_BinaryOutput5Direction (0 = Direct, 1 = Reverse); bit 11 = Cfg_BinaryOutput6Direction (0 = Direct, 1 = Reverse); bit 12 = Cfg_ FanSpeedOption (0 = Standard, 1 = Advanced (OE1)); bit 13 = Cfg_UserSysFanMode (0 = Disable, 1 = Enable); bit 14 = Cfg_HideFanDisplay (0 = No, 1 = Yes)
HR46doc 40047System option3BITMAP16Read/writebit 0 = DAYLIGHT_SAVINGS_STATUS (0 = Normal, 1 = Summer); bit 6 = Cfg_AnalogInput1MinVolt (0 = 0.0 Volt, 1 = 2.0 Volt); bit 7 = Cfg_AnalogInput2MinVolt (0 = 0.0 Volt, 1 = 2.0 Volt); bit 13 = Cfg_FloatingBO3/BO7Direction (0 = Direct, 1 = Reverse); bit 15 = Cfg_DeltaTempLogic (0 = Off, 1 = On)
HR47doc 40048System option4BITMAP16Read/writebit 0 = Cfg_CO2ControlSource (0 = Internal Sensor, 1 = External Sensor); bit 1 = Cfg_DisplayHumidity (0 = Display the temperature only, 1 = Display the temperature and humidity); bit 2 = Cfg_DisplayCO2 (0 = Don’t display CO2 control value, 1 = Display CO2 control value); bit 6 = Cfg_VFDTempSetpointSource (0 = VFDTempSetpoint, 1 = TempSetpoint); bit 8 = Cfg_AnalogOutput2OffVoltage (0 = Off, 1 = Minimum); bit 9 = Cfg_AnalogOutput3OffVoltage (0 = Off, 1 = Minimum); bit 12 = Cfg_AnalogOutputRatio (0 = Control Range, 1 = Electrical Range)
HR48doc 40049Display informationUINT16Read/write1 = Temperature and Demand; 2 = Setpoint and Demand; 3 = Temperature Only; 4 = Setpoint Only; 5 = Off
HR49doc 40050Temperature control sourceUINT16Read/write1 = Network Temp; 2 = Intern Temp; 3 = Extern Temp
HR50doc 40051Network fallback timeoutUINT16minRead/write
HR51doc 40052Minimum occupancy/day setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR52doc 40053Maximum occupancy/day setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR53doc 40054Cooling temperature setpoint in unoccupied or night modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR54doc 40055Heating temperature setpoint in unoccupied or night modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR55doc 40056Heating proportional band for ramp 1Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR56doc 40057Heating proportional band for ramp 2Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR57doc 40058Cooling proportional band for ramp 1Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR58doc 40059Cooling proportional band for ramp 2Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR59doc 40060Changeover proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR60doc 40061Heating deadband for ramp 1Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR61doc 40062Heating deadband for ramp 2Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR62doc 40063Cooling deadband for ramp 1Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR63doc 40064Cooling deadband for ramp 2Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR64doc 40065Changeover deadbandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR65doc 40066Changeover setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR66doc 40067Fan time out in secondsUINT16sRead/write
HR67doc 40068Fan damping factor in secondsUINT16sRead/write
HR68doc 40069Heating integral time factor in secondsUINT16sRead/write
HR69doc 40070Cooling integral time factor in secondsUINT16sRead/write
HR70doc 40071Cooling Heating SwitchTimer - Delay between cool and heat or vice versaUINT16minRead/write
HR71doc 40072Cooling anticycle delay in minutesUINT16minRead/write
HR72doc 40073NSB override delay in minutesUINT16minRead/write
HR73doc 40074Unoccupied override delay in minutesUINT16minRead/write
HR74doc 40075Occupancy minimum time in minutesUINT16minRead/write
HR75doc 40076Unoccupied override delay countdown in minutesUINT16minRead/write
HR76doc 40077Fan mode (speed) in unoccupied or NSB modeUINT16Read/write1 = Low; 2 = Med; 3 = High; 4 = Auto
HR77doc 40078Fan mode (speed) when window is opened (alarm)UINT16Read/write1 = Low; 2 = Med; 3 = High; 4 = Auto
HR78doc 40079Fan mode (speed) when door is opened (alarm)UINT16Read/write1 = Low; 2 = Med; 3 = High; 4 = Auto
HR79doc 40080System control modeUINT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 4 = Heat or Cool; 5 = Auto Lock
HR80doc 40081Override System occupancy/NSB modeUINT16Read/write1 = Locally; 2 = OFF; 3 = Occupied; 4 = Unoccupied; 5 = Day; 6 = Night
