Remote I/O module (engine / pump controller expansion) · Modbus register map
FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus register map
Updated 17 November 2026
The MX5-R2 is FW Murphy's I/O and communications expansion module for Centurion controllers, with 24 digital inputs, 10 analog inputs, a magnetic pickup, 16 digital outputs and 4 analog outputs. In Standard IO mode it is a Modbus RTU server on two RS-485 ports and RS-232 and a Modbus TCP server on Ethernet, all using one holding-register table. This map covers the whole published table.
This page lists 127 Modbus registers for the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) — 89 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from FW Murphy’s own free documentation (linked below) and checked against it.
- Manufacturer
- FW Murphy
- Model
- Interchange Comm Control Module MX5-R2 (Standard IO mode)
- Equipment type
- Remote I/O module (engine / pump controller expansion)
- Registers
- 127 (89 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 9600 baud
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Date code S8 or later; pulse engine registers 4.4.10111 / date code U10 or later
- Also known as
- MX5-R2, Interchange MX5-R2, Enovation Controls MX5-R2
Integration notes: FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)
Poll holding registers 400021-400038 for inputs, write 400061 and 400047-400050 for outputs, and set 400073 plus the comm-failure registers so outputs go to a safe state if the client stops polling.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20 | Digital inputs 1-16 | BITMAP16 | Digital inputs 1-16 | Read |
| HR 21 | Digital inputs 17-24 | BITMAP16 | Digital inputs 17-24 | Read |
| HR 23 | Analog input 1 | INT16 | Analog input 1 | Read |
| HR 37 | Frequency input | UINT16 | Frequency input | Read |
| HR 60 | Digital outputs 1-16 | BITMAP16 | Digital outputs 1-16 | Read/write |
| HR 46 | Analog output 1 signal | UINT16 | Analog output 1 | Read/write |
| HR 72 | Communication timeout | UINT16 | Comm timeout | Read/write |
| HR 0 | Hardware type | UINT16 | Hardware type check (33) | Read |
Enable Modbus control & writes
Standard IO mode is the default (COP LED code 4,2). To reload it: power up with DIP 5-8 closed and DIP 2 open, 1/3/4 closed. DIP 5-8 closed with 1-4 closed loads factory defaults (baud, Ethernet, channel configuration).
Communication loss & watchdog
Register 400073 sets a communication timeout in seconds; when no client talks on any port for that time, outputs go to the states in 400064 and 400069-400072. Pulse mode is also cancelled on comm loss.
Byte order & addressing
- Supported functions: 03, 06 and 16 only; invalid addresses return an exception.
- Polarity registers pack two inputs: high byte = odd channel, low byte = even channel.
- The firmware checksum is split MSW (400009) then LSW (400010).
Network setup
- RS-485: A (+) on terminals 61/62, B (-) on 80/81; twisted shielded pair, 120 ohm.
- Serial default 9600 baud, up to 115.2k via 400085; set the RTU client timeout to at least 400 ms.
- Ethernet default 192.168.0.100 / 255.255.255.0, gateway 0.0.0.0; change via 465197-465217.
Watch out for
- In Rockwell IO mode the Ethernet ports speak EtherNet/IP (CIP) only, not Modbus TCP.
- DIP switches 5-8 double as address switches; the special functions only act when they are closed at power-up.
FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 400001 | Hardware type | Module ID; MX5-R2 returns 33. | UINT16 | Read | ||||
| HR | 4doc 400005 | Bootloader build version | UINT16 | Read | |||||
| HR | 6doc 400007 | Firmware number | UINT16 | Read | |||||
| HR | 7doc 400008 | Firmware build version | UINT16 | Read | |||||
| HR | 8doc 400009-400010 | Firmware checksum | 32-bit; MSW in 400009, LSW in 400010. | UINT32 | ABCD | Read | |||
| HR | 10doc 400011 | Firmware major version | UINT16 | Read | |||||
| HR | 11doc 400012 | Firmware minor version | UINT16 | Read | |||||
| HR | 12doc 400013 | Bootloader major version | UINT16 | Read | |||||
| HR | 13doc 400014 | Bootloader minor version | UINT16 | Read | |||||
| HR | 20doc 400021 | Digital inputs 1-16 | 0 = open, 1 = closed; bit 0 = DI1. | BITMAP16 | Read | bit 0 = DI1 closed; bit 1 = DI2 closed; bit 2 = DI3 closed; bit 3 = DI4 closed; bit 4 = DI5 closed; bit 5 = DI6 closed; bit 6 = DI7 closed; bit 7 = DI8 closed; bit 8 = DI9 closed; bit 9 = DI10 closed; bit 10 = DI11 closed; bit 11 = DI12 closed; bit 12 = DI13 closed; bit 13 = DI14 closed; bit 14 = DI15 closed; bit 15 = DI16 closed | |||
| HR | 21doc 400022 | Digital inputs 17-24 | 0 = open, 1 = closed; bit 0 = DI17. | BITMAP16 | Read | bit 0 = DI17 closed; bit 1 = DI18 closed; bit 2 = DI19 closed; bit 3 = DI20 closed; bit 4 = DI21 closed; bit 5 = DI22 closed; bit 6 = DI23 closed; bit 7 = DI24 closed | |||
| HR | 22doc 400023 | System voltage | Supply voltage; 320 = 32.0 V DC. | UINT16 | × 0.1 | V | Read | ||
| HR | 23doc 400024 | Analog input 1 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 24doc 400025 | Analog input 2 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 25doc 400026 | Analog input 3 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 26doc 400027 | Analog input 4 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 27doc 400028 | Analog input 5 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 28doc 400029 | Analog input 6 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 29doc 400030 | Analog input 7 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 30doc 400031 | Analog input 8 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 31doc 400032 | Analog input 9 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 32doc 400033 | Analog input 10 | Raw A/D counts; full scale depends on the channel type register. | INT16 | counts | Read | |||
| HR | 37doc 400038 | Frequency input | Magnetic pickup input, 0-10,000. | UINT16 | Hz | Read | |||
| HR | 46doc 400047 | Analog output 1 signal | 0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428). | UINT16 | counts | Read/write | |||
| HR | 47doc 400048 | Analog output 2 signal | 0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428). | UINT16 | counts | Read/write | |||
| HR | 48doc 400049 | Analog output 3 signal | 0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428). | UINT16 | counts | Read/write | |||
| HR | 49doc 400050 | Analog output 4 signal | 0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428). | UINT16 | counts | Read/write | |||
| HR | 52doc 400053 | RTC seconds | Range 0-59; applied when 400060 = 1. | UINT16 | s | Read/write | |||
| HR | 53doc 400054 | RTC minutes | Range 0-59; applied when 400060 = 1. | UINT16 | min | Read/write | |||
| HR | 54doc 400055 | RTC hours | Range 0-23; applied when 400060 = 1. | UINT16 | h | Read/write | |||
| HR | 55doc 400056 | RTC day of week | Range 1-7; applied when 400060 = 1. | UINT16 | Read/write | ||||
| HR | 56doc 400057 | RTC day | Range 1-31; applied when 400060 = 1. | UINT16 | Read/write | ||||
| HR | 57doc 400058 | RTC month | Range 1-12; applied when 400060 = 1. | UINT16 | Read/write | ||||
| HR | 58doc 400059 | RTC year | Range 2000-3000; applied when 400060 = 1. | UINT16 | Read/write | ||||
| HR | 59doc 400060 | Clock set enable | Write 1 to load 400053-400059 into the clock. | UINT16 | Read/write | 0 = Disabled; 1 = Set clock | |||
| HR | 60doc 400061 | Digital outputs 1-16 | Bit 0 = DO1. | BITMAP16 | Read/write | bit 0 = DO1 on; bit 1 = DO2 on; bit 2 = DO3 on; bit 3 = DO4 on; bit 4 = DO5 on; bit 5 = DO6 on; bit 6 = DO7 on; bit 7 = DO8 on; bit 8 = DO9 on; bit 9 = DO10 on; bit 10 = DO11 on; bit 11 = DO12 on; bit 12 = DO13 on; bit 13 = DO14 on; bit 14 = DO15 on; bit 15 = DO16 on | |||
| HR | 62doc 400063 | Digital outputs at power-up | Stored state applied before any client talks; bit 0 = DO1. | BITMAP16 | Read/write | bit 0 = DO1 on; bit 1 = DO2 on; bit 2 = DO3 on; bit 3 = DO4 on; bit 4 = DO5 on; bit 5 = DO6 on; bit 6 = DO7 on; bit 7 = DO8 on; bit 8 = DO9 on; bit 9 = DO10 on; bit 10 = DO11 on; bit 11 = DO12 on; bit 12 = DO13 on; bit 13 = DO14 on; bit 14 = DO15 on; bit 15 = DO16 on | |||
