CTC CTC heat pumps and controllers via BMS (Modbus TCP) Modbus register map

Updated 19 November 2026

Short answer

CTC's heat pumps and system controllers expose a BMS register list over Modbus TCP from the display's Ethernet port. Everything is a 16-bit holding register: a 1000-block of control values the BMS must refresh, settings from 61500 (hot water, heating circuits 1-4, curves, cooling, pool, solar, add-on heat), and read-only values from 62000 (temperatures, heat pump status, pressures, compressor speed, energy and smart-grid state). Each setting has companion registers holding its max, min and step.

This page lists 340 Modbus registers for the CTC CTC heat pumps and controllers via BMS (Modbus TCP) — 208 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from CTC’s own free documentation (linked below) and checked against it.

Manufacturer
CTC
Model
CTC heat pumps and controllers via BMS (Modbus TCP)
Equipment type
Heat pump
Registers
340 (208 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
CTC EcoHeat 400, CTC EcoZenith i250, CTC GSi, CTC GS, CTC EcoZenith i350, CTC EcoVent i350F, CTC EcoZenith i550, CTC EcoPart 600M, CTC EcoPart Pro, CTC EcoLogic, CTC EcoLogic S, 16260016-3
Source document
Building Management System (BMS) · 16260016-3 CR01143 · rev. 2026-02-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: CTC CTC heat pumps and controllers via BMS (Modbus TCP)

Integration in brief

Define 'Modbus TCP' under Installer/Define/Remote control on a three-port display, then read 62000-62365 with function 3 and write the 1000-block (refreshed at least every 5 minutes) with function 16. Use the 615xx settings sparingly.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 62000Outdoor temperatureINT16Outdoor temperatureRead
HR 62003Hot water temperatureINT16Hot water temperatureRead
HR 62005StatusINT16System statusRead
HR 62017Heat pump 1 (A1): StatusINT16Heat pump A1 statusRead
HR 62011Heating system 1: Primary flow temperatureINT16Heating circuit 1 flow temperatureRead
HR 62193Heat pump 1 (A1): Current RPSINT16Compressor speed A1Read
HR 62301SGModeINT16Smart-grid modeRead
HR 1015Zone mode HC1UINT16Zone mode HC1Write
HR 1100Virtual digital inBITMAP16Virtual digital inputs (SmartGrid)Write
HR 61509Heating system 1: setting room tempINT16Room setpoint HC1Read/write

Enable Modbus control & writes

In the display menu Installer > Define > Remote control, define 'Modbus TCP' (connection through the display's Ethernet port). Only displays with three connection ports support BMS over TCP/IP.

Communication loss & watchdog

The 1000-block control registers must be rewritten within 5 minutes or they are reset; they are also reset on restart.

Byte order & addressing

Network setup

Watch out for

CTC CTC heat pumps and controllers via BMS (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

