Thermostat / heat pump and unitary controller · Modbus register map

Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The TUCB and TUHB are Neptronic wall-mount controllers with built-in sensors, six binary and two analog outputs, for fan coils, heat pumps (with reversing valve and emergency heat options) and other unitary equipment. Over Modbus RTU they expose temperatures, humidity (TUHB), CO2, ramp demands, output states, mode, fan and setpoint control and the configuration registers.

This page lists 133 Modbus registers for the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) — 109 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Equipment type
Thermostat / heat pump and unitary controller
Registers
133 (109 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB
Source document
TUCB & TUHB Series Universal Wall-Mount Controller Modbus Communication Module User Guide · TUXB-Modbus Guide-190515 · rev. 2019-05-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)

Integration in brief

Read holding registers with function 03 at the printed register index minus 40000 (40011 = address 11). Set the temperature unit for Modbus first, then use the mode, fan and setpoint registers for control.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 11Internal temperature sensor readingINT16Internal (room) temperature x100Read
HR 14Control temperature readingINT16Control temperature x100Read/write
HR 36System mode statusUINT16System modeRead/write
HR 37Fan speed selection by userUINT16Fan speedRead/write
HR 38Temperature setpoint in occupancy or day modeINT16Occupied setpoint x10Read/write
HR 23Actual heating demand of ramp 1UINT16Heating demand ramp 1Read
HR 25Actual cooling demand of ramp 1UINT16Cooling demand ramp 1Read
HR 9System Status 1BITMAP16Status 1Read
HR 10System Status 2BITMAP16Status 2 (alarms)Read
HR 39System option 1BITMAP16System option 1 (bit 1 = Modbus temp unit)Read/write

Enable Modbus control & writes

Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.

