Easy Modbus
  1. Home
  2. Modbus register maps
  3. Daikin
  4. EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)

Heat pump (air-to-water) Modbus interface · Modbus register map

Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps) Modbus register map

Updated 19 November 2026

Short answer

The Daikin HomeHub (EKRHH) connects to a Daikin Altherma system and offers a Modbus TCP (port 502, or 802 with TLS) or Modbus RTU slave. Holding registers set leaving-water and room setpoints, operation mode, on/off, quiet mode, hot-water reheat and booster, weather-dependent mode and the smart-grid mode with power limits; input registers return error state and code, pump/compressor/heater/defrost states, water, outdoor and refrigerant temperatures, flow, power use and setpoint limits. For air-to-air units only the smart-grid mode and demand-control power limit are offered.

This page lists 61 Modbus registers for the Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin
Model
EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)
Equipment type
Heat pump (air-to-water) Modbus interface
Registers
61 (25 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
9600 baud, 8N1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
EKRHH, Daikin HomeHub, 4P744838-1E, Daikin Altherma 3 Modbus, Altherma Smart Grid Modbus
Source document
Installer reference guide - Daikin HomeHub EKRHH · 4P744838-1E · rev. 2026-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)

Integration in brief

Enable Modbus in the ONECTA app, then read input registers 21-53 for state and temperatures and write holding registers 1-13 and 53-58 for setpoints, modes and smart-grid control. Refresh written values periodically because the HomeHub only forwards changes.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3Space heating/cooling ON/OFFINT16Space heating/cooling on/offRead/write
HR 2Operation modeINT16Operation modeRead/write
HR 0Leaving water Main Heating setpointINT16Leaving water heating setpointRead/write
HR 55Smart Grid operation modeINT16Smart grid modeRead/write
HR 57General power limitINT16General power limitRead/write
IR 20Unit abnormalityINT16Unit abnormalityRead
IR 21Unit abnormality codeSTRING[2]Error codeRead
IR 30Compressor runINT16Compressor runningRead
IR 43Outside air temperatureINT16Outside air temperatureRead
IR 50Heat pump power consumptionINT16Power consumptionRead

Enable Modbus control & writes

Modbus (RTU or TCP/IP) is configured in the ONECTA app settings for the HomeHub (installer reference guide section 13.1.1).