340 of 340 shown
CTC CTC heat pumps and controllers via BMS (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1005ElPriceModeElectricity price level from the BMS; refresh within 5 minutes.UINT16Write1 = Low; 2 = Normal; 3 = High
HR1007DHW ModeHot water comfort level; refresh within 5 minutes.UINT16Write0 = Economy; 1 = Normal; 2 = Comfort
HR1015Zone mode HC1Heating circuit 1 mode; refresh within 5 minutes.UINT16Write0 = Off; 1 = Heat; 2 = Cool; 3 = Auto; 4 = On
HR1016Zone mode HC2Heating circuit 2 mode; refresh within 5 minutes.UINT16Write0 = Off; 1 = Heat; 2 = Cool; 3 = Auto; 4 = On
HR1017Zone mode HC3Heating circuit 3 mode; refresh within 5 minutes.UINT16Write0 = Off; 1 = Heat; 2 = Cool; 3 = Auto; 4 = On
HR1018Zone mode HC4Heating circuit 4 mode; refresh within 5 minutes.UINT16Write0 = Off; 1 = Heat; 2 = Cool; 3 = Auto; 4 = On
HR1019Zone mode CoolCooling zone mode; refresh within 5 minutes.UINT16Write0 = Off; 1 = Heat; 2 = Cool; 3 = Auto; 4 = On
HR1022Vent modeVentilation mode; refresh within 5 minutes.INT16Write0 = Normal; 1 = Forced; -1 = Reduced
HR1100Virtual digital inSoftware copies of digital inputs DI0-DI7 (e.g. SmartGrid A/B); bit = 1 closed.BITMAP16Writebit 0 = DI0; bit 1 = DI1; bit 2 = DI2; bit 3 = DI3; bit 4 = DI4; bit 5 = DI5; bit 6 = DI6; bit 7 = DI7
HR61500Hot water modeLimits readable at 60000 (max), 60001 (min), 60002 (step).INT16Read/write0 = Ecomony; 1 = Normal; 2 = Comfort
HR61501Manual Stop temperature hot waterLimits readable at 60003 (max), 60004 (min), 60005 (step).INT16× 0.1°CRead/write
HR61502Setting outlet temperature hot waterLimits readable at 60006 (max), 60007 (min), 60008 (step).INT16× 0.1°CRead/write
HR61503Extra hot water timerLimits readable at 60009 (max), 60010 (min), 60011 (step).INT16× 0.5Read/write
HR61504Maximum time heating Heat pumpLimits readable at 60012 (max), 60013 (min), 60014 (step).INT16Read/write
HR61505Maximum time hot waterLimits readable at 60015 (max), 60016 (min), 60017 (step).INT16Read/write
HR61506Minimum RPS hot waterLimits readable at 60018 (max), 60019 (min), 60020 (step).INT16× 0.1rpsRead/write
HR61507Minimum RPS PoolLimits readable at 60021 (max), 60022 (min), 60023 (step).INT16× 0.1rpsRead/write
HR61508Number of vacation days timerLimits readable at 60024 (max), 60025 (min), 60026 (step).INT16Read/write
HR61509Heating system 1: setting room tempLimits readable at 60027 (max), 60028 (min), 60029 (step).INT16× 0.1°CRead/write
HR61510Heating system 2: setting room tempLimits readable at 60030 (max), 60031 (min), 60032 (step).INT16× 0.1°CRead/write
HR61511Heating system 3: setting room tempLimits readable at 60033 (max), 60034 (min), 60035 (step).INT16× 0.1°CRead/write
HR61512Heating system 4: setting room tempLimits readable at 60036 (max), 60037 (min), 60038 (step).INT16× 0.1°CRead/write
HR61513Heating system 1: Change inclinationLimits readable at 60039 (max), 60040 (min), 60041 (step).INT16× 0.1Read/write
HR61514Heating system 2: Change inclinationLimits readable at 60042 (max), 60043 (min), 60044 (step).INT16× 0.1Read/write
HR61515Heating system 3: Change inclinationLimits readable at 60045 (max), 60046 (min), 60047 (step).INT16× 0.1Read/write
HR61516Heating system 4: Change inclinationLimits readable at 60048 (max), 60049 (min), 60050 (step).INT16× 0.1Read/write
HR61517Room1: AdjustmentLimits readable at 60051 (max), 60052 (min), 60053 (step).INT16× 0.1Read/write
HR61518Room2: AdjustmentLimits readable at 60054 (max), 60055 (min), 60056 (step).INT16× 0.1Read/write
HR61519Room3: AdjustmentLimits readable at 60057 (max), 60058 (min), 60059 (step).INT16× 0.1Read/write
HR61520Room4: AdjustmentLimits readable at 60060 (max), 60061 (min), 60062 (step).INT16× 0.1Read/write
HR61521Heat pump 1 (A1): BlockedLimits readable at 60063 (max), 60064 (min), 60065 (step).INT16Read/write0 = Blocked; 1 = Allowed
HR61531Pool: Stop Temp settingLimits readable at 60093 (max), 60094 (min), 60095 (step).INT16× 0.1°CRead/write
HR61532Pool: Maximum timeLimits readable at 60096 (max), 60097 (min), 60098 (step).INT16Read/write
HR61533Pool: Start differenceLimits readable at 60099 (max), 60100 (min), 60101 (step).INT16× 0.1Read/write
HR61534Heating system 1: Max Primary flow °CLimits readable at 60102 (max), 60103 (min), 60104 (step).INT16× 0.1°CRead/write
HR61535Heating system 2: Max Primary flow °CLimits readable at 60105 (max), 60106 (min), 60107 (step).INT16× 0.1°CRead/write
HR61536Heating system 3: Max Primary flow °CLimits readable at 60108 (max), 60109 (min), 60110 (step).INT16× 0.1°CRead/write
HR61537Heating system 4: Max Primary flow °CLimits readable at 60111 (max), 60112 (min), 60113 (step).INT16× 0.1°CRead/write
HR61538Heating system 1: Min primary flow °C 140=OffLimits readable at 60114 (max), 60115 (min), 60116 (step).INT16× 0.1°CRead/write
HR61539Heating system 2: Min primary flow °C 140=OffLimits readable at 60117 (max), 60118 (min), 60119 (step).INT16× 0.1°CRead/write
HR61540Heating system 3: Min primary flow °C 140=OffLimits readable at 60120 (max), 60121 (min), 60122 (step).INT16× 0.1°CRead/write
HR61541Heating system 4: Min primary flow °C 140=OffLimits readable at 60123 (max), 60124 (min), 60125 (step).INT16× 0.1°CRead/write
HR61542Heating system 1: Heating modeLimits readable at 60126 (max), 60127 (min), 60128 (step).INT16Read/write0 = Auto; 1 = On; 2 = Off
HR61543Heating system 2: Heating modeLimits readable at 60129 (max), 60130 (min), 60131 (step).INT16Read/write0 = Auto; 1 = On; 2 = Off
HR61544Heating system 3: Heating modeLimits readable at 60132 (max), 60133 (min), 60134 (step).INT16Read/write0 = Auto; 1 = On; 2 = Off
