- Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
Heat pump (water-to-air heat pump controller) · Modbus register map
Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus register map
Updated 19 November 2026
The Bosch Control Air 5600 is a BACnet-native DDC controller for water-to-air heat pumps whose EIA-485 port can also run Modbus RTU or N2. The integration points list gives each point a BACnet object and a Modbus register. This map holds the binary commands, alarm and status bits and the mode registers; the floating-point temperatures and setpoints are left out.
This page lists 86 Modbus registers for the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Bosch’s own free documentation (linked below) and checked against it.
- Manufacturer
- Bosch
- Model
- Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
- Equipment type
- Heat pump (water-to-air heat pump controller)
- Registers
- 86 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- Water-to-air standard software, IPL version 1.03
- Also known as
- Control Air 5600, IPL WAZ, IPL_WAZ_1_03, Bosch water-to-air DDC controller, BTC 761601101
Integration notes: Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
Set the BAS port to Modbus and EIA-485, address the controller with the rotary dials, then poll discrete input 10002 (unit in alarm) and the UPM alarm bits, read the mode registers (30059/30060) and command occupancy with coil 00001.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Occupancy Command (BAS) | BIT | BAS occupancy command | Read/write |
| DI 1 | Alarm Status | BIT | Unit in alarm | Read |
| DI 7 | Comp Stage1 Output Cmd | BIT | Compressor stage 1 output | Read |
| DI 34 | UPM Safety - High Pressure Alarm | BIT | UPM high-pressure alarm | Read |
| IR 59 | Zone Mode Status | INT16 | Zone mode status | Read |
| HR 123 | Set Zone Mode | INT16 | Set zone mode | Read/write |
| CO 5 | BAS Loop Enable/Disable | BIT | BAS loop enable (heat/cool allowed) | Read/write |
Enable Modbus control & writes
Communications jumper in the top (EIA-485) position; BAS Port Settings DIP switches SW3/SW4 select Modbus and SW1/SW2 the baud (9.6, 19.2, 38.4 or 76.8 kbps). The Applications Manual gives the switch table.
Byte order & addressing
- All analog values are floats with an unstated word order, so only the binary and signed points are listed here.
- Runtime and UPM reset coils are momentary: write 1, then 0.
Network setup
- Rotary dials (tens/ones) set the address up to 99; the controller only reads them at power-up.
- Parity, stop bits and default address are not stated in the documents.
Watch out for
- Occupancy command (coil 00001) defaults to unoccupied, which keeps the unit off until the BAS sets it.
- Coil 00006 (BAS loop enable) must be 1 for heating/cooling.
Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | Occupancy Command (BAS) | BV:1 | BIT | Read/write | 0 = Unoccupied; 1 = Occupied (Enables Unit Operation) | |||
| CO | 1doc 00002 | Compressor 1 Runtime Reset | BV:13; momentary: write 1 then 0 | BIT | Read/write | 0 = Reset Off; 1 = Reset On | |||
| CO | 2doc 00003 | Compressor 2 Runtime Reset | BV:14; momentary: write 1 then 0 | BIT | Read/write | 0 = Reset Off; 1 = Reset On | |||
| CO | 3doc 00004 | Fan Response for Comp Lockout | BV:7 | BIT | Read/write | 0 = Do not lock fan upon compressor lockout; 1 = Lock fan upon compressor lockout | |||
