Heat pump (water-to-air heat pump controller) · Modbus register map

Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus register map

Updated 19 November 2026

Short answer

The Bosch Control Air 5600 is a BACnet-native DDC controller for water-to-air heat pumps whose EIA-485 port can also run Modbus RTU or N2. The integration points list gives each point a BACnet object and a Modbus register. This map holds the binary commands, alarm and status bits and the mode registers; the floating-point temperatures and setpoints are left out.

This page lists 86 Modbus registers for the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Bosch’s own free documentation (linked below) and checked against it.

Manufacturer
Bosch
Model
Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
Equipment type
Heat pump (water-to-air heat pump controller)
Registers
86 (14 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
Water-to-air standard software, IPL version 1.03
Also known as
Control Air 5600, IPL WAZ, IPL_WAZ_1_03, Bosch water-to-air DDC controller, BTC 761601101
Source document
IPL_WAZ_1_03 (Control Air 5600 integration points list, water-to-air; the sheet prints no title) · IPL_WAZ_1_03 (2025-06-05) · rev. 2025-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)

Integration in brief

Set the BAS port to Modbus and EIA-485, address the controller with the rotary dials, then poll discrete input 10002 (unit in alarm) and the UPM alarm bits, read the mode registers (30059/30060) and command occupancy with coil 00001.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0Occupancy Command (BAS)BITBAS occupancy commandRead/write
DI 1Alarm StatusBITUnit in alarmRead
DI 7Comp Stage1 Output CmdBITCompressor stage 1 outputRead
DI 34UPM Safety - High Pressure AlarmBITUPM high-pressure alarmRead
IR 59Zone Mode StatusINT16Zone mode statusRead
HR 123Set Zone ModeINT16Set zone modeRead/write
CO 5BAS Loop Enable/DisableBITBAS loop enable (heat/cool allowed)Read/write

Enable Modbus control & writes

Communications jumper in the top (EIA-485) position; BAS Port Settings DIP switches SW3/SW4 select Modbus and SW1/SW2 the baud (9.6, 19.2, 38.4 or 76.8 kbps). The Applications Manual gives the switch table.