HR61545Heating system 4: Heating modeLimits readable at 60135 (max), 60136 (min), 60137 (step).INT16Read/write0 = Auto; 1 = On; 2 = Off
HR61546Heating system 1: Heating off, out °CLimits readable at 60138 (max), 60139 (min), 60140 (step).INT16× 0.1°CRead/write
HR61547Heating system 2: Heating off, out °CLimits readable at 60141 (max), 60142 (min), 60143 (step).INT16× 0.1°CRead/write
HR61548Heating system 3: Heating off, out °CLimits readable at 60144 (max), 60145 (min), 60146 (step).INT16× 0.1°CRead/write
HR61549Heating system 4: Heating off, out °CLimits readable at 60147 (max), 60148 (min), 60149 (step).INT16× 0.1°CRead/write
HR61550Heating system 1: Heating off timeLimits readable at 60150 (max), 60151 (min), 60152 (step).INT16Read/write
HR61551Heating system 2: Heating off timeLimits readable at 60153 (max), 60154 (min), 60155 (step).INT16Read/write
HR61552Heating system 3: Heating off timeLimits readable at 60156 (max), 60157 (min), 60158 (step).INT16Read/write
HR61553Heating system 4: Heating off timeLimits readable at 60159 (max), 60160 (min), 60161 (step).INT16Read/write
HR61554Heating system 1: Room temp night reductionLimits readable at 60162 (max), 60163 (min), 60164 (step).INT16× 0.1°CRead/write
HR61555Heating system 2: Room temp night reductionLimits readable at 60165 (max), 60166 (min), 60167 (step).INT16× 0.1°CRead/write
HR61556Heating system 3: Room temp night reductionLimits readable at 60168 (max), 60169 (min), 60170 (step).INT16× 0.1°CRead/write
HR61557Heating system 4: Room temp night reductionLimits readable at 60171 (max), 60172 (min), 60173 (step).INT16× 0.1°CRead/write
HR61558Heating system 1: Primary flow Night reductionLimits readable at 60174 (max), 60175 (min), 60176 (step).INT16× 0.1Read/write
HR61559Heating system 2: Primary flow Night reductionLimits readable at 60177 (max), 60178 (min), 60179 (step).INT16× 0.1Read/write
HR61560Heating system 3: Primary flow Night reductionLimits readable at 60180 (max), 60181 (min), 60182 (step).INT16× 0.1Read/write
HR61561Heating system 4: Primary flow Night reductionLimits readable at 60183 (max), 60184 (min), 60185 (step).INT16× 0.1Read/write
HR61562Heating system 1: Outdoor temp night reductionLimits readable at 60186 (max), 60187 (min), 60188 (step).INT16× 0.1°CRead/write
HR61563Heating system 2: Outdoor temp night reductionLimits readable at 60189 (max), 60190 (min), 60191 (step).INT16× 0.1°CRead/write
HR61564Heating system 3: Outdoor temp night reductionLimits readable at 60192 (max), 60193 (min), 60194 (step).INT16× 0.1°CRead/write
HR61565Heating system 4: Outdoor temp night reductionLimits readable at 60195 (max), 60196 (min), 60197 (step).INT16× 0.1°CRead/write
HR61566Heating system 1: Alarm low room temperatureLimits readable at 60198 (max), 60199 (min), 60200 (step).INT16× 0.1°CRead/write
HR61567Heating system 2: Alarm low room temperatureLimits readable at 60201 (max), 60202 (min), 60203 (step).INT16× 0.1°CRead/write
HR61568Heating system 3: Alarm low room temperatureLimits readable at 60204 (max), 60205 (min), 60206 (step).INT16× 0.1°CRead/write
HR61569Heating system 4: Alarm low room temperatureLimits readable at 60207 (max), 60208 (min), 60209 (step).INT16× 0.1°CRead/write
HR61570Radiator pump setting %Limits readable at 60210 (max), 60211 (min), 60212 (step).INT16%Read/write
HR61571Start at degree minuteLimits readable at 60213 (max), 60214 (min), 60215 (step).INT16Read/write
HR61572Heat pump 1 (A1): Max RPSLimits readable at 60216 (max), 60217 (min), 60218 (step).INT16× 0.1rpsRead/write
HR61582E1: Start add heat, degree minuteLimits readable at 60246 (max), 60247 (min), 60248 (step).INT16Read/write
HR61583External boiler diffLimits readable at 60249 (max), 60250 (min), 60251 (step).INT16× 0.1Read/write
HR61584Blocking additional heat outdoor temp °CLimits readable at 60252 (max), 60253 (min), 60254 (step).INT16× 0.1°CRead/write
HR61585Boiler, open mixing valve °CLimits readable at 60255 (max), 60256 (min), 60257 (step).INT16× 0.1°CRead/write
HR61586Delay stop external boilerLimits readable at 60258 (max), 60259 (min), 60260 (step).INT16Read/write
HR61587Ext boiler modeLimits readable at 60261 (max), 60262 (min), 60263 (step).INT16Read/write0 = Auto; 1 = On; 2 = Off
HR61588EHS: open shunt degreesLimits readable at 60264 (max), 60265 (min), 60266 (step).INT16× 0.1Read/write
HR61589EHS: start stop diffLimits readable at 60267 (max), 60268 (min), 60269 (step).INT16Read/write
HR61590Max immersion heater kW LowerLimits readable at 60270 (max), 60271 (min), 60272 (step).INT16× 0.1kWRead/write
HR61591Max immersion heater DHW kW UpperLimits readable at 60273 (max), 60274 (min), 60275 (step).INT16× 0.1kWRead/write
HR61602Heating system 1: Holiday reductionLimits readable at 60306 (max), 60307 (min), 60308 (step).INT16× 0.1Read/write
HR61603Heating system 2: Holiday reductionLimits readable at 60309 (max), 60310 (min), 60311 (step).INT16× 0.1Read/write
HR61604Heating system 3: Holiday reductionLimits readable at 60312 (max), 60313 (min), 60314 (step).INT16× 0.1Read/write
HR61605Heating system 4: Holiday reductionLimits readable at 60315 (max), 60316 (min), 60317 (step).INT16× 0.1Read/write
HR61606Heating system 1: Primary flow Holiday reductionLimits readable at 60318 (max), 60319 (min), 60320 (step).INT16× 0.1Read/write
HR61607Heating system 2: Primary flow Holiday reductionLimits readable at 60321 (max), 60322 (min), 60323 (step).INT16× 0.1Read/write
HR61608Heating system 3: Primary flow Holiday reductionLimits readable at 60324 (max), 60325 (min), 60326 (step).INT16× 0.1Read/write
