- TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Thermostat / heat pump and unitary controller · Modbus register map
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus register map
Updated 19 November 2026
The TUCB and TUHB are Neptronic wall-mount controllers with built-in sensors, six binary and two analog outputs, for fan coils, heat pumps (with reversing valve and emergency heat options) and other unitary equipment. Over Modbus RTU they expose temperatures, humidity (TUHB), CO2, ramp demands, output states, mode, fan and setpoint control and the configuration registers.
This page lists 133 Modbus registers for the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) — 109 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
- Equipment type
- Thermostat / heat pump and unitary controller
- Registers
- 133 (109 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB
Integration notes: Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Read holding registers with function 03 at the printed register index minus 40000 (40011 = address 11). Set the temperature unit for Modbus first, then use the mode, fan and setpoint registers for control.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 11 | Internal temperature sensor reading | INT16 | Internal (room) temperature x100 | Read |
| HR 14 | Control temperature reading | INT16 | Control temperature x100 | Read/write |
| HR 36 | System mode status | UINT16 | System mode | Read/write |
| HR 37 | Fan speed selection by user | UINT16 | Fan speed | Read/write |
| HR 38 | Temperature setpoint in occupancy or day mode | INT16 | Occupied setpoint x10 | Read/write |
| HR 23 | Actual heating demand of ramp 1 | UINT16 | Heating demand ramp 1 | Read |
| HR 25 | Actual cooling demand of ramp 1 | UINT16 | Cooling demand ramp 1 | Read |
| HR 9 | System Status 1 | BITMAP16 | Status 1 | Read |
| HR 10 | System Status 2 | BITMAP16 | Status 2 (alarms) | Read |
| HR 39 | System option 1 | BITMAP16 | System option 1 (bit 1 = Modbus temp unit) | Read/write |
Enable Modbus control & writes
Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.
Byte order & addressing
- The table prints a 4 prefix on a 0-based register index (40000 = address 0), not the 40001 Modicon convention.
- Baud register holds baud/100 (384 = 38400); 0 means automatic baud detection.
Network setup
- RS-485 two-wire, RTU. Supported baud rates 9600, 19200, 38400 and 57600; automatic baud detection is the default.
- Parity/stop bits come from the communication-port register: 1 = none + 2 stop, 2 = even + 1 stop, 3 = odd + 1 stop.
Watch out for
- Changing the Modbus temperature-unit bit changes the meaning of every temperature register at once.
- Some registers only apply to models with a humidity, CO2 or other optional sensor.
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40000 | Address - Neptronic ID and Modbus address of current device | UINT16 | Read/write | |||||
| HR | 1doc 40001 | Baud rate (baud / 100) | 0 = automatic detection. | UINT16 | × 100 | Read/write | |||
| HR | 2doc 40002 | Communication port configuration | UINT16 | Read/write | 1 = No parity, 2 Stop bits; 2 = Even parity, 1 stop bit; 3 = Odd parity, 1 stop bit | ||||
| HR | 7doc 40007 | Controller Product_Version, actual firmware version | UINT16 | Read | |||||
| HR | 8doc 40008 | Controller parameters version | UINT16 | Read | |||||
| HR | 9doc 40009 | System Status 1 | BITMAP16 | Read | bit 0 = System operation (0 = Normal, 1 = Fault); bit 2 = System override by NSB or OCC (0 = Normal, 1 = OFF); bit 3 = ChangeOverMode (0 = Cooling, 1 = Heating); bit 4 = AL_FlowSwitch (0 = No alarm, 1 = Alarm activated); bit 6 = AL_DirtyFilter (0 = No alarm, 1 = Alarm activated) | ||||