Byte order & addressing

Network setup

Watch out for

Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

61 of 61 shown
Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR20doc 21Unit abnormalityINT16Read0 = No error; 1 = Fault; 2 = Warning
IR21doc 22Unit abnormality codeTwo ASCII characters, high byte first (e.g. 0x5538 = 'U8').STRING[2]Read
IR22doc 23Unit abnormality sub code0-99 on a unit error; 32766 if no error.INT16Read
IR29doc 30Circulation pump runningINT16Read0 = Off; 1 = On
IR30doc 31Compressor runINT16Read0 = Off; 1 = On
IR31doc 32Booster heater runINT16Read0 = Off; 1 = On
IR32doc 33Disinfection operationINT16Read0 = Off; 1 = On
IR34doc 35DefrostINT16Read0 = Off; 1 = On
IR35doc 36Hot StartINT16Read0 = Off; 1 = On
IR36doc 373-way valveINT16Read0 = Space heating; 1 = DHW
IR37doc 38Operation modeINT16Read1 = Heating; 2 = Cooling
IR39doc 40Leaving water temperature PHEAfter the plate heat exchanger.INT16× 0.01°CRead
IR40doc 41Leaving water temperature BUHAfter the backup heater.INT16× 0.01°CRead
IR41doc 42Return water temperatureINT16× 0.01°CRead
IR42doc 43Domestic Hot Water temperatureINT16× 0.01°CRead
IR43doc 44Outside air temperatureINT16× 0.01°CRead
IR44doc 45Liquid refrigerant temperatureINT16× 0.01°CRead
IR48doc 49Flow rateLitres per minute x 100.INT16× 0.01L/minRead
IR49doc 50Remote controller room temperature MainINT16× 0.01°CRead
IR50doc 51Heat pump power consumptionPow16: kW x 100.INT16× 0.01kWRead
IR51doc 52DHW normal operationINT16Read0 = Idle/buffering; 1 = Operating
IR52doc 53Space heating/cooling normal operationINT16Read0 = Idle/buffering; 1 = Operating
IR53doc 54Leaving water Main Heating setpoint Lower limitINT16× 0.01°CRead
IR54doc 55Leaving water Main Heating setpoint Upper limitINT16× 0.01°CRead
IR55doc 56Leaving water Main Cooling setpoint Lower limitINT16× 0.01°CRead
IR56doc 57Leaving water Main Cooling setpoint Upper limitINT16× 0.01°CRead
IR57doc 58Leaving water Add Heating setpoint Lower limitINT16× 0.01°CRead
IR58doc 59Leaving water Add Heating setpoint Upper limitINT16× 0.01°CRead
IR59doc 60Leaving water Add Cooling setpoint Lower limitINT16× 0.01°CRead
IR60doc 61Leaving water Add Cooling setpoint Upper limitINT16× 0.01°CRead
IR75doc 76Domestic Hot Water Upper temperatureINT16× 0.01°CRead
IR76doc 77Domestic Hot Water Lower temperatureINT16× 0.01°CRead
IR83doc 84Room Heating setpoint Lower limitINT16× 0.01°CRead
IR84doc 85Room Heating setpoint Upper limitINT16× 0.01°CRead
IR85doc 86Room Cooling setpoint Lower limitINT16× 0.01°CRead
IR86doc 87Room Cooling setpoint Upper limitINT16× 0.01°CRead
HR0doc 1Leaving water Main Heating setpointRange set by field settings.INT16°CRead/write
HR1doc 2Leaving water Main Cooling setpointRange set by field settings.INT16°CRead/write
HR2doc 3Operation modeReads 32766 on heating-only units.INT16Read/write0 = Auto; 1 = Heating; 2 = Cooling
HR3doc 4Space heating/cooling ON/OFFINT16Read/write0 = Off; 1 = On
HR5doc 6Room thermostat control Heating setpoint Main12-30 °C.INT16°CRead/write
HR6doc 7Room thermostat control Cooling setpoint Main15-35 °C.INT16°CRead/write
HR8doc 9Quiet mode operationINT16Read/write0 = Off; 1 = On
HR9doc 10DHW reheat setpoint30-60 °C; applied only with tank on, reheat-only mode and fixed setpoint.INT16°CRead/write
HR11doc 12DHW reheat ON/OFFINT16Read/write0 = Off; 1 = On
HR12doc 13DHW booster mode ON/OFF (Powerful)INT16Read/write0 = Off; 1 = On
HR52doc 53Weather dependent mode MainINT16Read/write0 = Fixed; 1 = Weather dependent; 2 = Fixed + scheduled; 3 = Weather dependent + scheduled
HR53doc 54Weather dependent mode Main LWT Heating setpoint offset-10 to 10 °C.INT16°CRead/write
HR54doc 55Weather dependent mode Main LWT Cooling setpoint offset-10 to 10 °C.INT16°CRead/write
HR55doc 56Smart Grid operation modeINT16Read/write0 = Free running; 1 = Forced off; 2 = Recommended on; 3 = Forced on
HR56doc 57Power limit during Recommended on / bufferingPow16: kW x 100, 0-20 kW.INT16× 0.01kWRead/write
HR57doc 58General power limitPow16: kW x 100, 0-20 kW.INT16× 0.01kWRead/write
HR58doc 59Thermostat Main Input AValid only with [C-05]=0 when [C-07]=1; not on Micon ID 20002203 units.INT16Read/write0 = Off; 1 = On
HR60doc 61Thermostat Add Input AValid only with [C-05]=0 when [C-07]=1; not on Micon ID 20002203 units.INT16Read/write0 = Off; 1 = On
HR62doc 63Leaving water Add Heating setpointRange set by field settings.INT16°CRead/write
HR63doc 64Leaving water Add Cooling setpointRange set by field settings.INT16°CRead/write
HR64doc 65Weather dependent mode AddINT16Read/write0 = Fixed; 1 = Weather dependent; 2 = Fixed + scheduled; 3 = Weather dependent + scheduled
HR65doc 66Weather dependent mode Add LWT Heating setpoint offset-10 to 10 °C.INT16°CRead/write
HR66doc 67Weather dependent mode Add LWT Cooling setpoint offset-10 to 10 °C.INT16°CRead/write
HR1000doc 1001Smart Grid operation mode (air-to-air use case)Use case 4 only; type not printed, same codes as offset 56.INT16Read/write0 = Free running; 1 = Forced off; 2 = Recommended on; 3 = Forced on
HR1001doc 1002Power limit for Demand Control (air-to-air use case)Use case 4 only. Pow16: kW x 100, 0-20 kW.INT16× 0.01kWRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)

What Modbus registers does the Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps) have?

This map lists 61 registers: 36 input registers, 25 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide lists register offsets 1-based and says PDU addressing is 0-based: register 1 is requested at PDU address 0. Every wire address here is the printed offset minus one.

What are the minimum Modbus registers to integrate the Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)?

Start with HR 3 Space heating/cooling ON/OFF (Space heating/cooling on/off); HR 2 Operation mode (Operation mode); HR 0 Leaving water Main Heating setpoint (Leaving water heating setpoint); HR 55 Smart Grid operation mode (Smart grid mode); HR 57 General power limit (General power limit); IR 20 Unit abnormality (Unit abnormality); IR 21 Unit abnormality code (Error code); IR 30 Compressor run (Compressor running); IR 43 Outside air temperature (Outside air temperature); IR 50 Heat pump power consumption (Power consumption).

How do I enable Modbus control of the Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)?

Modbus (RTU or TCP/IP) is configured in the ONECTA app settings for the HomeHub (installer reference guide section 13.1.1).

Where is the official Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps) Modbus documentation?

The source is Installer reference guide - Daikin HomeHub EKRHH (4P744838-1E), revision 2026-01, published free by Daikin at https://www.daikin.eu/content/dam/document-library/Installer-reference-guide/heat/accessories/ekrhh/EKRHH_Installer%20reference%20guide_4PEN744838-1E_English.pdf.

More Daikin Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Installer reference guide - Daikin HomeHub EKRHH · 4P744838-1E · rev. 2026-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.