HR61609Heating system 4: Primary flow Holiday reductionLimits readable at 60327 (max), 60328 (min), 60329 (step).INT16× 0.1Read/write
HR61610Heat pump : Diff Heat pump , degree minuteLimits readable at 60330 (max), 60331 (min), 60332 (step).INT16Read/write
HR61611Heat pump : Delay between Heat pumpLimits readable at 60333 (max), 60334 (min), 60335 (step).INT16Read/write
HR61612E1: Diff add heat, degree minuteLimits readable at 60336 (max), 60337 (min), 60338 (step).INT16Read/write
HR61613E2: Start 0-10V degree minuteLimits readable at 60339 (max), 60340 (min), 60341 (step).INT16Read/write
HR61614E2: Diff 0-10V, degree minuteLimits readable at 60342 (max), 60343 (min), 60344 (step).INT16Read/write
HR61615E3: Start EcoMiniEl, degree minuteLimits readable at 60345 (max), 60346 (min), 60347 (step).INT16Read/write
HR61616E3: Number of steps heatingLimits readable at 60348 (max), 60349 (min), 60350 (step).INT16Read/write
HR61617E3: Number of steps DHWLimits readable at 60351 (max), 60352 (min), 60353 (step).INT16Read/write
HR61618E3: Diff step EcoMiniElLimits readable at 60354 (max), 60355 (min), 60356 (step).INT16Read/write
HR61619E1: Delay add heat E1Limits readable at 60357 (max), 60358 (min), 60359 (step).INT16Read/write
HR61620E2: Delay add heat 0-10VLimits readable at 60360 (max), 60361 (min), 60362 (step).INT16Read/write
HR61621E2: Diff 0-10V delayLimits readable at 60363 (max), 60364 (min), 60365 (step).INT16Read/write
HR61622E3: Delay EcoMiniElLimits readable at 60366 (max), 60367 (min), 60368 (step).INT16Read/write
HR61623E3: Delay EcoMiniEl stepLimits readable at 60369 (max), 60370 (min), 60371 (step).INT16Read/write
HR61624Cooling: Primary flow at the outdoor temperature +20 °CLimits readable at 60372 (max), 60373 (min), 60374 (step).INT16°CRead/write
HR61625Cooling: Primary flow at the outdoor temperature +40 °CLimits readable at 60375 (max), 60376 (min), 60377 (step).INT16°CRead/write
HR61626Cooling: Min flow temperatureLimits readable at 60378 (max), 60379 (min), 60380 (step).INT16°CRead/write
HR61629Delay mixing valve setting 241=OffLimits readable at 60387 (max), 60388 (min), 60389 (step).INT16Read/write
HR61630Wood boiler start flue gas 490=OffLimits readable at 60390 (max), 60391 (min), 60392 (step).INT16× 0.1Read/write
HR61631Wood boiler start boiler temperatureLimits readable at 60393 (max), 60394 (min), 60395 (step).INT16× 0.1°CRead/write
HR61632Wood boiler hysteresisLimits readable at 60396 (max), 60397 (min), 60398 (step).INT16× 0.1Read/write
HR61633Boiler lower °CLimits readable at 60399 (max), 60400 (min), 60401 (step).INT16× 0.1°CRead/write
HR61634Boiler upper °CLimits readable at 60402 (max), 60403 (min), 60404 (step).INT16× 0.1°CRead/write
HR61635Boiler add heat °CLimits readable at 60405 (max), 60406 (min), 60407 (step).INT16× 0.1°CRead/write
HR61636Boiler DHW °CLimits readable at 60408 (max), 60409 (min), 60410 (step).INT16× 0.1°CRead/write
HR61637Diff thermostat start temp diffLimits readable at 60411 (max), 60412 (min), 60413 (step).INT16× 0.1°CRead/write
HR61638Diff thermostat stop temp diffLimits readable at 60414 (max), 60415 (min), 60416 (step).INT16× 0.1°CRead/write
HR61639Diff thermostat charge temperatureLimits readable at 60417 (max), 60418 (min), 60419 (step).INT16× 0.1°CRead/write
HR61640EcoLogic EcoZenith i550: Solar deltaT max Other: Solar start charge differenceLimits readable at 60420 (max), 60421 (min), 60422 (step).INT16× 0.1Read/write
HR61641EcoLogic EcoZenith i550: Solar deltaT min Other: Solar stop charge differenceLimits readable at 60423 (max), 60424 (min), 60425 (step).INT16× 0.1Read/write
HR61642Solar charge pump minLimits readable at 60426 (max), 60427 (min), 60428 (step).INT16Read/write
HR61643EcoLogic EcoZenith i550: Solar deltaT max borehole Other: Solar borehole charge start diffLimits readable at 60429 (max), 60430 (min), 60431 (step).INT16Read/write
HR61644EcoLogic EcoZenith i550: Solar deltaT min borehole Other: Solar borehole charge stop differenceLimits readable at 60432 (max), 60433 (min), 60434 (step).INT16Read/write
HR61645EcoHeat 400 EcoZenith i250: Solar H-tank charge temp GSi/EcoZenith i350: Solar EHS-tank harge tempLimits readable at 60435 (max), 60436 (min), 60437 (step).INT16°CRead/write
HR61646Solar: X-tank charge tempLimits readable at 60438 (max), 60439 (min), 60440 (step).INT16°CRead/write
HR61647Solar: Eco-tank charge tempLimits readable at 60441 (max), 60442 (min), 60443 (step).INT16°CRead/write
HR61648EcoHeat 400 EcoZenith i250: Solar charge H-tank start difference GSi/ EcoZenith i350: Solar EHS-tank charge start differenceLimits readable at 60444 (max), 60445 (min), 60446 (step).INT16Read/write
HR61649EcoHeat 400 EcoZenith i250: Solar H-tank charge stop difference GSi/ EcoZenith i350: Solar EHS-tank charge stop differenceLimits readable at 60447 (max), 60448 (min), 60449 (step).INT16Read/write
HR61650EcoHeat 400 EcoZenith i250: Solar H-tank charge stop temperature GSi/EcoZenith i350: Solar EHS-tank charge stop temperatureLimits readable at 60450 (max), 60451 (min), 60452 (step).INT16°CRead/write
HR61651Wood boiler buffer tank delay recharge timeLimits readable at 60453 (max), 60454 (min), 60455 (step).INT16Read/write
HR61652Setpoint for upper tank when el. heater is usedLimits readable at 60456 (max), 60457 (min), 60458 (step).INT16× 0.1Read/write
HR61653Capacity start point for charging DHWLimits readable at 60459 (max), 60460 (min), 60461 (step).INT16× 0.1Read/write
HR61654Lower temp sensor start point for charging DHWLimits readable at 60462 (max), 60463 (min), 60464 (step).INT16× 0.1°CRead/write