| CO | 5doc 00006 | BAS Loop Enable/Disable | BV:23 | BIT | Read/write | 0 = Disable Heat/Cool; 1 = Allow Heat/Cool Operation | |||
| CO | 6doc 00007 | Reset Fan Runtime | BV:19; momentary: write 1 then 0 | BIT | Read/write | 0 = Reset Off; 1 = Reset On | |||
| CO | 8doc 00009 | UPM Reset | BV:25; momentary: write 1 then 0 | BIT | Read/write | 0 = Reset Off; 1 = Reset On | |||
| CO | 9doc 00010 | Sensor Override Enable/Disable | BV:95 | BIT | Read/write | 0 = ZS Sensor Override NOT Allowed; 1 = ZS Sensor Override Allowed | |||
| CO | 10doc 00011 | Enable/Disable Fan Status Switch in IEM | BV:67 | BIT | Read/write | 0 = FSS on IEM disabled | |||
| CO | 11doc 00012 | Enable/Disable Valve Switch in IEM | BV:69 | BIT | Read/write | 0 = VES on IEM disabled | |||
| CO | 12doc 00013 | BAS Smoke Input / Emergency Shutdown | BV:75 | BIT | Read/write | 0 = Normal | |||
| CO | 13doc 00014 | Smoke Alarm Enable/Disable | BV:71 | BIT | Read/write | 0 = SDS on IEM disabled; 1 = SDS on IEM Enabled | |||
| DI | 0doc 10001 | Duplicate Input 1&2 Alarm | BV:2 | BIT | Read | 0 = Normal; 1 = Alarm (Check input configuration for conflicts) | |||
| DI | 1doc 10002 | Alarm Status | BV:24 | BIT | Read | 0 = System Normal; 1 = System in Alarm | |||
| DI | 2doc 10003 | Aux Heat Output Cmd | BV:20 | BIT | Read | 0 = Aux Heat Off; 1 = Aux Heat On | |||
| DI | 3doc 10004 | UPM Safety - Brownout Alarm | BV:10 | BIT | Read | 0 = Normal; 1 = Brownout Alarm (UPM-I code = 5; UPM-II code = 7) | |||
| DI | 4doc 10005 | Circulation Pump Output Command | BV:3 | BIT | Read | 0 = Pump Running; 1 = Pump Off | |||
| DI | 5doc 10006 | Compressor 1 Runtime | BV:35; the source prints the fan-mode text in this row, so states are not given | BIT | Read | ||||
| DI | 6doc 10007 | Compressor 2 Runtime | BV:36 | BIT | Read | 0 = Normal; 1 = Timer Has Expired | |||
| DI | 7doc 10008 | Comp Stage1 Output Cmd | BV:11 | BIT | Read | 0 = Compressor 1 Off; 1 = Compressor 1 On | |||
| DI | 8doc 10009 | Comp Stage2 Output Cmd | BV:12 | BIT | Read | 0 = Compressor 2 Off; 1 = Compressor 2 On | |||
| DI | 9doc 10010 | UPM Safety - High Condensate Alarm | BV:9 | BIT | Read | 0 = Normal; 1 = Condensate Overflow Alarm(UPM-I code = 4; UPM-II code = 6) | |||
| DI | 10doc 10011 | Fan Output Cmd | BV:17 | BIT | Read | 0 = Fan Output Off; 1 = Fan Output On | |||
| DI | 11doc 10012 | Secondary Condensate Pump Alarm | BV:50 | BIT | Read | 0 = Normal; 1 = Alarm Active | |||
| DI | 12doc 10013 | Night Setback (NSB) Status | BV:22 | BIT | Read | 0 = Night Setback disabled; 1 = Night Setback enabled | |||
| DI | 13doc 10014 | Occupancy Status | BV:21 | BIT | Read | 0 = Unoccupied; 1 = Occupied | |||
| DI | 14doc 10015 | Economizer Cooling Command | BV:92 | BIT | Read | 0 = On; 1 = Off | |||
| DI | 15doc 10016 | High Cooling Supply Air Temperature in DAC | BV:86 | BIT | Read | 0 = Normal; 1 = Alarm Active | |||
| DI | 16doc 10017 | Condenser Water Valve Output | BV:79 | BIT | Read | 0 = Closed; 1 = Open | |||
| DI | 17doc 10018 | Discharge Air Temperature Sensor | BV:31 | BIT | Read | 0 = Sensor Normal; 1 = Sensor Failure Alarm (Check Sensor Hardware Configuration) | |||
| DI | 18doc 10019 | Damper End Switch | BV:93 | BIT | Read | 0 = Damper Closed; 1 = Damper Open | |||
| DI | 19doc 10020 | Damper Command | BV:49 | BIT | Read | 0 = Closed; 1 = Open | |||
| DI | 20doc 10021 | High Discharge Air Temperature | BV:29 | BIT | Read | 0 = Normal; 1 = Alarm | |||
