- RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
Heat pump Modbus interface · Modbus register map
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus register map
Updated 19 November 2026
Modbus RTU slave for Daikin Altherma LT split hydroboxes. Holding registers set leaving-water, room and DHW setpoints, mode, on/off, quiet, boost and weather-dependent operation for main and multi-zone; input registers return status flags, temperatures x100, flow, run hours, setpoint limits and 32-bit energy consumed / produced.
This page lists 72 Modbus registers for the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Realtime Control Systems’s own free documentation (linked below) and checked against it.
- Manufacturer
- Realtime Control Systems
- Model
- RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
- Equipment type
- Heat pump Modbus interface
- Registers
- 72 (23 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA
Integration notes: Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
Set the address on SW1, wire DB/DA/GND, pick update mode 3 (send on change) if the BMS writes repeatedly, then write H0001-H0013 and poll I0021-I0051 plus the energy counters.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 4 | Space heating/cooling on/off | INT16 | Space heating/cooling on/off | Read/write |
| HR 3 | Operating mode | INT16 | Mode | Read/write |
| HR 1 | Main zone leaving water setpoint, heating | INT16 | Heating LWT setpoint | Read/write |
| HR 12 | DHW reheat on/off | INT16 | DHW reheat on/off | Read/write |
| IR 40 | Leaving water temperature | INT16 | Leaving water temperature (x100) | Read |
| IR 44 | Outdoor air temperature | INT16 | Outdoor temperature (x100) | Read |
| IR 21 | Unit error | INT16 | Unit error | Read |
| IR 62 | Total energy consumed | UINT32 ABCD | Total energy consumed (UINT32) | Read |
Enable Modbus control & writes
No enable switch; the update-mode register (+200) decides whether Modbus writes, the remote controller or both win.
Communication loss & watchdog
If P1/P2 communication is not restored within one minute the RTD raises an alarm on the fault relay.
Byte order & addressing
- Writing the same value repeatedly in 'last keypress' mode overrides user changes at the controller; use update mode 3.
- Changing weather-dependent mode (H0053 / H0063) resets the P1/P2 bus; the controller and the RTD show busy until the reset ends.
- Read at most 10 registers per request.
Network setup
- RS485 D-Bus: DB(+), DA(-) and GND, daisy chain only.
- Factory serial settings 9600 baud, no parity, 1 stop bit.
- Power 15..24 V DC SELV.
Watch out for
- The RTD works as SUB: an EKRUCAL1 must be configured as MAIN.
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 21doc I0021 | Unit error | INT16 | Read | 0 = No error; 1 = Error | ||||
| IR | 22doc I0022 | Unit error code | RTD ASCII format. | INT16 | Read | ||||
| IR | 23doc I0023 | Unit error sub-code | 0..99. | INT16 | Read | ||||
| IR | 28doc I0028 | Backup operation | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 29doc I0029 | Multizone mode running | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 30doc I0030 | Circulation pump running | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 31doc I0031 | Compressor running | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 32doc I0032 | Booster heater running | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 33doc I0033 | Disinfection operation | INT16 | Read | 0 = Idle; 1 = Busy | ||||
| IR | 34doc I0034 | Backup heater level | INT16 | Read | 0 = Off; 1 = Level 1; 2 = Level 2 | ||||
| IR | 35doc I0035 | Defrost / start-up mode | INT16 | Read | 0 = Idle; 1 = Busy | ||||
| IR | 36doc I0036 | Hot start | INT16 | Read | 0 = Idle; 1 = Busy | ||||
| IR | 37doc I0037 | 3-way valve | INT16 | Read | 0 = Space heating/cooling; 1 = Domestic hot water | ||||
| IR | 38doc I0038 | Solar pump | INT16 | Read | 0 = Off; 1 = On | ||||