Byte order & addressing

Network setup

Watch out for

Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

133 of 133 shown
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40000Address - Neptronic ID and Modbus address of current deviceUINT16Read/write
HR1doc 40001Baud rate (baud / 100)0 = automatic detection.UINT16× 100Read/write
HR2doc 40002Communication port configurationUINT16Read/write1 = No parity, 2 Stop bits; 2 = Even parity, 1 stop bit; 3 = Odd parity, 1 stop bit
HR7doc 40007Controller Product_Version, actual firmware versionUINT16Read
HR8doc 40008Controller parameters versionUINT16Read
HR9doc 40009System Status 1BITMAP16Readbit 0 = System operation (0 = Normal, 1 = Fault); bit 2 = System override by NSB or OCC (0 = Normal, 1 = OFF); bit 3 = ChangeOverMode (0 = Cooling, 1 = Heating); bit 4 = AL_FlowSwitch (0 = No alarm, 1 = Alarm activated); bit 6 = AL_DirtyFilter (0 = No alarm, 1 = Alarm activated)
HR10doc 40010System Status 2BITMAP16Readbit 0 = Selector Switch Status (0 = Remote Mode, 1 = Local Mode); bit 2 = CO2 Alarm (0 = Normal, 1 = Alarm); bit 7 = AL_Override (0 = Off, 1 = On); bit 8 = AL_WindowOpened (0 = Off, 1 = On); bit 9 = AL_DoorOpened (0 = Off, 1 = On); bit 10 = AL_BI1 (0 = Off, 1 = On); bit 11 = AL_BI2 (0 = Off, 1 = On); bit 12 = AL_AI1 (0 = Off, 1 = On); bit 13 = AL_AI2 (0 = Off, 1 = On); bit 15 = AL_OverHeat (0 = Off, 1 = On)
HR11doc 40011Internal temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead
HR12doc 40012External temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead
HR13doc 40013Changeover temperature sensor readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead
HR14doc 40014Control temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR15doc 40015Internal humidity sensor readingTUHB24C6X2 only.UINT16× 0.1%RHRead
HR16doc 40016External humidity sensor readingUINT16× 0.1%RHRead
HR17doc 40017Analog input 1 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR18doc 40018Analog input 2 readingVolts or temperature, depending on how the input is configured.INT16× 0.01V / °C / °FRead
HR19doc 40019CO2 sensor value in ppmINT16ppmRead
HR20doc 40020Binary input statuses of 2 binary inputsBITMAP16Readbit 0 = Binary Input 1 (0 = Open, 1 = Close); bit 1 = Binary Input 2 (0 = Open, 1 = Close)
HR21doc 40021Actual system occupancy stateUINT16Read1 = NoOccupancy; 2 = Occupancy; 3 = Override
HR22doc 40022Actual night setback state of the systemUINT16Read1 = Day; 2 = Night; 3 = Override
HR23doc 40023Actual heating demand of ramp 1UINT16× 0.1%Read
HR24doc 40024Actual heating demand of ramp 2UINT16× 0.1%Read
HR25doc 40025Actual cooling demand of ramp 1UINT16× 0.1%Read
HR26doc 40026Actual cooling demand of ramp 2UINT16× 0.1%Read
HR27doc 40027Actual changeover demandUINT16× 0.1%Read
HR28doc 40028Actual fan demandUINT16× 0.1%Read
HR29doc 40029Actual dehumidification demandUINT16× 0.1%Read
HR30doc 40030Actual humidification demandUINT16× 0.1%Read
HR31doc 40031Cooling/heating switch timer countdownUINT16sRead
HR32doc 40032Analog output 1 valueUINT16× 0.1%Read/write
HR33doc 40033Analog output 2 valueUINT16× 0.1%Read/write
HR34doc 40034Binary output - 6 relays output statusBITMAP16Read/writebit 0 = Binary Output 1 (0 = Open, 1 = Close); bit 1 = Binary Output 2 (0 = Open, 1 = Close); bit 2 = Binary Output 3 (0 = Open, 1 = Close); bit 3 = Binary Output 4 (0 = Open, 1 = Close); bit 4 = Binary Output 5 (0 = Open, 1 = Close); bit 5 = Binary Output 6 (0 = Open, 1 = Close)
HR35doc 40035System commandBITMAP16Read/writebit 0 = Cfg_ServiceDisplayAddress (0 = Normal, 1 = Display address on LCD); bit 1 = Cfg_CoolingRampLock (0 = Off, 1 = On); bit 3 = Cfg_HeatingRamp1Lock (0 = Off, 1 = On); bit 4 = Cfg_HeatingRamp2Lock (0 = Off, 1 = On); bit 5 = Cfg_ChangeOverRampLock (0 = Off, 1 = On); bit 7 = Cfg_HumidifyRampLock (0 = Off, 1 = On); bit 8 = Cfg_DehumidifyRampLock (0 = Off, 1 = On)
HR36doc 40036System mode statusEach mode is only accepted when the system control mode and option bits allow it.UINT16Read/write1 = Auto; 2 = Heating; 3 = Emergency heat (EMH); 4 = Cooling; 5 = Fan; 6 = Off
HR37doc 40037Fan speed selection by userUINT16Read/write1 = Auto; 2 = Low; 3 = Med; 4 = High
HR38doc 40038Temperature setpoint in occupancy or day modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR39doc 40039System option 1BITMAP16Read/writebit 0 = Cfg_TempUnitTstat (0 = °C, 1 = °F); bit 1 = Cfg_TempUnitModbus (0 = °C, 1 = °F); bit 2 = Cfg_TempSetPointLock (0 = Off, 1 = On); bit 3 = Cfg_HumSetPointLock (0 = Off, 1 = On); bit 4 = Cfg_ProgramModeLock (0 = Off, 1 = On); bit 7 = AL_FreezeProtection (0 = Off, 1 = On); bit 8 = Cfg_UserSysOffModes (0 = Enable, 1 = Disable); bit 9 = Cfg_KeyPadBottomLeftLock (0 = Off, 1 = On); bit 10 = Cfg_KeyPadUpperLeftLock (0 = Off, 1 = On); bit 11 = Cfg_KeyPadArrowsLock (0 = Off, 1 = On); bit 12 = Cfg_UserFanAutoMode (0 = Enable, 1 = Disable); bit 13 = Cfg_ NightOrNoOccMode (0 = Setpoint, 1 = OFF); bit 14 = Cfg_HumControlSource (0 = Intern Sensor, 1 = Extern Sensor (Writable only if an intern RH option is available) Only available on model TUHB24C6X2.); bit 15 = Time Mode (0 = 24h, 1 = 12h)