| HR | 10doc 40010 | System Status 2 | BITMAP16 | Read | bit 0 = Selector Switch Status (0 = Remote Mode, 1 = Local Mode); bit 2 = CO2 Alarm (0 = Normal, 1 = Alarm); bit 7 = AL_Override (0 = Off, 1 = On); bit 8 = AL_WindowOpened (0 = Off, 1 = On); bit 9 = AL_DoorOpened (0 = Off, 1 = On); bit 10 = AL_BI1 (0 = Off, 1 = On); bit 11 = AL_BI2 (0 = Off, 1 = On); bit 12 = AL_AI1 (0 = Off, 1 = On); bit 13 = AL_AI2 (0 = Off, 1 = On); bit 15 = AL_OverHeat (0 = Off, 1 = On) | ||||
| HR | 11doc 40011 | Internal temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 12doc 40012 | External temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 13doc 40013 | Changeover temperature sensor reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read | ||
| HR | 14doc 40014 | Control temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 15doc 40015 | Internal humidity sensor reading | TUHB24C6X2 only. | UINT16 | × 0.1 | %RH | Read | ||
| HR | 16doc 40016 | External humidity sensor reading | UINT16 | × 0.1 | %RH | Read | |||
| HR | 17doc 40017 | Analog input 1 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 18doc 40018 | Analog input 2 reading | Volts or temperature, depending on how the input is configured. | INT16 | × 0.01 | V / °C / °F | Read | ||
| HR | 19doc 40019 | CO2 sensor value in ppm | INT16 | ppm | Read | ||||
| HR | 20doc 40020 | Binary input statuses of 2 binary inputs | BITMAP16 | Read | bit 0 = Binary Input 1 (0 = Open, 1 = Close); bit 1 = Binary Input 2 (0 = Open, 1 = Close) | ||||
| HR | 21doc 40021 | Actual system occupancy state | UINT16 | Read | 1 = NoOccupancy; 2 = Occupancy; 3 = Override | ||||
| HR | 22doc 40022 | Actual night setback state of the system | UINT16 | Read | 1 = Day; 2 = Night; 3 = Override | ||||
| HR | 23doc 40023 | Actual heating demand of ramp 1 | UINT16 | × 0.1 | % | Read | |||
| HR | 24doc 40024 | Actual heating demand of ramp 2 | UINT16 | × 0.1 | % | Read | |||
| HR | 25doc 40025 | Actual cooling demand of ramp 1 | UINT16 | × 0.1 | % | Read | |||
| HR | 26doc 40026 | Actual cooling demand of ramp 2 | UINT16 | × 0.1 | % | Read | |||
| HR | 27doc 40027 | Actual changeover demand | UINT16 | × 0.1 | % | Read | |||
| HR | 28doc 40028 | Actual fan demand | UINT16 | × 0.1 | % | Read | |||
| HR | 29doc 40029 | Actual dehumidification demand | UINT16 | × 0.1 | % | Read | |||
| HR | 30doc 40030 | Actual humidification demand | UINT16 | × 0.1 | % | Read | |||
| HR | 31doc 40031 | Cooling/heating switch timer countdown | UINT16 | s | Read | ||||
| HR | 32doc 40032 | Analog output 1 value | UINT16 | × 0.1 | % | Read/write | |||
| HR | 33doc 40033 | Analog output 2 value | UINT16 | × 0.1 | % | Read/write | |||
| HR | 34doc 40034 | Binary output - 6 relays output status | BITMAP16 | Read/write | bit 0 = Binary Output 1 (0 = Open, 1 = Close); bit 1 = Binary Output 2 (0 = Open, 1 = Close); bit 2 = Binary Output 3 (0 = Open, 1 = Close); bit 3 = Binary Output 4 (0 = Open, 1 = Close); bit 4 = Binary Output 5 (0 = Open, 1 = Close); bit 5 = Binary Output 6 (0 = Open, 1 = Close) | ||||
| HR | 35doc 40035 | System command | BITMAP16 | Read/write | bit 0 = Cfg_ServiceDisplayAddress (0 = Normal, 1 = Display address on LCD); bit 1 = Cfg_CoolingRampLock (0 = Off, 1 = On); bit 3 = Cfg_HeatingRamp1Lock (0 = Off, 1 = On); bit 4 = Cfg_HeatingRamp2Lock (0 = Off, 1 = On); bit 5 = Cfg_ChangeOverRampLock (0 = Off, 1 = On); bit 7 = Cfg_HumidifyRampLock (0 = Off, 1 = On); bit 8 = Cfg_DehumidifyRampLock (0 = Off, 1 = On) | ||||
| HR | 36doc 40036 | System mode status | Each mode is only accepted when the system control mode and option bits allow it. | UINT16 | Read/write | 1 = Auto; 2 = Heating; 3 = Emergency heat (EMH); 4 = Cooling; 5 = Fan; 6 = Off | |||
