  3. Toshiba
  4. BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps

Heat pump (air-to-water) Modbus interface · Modbus register map

Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus register map

Updated 19 November 2026

Short answer

The BMS-IFMB0UEW-E clips onto the AB remote-controller bus (AW-LINK or TU2C-LINK) of a Toshiba ESTIA hydro unit and answers as a Modbus RTU slave. Everything is a signed 16-bit holding register: zone and hot-water on/off, mode, setpoints, the special functions (auto temp, night setback, boost, frost protection, anti-bacteria), alarm status and code, sensor temperatures, running-hour counters, the setpoint limits and the interface's own configuration.

This page lists 56 Modbus registers for the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Toshiba’s own free documentation (linked below) and checked against it.

Manufacturer
Toshiba
Model
BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Equipment type
Heat pump (air-to-water) Modbus interface
Registers
56 (12 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006
Source document
TOSHIBA MB interface BMS-IFMB0UEW-E User Manual (Modbus RTU (RS-485) Interface for Toshiba Air to Water Heat Pump) · EEU-006 · rev. 2021-05-31 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps

Integration in brief

Connect the interface to the hydro unit's AB terminals (TB07 on 4/5 Series, TB04 on R32 1 Series) and to RS-485, then poll 40001-40025 with function 3 and write single registers with function 6.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Zone1/2 ON/OFF setting/monitorINT16Zones on/offRead/write
HR 1HOT WATER On/OffINT16Hot water on/offRead/write
HR 2Zone1/Zone2 operation mode setting/monitorINT16Heat/cool modeRead/write
HR 3Zone1 temperature settingINT16Zone 1 setpointRead/write
HR 5HOT WATER temperature settingINT16Hot water setpointRead/write
HR 11Alarm statusINT16Alarm statusRead
HR 12Alarm codeINT16Alarm codeRead
HR 18Outside temperatureINT16Outside temperatureRead
HR 22Water outlet temperatureINT16Water outlet temperatureRead

Enable Modbus control & writes

No enable step: set the hydro unit type (S1), slave address and baud rate (S3) and temperature format/termination (S4) on the interface's DIP switches; the values can also be read over Modbus.