HR40doc 40040System option 2BITMAP16Read/writebit 0 = Cfg_WindowOpenedMode (0 = Setpoint, 1 = OFF); bit 1 = Cfg_DoorOpenedMode (0 = Setpoint, 1 = OFF); bit 2 = Baud Rate (0 = Auto, 1 = Manual); bit 3 = Cfg_ActivateSchedule (0 = Off, 1 = On); bit 4 = Cfg_AnalogOutput1Direction (0 = Direct, 1 = Reverse); bit 5 = Cfg_AnalogOutput2Direction (0 = Direct, 1 = Reverse); bit 6 = Cfg_BinaryOutput1Direction (0 = Direct, 1 = Reverse); bit 7 = Cfg_BinaryOutput2Direction (0 = Direct, 1 = Reverse); bit 8 = Cfg_BinaryOutput3Direction (0 = Direct, 1 = Reverse); bit 9 = Cfg_BinaryOutput4Direction (0 = Direct, 1 = Reverse); bit 10 = Cfg_BinaryOutput5Direction (0 = Direct, 1 = Reverse); bit 11 = Cfg_BinaryOutput6Direction (0 = Direct, 1 = Reverse); bit 12 = Cfg_ FanSpeedOption (0 = Standard, 1 = Advanced (OE1)); bit 13 = Cfg_UserSysFanMode (0 = Disable, 1 = Enable); bit 14 = Cfg_HideFanDisplay (0 = N0, 1 = Yes)
HR41doc 40041System option 3BITMAP16Read/writebit 0 = DAYLIGHT_SAVINGS_STATUS (0 = Normal, 1 = Summer); bit 1 = Cfg_EMHOutput (0 = Disable, 1 = Enable); bit 2 = Cfg_ HeatPumpMode (0 = Off (General Unit), 1 = On (HeatPump)); bit 3 = Cfg_ReversingValve (O/B) (0 = O, 1 = B); bit 4 = Cfg_EMHAutoMode (0 = No, 1 = Yes); bit 5 = Cfg_Y2Output (0 = Disable, 1 = Enable)
HR43doc 40043Display informationUINT16Read/write1 = Temperature and Demand; 2 = Setpoint and Demand; 3 = Temperature Only; 4 = Setpoint Only; 5 = Off
HR44doc 40044Temperature control sourceUINT16Read/write1 = Network Temp; 2 = Intern Temp; 3 = Extern Temp
HR45doc 40045Network fallback timeoutUINT16minRead/write
HR46doc 40046Minimum occupancy/day setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR47doc 40047Maximum occupancy/day setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR48doc 40048Cooling temperature setpoint in unoccupied or night modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR49doc 40049Heating temperature setpoint in unoccupied or night modeUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR50doc 40050Heating proportional band for ramp 1Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR51doc 40051Heating proportional band for ramp 2Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR52doc 40052Cooling proportional band for ramp 1Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR53doc 40053Cooling proportional band for ramp 2Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR54doc 40054Changeover proportional bandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR55doc 40055Heating deadband for ramp 1Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR56doc 40056Heating deadband for ramp 2Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR57doc 40057Cooling deadband for ramp 1Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR58doc 40058Cooling deadband for ramp 2Unit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR59doc 40059Changeover deadbandUnit follows the Modbus temperature-unit option (°C or °F).UINT16× 0.1°C / °FRead/write
HR60doc 40060Changeover setpointUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR61doc 40061Fan time out in secondsUINT16sRead/write
HR62doc 40062Fan damping factor in secondsUINT16sRead/write
HR63doc 40063Heating integral time factor in secondsUINT16sRead/write
HR64doc 40064Cooling integral time factor in secondsUINT16sRead/write
HR65doc 40065Delay between cooling and heatingUINT16minRead/write
HR66doc 40066Cooling anticycle delay in minutesUINT16minRead/write
HR67doc 40067NSB override delay in minutesUINT16minRead/write
HR68doc 40068Unoccupied override delay in minutesUINT16minRead/write
HR69doc 40069Occupancy minimum time in minutesUINT16minRead/write
HR70doc 40070Unoccupied override delay count down in minutesUINT16minRead/write
HR71doc 40071Fan mode (speed) in unoccupied or NSB modeUINT16Read/write1 = Low; 2 = Med; 3 = High; 4 = Auto
HR72doc 40072Fan mode (speed) when window is opened (alarm)UINT16Read/write1 = Low; 2 = Med; 3 = High; 4 = Auto
HR73doc 40073Fan mode (speed) when door is opened (alarm)UINT16Read/write1 = Low; 2 = Med; 3 = High; 4 = Auto
HR74doc 40074System control modeUINT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 4 = Heat or Cool; 5 = Auto Lock
HR75doc 40075Override System occupancy/NSB modeUINT16Read/write1 = Locally; 2 = OFF; 3 = Occupied; 4 = Unoccupied; 5 = Day; 6 = Night
HR76doc 40076Internal temperature sensor offset correctionUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR77doc 40077Analog Input 1 signalUINT16Read/write1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy binary input; 10 = NSB binary input; 11 = Override binary input; 12 = Window binary input; 13 = Door binary input; 14 = Dirty Filter binary input; 15 = Flow switch binary input; 16 = OverHeat binary input; 17 = Selector switch binary input; 18 = Humidity sensor 0-10V
HR78doc 40078Analog Input 2 signalUINT16Read/write1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy binary input; 10 = NSB binary input; 11 = Override binary input; 12 = Window binary input; 13 = Door binary input; 14 = Dirty Filter binary input; 15 = Flow switch binary input; 16 = OverHeat binary input; 17 = Selector switch binary input; 18 = Humidity sensor 0-10V
HR79doc 40079External temperature sensor offset correctionUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.01°C / °FRead/write
HR80doc 40080Changeover control modeUINT16Read/write1 = Local; 2 = Cool; 3 = Heat