HR61655Ventilation modeLimits readable at 60465 (max), 60466 (min), 60467 (step).INT16Read/write
HR61656Turn night cooling on or offLimits readable at 60468 (max), 60469 (min), 60470 (step).INT16Read/write
HR61657Ventilation away modeLimits readable at 60471 (max), 60472 (min), 60473 (step).INT16Read/write
HR61658Pool EnableLimits readable at 60474 (max), 60475 (min), 60476 (step).INT16Read/write
HR61659Room temp coolingLimits readable at 60477 (max), 60478 (min), 60479 (step).INT16× 0.1°CRead/write
HR61660Cooling permitted from outdoor temp °CLimits readable at 60480 (max), 60481 (min), 60482 (step).INT16× 0.1°CRead/write
HR61661Cooling delay active (minutes)Limits readable at 60483 (max), 60484 (min), 60485 (step).INT16minRead/write
HR61662Delay cooling from heating off (minutes)Limits readable at 60486 (max), 60487 (min), 60488 (step).INT16minRead/write
HR61663Cooling start delay (minutes)Limits readable at 60489 (max), 60490 (min), 60491 (step).INT16minRead/write
HR61664Cooling diff calc delay (minutes)Limits readable at 60492 (max), 60493 (min), 60494 (step).INT16minRead/write
HR61665Primary flow temp at outdoor +20 °CLimits readable at 60495 (max), 60496 (min), 60497 (step).INT16× 0.1°CRead/write
HR61666Primary flow temp at outdoor +40 °CLimits readable at 60498 (max), 60499 (min), 60500 (step).INT16× 0.1°CRead/write
HR61667Primary flow diff at outdoor +20 °CLimits readable at 60501 (max), 60502 (min), 60503 (step).INT16× 0.1°CRead/write
HR61668Primary flow diff at outdoor +40 °CLimits readable at 60504 (max), 60505 (min), 60506 (step).INT16× 0.1°CRead/write
HR61669Cooling max time HP active (minutes)Limits readable at 60507 (max), 60508 (min), 60509 (step).INT16minRead/write
HR61670Cooling HP Charge pump speedLimits readable at 60510 (max), 60511 (min), 60512 (step).INT16Read/write
HR61671Heating program HC1Limits readable at 60513 (max), 60514 (min), 60515 (step).INT16Read/write0 = Economy; 1 = Normal; 2 = Comfort; 3 = Custom
HR61672Heating program HC2Limits readable at 60516 (max), 60517 (min), 60518 (step).INT16Read/write0 = Economy; 1 = Normal; 2 = Comfort; 3 = Custom
HR61673Heating program HC3Limits readable at 60519 (max), 60520 (min), 60521 (step).INT16Read/write0 = Economy; 1 = Normal; 2 = Comfort; 3 = Custom
HR61674Heating program HC4Limits readable at 60522 (max), 60523 (min), 60524 (step).INT16Read/write0 = Economy; 1 = Normal; 2 = Comfort; 3 = Custom
HR61675HC1 Heating curve point 1 x-value (outside temp)Limits readable at 60525 (max), 60526 (min), 60527 (step).INT16°CRead/write
HR61676HC1 Heating curve point 1 y-value (setp temp)Limits readable at 60528 (max), 60529 (min), 60530 (step).INT16°CRead/write
HR61677HC1 Heating curve point 2 x-value (outside temp)Limits readable at 60531 (max), 60532 (min), 60533 (step).INT16°CRead/write
HR61678HC1 Heating curve point 2 y-value (setp temp)Limits readable at 60534 (max), 60535 (min), 60536 (step).INT16°CRead/write
HR61679HC1 Heating curve point 3 x-value (outside temp)Limits readable at 60537 (max), 60538 (min), 60539 (step).INT16°CRead/write
HR61680HC1 Heating curve point 3 y-value (setp temp)Limits readable at 60540 (max), 60541 (min), 60542 (step).INT16°CRead/write
HR61681HC1 Heating curve point 4 x-value (outside temp)Limits readable at 60543 (max), 60544 (min), 60545 (step).INT16°CRead/write
HR61682HC1 Heating curve point 4 y-value (setp temp)Limits readable at 60546 (max), 60547 (min), 60548 (step).INT16°CRead/write
HR61683HC1 Heating curve point 5 x-value (outside temp)Limits readable at 60549 (max), 60550 (min), 60551 (step).INT16°CRead/write
HR61684HC1 Heating curve point 5 y-value (setp temp)Limits readable at 60552 (max), 60553 (min), 60554 (step).INT16°CRead/write
HR61685HC2 Heating curve point 1 x-value (outside temp)Limits readable at 60555 (max), 60556 (min), 60557 (step).INT16°CRead/write
HR61686HC2 Heating curve point 1 y-value (setp temp)Limits readable at 60558 (max), 60559 (min), 60560 (step).INT16°CRead/write
HR61687HC2 Heating curve point 2 x-value (outside temp)Limits readable at 60561 (max), 60562 (min), 60563 (step).INT16°CRead/write
HR61688HC2 Heating curve point 2 y-value (setp temp)Limits readable at 60564 (max), 60565 (min), 60566 (step).INT16°CRead/write
HR61689HC2 Heating curve point 3 x-value (outside temp)Limits readable at 60567 (max), 60568 (min), 60569 (step).INT16°CRead/write
HR61690HC2 Heating curve point 3 y-value (setp temp)Limits readable at 60570 (max), 60571 (min), 60572 (step).INT16°CRead/write
HR61691HC2 Heating curve point 4 x-value (outside temp)Limits readable at 60573 (max), 60574 (min), 60575 (step).INT16°CRead/write
HR61692HC2 Heating curve point 4 y-value (setp temp)Limits readable at 60576 (max), 60577 (min), 60578 (step).INT16°CRead/write
HR61693HC2 Heating curve point 5 x-value (outside temp)Limits readable at 60579 (max), 60580 (min), 60581 (step).INT16°CRead/write
HR61694HC2 Heating curve point 5 y-value (setp temp)Limits readable at 60582 (max), 60583 (min), 60584 (step).INT16°CRead/write
HR61695HC3 Heating curve point 1 x-value (outside temp)Limits readable at 60585 (max), 60586 (min), 60587 (step).INT16°CRead/write
HR61696HC3 Heating curve point 1 y-value (setp temp)Limits readable at 60588 (max), 60589 (min), 60590 (step).INT16°CRead/write
HR61697HC3 Heating curve point 2 x-value (outside temp)Limits readable at 60591 (max), 60592 (min), 60593 (step).INT16°CRead/write
HR61698HC3 Heating curve point 2 y-value (setp temp)Limits readable at 60594 (max), 60595 (min), 60596 (step).INT16°CRead/write
HR61699HC3 Heating curve point 3 x-value (outside temp)Limits readable at 60597 (max), 60598 (min), 60599 (step).INT16°CRead/write