| IR | 40doc I0040 | Leaving water temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 41doc I0041 | Leaving water temperature, backup heater | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 42doc I0042 | Return water temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 43doc I0043 | DHW temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 44doc I0044 | Outdoor air temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 45doc I0045 | Refrigerant liquid temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 46doc I0046 | Main zone active leaving water setpoint | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 47doc I0047 | Multizone active leaving water setpoint | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 48doc I0048 | External sensor | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 49doc I0049 | Flow rate | Litres per second x 100. | INT16 | × 0.01 | l/s | Read | ||
| IR | 50doc I0050 | Measured room temperature | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 51doc I0051 | Active DHW setpoint | Signed °C x 100. | INT16 | × 0.01 | °C | Read | ||
| IR | 62doc I0062 / I0063 | Total energy consumed | kWh x 100; I0062 high word. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| IR | 72doc I0072 / I0073 | Total energy produced | kWh x 100; I0072 high word. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| IR | 80doc I0080 / I0081 | Accumulated pump run hours | I0080 high word. | UINT32 | ABCD | h | Read | ||
| IR | 82doc I0082 / I0083 | Accumulated compressor run hours | I0082 high word. | UINT32 | ABCD | h | Read | ||
| IR | 162doc I0162 / I0163 | Space heating energy consumed | kWh x 100. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| IR | 172doc I0172 / I0173 | Space heating energy produced | kWh x 100. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| IR | 201doc I0201 | Heat pump heating supported | INT16 | Read | 0 = No; 1 = Supported | ||||
| IR | 202doc I0202 | Heat pump cooling supported | INT16 | Read | 0 = No; 1 = Supported | ||||
| IR | 203doc I0203 | DHW installed | INT16 | Read | 0 = No; 1 = Installed | ||||
| IR | 204doc I0204 | Backup heater installed | INT16 | Read | 0 = No; 1 = Installed | ||||
| IR | 205doc I0205 | Room temperature control active | INT16 | Read | 0 = No; 1 = Active | ||||
| IR | 206doc I0206 | Leaving water temperature control active | INT16 | Read | 0 = No; 1 = Active | ||||
| IR | 262doc I0262 / I0263 | Space cooling energy consumed | kWh x 100. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| IR | 272doc I0272 / I0273 | Space cooling energy produced | kWh x 100. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| IR | 301doc I0301 | Min main zone heating LWT setpoint | Whole °C. | INT16 | °C | Read | |||
| IR | 302doc I0302 | Min main zone cooling LWT setpoint | Whole °C. | INT16 | °C | Read | |||
| IR | 305doc I0305 | Min DHW reheat setpoint | Whole °C. | INT16 | °C | Read | |||
| IR | 307doc I0307 | Capacity code | kW x 10. | INT16 | × 0.1 | kW | Read | ||
| IR | 362doc I0362 / I0363 | DHW tank energy consumed | kWh x 100. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| IR | 372doc I0372 / I0373 | DHW tank energy produced | kWh x 100. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| IR | 401doc I0401 | Max main zone heating LWT setpoint | Whole °C. | INT16 | °C | Read | |||
| IR | 402doc I0402 | Max main zone cooling LWT setpoint | Whole °C. | INT16 | °C | Read | |||
| IR | 405doc I0405 | Max DHW reheat setpoint | Whole °C. | INT16 | °C | Read | |||
| HR | 1doc H0001 | Main zone leaving water setpoint, heating | Whole °C, 25..55 (factory limits). Not available with weather-dependent mode. | INT16 | °C | Read/write | |||
| HR | 2doc H0002 | Main zone leaving water setpoint, cooling | Whole °C, 5..22 (factory limits). Not available with weather-dependent mode. | INT16 | °C | Read/write | |||
| HR | 3doc H0003 | Operating mode | INT16 | Read/write | 0 = Auto; 1 = Heating; 2 = Cooling | ||||
| HR | 4doc H0004 | Space heating/cooling on/off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 6doc H0006 | Room thermostat heating setpoint | Whole °C, 12..30. | INT16 | °C | Read/write | |||
| HR | 7doc H0007 | Room thermostat cooling setpoint | Whole °C, 15..35. | INT16 | °C | Read/write | |||