HR81doc 40081Minimum external temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR82doc 40082Maximum external temperature readingUnit follows the Modbus temperature-unit option (°C or °F).INT16× 0.1°C / °FRead/write
HR83doc 40083Maximum CO2 readingINT16ppmRead/write
HR84doc 40084Alarm level of CO2INT16ppmRead/write
HR85doc 40085Fan output signalUINT16Read/write1 = 1 speed; 2 = 2 speeds; 3 = 3 speeds; 4 = Analog; 5 = VFD
HR86doc 40086Ramp to control analog output 1UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 way valve
HR87doc 40087Minimum voltage for analog output 1 (volt)UINT16× 0.1VRead/write
HR88doc 40088Maximum voltage for analog output 1 (volt)UINT16× 0.1VRead/write
HR89doc 40089Ramp to control analog output 2UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 way valve; 12 = FAN
HR90doc 40090Minimum voltage for analog output 2 (volt)UINT16× 0.1VRead/write
HR91doc 40091Maximum voltage for analog output 2 (volt)UINT16× 0.1VRead/write
HR92doc 40092Position of CH1 AO output while heating (%)UINT16%Read/write
HR93doc 40093Ramp to control binary output 1UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm
HR94doc 40094Delay before activation of BO1 in minutesUINT16minRead/write
HR95doc 40095Close position percentage for contact BO1UINT16%Read/write
HR96doc 40096Open position percentage for contact BO1UINT16%Read/write
HR97doc 40097Ramp to control binary output 2UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm
HR98doc 40098Delay before activation of BO2 in minutesUINT16minRead/write
HR99doc 40099Close position percentage for contact BO2UINT16%Read/write
HR100doc 40100Open position percentage for contact BO2UINT16%Read/write
HR101doc 40101Ramp to control binary output 3UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm
HR102doc 40102Delay before activation of BO3 in minutesUINT16minRead/write
HR103doc 40103Close position percentage for contact BO3UINT16%Read/write
HR104doc 40104Open position percentage for contact BO3UINT16%Read/write
HR105doc 40105Ramp to control binary output 4UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN
HR106doc 40106Delay before activation of BO4 in minutesUINT16minRead/write
HR107doc 40107Close position percentage for contact BO4UINT16%Read/write
HR108doc 40108Open position percentage for contact BO4UINT16%Read/write
HR109doc 40109Ramp to control binary output 5UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN
HR110doc 40110Delay before activation of BO5 in minutesUINT16minRead/write
HR111doc 40111Close position percentage for contact BO5UINT16%Read/write
HR112doc 40112Open position percentage for contact BO5UINT16%Read/write
HR113doc 40113Ramp to control binary output 6UINT16Read/write1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN (only when the fan type is 1, 2 or 3 speeds)
HR114doc 40114Delay before activation of BO6 in minutesUINT16minRead/write
HR115doc 40115Close position percentage for contact BO6UINT16%Read/write
HR116doc 40116Open position percentage for contact BO6UINT16%Read/write
HR117doc 40117Input contact of binary input 1, 2 and analog input 1, 2BITMAP16Read/writebit 0 = Binary input 1 (0 = Normally Open, 1 = Normally Close); bit 1 = Binary input 2 (0 = Normally Open, 1 = Normally Close); bit 2 = Analog input 1 (0 = Normally Open, 1 = Normally Close); bit 3 = Analog input 2 (0 = Normally Open, 1 = Normally Close)
HR118doc 40118Configuration of binary input 1 modeUINT16Read/write1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode); 9 = Change over normally cool; 10 = Change over normally heat; 11 = NSB; 12 = Occupancy
HR119doc 40119Delay before activation of BI1 in secondsUINT16sRead/write
HR120doc 40120Configuration of binary input 2 modeUINT16Read/write1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode); 9 = Change over normally cool; 10 = Change over normally heat; 11 = NSB; 12 = Occupancy
HR121doc 40121Delay before activation of BI2 in secondsUINT16sRead/write
HR122doc 40122Delay before activation of AI1 in secondsUINT16sRead/write
HR123doc 40123Delay before activation of AI2 in secondsUINT16sRead/write
HR124doc 40124Humidity control mode statusUINT16Read/write1 = Auto; 2 = Dehumidification; 3 = Humidification; 4 = Off
HR125doc 40125Humidity setpoint (%RH) in occupancy or day modeUINT16× 0.1%RHRead/write
HR126doc 40126Dehumidification setpoint (%RH) in unoccupied or night modeUINT16× 0.1%RHRead/write
HR127doc 40127Humidification setpoint (%RH) in unoccupied or night modeUINT16× 0.1%RHRead/write
HR128doc 40128Minimum user setpointUINT16× 0.1%RHRead/write
HR129doc 40129Maximum user setpointUINT16× 0.1%RHRead/write
HR130doc 40130Humidity proportional bandUINT16× 0.1%RHRead/write
HR131doc 40131Humidity deadbandUINT16× 0.1%RHRead/write
HR132doc 40132Internal humidity sensor offset correctionTUHB24C6X2 only.INT16× 0.1%RHRead/write
HR133doc 40133External humidity sensor offset correctionINT16× 0.1%RHRead/write
HR134doc 40134Voltage required for closing the 6-way valveUINT16× 0.01VRead/write
HR135doc 40135Minimum output voltage required for cooling for the 6-way valveUINT16× 0.01VRead/write
HR136doc 40136Minimum output voltage required for heating for the 6-way valveUINT16× 0.01VRead/write
HR137doc 401376-way valve size selection in inchesUINT16Read/write1 = 1/2; 2 = 3/4; 3 = 1