| HR | 37doc 40037 | Fan speed selection by user | UINT16 | Read/write | 1 = Auto; 2 = Low; 3 = Med; 4 = High | ||||
| HR | 38doc 40038 | Temperature setpoint in occupancy or day mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 39doc 40039 | System option 1 | BITMAP16 | Read/write | bit 0 = Cfg_TempUnitTstat (0 = °C, 1 = °F); bit 1 = Cfg_TempUnitModbus (0 = °C, 1 = °F); bit 2 = Cfg_TempSetPointLock (0 = Off, 1 = On); bit 3 = Cfg_HumSetPointLock (0 = Off, 1 = On); bit 4 = Cfg_ProgramModeLock (0 = Off, 1 = On); bit 7 = AL_FreezeProtection (0 = Off, 1 = On); bit 8 = Cfg_UserSysOffModes (0 = Enable, 1 = Disable); bit 9 = Cfg_KeyPadBottomLeftLock (0 = Off, 1 = On); bit 10 = Cfg_KeyPadUpperLeftLock (0 = Off, 1 = On); bit 11 = Cfg_KeyPadArrowsLock (0 = Off, 1 = On); bit 12 = Cfg_UserFanAutoMode (0 = Enable, 1 = Disable); bit 13 = Cfg_ NightOrNoOccMode (0 = Setpoint, 1 = OFF); bit 14 = Cfg_HumControlSource (0 = Intern Sensor, 1 = Extern Sensor (Writable only if an intern RH option is available) Only available on model TUHB24C6X2.); bit 15 = Time Mode (0 = 24h, 1 = 12h) | ||||
| HR | 40doc 40040 | System option 2 | BITMAP16 | Read/write | bit 0 = Cfg_WindowOpenedMode (0 = Setpoint, 1 = OFF); bit 1 = Cfg_DoorOpenedMode (0 = Setpoint, 1 = OFF); bit 2 = Baud Rate (0 = Auto, 1 = Manual); bit 3 = Cfg_ActivateSchedule (0 = Off, 1 = On); bit 4 = Cfg_AnalogOutput1Direction (0 = Direct, 1 = Reverse); bit 5 = Cfg_AnalogOutput2Direction (0 = Direct, 1 = Reverse); bit 6 = Cfg_BinaryOutput1Direction (0 = Direct, 1 = Reverse); bit 7 = Cfg_BinaryOutput2Direction (0 = Direct, 1 = Reverse); bit 8 = Cfg_BinaryOutput3Direction (0 = Direct, 1 = Reverse); bit 9 = Cfg_BinaryOutput4Direction (0 = Direct, 1 = Reverse); bit 10 = Cfg_BinaryOutput5Direction (0 = Direct, 1 = Reverse); bit 11 = Cfg_BinaryOutput6Direction (0 = Direct, 1 = Reverse); bit 12 = Cfg_ FanSpeedOption (0 = Standard, 1 = Advanced (OE1)); bit 13 = Cfg_UserSysFanMode (0 = Disable, 1 = Enable); bit 14 = Cfg_HideFanDisplay (0 = N0, 1 = Yes) | ||||
| HR | 41doc 40041 | System option 3 | BITMAP16 | Read/write | bit 0 = DAYLIGHT_SAVINGS_STATUS (0 = Normal, 1 = Summer); bit 1 = Cfg_EMHOutput (0 = Disable, 1 = Enable); bit 2 = Cfg_ HeatPumpMode (0 = Off (General Unit), 1 = On (HeatPump)); bit 3 = Cfg_ReversingValve (O/B) (0 = O, 1 = B); bit 4 = Cfg_EMHAutoMode (0 = No, 1 = Yes); bit 5 = Cfg_Y2Output (0 = Disable, 1 = Enable) | ||||
| HR | 43doc 40043 | Display information | UINT16 | Read/write | 1 = Temperature and Demand; 2 = Setpoint and Demand; 3 = Temperature Only; 4 = Setpoint Only; 5 = Off | ||||
| HR | 44doc 40044 | Temperature control source | UINT16 | Read/write | 1 = Network Temp; 2 = Intern Temp; 3 = Extern Temp | ||||
| HR | 45doc 40045 | Network fallback timeout | UINT16 | min | Read/write | ||||
| HR | 46doc 40046 | Minimum occupancy/day setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 47doc 40047 | Maximum occupancy/day setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 48doc 40048 | Cooling temperature setpoint in unoccupied or night mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 49doc 40049 | Heating temperature setpoint in unoccupied or night mode | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 50doc 40050 | Heating proportional band for ramp 1 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 51doc 40051 | Heating proportional band for ramp 2 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 52doc 40052 | Cooling proportional band for ramp 1 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 53doc 40053 | Cooling proportional band for ramp 2 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 