| HR | 9doc H0009 | Quiet mode | INT16 | Read/write | 0 = Disable; 1 = Enable; 2 = Auto | ||||
| HR | 10doc H0010 | DHW reheat setpoint | Whole °C, 30..60. | INT16 | °C | Read/write | |||
| HR | 12doc H0012 | DHW reheat on/off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 13doc H0013 | DHW boost mode on/off | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 20doc H0020 | Pump run-hour counter reset | Write 55555 to reset. | UINT16 | Write | 55555 = Reset | |||
| HR | 21doc H0021 | Compressor run-hour counter reset | Write 55555 to reset. | UINT16 | Write | 55555 = Reset | |||
| HR | 50doc H0050 | Simulated room temperature | Whole °C, 0..50; 0 = not used. | INT16 | °C | Read/write | |||
| HR | 53doc H0053 | Main zone weather-dependent mode | Changing it restarts the P1/P2 bus. | INT16 | Read/write | 0 = Not active; 1 = Active, heating only; 2 = Not supported; 3 = Active, heating and cooling | |||
| HR | 54doc H0054 | Main zone weather-dependent heating offset | -10..+10 °C. | INT16 | °C | Read/write | |||
| HR | 55doc H0055 | Main zone weather-dependent cooling offset | -10..+10 °C. | INT16 | °C | Read/write | |||
| HR | 61doc H0061 | Multizone leaving water setpoint, heating | Whole °C, 25..55. Two-zone systems only. | INT16 | °C | Read/write | |||
| HR | 62doc H0062 | Multizone leaving water setpoint, cooling | Whole °C, 5..22. Two-zone systems only. | INT16 | °C | Read/write | |||
| HR | 63doc H0063 | Multizone weather-dependent mode | INT16 | Read/write | 0 = Not active; 1 = Active, heating only; 2 = Not supported; 3 = Active, heating and cooling | ||||
| HR | 64doc H0064 | Multizone weather-dependent heating offset | -10..+10 °C. | INT16 | °C | Read/write | |||
| HR | 65doc H0065 | Multizone weather-dependent cooling offset | -10..+10 °C. | INT16 | °C | Read/write | |||
| HR | 66doc H0066 | Leaving water on/off (two-zone with room control) | INT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 201doc H0201 | Update mode for H0001 | Each control register has an update-mode register at +200. | INT16 | Read/write | 0 = Last keypress; 1 = Central (keypad locked); 2 = Local (Modbus not sent); 3 = Changeover (send on change) |
Notes on this map
- The source is the French edition of the Realtime Control Systems installation instructions, from a Sonepar (distributor) file host. The maker's own site (realtime-controls.co.uk) was offline and no Daikin-hosted copy was found, so the link is marked unofficial.
- All values are 16-bit unless stated. Temperatures marked 'x100' are signed: raw 2150 = 21.50 °C, raw 65036 = -5.00 °C. Holding-register setpoints are printed in whole °C with no x100 marking and are listed at scale 1.
- Fault codes are in the 'RTD ASCII' format described in the RTD-NET instructions (two characters packed high byte / low byte).
- Supported function codes: 03 and 04 (1..10 registers), 06, and 16 (1..10 registers).
- 32-bit counters (energy, run hours) are unsigned with the high word in the lower register, as both the data-type table and the register tables state.
- Special values: 32767 = register not implemented, 32768 = function not available, 32769 = waiting for a value from the unit.
- Each control register has an update-mode register at +200 (H0201 for H0001 and so on); only H0201 is listed.
- Min/max setpoint registers for multizone (I0303/I0304, I0403/I0404) and DHW boost (I0306/I0406) follow the same pattern and are not listed.
- In Sequencer mode the map changes to the RTD-W map; this file does not cover Sequencer mode.
- Modbus address 0..63 on SW1 (0..15 in Smart Grid mode).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
What Modbus registers does the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps have?
This map lists 72 registers: 49 input registers, 23 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states register base 0 and writes H0010 / I0010 for holding / input register 10, so the number after H or I is the wire address. 32-bit values use two consecutive registers, high word first.
What byte order does the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps?