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)

What Modbus registers does the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) have?

This map lists 133 registers: 133 holding registers. 109 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. This older guide prints a "Register Index" with a 4 prefix starting at 40000. Its introduction places the device address at holding register index 0 and the baud rate at index 1, which the table shows as 40000 and 40001, so wire address = printed number - 40000 (not the usual 40001 rule).

What are the minimum Modbus registers to integrate the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)?

Start with HR 11 Internal temperature sensor reading (Internal (room) temperature x100); HR 14 Control temperature reading (Control temperature x100); HR 36 System mode status (System mode); HR 37 Fan speed selection by user (Fan speed); HR 38 Temperature setpoint in occupancy or day mode (Occupied setpoint x10); HR 23 Actual heating demand of ramp 1 (Heating demand ramp 1); HR 25 Actual cooling demand of ramp 1 (Cooling demand ramp 1); HR 9 System Status 1 (Status 1); HR 10 System Status 2 (Status 2 (alarms)); HR 39 System option 1 (System option 1 (bit 1 = Modbus temp unit)).

How do I enable Modbus control of the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)?

Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.

Where is the official Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus documentation?

The source is TUCB & TUHB Series Universal Wall-Mount Controller Modbus Communication Module User Guide (TUXB-Modbus Guide-190515), revision 2019-05-15, published free by Neptronic at https://www.neptronic.com/Controls/PDF/20190515/TUXB-Modbus%20Guide-190515.pdf.

More Neptronic Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: TUCB & TUHB Series Universal Wall-Mount Controller Modbus Communication Module User Guide · TUXB-Modbus Guide-190515 · rev. 2019-05-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.