- EAH heat pump and HAH gas-heat AC control board (Modbus RTU)
Heat pump (packaged wall-mount) · Modbus register map
Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU) Modbus register map
Updated 19 November 2026
Eubank EAH wall-mount heat pumps and HAH gas-heat air conditioners (AirX brand, sister to Marvair) use an electronic control board with two RJ11 Modbus RTU ports. Over Modbus the board accepts thermostat and reversing-valve calls, reports switch, relay and sensor states and an alarm word, and exposes fan, economizer and calibration settings.
This page lists 69 Modbus registers for the Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU) — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eubank’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eubank
- Model
- EAH heat pump and HAH gas-heat AC control board (Modbus RTU)
- Equipment type
- Heat pump (packaged wall-mount)
- Registers
- 69 (32 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- EAH1020H, EAH1024H, EAH1030H, EAH1036H, EAH1042H, EAH1048H, EAH1060H, EAH2024H, EAH2042H, HAH1024A, HAH1030A, HAH1036A, HAH1042A, HAH1048A, HAH1060A, Eubank EAH heat pump, Eubank HAH
Integration notes: Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU)
Set coil 17 = 1 (communicating mode; the map says it mirrors parameter P22), then drive the unit with the Y1/Y2/G/W2/humidity/O call coils (0-4, 24). Read temperatures, relay states, pressure switches and the alarm word (input register 18) to monitor it.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 17 | Communicating thermostat mode | BIT | Communicating (Modbus) thermostat mode | Read/write |
| CO 0 | Y1 compressor call | BIT | Y1 cooling call | Read/write |
| CO 3 | G fan call | BIT | G fan call | Read/write |
| DI 13 | Compressor 1 relay output | BIT | Compressor 1 relay state | Read |
| IR 18 | Alarm status | BITMAP16 | Alarm status bits | Read |
| IR 14 | P1 temperature | UINT16 | P1 temperature | Read |
| IR 27 | Outdoor temperature | UINT16 | Outdoor temperature | Read |
| HR 8 | Modbus timeout | UINT16 | Modbus timeout (minutes) | Read/write |
Enable Modbus control & writes
In the source manual's configuration menu set item 23 (T'STAT Select; item numbers may differ in the other manuals that share this table) to C for a communicating thermostat via Modbus, or write coil 17 = 1 (the Modbus map says coil 17 reads and changes 'P22', the thermostat-type setting). The Modbus ID (item 24, 1-99, default 1) and baud (item 25: 9.6 or 19 = 9600/19200) are set in the board configuration menu.
Communication loss & watchdog
Register 8 / configuration item 26 sets the Modbus timeout (1-60 min, default 10). After that long without Modbus traffic the board falls back to hardware thermostat calls.
Byte order & addressing
- Only single-coil (05) and single-register (06) writes are accepted.
- Register reads are documented with function 04 only, including the writable ones.
- Temperature value 255 means no sensor or a failed sensor.
Network setup
- Default slave ID 1, 19200 baud, 8 data bits, no parity, 1 stop bit.
- The board has two RJ11 Modbus ports wired in parallel; both carry the same bus.
Watch out for
- Until the thermostat type is C (menu item 23, or coil 17 = 1) the board keeps following its hardwired thermostat inputs.
- After the Modbus timeout with no traffic the board switches back to its hardware thermostat inputs, so poll faster than the timeout.
Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0 | Y1 compressor call | Stage 1 cooling request | BIT | Read/write | 0 = No call; 1 = Call | |||
| CO | 1 | Y2 compressor call | Stage 2 cooling request | BIT | Read/write | 0 = No call; 1 = Call | |||
| CO | 2 | Humidity call | Dehumidification request | BIT | Read/write | 0 = No call; 1 = Call | |||
| CO | 3 | G fan call | Fan-only request | BIT | Read/write | 0 = No call; 1 = Call | |||
| CO | 4 | W2 electric heat call | BIT | Read/write | 0 = No call; 1 = Call | ||||
| CO | 17 | Communicating thermostat mode | Same as parameter P22: take calls from Modbus instead of hardware inputs | BIT | Read/write | 0 = Hardware calls (H); 1 = Comm/Modbus calls (C) | |||
| CO | 18 | Read hardware call inputs | 1 = still read hardware thermostat inputs while P22 = C | BIT | Read/write | 0 = Normal (per P22); 1 = Read hardware calls | |||
| CO | 24 | O reversing valve request | BIT | Read/write | 0 = No call; 1 = Call | ||||
| CO | 26 | Emergency ventilation request | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 27 | Pulse reheat | Default on | BIT | Read/write | 0 = Off; 1 = On | |||
| DI | 5 | FCC call | BIT | Read | 0 = No call; 1 = Call | ||||
| DI | 6 | High pressure switch 1 | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 7 | High pressure switch 2 | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 8 | Low pressure switch 1 | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 9 | Low pressure switch 2 | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 10 | OFM mode selection | Outdoor fan motor signal type | BIT | Read | 0 = PWM; 1 = 0-10 V | |||
| DI | 11 | IFM mode selection | Indoor fan motor signal type | BIT | Read | 0 = PWM; 1 = 0-10 V | |||
| DI | 12 | Technician speedup test mode | BIT | Read | 0 = Normal; 1 = Test mode | ||||
| DI | 13 | Compressor 1 relay output | BIT | Read | 0 = Off; 1 = Energized | ||||
| DI | 14 | Compressor 2 relay output | BIT | Read | 0 = Off; 1 = Energized | ||||
| DI | 15 | RH relay output | BIT | Read | 0 = Off; 1 = Energized | ||||
| DI | 16 | W2 relay output | BIT | Read | 0 = Off; 1 = Energized | ||||
| DI | 19 | AC / HP | Unit type | BIT | Read | 0 = AC; 1 = Heat pump | |||
| DI | 20 | EHDD | EHDD option setting | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 21 | SCKT | SCKT option setting | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 22 | Economizer enabled | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 23 | Economizer sensor type | BIT | Read | 0 = Dry bulb; 1 = Enthalpy | ||||
| DI | 25 | RV output | Reversing valve output | BIT | Read | 0 = Off; 1 = Energized | |||
| DI | 28 | Emergency ventilation status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 29 | EC relay output | BIT | Read | 0 = Off; 1 = On | ||||
| IR | 9 | Current OFM speed | 0-1023 | UINT16 | Read | ||||
| IR | 10 | Current IFM speed | 0-1023 | UINT16 | Read | ||||
| IR | 11 | Anti-short-cycle compressor 1 | 0-360 counts of 0.5 s | UINT16 | × 0.5 | s | Read | ||
| IR | 12 | Anti-short-cycle compressor 2 | 0-360 counts of 0.5 s | UINT16 | × 0.5 | s | Read | ||
| IR | 13 | Voltage reading | 0-1023; 1023 = above 20 V, 965 = 18 V cutoff | UINT16 | Read | ||||
| IR | 14 | P1 temperature | 0-160 °F; 255 = no sensor | UINT16 | °F | Read | 255 = No sensor | ||
| IR | 15 | P2 temperature | 0-160 °F; 255 = no sensor | UINT16 | °F | Read | 255 = No sensor | ||
| IR | 16 | Freeze sensor 1 temperature | 0-160 °F; 255 = no sensor | UINT16 | °F | Read | 255 = No sensor | ||
| IR | 17 | Freeze sensor 2 temperature | 0-160 °F; 255 = no sensor | UINT16 | °F | Read | 255 = No sensor | ||