| DI | 21doc 10022 | Discharge Air Temperature Alarm | BV:30 | BIT | Read | 0 = Normal; 1 = Low DAT Alarm | |||
| DI | 22doc 10023 | Digital Override Lock Alarm | BV:37 | BIT | Read | 0 = Normal; 1 = Digital Override Enabled Alarm | |||
| DI | 23doc 10024 | Differential Pressure Switch (DPS) Alarm | BV:77 | BIT | Read | 0 = Normal; 1 = Alarm | |||
| DI | 24doc 10025 | Hot Gas ReHeat Valve Status | BV:44 | BIT | Read | 0 = Valve Off; 1 = Valve On | |||
| DI | 25doc 10026 | Entering Water Temperature Sensor Alarm | BV:80 | BIT | Read | 0 = Normal; 1 = Sensor Failure Alarm (Check Hardware) | |||
| DI | 26doc 10027 | Fan Hand Mode Alarm | BV:83; fan running but not commanded by the controller | BIT | Read | ||||
| DI | 27doc 10028 | Fan Running Status | BV:66 | BIT | Read | 0 = Off; 1 = On - Fan Running | |||
| DI | 28doc 10029 | Filter Service Alarm | BV:40 | BIT | Read | 0 = Off; 1 = Service Filter Alarm | |||
| DI | 29doc 10030 | UPM Safety - Condenser Coil Freeze Alarm | BV:8 | BIT | Read | 0 = Normal; 1 = Condenser Freeze Alarm(UPM-I code = 3; UPM-II codes = 5,9) | |||
| DI | 30doc 10031 | UPM Safety - Evaporator Coil Freeze Alarm | BV:90 | BIT | Read | 0 = Normal; 1 = Evaporator Freeze Alarm (UPM-I code = 6; UPM-II codes = 8,10 | |||
| DI | 31doc 10032 | Air Economizer Status | BV:6 | BIT | Read | 0 = Inactive; 1 = Active | |||
| DI | 33doc 10034 | Boilerless Status | BV:91 | BIT | Read | 0 = Off; 1 = On (Electric Heating) | |||
| DI | 34doc 10035 | UPM Safety - High Pressure Alarm | BV:5 | BIT | Read | 0 = Normal; 1 = High Pressure Alarm (UPM-I code = 1; UPM-II codes = 1,3) | |||
| DI | 36doc 10037 | Low Heating Supply Air Temperature in DAC | BV:149 | BIT | Read | 0 = Normal; 1 = Active | |||
| DI | 37doc 10038 | Inputs Override Status | BV:38 | BIT | Read | 0 = Normal; 1 = Software Lock Enabled | |||
| DI | 38doc 10039 | UPM Safety - Low Pressure Alarm | BV:4 | BIT | Read | 0 = Normal; 1 = Low Pressure Alarm (UPM-I code = 2; UPM-II codes = 2,4) | |||
| DI | 40doc 10041 | High Leaving Water Temperature | BV:32 | BIT | Read | 0 = Normal; 1 = Alarm | |||
| DI | 41doc 10042 | Low Leaving Water Temperature | BV:33 | BIT | Read | 0 = Normal; 1 = Alarm | |||
| DI | 42doc 10043 | Leaving Water Temperature Sensor Failure | BV:34 | BIT | Read | 0 = Normal; 1 = Sensor Failure (Check Sensor Hardware | |||
| DI | 43doc 10044 | Low Mixed Air Temperature | BV:89 | BIT | Read | 0 = Normal; 1 = Alarm | |||
| DI | 44doc 10045 | Mix Air Temperature Sensor Failure | BV:88 | BIT | Read | 0 = Normal; 1 = Sensor Failure (Check Sensor Hardware | |||
| DI | 45doc 10046 | Outside Air Temperature Sensor Failure | BV:87 | BIT | Read | 0 = Normal; 1 = Sensor Failure (Check Sensor Hardware | |||
| DI | 46doc 10047 | Circulation Pump Switch Failure Alarm | BV:56 | BIT | Read | 0 = Normal; 1 = Active | |||
| DI | 47doc 10048 | Pump Switch Status | BV:57 | BIT | Read | 0 = Off; 1 = Pump Switch Detected | |||
| DI | 48doc 10049 | Circulation Pump Switch In Hand Alarm | BV:58; pump running but not commanded by the controller | BIT | Read | ||||
| DI | 49doc 10050 | Reversing Valve Output Status | BV:15 | BIT | Read | 0 = Reversing Valve De-energized; 1 = Reversing Valve Energized | |||
| DI | 50doc 10051 | Static Air Pressure Sensor Hardware Alarm | BV:65 | BIT | Read | 0 = Normal; 1 = Sensor Failure (Check Static Pressure Hardware Configuration | |||
