Heat pump (air-to-water) Modbus interface · Modbus register map
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus register map
Updated 19 November 2026
The BMS-IFMB0UEW-E clips onto the AB remote-controller bus (AW-LINK or TU2C-LINK) of a Toshiba ESTIA hydro unit and answers as a Modbus RTU slave. Everything is a signed 16-bit holding register: zone and hot-water on/off, mode, setpoints, the special functions (auto temp, night setback, boost, frost protection, anti-bacteria), alarm status and code, sensor temperatures, running-hour counters, the setpoint limits and the interface's own configuration.
This page lists 56 Modbus registers for the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Toshiba’s own free documentation (linked below) and checked against it.
- Manufacturer
- Toshiba
- Model
- BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
- Equipment type
- Heat pump (air-to-water) Modbus interface
- Registers
- 56 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006
Integration notes: Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Connect the interface to the hydro unit's AB terminals (TB07 on 4/5 Series, TB04 on R32 1 Series) and to RS-485, then poll 40001-40025 with function 3 and write single registers with function 6.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Zone1/2 ON/OFF setting/monitor | INT16 | Zones on/off | Read/write |
| HR 1 | HOT WATER On/Off | INT16 | Hot water on/off | Read/write |
| HR 2 | Zone1/Zone2 operation mode setting/monitor | INT16 | Heat/cool mode | Read/write |
| HR 3 | Zone1 temperature setting | INT16 | Zone 1 setpoint | Read/write |
| HR 5 | HOT WATER temperature setting | INT16 | Hot water setpoint | Read/write |
| HR 11 | Alarm status | INT16 | Alarm status | Read |
| HR 12 | Alarm code | INT16 | Alarm code | Read |
| HR 18 | Outside temperature | INT16 | Outside temperature | Read |
| HR 22 | Water outlet temperature | INT16 | Water outlet temperature | Read |
Enable Modbus control & writes
No enable step: set the hydro unit type (S1), slave address and baud rate (S3) and temperature format/termination (S4) on the interface's DIP switches; the values can also be read over Modbus.
Byte order & addressing
- Function 16 is accepted but only with a length of 1; write one register per request.
- Temperature reads of 0x8000 mean no sensor or a sensor error.
- Temperatures are whole degrees unless DIP S4 bit 1 is ON, so the same register reads 45 or 450 depending on the switch.
Network setup
- Serial format is 8 data bits, no parity, 2 stop bits (8N1-compatible); baud 2400/4800/9600 (default)/19200 via DIP S3.
- Slave address 1-63 via DIP S3 (default 1).
- Only one remote controller (header) may stay on the AB bus; a sub remote controller cannot be connected.
- The AB bus between interface and hydro unit is unpolarised and limited to 50 m; RS-485 is polarised (A+, B-), up to 500 m, with 120 ohm termination at each end (on-board resistor via S4 bit 4).
Watch out for
- Setting zone temperatures from Modbus may still give lower water temperatures, depending on the remote controller's FC/DN settings.
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Zone1/2 ON/OFF setting/monitor | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1doc 40002 | HOT WATER On/Off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2doc 40003 | Zone1/Zone2 operation mode setting/monitor | Do not select cool if cool mode is prohibited. | INT16 | Read/write | 1 = Heat; 2 = Cool | |||
| HR | 3doc 40004 | Zone1 temperature setting | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read/write | |||
| HR | 4doc 40005 | Zone2 temperature setting | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read/write | |||
| HR | 5doc 40006 | HOT WATER temperature setting | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read/write | |||
| HR | 6doc 40007 | AUTO TEMP operation On/Off | Weather-compensated (auto temperature) operation. | INT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 7doc 40008 | Night setback operation On/Off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 8doc 40009 | HOT WATER boost On/Off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 9doc 40010 | Frost protection operation On/Off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 10doc 40011 | ANTI BACTERIA operation On/Off | Legionella (anti-bacteria) cycle. | INT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 11doc 40012 | Alarm status | INT16 | Read | 0 = No alarm condition; 1 = Alarm condition | ||||
| HR | 12doc 40013 | Alarm code | Check code number (list in the manual's section 6) or a negative status value. | INT16 | Read | -1 = Communication error; -3 = Paused; -4 = Initialization | |||
| HR | 13doc 40014 | Alarm unit | Which device raised the alarm. | INT16 | Read | 0 = Interface (0x00); 96 = Remote controller (0x60); 112 = Hydro unit 0 (0x70); 113 = Hydro unit 1 (0x71); 114 = Hydro unit 2 (0x72); 115 = Hydro unit 3 (0x73); 116 = Hydro unit 4 (0x74); 117 = Hydro unit 5 (0x75); 118 = Hydro unit 6 (0x76); 119 = Hydro unit 7 (0x77) | |||