Byte order & addressing

Network setup

Watch out for

Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

86 of 86 shown
Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1Occupancy Command (BAS)BV:1BITRead/write0 = Unoccupied; 1 = Occupied (Enables Unit Operation)
CO1doc 00002Compressor 1 Runtime ResetBV:13; momentary: write 1 then 0BITRead/write0 = Reset Off; 1 = Reset On
CO2doc 00003Compressor 2 Runtime ResetBV:14; momentary: write 1 then 0BITRead/write0 = Reset Off; 1 = Reset On
CO3doc 00004Fan Response for Comp LockoutBV:7BITRead/write0 = Do not lock fan upon compressor lockout; 1 = Lock fan upon compressor lockout
CO5doc 00006BAS Loop Enable/DisableBV:23BITRead/write0 = Disable Heat/Cool; 1 = Allow Heat/Cool Operation
CO6doc 00007Reset Fan RuntimeBV:19; momentary: write 1 then 0BITRead/write0 = Reset Off; 1 = Reset On
CO8doc 00009UPM ResetBV:25; momentary: write 1 then 0BITRead/write0 = Reset Off; 1 = Reset On
CO9doc 00010Sensor Override Enable/DisableBV:95BITRead/write0 = ZS Sensor Override NOT Allowed; 1 = ZS Sensor Override Allowed
CO10doc 00011Enable/Disable Fan Status Switch in IEMBV:67BITRead/write0 = FSS on IEM disabled
CO11doc 00012Enable/Disable Valve Switch in IEMBV:69BITRead/write0 = VES on IEM disabled
CO12doc 00013BAS Smoke Input / Emergency ShutdownBV:75BITRead/write0 = Normal
CO13doc 00014Smoke Alarm Enable/DisableBV:71BITRead/write0 = SDS on IEM disabled; 1 = SDS on IEM Enabled
DI0doc 10001Duplicate Input 1&2 AlarmBV:2BITRead0 = Normal; 1 = Alarm (Check input configuration for conflicts)
DI1doc 10002Alarm StatusBV:24BITRead0 = System Normal; 1 = System in Alarm
DI2doc 10003Aux Heat Output CmdBV:20BITRead0 = Aux Heat Off; 1 = Aux Heat On
DI3doc 10004UPM Safety - Brownout AlarmBV:10BITRead0 = Normal; 1 = Brownout Alarm (UPM-I code = 5; UPM-II code = 7)
DI4doc 10005Circulation Pump Output CommandBV:3BITRead0 = Pump Running; 1 = Pump Off
DI5doc 10006Compressor 1 RuntimeBV:35; the source prints the fan-mode text in this row, so states are not givenBITRead
DI6doc 10007Compressor 2 RuntimeBV:36BITRead0 = Normal; 1 = Timer Has Expired
DI7doc 10008Comp Stage1 Output CmdBV:11BITRead0 = Compressor 1 Off; 1 = Compressor 1 On
DI8doc 10009Comp Stage2 Output CmdBV:12BITRead0 = Compressor 2 Off; 1 = Compressor 2 On
DI9doc 10010UPM Safety - High Condensate AlarmBV:9BITRead0 = Normal; 1 = Condensate Overflow Alarm(UPM-I code = 4; UPM-II code = 6)
DI10doc 10011Fan Output CmdBV:17BITRead0 = Fan Output Off; 1 = Fan Output On
DI11doc 10012Secondary Condensate Pump AlarmBV:50BITRead0 = Normal; 1 = Alarm Active
DI12doc 10013Night Setback (NSB) StatusBV:22BITRead0 = Night Setback disabled; 1 = Night Setback enabled
DI13doc 10014Occupancy StatusBV:21BITRead0 = Unoccupied; 1 = Occupied
DI14doc 10015Economizer Cooling CommandBV:92BITRead0 = On; 1 = Off
DI15doc 10016High Cooling Supply Air Temperature in DACBV:86BITRead0 = Normal; 1 = Alarm Active
DI16doc 10017Condenser Water Valve OutputBV:79BITRead0 = Closed; 1 = Open
DI17doc 10018Discharge Air Temperature SensorBV:31BITRead0 = Sensor Normal; 1 = Sensor Failure Alarm (Check Sensor Hardware Configuration)
DI18doc 10019Damper End SwitchBV:93BITRead0 = Damper Closed; 1 = Damper Open
DI19doc 10020Damper CommandBV:49BITRead0 = Closed; 1 = Open
DI20doc 10021High Discharge Air TemperatureBV:29BITRead0 = Normal; 1 = Alarm
DI21doc 10022Discharge Air Temperature AlarmBV:30BITRead0 = Normal; 1 = Low DAT Alarm
DI22doc 10023Digital Override Lock AlarmBV:37BITRead0 = Normal; 1 = Digital Override Enabled Alarm
DI23doc 10024Differential Pressure Switch (DPS) AlarmBV:77BITRead0 = Normal; 1 = Alarm
DI24doc 10025Hot Gas ReHeat Valve StatusBV:44BITRead0 = Valve Off; 1 = Valve On
DI25doc 10026Entering Water Temperature Sensor AlarmBV:80BITRead0 = Normal; 1 = Sensor Failure Alarm (Check Hardware)
DI26doc 10027Fan Hand Mode AlarmBV:83; fan running but not commanded by the controllerBITRead
DI27doc 10028Fan Running StatusBV:66BITRead0 = Off; 1 = On - Fan Running
DI28doc 10029Filter Service AlarmBV:40BITRead0 = Off; 1 = Service Filter Alarm
DI29doc 10030UPM Safety - Condenser Coil Freeze AlarmBV:8BITRead0 = Normal; 1 = Condenser Freeze Alarm(UPM-I code = 3; UPM-II codes = 5,9)