| DI | 51doc 10052 | Supply Air Fan Switch Failure | BV:82 | BIT | Read | 0 = Normal; 1 = Alarm (Check Fan Hardware) | |||
| DI | 52doc 10053 | High Static Pressure Alarm | BV:64 | BIT | Read | 0 = Normal; 1 = High Static Pressure | |||
| DI | 53doc 10054 | Smoke Event Alarm Notification | BV:81 | BIT | Read | 0 = Normal; 1 = Alarm | |||
| DI | 54doc 10055 | Smoke Event Status | BV:70 | BIT | Read | 0 = Normal; 1 = Smoke Detector Active | |||
| DI | 55doc 10056 | CO2 Hardware Failure Alarm | BV:51 | BIT | Read | 0 = Normal; 1 = Sensor Failure (Check CO2 Hardware Configuration) | |||
| DI | 56doc 10057 | High CO2 Alarm | BV:48 | BIT | Read | 0 = Normal; 1 = High CO2 Level | |||
| DI | 57doc 10058 | ZS Zone Sensor Hardware Failure Alarm | BV:28 | BIT | Read | 0 = Normal; 1 = Sensor Failure (Check: ZS Sensor Hardware) | |||
| DI | 58doc 10059 | Remote Temperature Sensor Hardware Failure Alarm | BV:43 | BIT | Read | 0 = Normal; 1 = Sensor Failure (Check Remote Sensor Hardware) | |||
| DI | 59doc 10060 | High Remote Temperature Alarm | BV:41 | BIT | Read | 0 = Normal; 1 = High Zone Temperature | |||
| DI | 60doc 10061 | Low Remote Temperature Alarm | BV:42 | BIT | Read | 0 = Normal; 1 = Low Zone Temperature | |||
| DI | 61doc 10062 | High ZS Zone Sensor Temperature Alarm | BV:26 | BIT | Read | 0 = Normal; 1 = High Zone Temperature | |||
| DI | 62doc 10063 | Low ZS Zone Sensor Temperature Alarm | BV:27 | BIT | Read | 0 = Normal; 1 = Low Zone Temperature | |||
| DI | 63doc 10064 | UPM Input Alarm | BV:39 | BIT | Read | 0 = UPM Connected; 1 = UPM Connection Failure(Check Alarm Hardware Configuration) | |||
| DI | 64doc 10065 | Valve End Switch Status | BV:68 | BIT | Read | 0 = Off; 1 = Valve End Switch Detected | |||
| DI | 65doc 10066 | Valve Switch Hand | BV:150; valve engaged but not commanded by the controller | BIT | Read | ||||
| DI | 66doc 10067 | Valve End Switch Alarm | BV:151 | BIT | Read | 0 = Normal; 1 = Active | |||
| DI | 67doc 10068 | High Humidity Alarm | BV:45 | BIT | Read | 0 = Normal; 1 = High Humidity | |||
| DI | 68doc 10069 | Low Humidity Alarm | BV:46 | BIT | Read | 0 = Normal; 1 = Low Humidity | |||
| DI | 69doc 10070 | Humidity Sensor Hardware Failure Alarm | BV:47 | BIT | Read | 0 = Normal; 1 = Sensor Failure (Check RH Sensor Hardware Configuration) | |||
| DI | 71doc 10072 | Override Status | BV:94 | BIT | Read | 0 = Normal; 1 = ZS Sensor in Override Mode | |||
| DI | 103doc 10104 | UPM Safety - A2L Alarm | BV:104 | BIT | Read | 0 = Normal; 1 = A2L Alarm (UPM-I code = 7; UPM-II codes = 11) | |||
| DI | 105doc 10106 | UPM Safety - Communication Alarm | BV:106 | BIT | Read | 0 = Normal; 1 = Communication Alarm (UPM-II codes = 12) | |||
| IR | 58doc 30059 | Fan Mode Status | MSV:1 | INT16 | Read | 1 = Auto (Cycel with Compressor); 4 = On | |||
| IR | 59doc 30060 | Zone Mode Status | MSV:4 | INT16 | Read | 1 = Auto; 2 = Heat; 3 = Cool; 5 = Off | |||
| HR | 122doc 40123 | Set Fan Mode | MSV:2 | INT16 | Read/write | 1 = Auto (Cycel with Compressor); 4 = On | |||
| HR | 123doc 40124 | Set Zone Mode | MSV:3 | INT16 | Read/write | 1 = Auto; 2 = Heat; 3 = Cool; 5 = Off |
Notes on this map
- Left out: every point typed 'Holding Register (Float)' or 'Input Register (Float)' (setpoints, temperatures, configuration values, demand percentages). They are IEEE floats over two registers, and neither the points list nor the Control Air 5600 Applications Manual states the word order.