54doc 40054 | Changeover proportional band | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 55doc 40055 | Heating deadband for ramp 1 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 56doc 40056 | Heating deadband for ramp 2 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 57doc 40057 | Cooling deadband for ramp 1 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 58doc 40058 | Cooling deadband for ramp 2 | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 59doc 40059 | Changeover deadband | Unit follows the Modbus temperature-unit option (°C or °F). | UINT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 60doc 40060 | Changeover setpoint | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 61doc 40061 | Fan time out in seconds | UINT16 | s | Read/write | ||||
| HR | 62doc 40062 | Fan damping factor in seconds | UINT16 | s | Read/write | ||||
| HR | 63doc 40063 | Heating integral time factor in seconds | UINT16 | s | Read/write | ||||
| HR | 64doc 40064 | Cooling integral time factor in seconds | UINT16 | s | Read/write | ||||
| HR | 65doc 40065 | Delay between cooling and heating | UINT16 | min | Read/write | ||||
| HR | 66doc 40066 | Cooling anticycle delay in minutes | UINT16 | min | Read/write | ||||
| HR | 67doc 40067 | NSB override delay in minutes | UINT16 | min | Read/write | ||||
| HR | 68doc 40068 | Unoccupied override delay in minutes | UINT16 | min | Read/write | ||||
| HR | 69doc 40069 | Occupancy minimum time in minutes | UINT16 | min | Read/write | ||||
| HR | 70doc 40070 | Unoccupied override delay count down in minutes | UINT16 | min | Read/write | ||||
| HR | 71doc 40071 | Fan mode (speed) in unoccupied or NSB mode | UINT16 | Read/write | 1 = Low; 2 = Med; 3 = High; 4 = Auto | ||||
| HR | 72doc 40072 | Fan mode (speed) when window is opened (alarm) | UINT16 | Read/write | 1 = Low; 2 = Med; 3 = High; 4 = Auto | ||||
| HR | 73doc 40073 | Fan mode (speed) when door is opened (alarm) | UINT16 | Read/write | 1 = Low; 2 = Med; 3 = High; 4 = Auto | ||||
| HR | 74doc 40074 | System control mode | UINT16 | Read/write | 1 = Auto; 2 = Heat; 3 = Cool; 4 = Heat or Cool; 5 = Auto Lock | ||||
| HR | 75doc 40075 | Override System occupancy/NSB mode | UINT16 | Read/write | 1 = Locally; 2 = OFF; 3 = Occupied; 4 = Unoccupied; 5 = Day; 6 = Night | ||||
| HR | 76doc 40076 | Internal temperature sensor offset correction | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 77doc 40077 | Analog Input 1 signal | UINT16 | Read/write | 1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy binary input; 10 = NSB binary input; 11 = Override binary input; 12 = Window binary input; 13 = Door binary input; 14 = Dirty Filter binary input; 15 = Flow switch binary input; 16 = OverHeat binary input; 17 = Selector switch binary input; 18 = Humidity sensor 0-10V | ||||
| HR | 78doc 40078 | Analog Input 2 signal | UINT16 | Read/write | 1 = OFF; 2 = Extern sensor 10K; 3 = Change over sensor; 4 = Change over normally cool; 5 = Change over normally heat; 6 = Outside air sensor; 7 = Extern sensor 0-10V; 8 = CO2 sensor 0-10V; 9 = Occupancy binary input; 10 = NSB binary input; 11 = Override binary input; 12 = Window binary input; 13 = Door binary input; 14 = Dirty Filter binary input; 15 = Flow switch binary input; 16 = OverHeat binary input; 17 = Selector switch binary input; 18 = Humidity sensor 0-10V | ||||
| HR | 79doc 40079 | External temperature sensor offset correction | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 80doc 40080 | Changeover control mode | UINT16 | Read/write | 1 = Local; 2 = Cool; 3 = Heat | ||||