HR81doc 40082Internal temperature sensor offset correctionUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR82doc 40083Universal Input 1 signalUINT16Read/write1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy binary input; 10 = NSB binary input; 11 = Override binary input; 12 = Window binary input; 13 = Door binary input; 14 = Dirty Filter binary input; 15 = Flow switch binary input; 16 = OverHeat binary input; 17 = Selector switch binary input; 18 = Fan Feedback; 19 = Humidity sensor 0-10V; 20 = Pressure sensor 0-10V; 21 = Extern sensor TT-012; 22 = Delta T Inlet 10K; 23 = Delta T Inlet 0-10V; 24 = Delta T Outlet 10K; 25 = Delta T Outlet 0-10V
HR83doc 40084Universal Input 2 signalUINT16Read/write1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy binary input; 10 = NSB binary input; 11 = Override binary input; 12 = Window binary input; 13 = Door binary input; 14 = Dirty Filter binary input; 15 = Flow switch binary input; 16 = OverHeat binary input; 17 = Selector switch binary input; 18 = Fan Feedback; 19 = Humidity sensor 0-10V; 20 = Pressure sensor 0-10V; 21 = Extern sensor TT-012; 22 = Delta T Inlet 10K; 23 = Delta T Inlet 0-10V; 24 = Delta T Outlet 10K; 25 = Delta T Outlet 0-10V
HR86doc 40087External temperature sensor offset correctionUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR87doc 40088Changeover control modeUINT16Read/write1 = Local; 2 = Cool; 3 = Heat
HR88doc 40089Minimum external temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR89doc 40090Maximum external temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR90doc 40091Maximum CO2 readingINT16ppmRead/write
HR91doc 40092Alarm level of CO2INT16ppmRead/write
HR92doc 40093Fan output signalUINT16Read/write1 = 1 speed; 2 = 2 speeds; 3 = 3 speeds; 4 = Analog
HR96doc 40097Ramp to control analog output 2UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 Way Valve; 12 = Delta temperature; 13 = VFD/ECMTempLoopEnable; 14 = VFD Pressure Loop; 15 = FAN
HR97doc 40098Minimum voltage for analog output 2 (volt)UINT16× 0.1VRead/write
HR98doc 40099Maximum voltage for analog output 2 (volt)UINT16× 0.1VRead/write
HR100doc 40101Minimum voltage for analog output 3 (volt)UINT16× 0.1VRead/write
HR101doc 40102Maximum voltage for analog output 3 (volt)UINT16× 0.1VRead/write
HR105doc 40106Position of CH1 AO output while heating (%)UINT16%Read/write
HR114doc 40115Ramp to control binary output 3UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm
HR115doc 40116Delay before activation of BO3 in minutesUINT16minRead/write
HR116doc 40117Close position percentage for contact BO3UINT16%Read/write
HR117doc 40118Open position percentage for contact BO3UINT16%Read/write
HR118doc 40119Ramp to control binary output 4UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN
HR119doc 40120Delay before activation of BO4 in minutesUINT16minRead/write
HR120doc 40121Close position percentage for contact BO4UINT16%Read/write
HR121doc 40122Open position percentage for contact BO4UINT16%Read/write
HR122doc 40123Ramp to control binary output 5UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN
HR123doc 40124Delay before activation of BO5 in minutesUINT16minRead/write
HR124doc 40125Close position percentage for contact BO5UINT16%Read/write
HR125doc 40126Open position percentage for contact BO5UINT16%Read/write
HR126doc 40127Ramp to control binary output 6UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 Way valve; 12 = Delta temperature; 13 = FAN (available only if fan type is 1-2-3 speeds); 14 = VFD/ECMTempLoopEnable; 15 = VFD Pressure Loop
HR127doc 40128Delay before activation of BO6 in minutesUINT16minRead/write
HR128doc 40129Close position percentage for contact BO6UINT16%Read/write
HR129doc 40130Open position percentage for contact BO6UINT16%Read/write
HR130doc 40131Ramp to control binary output 7UINT16Read/write1 = Off; 2 = Change Over with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm
HR131doc 40132Delay before activation of BO7 in minutesUINT16minRead/write
HR132doc 40133Close position percentage for contact BO7UINT16%Read/write
HR133doc 40134Open position percentage for contact BO7UINT16%Read/write
HR134doc 40135Input contact of analog input 1 and 2BITMAP16Read/writebit 0 = Analog input 1 (0 = Normally Open, 1 = Normally Close); bit 1 = Analog input 2 (0 = Normally Open, 1 = Normally Close)