| HR | 14doc 40015 | Zone1 control temperature | x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 15doc 40016 | Zone2 control temperature | x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 16doc 40017 | HOT WATER control temperature | x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 17doc 40018 | Control temperature | ESTIA control value. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 18doc 40019 | Outside temperature | TO sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 19doc 40020 | DHW cylinder water temperature | TTW sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 21doc 40022 | Water inlet temperature | TWI sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 22doc 40023 | Water outlet temperature | TWO sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 23doc 40024 | Water heater outlet temperature | THO sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 24doc 40025 | Floor heating circuit inlet temperature | TFI sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty. | INT16 | °C | Read | |||
| HR | 34doc 40035 | DHW mode compressor ON integrated time | INT16 | h | Read | ||||
| HR | 35doc 40036 | Heating mode compressor ON integrated time | INT16 | h | Read | ||||
| HR | 36doc 40037 | Cooling mode compressor ON integrated time | INT16 | h | Read | ||||
| HR | 37doc 40038 | Hydro unit water pump operation integrated time | INT16 | h | Read | ||||
| HR | 38doc 40039 | DHW cylinder heater ON integrated time | INT16 | h | Read | ||||
| HR | 39doc 40040 | Hydro unit back up heater ON integrated time | INT16 | h | Read | ||||
| HR | 40doc 40041 | Modbus baud rate | INT16 | Read | 0 = 2400 bps; 1 = 4800 bps; 2 = 9600 bps; 3 = 19200 bps | ||||
| HR | 41doc 40042 | Modbus slave address | 1 to 63. | INT16 | Read | ||||
| HR | 49doc 40050 | Device definition | Reads 0x2C00. | INT16 | Read | ||||
| HR | 50doc 40051 | Software version | INT16 | Read | |||||
| HR | 51doc 40052 | Hydro unit type | INT16 | Read | 4 = 4 Series (0x0004); 5 = 5 Series (0x0005); 257 = R32 1 Series (0x0101) | ||||
| HR | 65doc 40066 | Permit/Prohibit remote controller | Per bit: 0 = remote controller allowed, 1 = prohibited. R32 1 Series only. | BITMAP16 | Read/write | bit 0 = ON/OFF prohibited; bit 1 = Mode prohibited; bit 2 = Temperature setting prohibited | |||
| HR | 200doc 40201 | Zone1 device connection status | INT16 | Read | 0 = No connection; 1 = Connected | ||||
| HR | 201doc 40202 | Zone2 device connection status | INT16 | Read | 0 = No connection; 1 = Connected | ||||
| HR | 202doc 40203 | HOT WATER device connection status | INT16 | Read | 0 = No connection; 1 = Connected | ||||
| HR | 203doc 40204 | Zone1 and 2 cooling upper limit setting temperature (MAX) | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 204doc 40205 | Zone1 and 2 cooling lower limit setting temperature (MIN) | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 205doc 40206 | Zone1 heating mode upper limit water temperature (MAX) | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 206doc 40207 | Zone1 heating mode lower limit water temperature (MIN) | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 207doc 40208 | Zone2 heating mode upper limit water temperature (MAX) | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 208doc 40209 | Zone2 heating mode lower limit water temperature (MIN) | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 209doc 40210 | Hot water mode upper limit water temperature (MAX) | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 210doc 40211 | Hot water mode lower limit water temperature (MIN) | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 211doc 40212 | Frost protection setting temperature | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 212doc 40213 | HOT WATER boost setting temperature | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 213doc 40214 | ANTIBACTERIA setting temperature | Whole degrees, or tenths if DIP S4 bit 1 is ON. | INT16 | °C | Read | |||
| HR | 214doc 40215 | Operation mode permit/prohibit | INT16 | Read | 0 = All modes prohibited; 1 = Cooling only; 2 = Heating only; 3 = Heating and cooling | ||||
| HR | 215doc 40216 | Auto temp setting function setting | INT16 | Read | 0 = Unused; 1 = Use | ||||
| HR | 216doc 40217 | Frost protection function setting status | INT16 | Read | 0 = Unused; 1 = Use | ||||
| HR | 218doc 40219 | Night set back function setting status | INT16 | Read | 0 = Unused; 1 = Use | ||||
| HR | 219doc 40220 | Hot water boost function status | INT16 | Read | 0 = Unused; 1 = Use | ||||
| HR | 220doc 40221 | AntiBacteria function status | INT16 | Read | 0 = Unused; 1 = Use |
Notes on this map
- Toshiba does not appear to host this manual publicly; the link is an unaltered copy of Toshiba Carrier Air-Conditioning Europe's manual on the Dutch distributor Intercool's download centre.
- The manual states every register is a 16-bit signed holding register, so all entries are INT16 (the bit field 40066 is shown as BITMAP16).
- Temperature scale is chosen by DIP switch S4 bit 1: whole degrees (x1, default) or decidegrees (x10). A further S4 switch selects Celsius (default) or Fahrenheit. The files' scale of 1 matches the default; set scale 0.1 if S4 bit 1 is ON.
- The manual marks per register which of R32 1 Series, 5 Series and 4 Series supports it. Every listed register is marked for all three, except 40018 (not on 4 Series) and 40066 (R32 1 Series only).