- Also left out: row 39 'Cooling Demand Percentage' (type cell cut to 'Holding', probably float) and rows 18-19 (Equipment Touch selections with no register).
- The 'Signed' multi-state registers are treated as one 16-bit signed register each.
- Row 91 (Compressor 1 Runtime, discrete input 10006) carries the fan-mode text in the source; its states are not given here. Compressor 2 runtime (10007) is 1 = run-time timer expired.
- Some state texts are printed the opposite way to their neighbours (10015 economizer cooling 0 = On, 10005 circulation pump 0 = running); they are copied as printed.
- The same register list appears as section 13 of the Control Air 5600 Applications Manual BTC 761601101 C (01.2026), which also covers the DIP switches and rotary address: https://www.bosch-homecomfort.com/us/media/country_pool/documents/application-manual/controls/control_air_5600_applications_manual_01.2026.pdf
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
What Modbus registers does the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) have?
This map lists 86 registers: 12 coils, 70 discrete inputs, 2 input registers, 2 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed Modicon style: coils 00001 up, discrete inputs 10001 up, input registers 30001 up, holding registers 40001 up. Subtract the base (and 1) for the wire address, e.g. discrete input 10013 = wire 12.
What are the minimum Modbus registers to integrate the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)?
Start with CO 0 Occupancy Command (BAS) (BAS occupancy command); DI 1 Alarm Status (Unit in alarm); DI 7 Comp Stage1 Output Cmd (Compressor stage 1 output); DI 34 UPM Safety - High Pressure Alarm (UPM high-pressure alarm); IR 59 Zone Mode Status (Zone mode status); HR 123 Set Zone Mode (Set zone mode); CO 5 BAS Loop Enable/Disable (BAS loop enable (heat/cool allowed)).
How do I enable Modbus control of the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)?
Communications jumper in the top (EIA-485) position; BAS Port Settings DIP switches SW3/SW4 select Modbus and SW1/SW2 the baud (9.6, 19.2, 38.4 or 76.8 kbps). The Applications Manual gives the switch table.
Where is the official Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus documentation?
The source is IPL_WAZ_1_03 (Control Air 5600 integration points list, water-to-air; the sheet prints no title) (IPL_WAZ_1_03 (2025-06-05)), revision 2025-06, published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ipl_waz_1_03_10-25.pdf.
Other pumps register maps
- Heat pump (packaged wall-mount)
Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU)
Eubank EAH1020H-1060H / EAH2024H-2042H wall-mount heat pumps (I&O manual rev. 6); the HAH1024-1060 A/C with gas heat manual (rev. 5) prints the same table.
Also known as: EAH1020H, EAH1024H, EAH1030H, EAH1036H, EAH1042H, EAH1048H, EAH1060H, EAH2024H, EAH2042H, HAH1024A, HAH1030A, HAH1036A, HAH1042A, HAH1048A, HAH1060A, Eubank EAH heat pump, Eubank HAH - Pump motor protection relay
Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
Grundfos MP 204 electronic motor protector connected over GENIbus to a CIU 200 (Modbus RTU), CIU 250 (GSM/GPRS) or CIU 500 (Modbus TCP) box; functional profile 98393513 (2014-11).
Also known as: MP 204, CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Modbus TCP, 98393513 - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Heat pump
Acond Acond heat pumps (Modbus TCP interface v2.35)
Acond air-to-water and brine heat pumps with the ModbusTCP function activated, interface description version 2.35 dated 01.12.2022.
Also known as: Acond PRO series, Acond ModbusTCP v2.35
All pumps Modbus register maps →
Source: IPL_WAZ_1_03 (Control Air 5600 integration points list, water-to-air; the sheet prints no title) · IPL_WAZ_1_03 (2025-06-05) · rev. 2025-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.