HR135doc 40136Delay before activation of UI1 in secondsUINT16sRead/write
HR136doc 40137Delay before activation of UI2 in secondsUINT16sRead/write
HR139doc 40140Humidity control mode statusUINT16Read/write1 = Auto; 2 = Dehumidification; 3 = Humidification; 4 = Off
HR140doc 40141Humidity setpoint (%RH) in occupancy or day modeUINT16× 0.1%RHRead/write
HR141doc 40142Dehumidification setpoint (%RH) in unoccupied or night modeUINT16× 0.1%RHRead/write
HR142doc 40143Humidification setpoint (%RH) in unoccupied or night modeUINT16× 0.1%RHRead/write
HR143doc 40144Minimum user setpointUINT16× 0.1%RHRead/write
HR144doc 40145Maximum user setpointUINT16× 0.1%RHRead/write
HR145doc 40146Humidity proportional bandUINT16× 0.1%RHRead/write
HR146doc 40147Humidity deadbandUINT16× 0.1%RHRead/write
HR147doc 40148Internal humidity sensor offset correctionNot on every model.INT16× 0.1%RHRead/write
HR148doc 40149External humidity sensor offset correctionINT16× 0.1%RHRead/write
HR149doc 40150Pressure sensor value in PascalsUINT16PaRead
HR150doc 40151Maximum pressure value rangeUINT16PaRead/write
HR151doc 40152Actual VFD pressure loop x 10 (%)UINT16× 0.1%Read
HR152doc 40153VFD pressure loop setpointUINT16PaRead/write
HR153doc 40154VFD pressure loop deadbandUINT16PaRead/write
HR154doc 40155VFD pressure loop proportional bandUINT16PaRead/write
HR155doc 40156VFD pressure loop integral timeUINT16sRead/write
HR156doc 40157Actual VFD temperature loop while cooling x 10 (%)UINT16× 0.1%Read
HR157doc 40158Actual VFD temperature loop while heating x 10 (%)UINT16× 0.1%Read
HR158doc 40159VFD temperature loop setpoint x 10 (ºC or ºF)Unit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR159doc 40160VFD temperature loop deadband x 10 (ºC or ºF)Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR160doc 40161VFD temperature loop proportional band x 10 (ºC or ºF)Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR161doc 40162VFD temperature loop integral timeUINT16sRead/write
HR162doc 40163Voltage required for closing the 6-way valveUINT16× 0.01VRead/write
HR163doc 40164Minimum output voltage required for cooling for the 6-way valveUINT16× 0.01VRead/write
HR164doc 40165Minimum output voltage required for heating for the 6-way valveUINT16× 0.01VRead/write
HR165doc 401666-way valve size selection in inchesUINT16Read/write1 = 1/2; 2 = 3/4; 3 = 1
HR167doc 40168Signal type for Analog output 2UINT16Read/write1 = Analog; 2 = On-Off; 3 = Pulsing
HR168doc 40169Signal type for Analog output 3UINT16Read/write1 = Analog; 2 = On-Off; 3 = Pulsing
HR172doc 40173Signal type for Binary output 3UINT16Read/write1 = Pulsing; 2 = On-Off; 3 = Floating
HR173doc 40174Signal type for Binary output 4UINT16Read/write1 = Pulsing; 2 = On-Off
HR174doc 40175Signal type for Binary output 5UINT16Read/write1 = Pulsing; 2 = On-Off
HR175doc 40176Signal type for Binary output 6UINT16Read/write1 = Pulsing; 2 = On-Off
HR176doc 40177Signal type for Binary output 7UINT16Read/write1 = Pulsing; 2 = On-Off
HR177doc 40178PIR Relay sensorUINT16Read/write0 = Relay was not activated; 1 = Relay was activated
HR179doc 40180Floating output motor timing for BO3/BO7UINT16sRead/write
HR199doc 40200User backlight or contrast intensityUINT16%Read/write
HR200doc 40201Occupancy backlight or contrast intensityUINT16%Read/write
HR201doc 40202Unoccupancy backlight or contrast intensityUINT16%Read/write
HR202doc 40203Configuration value to select the source for VFD temperature controlUINT16Read/write1 = InternSensor; 2 = ExternSensor; 3 = ExternSensor2
HR203doc 40204External Temperature sensor 2 readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead
HR204doc 40205Configuration value used to calibrate External Temp Sensor 2 offsetUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR205doc 40206External Temp 2 reading minimum value for voltage sensorUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR206doc 40207External Temp 2 reading maximum value for voltage sensorUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR208doc 40209AO2 voltage present valueINT16× 0.01VRead
HR209doc 40210AO3 voltage present valueINT16× 0.01VRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic TSUB Series universal wall-mount controller (Modbus RTU)