- The check-code list (section 6) maps alarm-code numbers to remote-controller codes such as A01 or E03; it is not copied here because the extracted table rows do not line up reliably.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
What Modbus registers does the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps have?
This map lists 56 registers: 56 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual gives the rule directly: start address in the request = printed register number - 40001. So 40001 is wire address 0 and 40201 is wire address 200.
What are the minimum Modbus registers to integrate the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps?
Start with HR 0 Zone1/2 ON/OFF setting/monitor (Zones on/off); HR 1 HOT WATER On/Off (Hot water on/off); HR 2 Zone1/Zone2 operation mode setting/monitor (Heat/cool mode); HR 3 Zone1 temperature setting (Zone 1 setpoint); HR 5 HOT WATER temperature setting (Hot water setpoint); HR 11 Alarm status (Alarm status); HR 12 Alarm code (Alarm code); HR 18 Outside temperature (Outside temperature); HR 22 Water outlet temperature (Water outlet temperature).
How do I enable Modbus control of the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps?
No enable step: set the hydro unit type (S1), slave address and baud rate (S3) and temperature format/termination (S4) on the interface's DIP switches; the values can also be read over Modbus.
Where is the official Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus documentation?
The source is TOSHIBA MB interface BMS-IFMB0UEW-E User Manual (Modbus RTU (RS-485) Interface for Toshiba Air to Water Heat Pump) (EEU-006), revision 2021-05-31. Toshiba doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.intercool.nl/intercool/downloadcenter/download/attachment/3356/16. It may be an older revision, so check it against the live unit.
More Toshiba Modbus register maps
- Variable frequency drive
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Toshiba TOSVERT VF-AS3 inverters on RS485 port 1 or 2 with the protocol set to MODBUS (F807/F827 = 1); RS485 Communication Function Instruction Manual E6582143.
Also known as: VF-AS3, TOSVERT VF-AS3 - Variable frequency drive
Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)
Toshiba TOSVERT VF-nC3 series inverters using the built-in RS-485 port with f829 = 1 (Modbus RTU), per manual E6581657.
Also known as: VF-nC3, VF-nC3M, TOSVERT VF-nC3, VFNC3
Other pumps register maps
- Pump system
Wilo SiFresh with CIF module Modbus RTU
Wilo SiFresh pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-SiFresh - Heat pump Modbus interface
Airzone Aidoo Pro Modbus control for air-to-water heat pumps
Airzone Aidoo Pro units configured for Modbus output and connected to an air-to-water heat pump; register table 'Registers for Air-to-Water HP units' of the Aidoo - Modbus integration manual (v. 201).
Also known as: Aidoo Pro, Aidoo Pro Modbus air-to-water, Airzone Aidoo Modbus aerothermal - Heat pump
Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)
Ecoforest ecoGEO, ecoGEO HP and ecoAIR heat pumps on software AWD24, WWD24, WWC24 or later, register list API HP24_V01.02 (heat pump list only; supervisor and source-manager lists not included).
Also known as: ecoGEO, ecoGEO B&C, ecoGEO HP, ecoAIR, AWD24, WWD24, WWC24, API HP24_V01.02 - Pump protection / monitoring module (Sensor)
Grundfos IO 113 pump protection module (Modbus RTU)
Grundfos IO 113 interface module for wastewater and sewage pumps (with or without the SM 113 sensor board) set to Modbus with DIP switch 9; document edition 1.7, January 2015.
Also known as: IO113, IO 113 with SM 113, 98288208 - Heat pump (packaged wall-mount / classroom unit)
Marvair MAH heat pump and VAH/VDH Vanguard control board (Modbus RTU)
Marvair MAH1020H-1060H and MAH2024H-2060H wall-mount heat pumps (I&O manual rev. 6); the GAH1024-1060 gas-heat AC manual (rev. 5) and the VAH/VDH Vanguard classroom unit appendices (08/2026) print the same table.
Also known as: MAH1020H, MAH1024H, MAH1030H, MAH1036H, MAH1042H, MAH1048H, MAH1060H, MAH2024H, MAH2030H, MAH2036H, MAH2042H, MAH2048H, MAH2060H, Vanguard VAH, Vanguard VDH, VAH2030, VDH2060, GAH1024, GAH1030, GAH1036, GAH1042, GAH1048, GAH1060, Marvair GAH, Scholar 2 VAH/VDH, Scholar QR VAH/VDH - Heat pump Modbus interface
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
RTD-LT/CA on the P1/P2 bus of Daikin Altherma Split LT CA hydroboxes (heating only and heating/cooling), with an EKRUCAL1 as main controller; all modes except Sequencer. Instructions 22570-2.09.12.
Also known as: RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA
All pumps Modbus register maps →
Source: TOSHIBA MB interface BMS-IFMB0UEW-E User Manual (Modbus RTU (RS-485) Interface for Toshiba Air to Water Heat Pump) · EEU-006 · rev. 2021-05-31 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.