  4. RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps

Heat pump Modbus interface · Modbus register map

Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus register map

Updated 19 November 2026

Short answer

Modbus RTU slave for Daikin Altherma LT split hydroboxes. Holding registers set leaving-water, room and DHW setpoints, mode, on/off, quiet, boost and weather-dependent operation for main and multi-zone; input registers return status flags, temperatures x100, flow, run hours, setpoint limits and 32-bit energy consumed / produced.

This page lists 72 Modbus registers for the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Realtime Control Systems’s own free documentation (linked below) and checked against it.

Manufacturer
Realtime Control Systems
Model
RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
Equipment type
Heat pump Modbus interface
Registers
72 (23 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA
Source document
Instructions pour l'installation de la RTD-LT/CA (RTD-LT/CA Installation Instructions, French) · 22570-2.09.12 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps

Integration in brief

Set the address on SW1, wire DB/DA/GND, pick update mode 3 (send on change) if the BMS writes repeatedly, then write H0001-H0013 and poll I0021-I0051 plus the energy counters.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4Space heating/cooling on/offINT16Space heating/cooling on/offRead/write
HR 3Operating modeINT16ModeRead/write
HR 1Main zone leaving water setpoint, heatingINT16Heating LWT setpointRead/write
HR 12DHW reheat on/offINT16DHW reheat on/offRead/write
IR 40Leaving water temperatureINT16Leaving water temperature (x100)Read
IR 44Outdoor air temperatureINT16Outdoor temperature (x100)Read
IR 21Unit errorINT16Unit errorRead
IR 62Total energy consumedUINT32 ABCDTotal energy consumed (UINT32)Read

Enable Modbus control & writes

No enable switch; the update-mode register (+200) decides whether Modbus writes, the remote controller or both win.

Communication loss & watchdog

If P1/P2 communication is not restored within one minute the RTD raises an alarm on the fault relay.