| HR | 81doc 40081 | Minimum external temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 82doc 40082 | Maximum external temperature reading | Unit follows the Modbus temperature-unit option (°C or °F). | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 83doc 40083 | Maximum CO2 reading | INT16 | ppm | Read/write | ||||
| HR | 84doc 40084 | Alarm level of CO2 | INT16 | ppm | Read/write | ||||
| HR | 85doc 40085 | Fan output signal | UINT16 | Read/write | 1 = 1 speed; 2 = 2 speeds; 3 = 3 speeds; 4 = Analog; 5 = VFD | ||||
| HR | 86doc 40086 | Ramp to control analog output 1 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 way valve | ||||
| HR | 87doc 40087 | Minimum voltage for analog output 1 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 88doc 40088 | Maximum voltage for analog output 1 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 89doc 40089 | Ramp to control analog output 2 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = 6 way valve; 12 = FAN | ||||
| HR | 90doc 40090 | Minimum voltage for analog output 2 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 91doc 40091 | Maximum voltage for analog output 2 (volt) | UINT16 | × 0.1 | V | Read/write | |||
| HR | 92doc 40092 | Position of CH1 AO output while heating (%) | UINT16 | % | Read/write | ||||
| HR | 93doc 40093 | Ramp to control binary output 1 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm | ||||
| HR | 94doc 40094 | Delay before activation of BO1 in minutes | UINT16 | min | Read/write | ||||
| HR | 95doc 40095 | Close position percentage for contact BO1 | UINT16 | % | Read/write | ||||
| HR | 96doc 40096 | Open position percentage for contact BO1 | UINT16 | % | Read/write | ||||
| HR | 97doc 40097 | Ramp to control binary output 2 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm | ||||
| HR | 98doc 40098 | Delay before activation of BO2 in minutes | UINT16 | min | Read/write | ||||
| HR | 99doc 40099 | Close position percentage for contact BO2 | UINT16 | % | Read/write | ||||
| HR | 100doc 40100 | Open position percentage for contact BO2 | UINT16 | % | Read/write | ||||
| HR | 101doc 40101 | Ramp to control binary output 3 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm | ||||
| HR | 102doc 40102 | Delay before activation of BO3 in minutes | UINT16 | min | Read/write | ||||
| HR | 103doc 40103 | Close position percentage for contact BO3 | UINT16 | % | Read/write | ||||
| HR | 104doc 40104 | Open position percentage for contact BO3 | UINT16 | % | Read/write | ||||
| HR | 105doc 40105 | Ramp to control binary output 4 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN | ||||
| HR | 106doc 40106 | Delay before activation of BO4 in minutes | UINT16 | min | Read/write | ||||
| HR | 107doc 40107 | Close position percentage for contact BO4 | UINT16 | % | Read/write | ||||
| HR | 108doc 40108 | Open position percentage for contact BO4 | UINT16 | % | Read/write | ||||
| HR | 109doc 40109 | Ramp to control binary output 5 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN | ||||
| HR | 110doc 40110 | Delay before activation of BO5 in minutes | UINT16 | min | Read/write | ||||
| HR | 111doc 40111 | Close position percentage for contact BO5 | UINT16 | % | Read/write | ||||
| HR | 112doc 40112 | Open position percentage for contact BO5 | UINT16 | % | Read/write | ||||
| HR | 113doc 40113 | Ramp to control binary output 6 | UINT16 | Read/write | 1 = Off; 2 = Changeover with fan; 3 = Cooling 1 with fan; 4 = Cooling 2 with fan; 5 = Heating 1 with fan; 6 = Heating 2 with fan; 7 = Heating 2; 8 = Cooling 1 Heating 1 With Fan; 9 = HumidifyWithFan; 10 = CO2 alarm; 11 = FAN (only when the fan type is 1, 2 or 3 speeds) | ||||
| HR | 114doc 40114 | Delay before activation of BO6 in minutes | UINT16 | min | Read/write | ||||
