Toshiba Modbus register maps
Updated 19 November 2026
3 Toshiba models, 165 registers in all, each re-typed from Toshiba’s own free documentation and checked against it.
- Heat pump (air-to-water) Modbus interface
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Toshiba BMS-IFMB0UEW-E MB interface on ESTIA R410A 4 Series and 5 Series (WM type) and R32 1 Series (WM and AIO type) hydro units, user manual EEU-006 issued 31/05/2021.
Also known as: BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006 - Variable frequency drive
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Toshiba TOSVERT VF-AS3 inverters on RS485 port 1 or 2 with the protocol set to MODBUS (F807/F827 = 1); RS485 Communication Function Instruction Manual E6582143.
Also known as: VF-AS3, TOSVERT VF-AS3 - Variable frequency drive
Toshiba TOSVERT VF-nC3 compact inverter (Modbus RTU)
Toshiba TOSVERT VF-nC3 series inverters using the built-in RS-485 port with f829 = 1 (Modbus RTU), per manual E6581657.
Also known as: VF-nC3, VF-nC3M, TOSVERT VF-nC3, VFNC3
Toshiba: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps | RTU | 1 | 9600 baud, 8N2 | 16-bit only | Modicon | 56 |
| TOSVERT VF-AS3 inverter (RS485 Modbus RTU) | RTU | 0 | 19200 baud, 8E1 | 16-bit only | hex 0-based | 57 |
| TOSVERT VF-nC3 compact inverter (Modbus RTU) | RTU | 0 | 19200 baud, 8E1 | 16-bit only | hex 0-based | 52 |