Byte order & addressing

Network setup

Watch out for

Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

72 of 72 shown
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR21doc I0021Unit errorINT16Read0 = No error; 1 = Error
IR22doc I0022Unit error codeRTD ASCII format.INT16Read
IR23doc I0023Unit error sub-code0..99.INT16Read
IR28doc I0028Backup operationINT16Read0 = Off; 1 = On
IR29doc I0029Multizone mode runningINT16Read0 = Off; 1 = On
IR30doc I0030Circulation pump runningINT16Read0 = Off; 1 = On
IR31doc I0031Compressor runningINT16Read0 = Off; 1 = On
IR32doc I0032Booster heater runningINT16Read0 = Off; 1 = On
IR33doc I0033Disinfection operationINT16Read0 = Idle; 1 = Busy
IR34doc I0034Backup heater levelINT16Read0 = Off; 1 = Level 1; 2 = Level 2
IR35doc I0035Defrost / start-up modeINT16Read0 = Idle; 1 = Busy
IR36doc I0036Hot startINT16Read0 = Idle; 1 = Busy
IR37doc I00373-way valveINT16Read0 = Space heating/cooling; 1 = Domestic hot water
IR38doc I0038Solar pumpINT16Read0 = Off; 1 = On
IR40doc I0040Leaving water temperatureSigned °C x 100.INT16× 0.01°CRead
IR41doc I0041Leaving water temperature, backup heaterSigned °C x 100.INT16× 0.01°CRead
IR42doc I0042Return water temperatureSigned °C x 100.INT16× 0.01°CRead
IR43doc I0043DHW temperatureSigned °C x 100.INT16× 0.01°CRead
IR44doc I0044Outdoor air temperatureSigned °C x 100.INT16× 0.01°CRead
IR45doc I0045Refrigerant liquid temperatureSigned °C x 100.INT16× 0.01°CRead
IR46doc I0046Main zone active leaving water setpointSigned °C x 100.INT16× 0.01°CRead
IR47doc I0047Multizone active leaving water setpointSigned °C x 100.INT16× 0.01°CRead
IR48doc I0048External sensorSigned °C x 100.INT16× 0.01°CRead
IR49doc I0049Flow rateLitres per second x 100.INT16× 0.01l/sRead
IR50doc I0050Measured room temperatureSigned °C x 100.INT16× 0.01°CRead
IR51doc I0051Active DHW setpointSigned °C x 100.INT16× 0.01°CRead
IR62doc I0062 / I0063Total energy consumedkWh x 100; I0062 high word.UINT32ABCD× 0.01kWhRead
IR72doc I0072 / I0073Total energy producedkWh x 100; I0072 high word.UINT32ABCD× 0.01kWhRead
IR80doc I0080 / I0081Accumulated pump run hoursI0080 high word.UINT32ABCDhRead
IR82doc I0082 / I0083Accumulated compressor run hoursI0082 high word.UINT32ABCDhRead
IR162doc I0162 / I0163Space heating energy consumedkWh x 100.UINT32ABCD× 0.01kWhRead
IR172doc I0172 / I0173Space heating energy producedkWh x 100.UINT32ABCD× 0.01kWhRead
IR201doc I0201Heat pump heating supportedINT16Read0 = No; 1 = Supported
IR202doc I0202Heat pump cooling supportedINT16Read0 = No; 1 = Supported
IR203doc I0203DHW installedINT16Read0 = No; 1 = Installed
IR204doc I0204Backup heater installedINT16Read0 = No; 1 = Installed
IR205doc I0205Room temperature control activeINT16Read0 = No; 1 = Active
IR206doc I0206Leaving water temperature control activeINT16Read0 = No; 1 = Active
IR262doc I0262 / I0263Space cooling energy consumedkWh x 100.UINT32ABCD× 0.01kWhRead
IR272doc I0272 / I0273Space cooling energy producedkWh x 100.UINT32ABCD× 0.01kWhRead
IR301doc I0301Min main zone heating LWT setpointWhole °C.INT16°CRead
IR302doc I0302Min main zone cooling LWT setpointWhole °C.INT16°CRead
IR305doc I0305Min DHW reheat setpointWhole °C.INT16°CRead
IR307doc I0307Capacity codekW x 10.INT16× 0.1kWRead
IR362doc I0362 / I0363DHW tank energy consumedkWh x 100.UINT32ABCD× 0.01kWhRead
IR372doc I0372 / I0373DHW tank energy producedkWh x 100.UINT32ABCD× 0.01kWhRead
IR401doc I0401Max main zone heating LWT setpointWhole °C.INT16°CRead
IR402doc I0402Max main zone cooling LWT setpointWhole °C.INT16°CRead
IR405doc I0405Max DHW reheat setpointWhole °C.INT16°CRead
HR1doc H0001Main zone leaving water setpoint, heatingWhole °C, 25..55 (factory limits). Not available with weather-dependent mode.INT16°CRead/write
HR2doc H0002Main zone leaving water setpoint, coolingWhole °C, 5..22 (factory limits). Not available with weather-dependent mode.INT16°CRead/write
HR3doc H0003Operating modeINT16Read/write0 = Auto; 1 = Heating; 2 = Cooling
HR4doc H0004Space heating/cooling on/offINT16Read/write0 = Off; 1 = On
HR6doc H0006Room thermostat heating setpointWhole °C, 12..30.INT16°CRead/write
HR7doc H0007Room thermostat cooling setpointWhole °C, 15..35.INT16°CRead/write
HR9doc H0009Quiet modeINT16Read/write0 = Disable; 1 = Enable; 2 = Auto
HR10doc H0010DHW reheat setpointWhole °C, 30..60.INT16°CRead/write
HR12doc H0012DHW reheat on/offINT16Read/write0 = Off; 1 = On
HR13doc H0013DHW boost mode on/offINT16Read/write0 = Off; 1 = On
HR20doc H0020Pump run-hour counter resetWrite 55555 to reset.UINT16Write55555 = Reset
HR21doc H0021Compressor run-hour counter resetWrite 55555 to reset.UINT16Write55555 = Reset
HR50doc H0050Simulated room temperatureWhole °C, 0..50; 0 = not used.INT16°CRead/write
HR53doc H0053Main zone weather-dependent modeChanging it restarts the P1/P2 bus.INT16Read/write0 = Not active; 1 = Active, heating only; 2 = Not supported; 3 = Active, heating and cooling
HR54doc H0054Main zone weather-dependent heating offset-10..+10 °C.INT16°CRead/write
HR55doc H0055Main zone weather-dependent cooling offset-10..+10 °C.INT16°CRead/write
HR61doc H0061Multizone leaving water setpoint, heatingWhole °C, 25..55. Two-zone systems only.INT16°CRead/write
HR62doc H0062Multizone leaving water setpoint, coolingWhole °C, 5..22. Two-zone systems only.INT16°CRead/write
HR63doc H0063Multizone weather-dependent modeINT16Read/write0 = Not active; 1 = Active, heating only; 2 = Not supported; 3 = Active, heating and cooling
HR64doc H0064Multizone weather-dependent heating offset-10..+10 °C.INT16°CRead/write
HR65doc H0065Multizone weather-dependent cooling offset-10..+10 °C.INT16°CRead/write
HR66doc H0066Leaving water on/off (two-zone with room control)INT16Read/write0 = Off; 1 = On
HR201doc H0201Update mode for H0001Each control register has an update-mode register at +200.INT16Read/write0 = Last keypress; 1 = Central (keypad locked); 2 = Local (Modbus not sent); 3 = Changeover (send on change)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps

What Modbus registers does the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps have?

This map lists 72 registers: 49 input registers, 23 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states register base 0 and writes H0010 / I0010 for holding / input register 10, so the number after H or I is the wire address. 32-bit values use two consecutive registers, high word first.

What byte order does the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps?

Start with HR 4 Space heating/cooling on/off (Space heating/cooling on/off); HR 3 Operating mode (Mode); HR 1 Main zone leaving water setpoint, heating (Heating LWT setpoint); HR 12 DHW reheat on/off (DHW reheat on/off); IR 40 Leaving water temperature (Leaving water temperature (x100)); IR 44 Outdoor air temperature (Outdoor temperature (x100)); IR 21 Unit error (Unit error); IR 62 Total energy consumed (Total energy consumed (UINT32)).

How do I enable Modbus control of the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps?

No enable switch; the update-mode register (+200) decides whether Modbus writes, the remote controller or both win.

What happens when the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps loses Modbus communication?

If P1/P2 communication is not restored within one minute the RTD raises an alarm on the fault relay.

Where is the official Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus documentation?

The source is Instructions pour l'installation de la RTD-LT/CA (RTD-LT/CA Installation Instructions, French) (22570-2.09.12). Realtime Control Systems doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/sonepar-fr/raw/upload/s--STyMjHQz--/v1/documents/121/FR_RTD-LT-CA_Installation_Instructions_22570-2.09.12.pdf. It may be an older revision, so check it against the live unit.

More Realtime Control Systems Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Instructions pour l'installation de la RTD-LT/CA (RTD-LT/CA Installation Instructions, French) · 22570-2.09.12 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.