| HR | 115doc 40115 | Close position percentage for contact BO6 | UINT16 | % | Read/write | ||||
| HR | 116doc 40116 | Open position percentage for contact BO6 | UINT16 | % | Read/write | ||||
| HR | 117doc 40117 | Input contact of binary input 1, 2 and analog input 1, 2 | BITMAP16 | Read/write | bit 0 = Binary input 1 (0 = Normally Open, 1 = Normally Close); bit 1 = Binary input 2 (0 = Normally Open, 1 = Normally Close); bit 2 = Analog input 1 (0 = Normally Open, 1 = Normally Close); bit 3 = Analog input 2 (0 = Normally Open, 1 = Normally Close) | ||||
| HR | 118doc 40118 | Configuration of binary input 1 mode | UINT16 | Read/write | 1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode); 9 = Change over normally cool; 10 = Change over normally heat; 11 = NSB; 12 = Occupancy | ||||
| HR | 119doc 40119 | Delay before activation of BI1 in seconds | UINT16 | s | Read/write | ||||
| HR | 120doc 40120 | Configuration of binary input 2 mode | UINT16 | Read/write | 1 = OFF; 2 = Override; 3 = Window; 4 = Door; 5 = DirtyFilter; 6 = FlowSwitch; 7 = OverHeat; 8 = Selector switch (use together with a flow switch; fan stays off in local mode); 9 = Change over normally cool; 10 = Change over normally heat; 11 = NSB; 12 = Occupancy | ||||
| HR | 121doc 40121 | Delay before activation of BI2 in seconds | UINT16 | s | Read/write | ||||
| HR | 122doc 40122 | Delay before activation of AI1 in seconds | UINT16 | s | Read/write | ||||
| HR | 123doc 40123 | Delay before activation of AI2 in seconds | UINT16 | s | Read/write | ||||
| HR | 124doc 40124 | Humidity control mode status | UINT16 | Read/write | 1 = Auto; 2 = Dehumidification; 3 = Humidification; 4 = Off | ||||
| HR | 125doc 40125 | Humidity setpoint (%RH) in occupancy or day mode | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 126doc 40126 | Dehumidification setpoint (%RH) in unoccupied or night mode | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 127doc 40127 | Humidification setpoint (%RH) in unoccupied or night mode | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 128doc 40128 | Minimum user setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 129doc 40129 | Maximum user setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 130doc 40130 | Humidity proportional band | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 131doc 40131 | Humidity deadband | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 132doc 40132 | Internal humidity sensor offset correction | TUHB24C6X2 only. | INT16 | × 0.1 | %RH | Read/write | ||
| HR | 133doc 40133 | External humidity sensor offset correction | INT16 | × 0.1 | %RH | Read/write | |||
| HR | 134doc 40134 | Voltage required for closing the 6-way valve | UINT16 | × 0.01 | V | Read/write | |||
| HR | 135doc 40135 | Minimum output voltage required for cooling for the 6-way valve | UINT16 | × 0.01 | V | Read/write | |||
| HR | 136doc 40136 | Minimum output voltage required for heating for the 6-way valve | UINT16 | × 0.01 | V | Read/write | |||
| HR | 137doc 40137 | 6-way valve size selection in inches | UINT16 | Read/write | 1 = 1/2; 2 = 3/4; 3 = 1 |
Notes on this map
- Every register is a 16-bit holding register; there are no 32-bit values.
- Temperatures, setpoints and bands follow the Modbus temperature-unit bit of system option 1 (°C or °F); sensor readings and offsets are x100, setpoints and bands x10.
- Do not apply the 40001 rule: in this guide 40000 is register 0.
- Left out: the four ASCII product-name registers and register 40042 (all bits reserved).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
What Modbus registers does the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) have?