Start with HR 4 Space heating/cooling on/off (Space heating/cooling on/off); HR 3 Operating mode (Mode); HR 1 Main zone leaving water setpoint, heating (Heating LWT setpoint); HR 12 DHW reheat on/off (DHW reheat on/off); IR 40 Leaving water temperature (Leaving water temperature (x100)); IR 44 Outdoor air temperature (Outdoor temperature (x100)); IR 21 Unit error (Unit error); IR 62 Total energy consumed (Total energy consumed (UINT32)).
How do I enable Modbus control of the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps?
No enable switch; the update-mode register (+200) decides whether Modbus writes, the remote controller or both win.
What happens when the Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps loses Modbus communication?
If P1/P2 communication is not restored within one minute the RTD raises an alarm on the fault relay.
Where is the official Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps Modbus documentation?
The source is Instructions pour l'installation de la RTD-LT/CA (RTD-LT/CA Installation Instructions, French) (22570-2.09.12). Realtime Control Systems doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/sonepar-fr/raw/upload/s--STyMjHQz--/v1/documents/121/FR_RTD-LT-CA_Installation_Instructions_22570-2.09.12.pdf. It may be an older revision, so check it against the live unit.
More Realtime Control Systems Modbus register maps
- VRF / split AC gateway
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
RTD-NET on the Daikin P1/P2 bus (VRV, Sky Air, VAM/VKM), up to 16 indoor units as one group; RTD-10 with the same firmware uses the same layout.
Also known as: RTD-NET, RTD-10, Daikin RTD-NET - VRF / split AC gateway
Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners
RTD-RA plugged into the S21 port of a Daikin room air conditioner (split) indoor unit, installation instructions 21070-1.07.04.
Also known as: RTD-RA, Daikin RTD-RA - Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W
Other pumps register maps
- Pump (pressure-boosting pump)
Wilo Isar MODH1-E with CIF module Modbus RTU
Wilo Isar MODH1-E pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Isar MODH1-E - Pump (high-efficiency inline circulator)
Wilo Yonos GIGA2.0 with CIF module Modbus RTU
Wilo Yonos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Yonos GIGA2.0-I, Yonos GIGA2.0-D, Wilo-Yonos GIGA2.0 - Heat pump (air-to-water) Modbus interface
Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)
Daikin HomeHub EKRHH in use case 3 (Modbus for Daikin Altherma air-to-water heat pumps) and use case 4 (Modbus smart-grid control of air-to-air heat pumps), installer reference guide 4P744838-1E (2026.01).
Also known as: EKRHH, Daikin HomeHub, 4P744838-1E, Daikin Altherma 3 Modbus, Altherma Smart Grid Modbus - Pump (booster system / multi-pump controller)
Grundfos Booster systems (Hydro MPC, Hydro Multi-E, Multi-B) via CIM 200 / CIM 500
Grundfos booster systems: Hydro MPC / Control MPC (CU 352), GENIECON MPC, Hydro Multi-B (CU 323), DDD (CU 354), Hydro Multi-E, TPED and MAGNA3-D twin pumps, with CIM/CIU 200, CIM/CIU 500 or SoftCIM.
Also known as: Hydro MPC, Control MPC, CU 352, GENIECON MPC, Hydro Multi-E, Hydro Multi-B, CU 323, DDD, CU 354, TPED, MAGNA3-D, CIM 200, CIM 500, SoftCIM Modbus TCP - Pump (diesel fire pump controller)
Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers
FFL700DP and FFL800DP diesel engine fire pump controllers (built-in RS-485, optical port, EXP1012T/EXP1013T modules on FFL800DP), per protocol document I557 GB I 11 17.
Also known as: FFL700DP, FFL800DP, FFL 700 DP, FFL 800 DP - Heat pump
Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)
Novelan (ait-deutschland) heat pumps whose heating and heat pump controller runs software V1.74 / V2.74 / V3.76 / V4.76 or later, with the GLT function licensed via the Novelan GLT USB dongle; operating manual 83055703hDE.
Also known as: Novelan GLT, 83055703, ait-deutschland GLT
All pumps Modbus register maps →
Source: Instructions pour l'installation de la RTD-LT/CA (RTD-LT/CA Installation Instructions, French) · 22570-2.09.12 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.