DI30doc 10031UPM Safety - Evaporator Coil Freeze AlarmBV:90BITRead0 = Normal; 1 = Evaporator Freeze Alarm (UPM-I code = 6; UPM-II codes = 8,10
DI31doc 10032Air Economizer StatusBV:6BITRead0 = Inactive; 1 = Active
DI33doc 10034Boilerless StatusBV:91BITRead0 = Off; 1 = On (Electric Heating)
DI34doc 10035UPM Safety - High Pressure AlarmBV:5BITRead0 = Normal; 1 = High Pressure Alarm (UPM-I code = 1; UPM-II codes = 1,3)
DI36doc 10037Low Heating Supply Air Temperature in DACBV:149BITRead0 = Normal; 1 = Active
DI37doc 10038Inputs Override StatusBV:38BITRead0 = Normal; 1 = Software Lock Enabled
DI38doc 10039UPM Safety - Low Pressure AlarmBV:4BITRead0 = Normal; 1 = Low Pressure Alarm (UPM-I code = 2; UPM-II codes = 2,4)
DI40doc 10041High Leaving Water TemperatureBV:32BITRead0 = Normal; 1 = Alarm
DI41doc 10042Low Leaving Water TemperatureBV:33BITRead0 = Normal; 1 = Alarm
DI42doc 10043Leaving Water Temperature Sensor FailureBV:34BITRead0 = Normal; 1 = Sensor Failure (Check Sensor Hardware
DI43doc 10044Low Mixed Air TemperatureBV:89BITRead0 = Normal; 1 = Alarm
DI44doc 10045Mix Air Temperature Sensor FailureBV:88BITRead0 = Normal; 1 = Sensor Failure (Check Sensor Hardware
DI45doc 10046Outside Air Temperature Sensor FailureBV:87BITRead0 = Normal; 1 = Sensor Failure (Check Sensor Hardware
DI46doc 10047Circulation Pump Switch Failure AlarmBV:56BITRead0 = Normal; 1 = Active
DI47doc 10048Pump Switch StatusBV:57BITRead0 = Off; 1 = Pump Switch Detected
DI48doc 10049Circulation Pump Switch In Hand AlarmBV:58; pump running but not commanded by the controllerBITRead
DI49doc 10050Reversing Valve Output StatusBV:15BITRead0 = Reversing Valve De-energized; 1 = Reversing Valve Energized
DI50doc 10051Static Air Pressure Sensor Hardware AlarmBV:65BITRead0 = Normal; 1 = Sensor Failure (Check Static Pressure Hardware Configuration
DI51doc 10052Supply Air Fan Switch FailureBV:82BITRead0 = Normal; 1 = Alarm (Check Fan Hardware)
DI52doc 10053High Static Pressure AlarmBV:64BITRead0 = Normal; 1 = High Static Pressure
DI53doc 10054Smoke Event Alarm NotificationBV:81BITRead0 = Normal; 1 = Alarm
DI54doc 10055Smoke Event StatusBV:70BITRead0 = Normal; 1 = Smoke Detector Active
DI55doc 10056CO2 Hardware Failure AlarmBV:51BITRead0 = Normal; 1 = Sensor Failure (Check CO2 Hardware Configuration)
DI56doc 10057High CO2 AlarmBV:48BITRead0 = Normal; 1 = High CO2 Level
DI57doc 10058ZS Zone Sensor Hardware Failure AlarmBV:28BITRead0 = Normal; 1 = Sensor Failure (Check: ZS Sensor Hardware)
DI58doc 10059Remote Temperature Sensor Hardware Failure AlarmBV:43BITRead0 = Normal; 1 = Sensor Failure (Check Remote Sensor Hardware)
DI59doc 10060High Remote Temperature AlarmBV:41BITRead0 = Normal; 1 = High Zone Temperature
DI60doc 10061Low Remote Temperature AlarmBV:42BITRead0 = Normal; 1 = Low Zone Temperature
DI61doc 10062High ZS Zone Sensor Temperature AlarmBV:26BITRead0 = Normal; 1 = High Zone Temperature
DI62doc 10063Low ZS Zone Sensor Temperature AlarmBV:27BITRead0 = Normal; 1 = Low Zone Temperature
DI63doc 10064UPM Input AlarmBV:39BITRead0 = UPM Connected; 1 = UPM Connection Failure(Check Alarm Hardware Configuration)
DI64doc 10065Valve End Switch StatusBV:68BITRead0 = Off; 1 = Valve End Switch Detected
DI65doc 10066Valve Switch HandBV:150; valve engaged but not commanded by the controllerBITRead
DI66doc 10067Valve End Switch AlarmBV:151BITRead0 = Normal; 1 = Active
DI67doc 10068High Humidity AlarmBV:45BITRead0 = Normal; 1 = High Humidity
DI68doc 10069Low Humidity AlarmBV:46BITRead0 = Normal; 1 = Low Humidity
DI69doc 10070Humidity Sensor Hardware Failure AlarmBV:47BITRead0 = Normal; 1 = Sensor Failure (Check RH Sensor Hardware Configuration)
DI71doc 10072Override StatusBV:94BITRead0 = Normal; 1 = ZS Sensor in Override Mode
DI103doc 10104UPM Safety - A2L AlarmBV:104BITRead0 = Normal; 1 = A2L Alarm (UPM-I code = 7; UPM-II codes = 11)
DI105doc 10106UPM Safety - Communication AlarmBV:106BITRead0 = Normal; 1 = Communication Alarm (UPM-II codes = 12)
IR58doc 30059Fan Mode StatusMSV:1INT16Read1 = Auto (Cycel with Compressor); 4 = On
IR59doc 30060Zone Mode StatusMSV:4INT16Read1 = Auto; 2 = Heat; 3 = Cool; 5 = Off
HR122doc 40123Set Fan ModeMSV:2INT16Read/write1 = Auto (Cycel with Compressor); 4 = On
HR123doc 40124Set Zone ModeMSV:3INT16Read/write1 = Auto; 2 = Heat; 3 = Cool; 5 = Off