| IR | 18 | Alarm status | 0 = no fault | BITMAP16 | Read | bit 0 = Flat circuit fault; bit 1 = HPS1 fault; bit 2 = Low voltage; bit 6 = LPS1 fault; bit 14 = Y1 locked out; bit 15 = Y2 locked out | |||
| IR | 24 | Software version | Decimal | UINT16 | Read | ||||
| IR | 25 | Supply / mixed air temperature | 0-160 °F | UINT16 | °F | Read | |||
| IR | 27 | Outdoor temperature | 0-160 °F | UINT16 | °F | Read | |||
| IR | 29 | Suction line temperature (LPS1) | 0-160 °F; 255 = open or shorted sensor | UINT16 | °F | Read | 255 = Sensor open/shorted | ||
| IR | 31 | Liquid line temperature (FCC1) | 0-160 °F; 255 = open or shorted sensor | UINT16 | °F | Read | 255 = Sensor open/shorted | ||
| IR | 33 | Defrost sensor temperature | 0-160 °F | UINT16 | °F | Read | |||
| IR | 38 | Economizer output | 0 = off, 20-100 | UINT16 | Read | 0 = Off | |||
| HR | 0 | Heat set point | Reserved for future use; 45-100 °F | UINT16 | °F | Read/write | |||
| HR | 1 | Cool set point | Reserved for future use; 45-100 °F | UINT16 | °F | Read/write | |||
| HR | 2 | Temperature calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 3 | W2 speed multiplier | Percent of Y2 fan speed, 0-100, default 80 | UINT16 | % | Read/write | |||
| HR | 4 | Dehumidification speed multiplier | Percent of Y2 fan speed, 0-100, default 80 | UINT16 | % | Read/write | |||
| HR | 5 | OFM set speed | Outdoor fan speed, 0-1023 | UINT16 | Read/write | ||||
| HR | 6 | IFM Y1 set speed | Indoor fan speed for Y1, 0-1023 | UINT16 | Read/write | ||||
| HR | 7 | IFM Y2 set speed | Indoor fan speed for Y2, 0-1023 | UINT16 | Read/write | ||||
| HR | 8 | Modbus timeout | Minutes without Modbus before reverting to hardware calls; 1-60, default 10 | UINT16 | min | Read/write | |||
| HR | 19 | Minimum position | Economizer minimum position: 20 = minimum, 20-100 = open % | UINT16 | % | Read/write | |||
| HR | 20 | Economizer dry bulb set point | 20-105 °F, default 70 | UINT16 | °F | Read/write | |||
| HR | 21 | ODS set | 0-70, default 50 | UINT16 | Read/write | ||||
| HR | 22 | Fan purge | 0 = no, 10-90 s, default 90 | UINT16 | s | Read/write | 0 = No purge | ||
| HR | 23 | Defrost timer | 30, 60 or 90 min (default 30) | UINT16 | min | Read/write | |||
| HR | 26 | SAS/MAS calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 28 | ODS calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 30 | Suction line temp calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 32 | Liquid line temp calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 34 | DS calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 35 | Dehumidifier set point | 70-75 °F, default 72 | UINT16 | °F | Read/write | |||
| HR | 36 | Pulse reheat differential | 5-10 °F, default 5 | UINT16 | °F | Read/write | |||
| HR | 37 | Economizer enthalpy set point | Modes A..E as 0..4, default 3 (D) | UINT16 | Read/write | 0 = A; 1 = B; 2 = C; 3 = D; 4 = E |
Notes on this map
- The manual prints two columns: a zero-based 'packet register ID' (used as the address here) and a one-based reference ID. Coils and registers each start at zero-based ID 0.
- Bit points: the board reads all of them with function 02 and writes the RW ones with function 05 (single coil only, no function 15). Coils and discrete inputs share one address space. RW bits are listed as coils, read-only bits as discrete inputs.
- Registers: the board reads them with function 04 and writes RW ones with function 06 (single register only, no function 16). RW registers are listed as holding registers so they can be written; the manual only documents reading them with function 04 at the same address. Whether function 01/03 reads work is not stated.
- Writes to read-only points return an error.
- Calibration registers hold 0-18 with 9 = no correction; the applied correction is the value minus 9.