HR61700HC3 Heating curve point 3 y-value (setp temp)Limits readable at 60600 (max), 60601 (min), 60602 (step).INT16°CRead/write
HR61701HC3 Heating curve point 4 x-value (outside temp)Limits readable at 60603 (max), 60604 (min), 60605 (step).INT16°CRead/write
HR61702HC3 Heating curve point 4 y-value (setp temp)Limits readable at 60606 (max), 60607 (min), 60608 (step).INT16°CRead/write
HR61703HC3 Heating curve point 5 x-value (outside temp)Limits readable at 60609 (max), 60610 (min), 60611 (step).INT16°CRead/write
HR61704HC3 Heating curve point 5 y-value (setp temp)Limits readable at 60612 (max), 60613 (min), 60614 (step).INT16°CRead/write
HR61705HC4 Heating curve point 1 x-value (outside temp)Limits readable at 60615 (max), 60616 (min), 60617 (step).INT16°CRead/write
HR61706HC4 Heating curve point 1 y-value (setp temp)Limits readable at 60618 (max), 60619 (min), 60620 (step).INT16°CRead/write
HR61707HC4 Heating curve point 2 x-value (outside temp)Limits readable at 60621 (max), 60622 (min), 60623 (step).INT16°CRead/write
HR61708HC4 Heating curve point 2 y-value (setp temp)Limits readable at 60624 (max), 60625 (min), 60626 (step).INT16°CRead/write
HR61709HC4 Heating curve point 3 x-value (outside temp)Limits readable at 60627 (max), 60628 (min), 60629 (step).INT16°CRead/write
HR61710HC4 Heating curve point 3 y-value (setp temp)Limits readable at 60630 (max), 60631 (min), 60632 (step).INT16°CRead/write
HR61711HC4 Heating curve point 4 x-value (outside temp)Limits readable at 60633 (max), 60634 (min), 60635 (step).INT16°CRead/write
HR61712HC4 Heating curve point 4 y-value (setp temp)Limits readable at 60636 (max), 60637 (min), 60638 (step).INT16°CRead/write
HR61713HC4 Heating curve point 5 x-value (outside temp)Limits readable at 60639 (max), 60640 (min), 60641 (step).INT16°CRead/write
HR61714HC4 Heating curve point 5 y-value (setp temp)Limits readable at 60642 (max), 60643 (min), 60644 (step).INT16°CRead/write
HR61715Cooling curve point 1 x-value (outside temp)Limits readable at 60645 (max), 60646 (min), 60647 (step).INT16°CRead/write
HR61716Cooling curve point 1 y-value (setp temp)Limits readable at 60648 (max), 60649 (min), 60650 (step).INT16°CRead/write
HR61717Cooling curve point 2 x-value (outside temp)Limits readable at 60651 (max), 60652 (min), 60653 (step).INT16°CRead/write
HR61718Cooling curve point 2 y-value (setp temp)Limits readable at 60654 (max), 60655 (min), 60656 (step).INT16°CRead/write
HR61719Cooling curve point 3 x-value (outside temp)Limits readable at 60657 (max), 60658 (min), 60659 (step).INT16°CRead/write
HR61720Cooling curve point 3 y-value (setp temp)Limits readable at 60660 (max), 60661 (min), 60662 (step).INT16°CRead/write
HR61721Cooling curve point 4 x-value (outside temp)Limits readable at 60663 (max), 60664 (min), 60665 (step).INT16°CRead/write
HR61722Cooling curve point 4 y-value (setp temp)Limits readable at 60666 (max), 60667 (min), 60668 (step).INT16°CRead/write
HR61723Cooling curve point 5 x-value (outside temp)Limits readable at 60669 (max), 60670 (min), 60671 (step).INT16°CRead/write
HR61724Cooling curve point 5 y-value (setp temp)Limits readable at 60672 (max), 60673 (min), 60674 (step).INT16°CRead/write
HR61725Heating system 1: Heating on timeLimits readable at 60675 (max), 60676 (min), 60677 (step).INT16Read/write
HR61726Heating system 2: Heating on timeLimits readable at 60678 (max), 60679 (min), 60680 (step).INT16Read/write
HR61727Heating system 3: Heating on timeLimits readable at 60681 (max), 60682 (min), 60683 (step).INT16Read/write
HR61728Heating system 4: Heating on timeLimits readable at 60684 (max), 60685 (min), 60686 (step).INT16Read/write
HR62000Outdoor temperatureINT16× 0.1°CRead
HR62001Stop temperature DHWINT16× 0.1°CRead
HR62002Setpoint outlet temperature DHWINT16°CRead
HR62003Hot water temperatureINT16× 0.1°CRead
HR62004Delay mixing valveINT16Read
HR62005StatusINT16Read0 = HP upper; 1 = HP lower; 2 = Add; 3 = HP + Add; 4 = HC; 5 = DHW; 6 = Pool; 7 = Off; 8 = Heating mix; 9 = Wood; 10 = DHW/HC; 11 = Cooling; 12 = Swap
HR62006Radiator WaterINT16× 0.1Read
HR62007Heating system 1: Temperature setpoint primary flowINT16× 0.1°CRead
HR62008Heating system 2: Temperature setpoint primary flowINT16× 0.1°CRead
HR62009Heating system 3: Temperature setpoint primary flowINT16× 0.1°CRead
HR62010Heating system 4: Temperature setpoint primary flowINT16× 0.1°CRead
HR62011Heating system 1: Primary flow temperatureINT16× 0.1°CRead
HR62012Heating system 2: Primary flow temperatureINT16× 0.1°CRead
HR62013Heating system 3: Primary flow temperatureINT16× 0.1°CRead
HR62014Heating system 4: Primary flow temperatureINT16× 0.1°CRead
HR62015Return tempINT16× 0.1°CRead
HR62016DHW circulationINT16Read
HR62017Heat pump 1 (A1): StatusINT16Read0 = Compressor_off_start_delay; 1 = Compressor_off_redy_to_start; 2 = Compressor_wait_until_flow; 3 = Comperssor_on_heating; 4 = Defrost_active; 5 = Compressor_on_cooling; 6 = Compressor_off_blocked; 7 = Compressor_off_alarm; 8 = Function_test; 30 = HP not defined; 31 = Compressor not enabled; 32 = Communication error; 33 = Charge dhw
HR62027Heat pump 1 (A1) HP inINT16× 0.1Read
HR62037Heat pump 1 (A1) HP outINT16× 0.1Read
HR62047Heat pump 1 (A1): Discharge temperatureINT16× 0.1°CRead
HR62057Heat pump 1 (A1): Suction gas temperatureINT16× 0.1°CRead
HR62067Heat pump 1 (A1): High pressureINT16× 0.1Read
HR62077Heat pump 1 (A1): Low PressureINT16× 0.1Read
HR62087Heat pump 1 (A1): Brine inINT16× 0.1Read
HR62097Heat pump 1 (A1): Brine outINT16× 0.1Read
HR62107Heat pump 1 (A1): Charge pumpINT16× 0.1Read