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)

What Modbus registers does the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) have?

This map lists 86 registers: 12 coils, 70 discrete inputs, 2 input registers, 2 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed Modicon style: coils 00001 up, discrete inputs 10001 up, input registers 30001 up, holding registers 40001 up. Subtract the base (and 1) for the wire address, e.g. discrete input 10013 = wire 12.

What are the minimum Modbus registers to integrate the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)?

Start with CO 0 Occupancy Command (BAS) (BAS occupancy command); DI 1 Alarm Status (Unit in alarm); DI 7 Comp Stage1 Output Cmd (Compressor stage 1 output); DI 34 UPM Safety - High Pressure Alarm (UPM high-pressure alarm); IR 59 Zone Mode Status (Zone mode status); HR 123 Set Zone Mode (Set zone mode); CO 5 BAS Loop Enable/Disable (BAS loop enable (heat/cool allowed)).

How do I enable Modbus control of the Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)?

Communications jumper in the top (EIA-485) position; BAS Port Settings DIP switches SW3/SW4 select Modbus and SW1/SW2 the baud (9.6, 19.2, 38.4 or 76.8 kbps). The Applications Manual gives the switch table.

Where is the official Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software) Modbus documentation?

The source is IPL_WAZ_1_03 (Control Air 5600 integration points list, water-to-air; the sheet prints no title) (IPL_WAZ_1_03 (2025-06-05)), revision 2025-06, published free by Bosch at https://www.bosch-homecomfort.com/us/media/country_pool/service/technical_guides/ipl_waz_1_03_10-25.pdf.

Other pumps register maps

All pumps Modbus register maps →

Source: IPL_WAZ_1_03 (Control Air 5600 integration points list, water-to-air; the sheet prints no title) · IPL_WAZ_1_03 (2025-06-05) · rev. 2025-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.