What Modbus registers does the Neptronic TSUB Series universal wall-mount controller (Modbus RTU) have?

This map lists 157 registers: 157 holding registers. 126 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic TSUB Series universal wall-mount controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints both the protocol (wire) address, starting at 0, and the 40001-style notation; e.g. 40046 is protocol address 45. The documented field holds the 4xxxx notation.

What are the minimum Modbus registers to integrate the Neptronic TSUB Series universal wall-mount controller (Modbus RTU)?

Start with HR 11 Internal temperature sensor reading (Internal (room) temperature x100); HR 14 Control temperature reading (Control temperature x100); HR 41 System mode status (System mode); HR 42 Fan speed selection by user (Fan speed); HR 43 Temperature setpoint in occupancy or day mode (Occupied setpoint x10); HR 26 Actual heating demand of ramp 1 (Heating demand ramp 1); HR 28 Actual cooling demand of ramp 1 (Cooling demand ramp 1); HR 9 System Status 1 (Status 1); HR 10 System Status 2 (Status 2 (alarms)); HR 44 System option1 (System option 1 (bit 1 = Modbus temp unit)).

How do I enable Modbus control of the Neptronic TSUB Series universal wall-mount controller (Modbus RTU)?

Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.

Where is the official Neptronic TSUB Series universal wall-mount controller (Modbus RTU) Modbus documentation?

The source is TSUB Series Universal Wall-Mount Controller Modbus Communication Module User Guide (TSUB-Modbus Guide-250829 (V1.13)), revision 2025-08-29, published free by Neptronic at https://www.neptronic.com/controls/PDF/2025/TSUB-Modbus%20Guide-250829%20(V1.13).pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: TSUB Series Universal Wall-Mount Controller Modbus Communication Module User Guide · TSUB-Modbus Guide-250829 (V1.13) · rev. 2025-08-29. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.