This map lists 133 registers: 133 holding registers. 109 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. This older guide prints a "Register Index" with a 4 prefix starting at 40000. Its introduction places the device address at holding register index 0 and the baud rate at index 1, which the table shows as 40000 and 40001, so wire address = printed number - 40000 (not the usual 40001 rule).
What are the minimum Modbus registers to integrate the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)?
Start with HR 11 Internal temperature sensor reading (Internal (room) temperature x100); HR 14 Control temperature reading (Control temperature x100); HR 36 System mode status (System mode); HR 37 Fan speed selection by user (Fan speed); HR 38 Temperature setpoint in occupancy or day mode (Occupied setpoint x10); HR 23 Actual heating demand of ramp 1 (Heating demand ramp 1); HR 25 Actual cooling demand of ramp 1 (Cooling demand ramp 1); HR 9 System Status 1 (Status 1); HR 10 System Status 2 (Status 2 (alarms)); HR 39 System option 1 (System option 1 (bit 1 = Modbus temp unit)).
How do I enable Modbus control of the Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)?
Modbus is the controller's native protocol; set the address (1-246) and, if needed, a fixed baud rate and parity from the device menu or registers 0-2.
Where is the official Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU) Modbus documentation?
The source is TUCB & TUHB Series Universal Wall-Mount Controller Modbus Communication Module User Guide (TUXB-Modbus Guide-190515), revision 2019-05-15, published free by Neptronic at https://www.neptronic.com/Controls/PDF/20190515/TUXB-Modbus%20Guide-190515.pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other pumps register maps
- Heat pump (air-to-water) Modbus interface
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Toshiba BMS-IFMB0UEW-E MB interface on ESTIA R410A 4 Series and 5 Series (WM type) and R32 1 Series (WM and AIO type) hydro units, user manual EEU-006 issued 31/05/2021.
Also known as: BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006 - Pump system
Wilo SiFresh with CIF module Modbus RTU
Wilo SiFresh pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-SiFresh - Heat pump Modbus interface
Airzone Aidoo Pro Modbus control for air-to-water heat pumps
Airzone Aidoo Pro units configured for Modbus output and connected to an air-to-water heat pump; register table 'Registers for Air-to-Water HP units' of the Aidoo - Modbus integration manual (v. 201).
Also known as: Aidoo Pro, Aidoo Pro Modbus air-to-water, Airzone Aidoo Modbus aerothermal - Heat pump
Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)
Ecoforest ecoGEO, ecoGEO HP and ecoAIR heat pumps on software AWD24, WWD24, WWC24 or later, register list API HP24_V01.02 (heat pump list only; supervisor and source-manager lists not included).
Also known as: ecoGEO, ecoGEO B&C, ecoGEO HP, ecoAIR, AWD24, WWD24, WWC24, API HP24_V01.02 - Pump protection / monitoring module (Sensor)
Grundfos IO 113 pump protection module (Modbus RTU)
Grundfos IO 113 interface module for wastewater and sewage pumps (with or without the SM 113 sensor board) set to Modbus with DIP switch 9; document edition 1.7, January 2015.
Also known as: IO113, IO 113 with SM 113, 98288208 - Heat pump (packaged wall-mount / classroom unit)
Marvair MAH heat pump and VAH/VDH Vanguard control board (Modbus RTU)
Marvair MAH1020H-1060H and MAH2024H-2060H wall-mount heat pumps (I&O manual rev. 6); the GAH1024-1060 gas-heat AC manual (rev. 5) and the VAH/VDH Vanguard classroom unit appendices (08/2026) print the same table.
Also known as: MAH1020H, MAH1024H, MAH1030H, MAH1036H, MAH1042H, MAH1048H, MAH1060H, MAH2024H, MAH2030H, MAH2036H, MAH2042H, MAH2048H, MAH2060H, Vanguard VAH, Vanguard VDH, VAH2030, VDH2060, GAH1024, GAH1030, GAH1036, GAH1042, GAH1048, GAH1060, Marvair GAH, Scholar 2 VAH/VDH, Scholar QR VAH/VDH
All pumps Modbus register maps →
Source: TUCB & TUHB Series Universal Wall-Mount Controller Modbus Communication Module User Guide · TUXB-Modbus Guide-190515 · rev. 2019-05-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.