Byte order & addressing

Network setup

Watch out for

Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

56 of 56 shown
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Zone1/2 ON/OFF setting/monitorINT16Read/write0 = Off; 1 = On
HR1doc 40002HOT WATER On/OffINT16Read/write0 = Off; 1 = On
HR2doc 40003Zone1/Zone2 operation mode setting/monitorDo not select cool if cool mode is prohibited.INT16Read/write1 = Heat; 2 = Cool
HR3doc 40004Zone1 temperature settingWhole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead/write
HR4doc 40005Zone2 temperature settingWhole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead/write
HR5doc 40006HOT WATER temperature settingWhole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead/write
HR6doc 40007AUTO TEMP operation On/OffWeather-compensated (auto temperature) operation.INT16Read/write0 = Off; 1 = On
HR7doc 40008Night setback operation On/OffINT16Read/write0 = Off; 1 = On
HR8doc 40009HOT WATER boost On/OffINT16Read/write0 = Off; 1 = On
HR9doc 40010Frost protection operation On/OffINT16Read/write0 = Off; 1 = On
HR10doc 40011ANTI BACTERIA operation On/OffLegionella (anti-bacteria) cycle.INT16Read/write0 = Off; 1 = On
HR11doc 40012Alarm statusINT16Read0 = No alarm condition; 1 = Alarm condition
HR12doc 40013Alarm codeCheck code number (list in the manual's section 6) or a negative status value.INT16Read-1 = Communication error; -3 = Paused; -4 = Initialization
HR13doc 40014Alarm unitWhich device raised the alarm.INT16Read0 = Interface (0x00); 96 = Remote controller (0x60); 112 = Hydro unit 0 (0x70); 113 = Hydro unit 1 (0x71); 114 = Hydro unit 2 (0x72); 115 = Hydro unit 3 (0x73); 116 = Hydro unit 4 (0x74); 117 = Hydro unit 5 (0x75); 118 = Hydro unit 6 (0x76); 119 = Hydro unit 7 (0x77)
HR14doc 40015Zone1 control temperaturex1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR15doc 40016Zone2 control temperaturex1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR16doc 40017HOT WATER control temperaturex1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR17doc 40018Control temperatureESTIA control value. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR18doc 40019Outside temperatureTO sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR19doc 40020DHW cylinder water temperatureTTW sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR21doc 40022Water inlet temperatureTWI sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR22doc 40023Water outlet temperatureTWO sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR23doc 40024Water heater outlet temperatureTHO sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR24doc 40025Floor heating circuit inlet temperatureTFI sensor. x1, or x10 with DIP S4 bit 1 ON; 0x8000 = sensor missing/faulty.INT16°CRead
HR34doc 40035DHW mode compressor ON integrated timeINT16hRead
HR35doc 40036Heating mode compressor ON integrated timeINT16hRead
HR36doc 40037Cooling mode compressor ON integrated timeINT16hRead
HR37doc 40038Hydro unit water pump operation integrated timeINT16hRead
HR38doc 40039DHW cylinder heater ON integrated timeINT16hRead
HR39doc 40040Hydro unit back up heater ON integrated timeINT16hRead
HR40doc 40041Modbus baud rateINT16Read0 = 2400 bps; 1 = 4800 bps; 2 = 9600 bps; 3 = 19200 bps
HR41doc 40042Modbus slave address1 to 63.INT16Read
HR49doc 40050Device definitionReads 0x2C00.INT16Read
HR50doc 40051Software versionINT16Read
HR51doc 40052Hydro unit typeINT16Read4 = 4 Series (0x0004); 5 = 5 Series (0x0005); 257 = R32 1 Series (0x0101)
HR65doc 40066Permit/Prohibit remote controllerPer bit: 0 = remote controller allowed, 1 = prohibited. R32 1 Series only.BITMAP16Read/writebit 0 = ON/OFF prohibited; bit 1 = Mode prohibited; bit 2 = Temperature setting prohibited
HR200doc 40201Zone1 device connection statusINT16Read0 = No connection; 1 = Connected
HR201doc 40202Zone2 device connection statusINT16Read0 = No connection; 1 = Connected
HR202doc 40203HOT WATER device connection statusINT16Read0 = No connection; 1 = Connected
HR203doc 40204Zone1 and 2 cooling upper limit setting temperature (MAX)Whole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR204doc 40205Zone1 and 2 cooling lower limit setting temperature (MIN)Whole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR205doc 40206Zone1 heating mode upper limit water temperature (MAX)Whole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR206doc 40207Zone1 heating mode lower limit water temperature (MIN)Whole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR207doc 40208Zone2 heating mode upper limit water temperature (MAX)Whole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR208doc 40209Zone2 heating mode lower limit water temperature (MIN)Whole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR209doc 40210Hot water mode upper limit water temperature (MAX)Whole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR210doc 40211Hot water mode lower limit water temperature (MIN)Whole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR211doc 40212Frost protection setting temperatureWhole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR212doc 40213HOT WATER boost setting temperatureWhole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR213doc 40214ANTIBACTERIA setting temperatureWhole degrees, or tenths if DIP S4 bit 1 is ON.INT16°CRead
HR214doc 40215Operation mode permit/prohibitINT16Read0 = All modes prohibited; 1 = Cooling only; 2 = Heating only; 3 = Heating and cooling
HR215doc 40216Auto temp setting function settingINT16Read0 = Unused; 1 = Use
HR216doc 40217Frost protection function setting statusINT16Read0 = Unused; 1 = Use
HR218doc 40219Night set back function setting statusINT16Read0 = Unused; 1 = Use
HR219doc 40220Hot water boost function statusINT16Read0 = Unused; 1 = Use
HR220doc 40221AntiBacteria function statusINT16Read0 = Unused; 1 = Use

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps

What Modbus registers does the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps have?

This map lists 56 registers: 56 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual gives the rule directly: start address in the request = printed register number - 40001. So 40001 is wire address 0 and 40201 is wire address 200.

What are the minimum Modbus registers to integrate the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps?

Start with HR 0 Zone1/2 ON/OFF setting/monitor (Zones on/off); HR 1 HOT WATER On/Off (Hot water on/off); HR 2 Zone1/Zone2 operation mode setting/monitor (Heat/cool mode); HR 3 Zone1 temperature setting (Zone 1 setpoint); HR 5 HOT WATER temperature setting (Hot water setpoint); HR 11 Alarm status (Alarm status); HR 12 Alarm code (Alarm code); HR 18 Outside temperature (Outside temperature); HR 22 Water outlet temperature (Water outlet temperature).

How do I enable Modbus control of the Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps?

No enable step: set the hydro unit type (S1), slave address and baud rate (S3) and temperature format/termination (S4) on the interface's DIP switches; the values can also be read over Modbus.

Where is the official Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps Modbus documentation?

The source is TOSHIBA MB interface BMS-IFMB0UEW-E User Manual (Modbus RTU (RS-485) Interface for Toshiba Air to Water Heat Pump) (EEU-006), revision 2021-05-31. Toshiba doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.intercool.nl/intercool/downloadcenter/download/attachment/3356/16. It may be an older revision, so check it against the live unit.