HR62117Heat pump 1 (A1): Brine pumpINT16× 0.1Read
HR62127Heat pump 1 (A1): FanINT16× 0.1Read
HR62137Heat pump 1 (A1): Defrost timerINT16Read
HR62147Heat pump 1 (A1): Outdoor tempINT16× 0.1°CRead
HR62157Heat pump 1 (A1): Software versionINT16Read
HR62167Degree minuteINT16× 0.1Read
HR62168Power kW immersion heaterINT16× 0.1kWRead
HR62169Power kW immersion heater lowerINT16× 0.1kWRead
HR62170Maximum currentINT16× 0.1Read
HR62171Current L1INT16× 0.1Read
HR62172Current L2INT16× 0.1Read
HR62173Current L3INT16× 0.1Read
HR62174Pump Diff thermostatINT16Read
HR62175Diff thermostat °CINT16× 0.1°CRead
HR62176EHS: TemperatureINT16× 0.1°CRead
HR62177EHS: Primary flow -> ModeINT16Read
HR62178Pool ModeINT16Read
HR62179Pool: TemperatureINT16× 0.1°CRead
HR62180Pool: Stop temperatureINT16× 0.1°CRead
HR62181Solar: ModeINT16Read0 = Off; 1 = On
HR62182Solar: Temperature outINT16× 0.1°CRead
HR62183Solar: Temperature inINT16× 0.1°CRead
HR62184Solar: Pump panelINT16Read
HR62185Tank TimerINT16Read
HR62186doc 62186-62187Stat: Total Operation32-bit counter: low word first (LSB at 62186, MSB at 62187).UINT32CDABRead
HR62191Stat: Immersion heater kWhLow word of the immersion heater kWh counter (printed signed); high word at 62329.INT16kWhRead
HR62192Function TestINT16Read
HR62193Heat pump 1 (A1): Current RPSINT16× 0.1rpsRead
HR62203Current room temp 1INT16× 0.1°CRead
HR62204Current room temp 2INT16× 0.1°CRead
HR62205Current room temp 3INT16× 0.1°CRead
HR62206Current room temp 4INT16× 0.1°CRead
HR62207System TypeINT16Read
HR62208Wood: Flue gas temperature (B8)INT16°CRead
HR62209Wood: Temperature boiler (B9)INT16°CRead
HR62210E1: Boiler temperature (B9)INT16× 0.1°CRead
HR62211E1: Temperature boiler out (B10)INT16× 0.1°CRead
HR62212E2: Number of stepsINT16Read
HR62213E3: StatusINT16Read
HR62214doc 62214-62215State: Compressor 1 operating time32-bit counter: low word first (LSB at 62214, MSB at 62215).UINT32CDABRead
HR62234State: Compressor 1 last 24hUINT16Read
HR62244Software version Display month dayINT16Read
HR62245Software version Display yearINT16Read
HR62246Heating system 1 statusINT16Read0 = Heating off; 1 = Vacation; 2 = Night reduction; 3 = On (normal mode)
HR62247Heating system 2 statusINT16Read0 = Heating off; 1 = Vacation; 2 = Night reduction; 3 = On (normal mode)
HR62248Heating system 3 statusINT16Read0 = Heating off; 1 = Vacation; 2 = Night reduction; 3 = On (normal mode)
HR62249Heating system 4 statusINT16Read0 = Heating off; 1 = Vacation; 2 = Night reduction; 3 = On (normal mode)
HR62250Ext buffer tank upper B41INT16× 0.1Read
HR62251Ext buffer tank lower B42INT16× 0.1Read
HR62252Ext DHW buffer tank B43INT16× 0.1Read
HR62253Product typeINT16Read
HR62254Heat pump 1 (A1) typeINT16Read
HR62264Heat pump 1 (A1) compressor modelINT16Read
HR62274Setpoint lower tankINT16× 0.1Read
HR62275Actual temperature DHW lowerINT16× 0.1°CRead
HR62276Actual temperature DHWINT16× 0.1°CRead
HR62277Actual temperature tank solar coilINT16× 0.1°CRead
HR62278Calculated setpoint for upper tank when el. heater is usedINT16× 0.1Read
HR62279Current DHW capacity in percentINT16× 0.1%Read
HR62280Exhaust fan speed percentINT16%Read
HR62281Highest measured CO2INT16Read
HR62282Highest measured humidityINT16Read
HR62283Days until filter maintenanceINT16Read
HR62284Ventilation night cooling statusINT16Read
HR62288Cooling tank setpINT16× 0.1Read
HR62289Cooling tank tempINT16× 0.1°CRead
HR62290Active cooling return tempINT16× 0.1°CRead
HR62291Heat pump 1 (A1) Primary system flowINT16× 0.1Read
HR62301SGModeINT16Read0 = None/Normal; 1 = Block; 2 = Low price; 3 = High cap
HR62302Elspot Price/MWh Integer (Currency depending on region)INT16Read
HR62303Elspot Price/MWh 4 decimalsUINT16Read
HR62304RadiatorPump1UINT16Read
HR62305RadiatorPump2UINT16Read
HR62306RadiatorPump3_G3UINT16Read
HR62307RadiatorPump4_G4UINT16Read
HR62308Heating system 1: Shunt stateUINT16Read0 = Close; 1 = Inactive; 2 = Open
HR62309Heating system 2: Shunt stateUINT16Read0 = Close; 1 = Inactive; 2 = Open
HR62310Heating system 3: Shunt stateUINT16Read0 = Close; 1 = Inactive; 2 = Open
HR62311Heating system 4: Shunt stateUINT16Read0 = Close; 1 = Inactive; 2 = Open
HR62312PumpG41 Extern DHWUINT16Read
HR62313HotWaterValveUINT16Read
HR62314ExtBoilerOnUINT16Read
HR62315EL1 RelayBITMAP16Readbit 0 = Relay A; bit 1 = Relay B
HR62316EL2 RelayBITMAP16Readbit 0 = Relay A; bit 1 = Relay B
HR62317EL3 RelayBITMAP16Readbit 0 = Relay A; bit 1 = Relay B
HR62318ElHeater3_6kWUINT16Read
HR62319EVK: Shunt stateUINT16Read0 = Close; 1 = Inactive; 2 = Open
HR62320ExtBoiler: Shunt stateUINT16Read0 = Close; 1 = Inactive; 2 = Open
HR62321Active Cooling: ValveUINT16Read
HR62322Active Cooling: DemandUINT16Read
HR62323DHWPump: 0-100Hot water pump output, printed as 0-100 with no unit.UINT16Read
HR62324SolarTankSelectionUINT16Read
HR62325SolarBedrockSelectionUINT16Read
HR62326HotWaterValve2UINT16Read
HR62327E4UINT16Read
HR62328E1UINT16Read
HR62329Stat: Immersion heater kWh MSBHigh word of the immersion heater kWh counter (low word 62191).UINT16Read
HR62330Current room temp coolingINT16× 0.1°CRead
HR62331HP1 Power consumption kWUINT16× 0.1kWRead
HR62341doc 62341-62342Compressor 1 Power consumption kWh32-bit counter: low word first (LSB at 62341, MSB at 62342).UINT32CDABkWhRead
HR62361Power kW immersion heater(s)UINT16× 0.1kWRead
HR62362HBT top tempUINT16°CRead
HR62363DHW tank top tempUINT16°CRead
HR62364Cooling tank top tempUINT16°CRead
HR62365Periodic extra DHW statusUINT16Read0 = Periodic extra DHW not defined; 1 = Periodic extra DHW active; 2 = Periodic extra DHW off, normal; 3 = Periodic extra DHW off, last DHW increase failed