- Heat and cool set points (registers 0-1) are writable but marked 'not currently used, for future use'.
- Anti-short-cycle timers count in 0.5 s steps (scale 0.5).
- The Eubank HAH1024-1060 A/C with gas heat I&O manual (rev. 5, 10/2025, Appendix A, PDF pp. 73-75) prints the same table: https://eubankwallmount.com/doc/65/HAH1024-1060%20AC%20wGas%20Heat%20Manual%20Rev%205
- In this table IFM Y1/Y2 set speeds are 0-1023 and alarm bit 0 is 'flat circuit fault'; registers stop at 38.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU)
What Modbus registers does the Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU) have?
This map lists 69 registers: 10 coils, 20 discrete inputs, 17 input registers, 22 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints a zero-based packet ID next to a reference ID (coils 1-30, registers 40001-40039). The zero-based ID is the wire address.
What are the minimum Modbus registers to integrate the Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU)?
Start with CO 17 Communicating thermostat mode (Communicating (Modbus) thermostat mode); CO 0 Y1 compressor call (Y1 cooling call); CO 3 G fan call (G fan call); DI 13 Compressor 1 relay output (Compressor 1 relay state); IR 18 Alarm status (Alarm status bits); IR 14 P1 temperature (P1 temperature); IR 27 Outdoor temperature (Outdoor temperature); HR 8 Modbus timeout (Modbus timeout (minutes)).
How do I enable Modbus control of the Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU)?
In the source manual's configuration menu set item 23 (T'STAT Select; item numbers may differ in the other manuals that share this table) to C for a communicating thermostat via Modbus, or write coil 17 = 1 (the Modbus map says coil 17 reads and changes 'P22', the thermostat-type setting). The Modbus ID (item 24, 1-99, default 1) and baud (item 25: 9.6 or 19 = 9600/19200) are set in the board configuration menu.
What happens when the Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU) loses Modbus communication?
Register 8 / configuration item 26 sets the Modbus timeout (1-60 min, default 10). After that long without Modbus traffic the board falls back to hardware thermostat calls.
Where is the official Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU) Modbus documentation?
The source is EAH1020H-1048H-2024H-2042H Wall Mount HP Installation & Operation Manual (Rev. 6), revision 2026-05, published free by Eubank at https://eubankwallmount.com/doc/59/EAH1020H-1048H-2024H-2042H%20Wall%20Mount%20HP%20Manual%20Rev%206.
More Eubank Modbus register maps
Other pumps register maps
- Pump motor protection relay
Grundfos MP 204 motor protector with CIU 200 / CIU 500 (Modbus)
Grundfos MP 204 electronic motor protector connected over GENIbus to a CIU 200 (Modbus RTU), CIU 250 (GSM/GPRS) or CIU 500 (Modbus TCP) box; functional profile 98393513 (2014-11).
Also known as: MP 204, CIU 200 Modbus RTU, CIU 250 GSM/GPRS, CIU 500 Modbus TCP, 98393513 - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Heat pump / chiller Modbus interface
Realtime Control Systems RTD-W Modbus interface for Daikin Altherma HT hydrobox and small inverter chillers
RTD-W on the P1/P2 bus with a BRC21 controller as main: Daikin Altherma HT hydroboxes, small inverter chillers EWA/YQ16..64 and the heating-only VRV hydrobox; up to 16 units as one group. Instructions 20670-1.07.12.
Also known as: RTD-W, Daikin RTD-W - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Heat pump
Acond Acond heat pumps (Modbus TCP interface v2.35)
Acond air-to-water and brine heat pumps with the ModbusTCP function activated, interface description version 2.35 dated 01.12.2022.
Also known as: Acond PRO series, Acond ModbusTCP v2.35 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204
All pumps Modbus register maps →
Source: EAH1020H-1048H-2024H-2042H Wall Mount HP Installation & Operation Manual · Rev. 6 · rev. 2026-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.