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the CTC CTC heat pumps and controllers via BMS (Modbus TCP)

What Modbus registers does the CTC CTC heat pumps and controllers via BMS (Modbus TCP) have?

This map lists 340 registers: 340 holding registers. 208 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the CTC CTC heat pumps and controllers via BMS (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document says the base address is always 0 ('Offset: 0'), so the printed register number is the wire address: 61502 is requested as 61502 and 1000 as 1000. All registers are above standard Modbus numbering (larger than 49999) except the 1000/1100 control block.

What byte order does the CTC CTC heat pumps and controllers via BMS (Modbus TCP) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the CTC CTC heat pumps and controllers via BMS (Modbus TCP)?

Start with HR 62000 Outdoor temperature (Outdoor temperature); HR 62003 Hot water temperature (Hot water temperature); HR 62005 Status (System status); HR 62017 Heat pump 1 (A1): Status (Heat pump A1 status); HR 62011 Heating system 1: Primary flow temperature (Heating circuit 1 flow temperature); HR 62193 Heat pump 1 (A1): Current RPS (Compressor speed A1); HR 62301 SGMode (Smart-grid mode); HR 1015 Zone mode HC1 (Zone mode HC1); HR 1100 Virtual digital in (Virtual digital inputs (SmartGrid)); HR 61509 Heating system 1: setting room temp (Room setpoint HC1).

How do I enable Modbus control of the CTC CTC heat pumps and controllers via BMS (Modbus TCP)?

In the display menu Installer > Define > Remote control, define 'Modbus TCP' (connection through the display's Ethernet port). Only displays with three connection ports support BMS over TCP/IP.

What happens when the CTC CTC heat pumps and controllers via BMS (Modbus TCP) loses Modbus communication?

The 1000-block control registers must be rewritten within 5 minutes or they are reset; they are also reset on restart.

Where is the official CTC CTC heat pumps and controllers via BMS (Modbus TCP) Modbus documentation?

The source is Building Management System (BMS) (16260016-3 CR01143), revision 2026-02-02, published free by CTC at https://ctc.se/file-download/8d8da8b1da79dae7a2f41a08c712f910.pdf.

Other pumps register maps

All pumps Modbus register maps →

Source: Building Management System (BMS) · 16260016-3 CR01143 · rev. 2026-02-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.