| HR | 63doc 400064 | Digital outputs at comm failure | State applied after the 400073 timeout; bit 0 = DO1. | BITMAP16 | Read/write | bit 0 = DO1 on; bit 1 = DO2 on; bit 2 = DO3 on; bit 3 = DO4 on; bit 4 = DO5 on; bit 5 = DO6 on; bit 6 = DO7 on; bit 7 = DO8 on; bit 8 = DO9 on; bit 9 = DO10 on; bit 10 = DO11 on; bit 11 = DO12 on; bit 12 = DO13 on; bit 13 = DO14 on; bit 14 = DO15 on; bit 15 = DO16 on | |||
| HR | 64doc 400065 | Analog output 1 at power-up | D/A counts, 65535 = 24 mA; stored. | UINT16 | counts | Read/write | |||
| HR | 65doc 400066 | Analog output 2 at power-up | D/A counts, 65535 = 24 mA; stored. | UINT16 | counts | Read/write | |||
| HR | 66doc 400067 | Analog output 3 at power-up | D/A counts, 65535 = 24 mA; stored. | UINT16 | counts | Read/write | |||
| HR | 67doc 400068 | Analog output 4 at power-up | D/A counts, 65535 = 24 mA; stored. | UINT16 | counts | Read/write | |||
| HR | 68doc 400069 | Analog output 1 at comm failure | D/A counts, 65535 = 24 mA; stored. | UINT16 | counts | Read/write | |||
| HR | 69doc 400070 | Analog output 2 at comm failure | D/A counts, 65535 = 24 mA; stored. | UINT16 | counts | Read/write | |||
| HR | 70doc 400071 | Analog output 3 at comm failure | D/A counts, 65535 = 24 mA; stored. | UINT16 | counts | Read/write | |||
| HR | 71doc 400072 | Analog output 4 at comm failure | D/A counts, 65535 = 24 mA; stored. | UINT16 | counts | Read/write | |||
| HR | 72doc 400073 | Communication timeout | Silence on all ports for this long switches outputs to their comm-failure states. | UINT16 | s | Read/write | |||
| HR | 73doc 400074 | Analog input 1 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA | |||
| HR | 74doc 400075 | Analog input 2 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA | |||
| HR | 75doc 400076 | Analog input 3 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA | |||
| HR | 76doc 400077 | Analog input 4 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA | |||
| HR | 77doc 400078 | Analog input 5 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA | |||
| HR | 78doc 400079 | Analog input 6 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA | |||
| HR | 79doc 400080 | Analog input 7 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA; 2 = 5 kohm resistive; 3 = 3 kohm resistive; 4 = 10 kohm resistive; 5 = 30 kohm resistive | |||
| HR | 80doc 400081 | Analog input 8 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA; 2 = 5 kohm resistive; 3 = 3 kohm resistive; 4 = 10 kohm resistive; 5 = 30 kohm resistive | |||
| HR | 81doc 400082 | Analog input 9 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA; 2 = 5 kohm resistive; 3 = 3 kohm resistive; 4 = 10 kohm resistive; 5 = 30 kohm resistive | |||
| HR | 82doc 400083 | Analog input 10 type | Stored setting. | UINT16 | Read/write | 0 = 0-5 V DC; 1 = 0-25 mA; 2 = 5 kohm resistive; 3 = 3 kohm resistive; 4 = 10 kohm resistive; 5 = 30 kohm resistive | |||
| HR | 84doc 400085 | Serial port baud rate | UINT16 | Read/write | 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 115200 | ||||
| HR | 85doc 400086 | Digital input 1-2 polarity | High byte DI1, low byte DI2: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 86doc 400087 | Digital input 3-4 polarity | High byte DI3, low byte DI4: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 87doc 400088 | Digital input 5-6 polarity | High byte DI5, low byte DI6: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 88doc 400089 | Digital input 7-8 polarity | High byte DI7, low byte DI8: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 89doc 400090 | Digital input 9-10 polarity | High byte DI9, low byte DI10: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 90doc 400091 | Digital input 11-12 polarity | High byte DI11, low byte DI12: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 91doc 400092 | Digital input 13-14 polarity | High byte DI13, low byte DI14: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 92doc 400093 | Digital input 15-16 polarity | High byte DI15, low byte DI16: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 93doc 400094 | Digital input 17-18 polarity | High byte DI17, low byte DI18: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 94doc 400095 | Digital input 19-20 polarity | High byte DI19, low byte DI20: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 95doc 400096 | Digital input 21-22 polarity | High byte DI21, low byte DI22: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 96doc 400097 | Digital input 23-24 polarity | High byte DI23, low byte DI24: 0 closed DC-, 1 closed DC+, 2 open. | UINT16 | Read | ||||
| HR | 115doc *400116 | High-resolution pulse enable | Bit 0 = DO1; pulse on/off times then override 400061. | BITMAP16 | Read/write | bit 0 = DO1 pulse enabled; bit 1 = DO2 pulse enabled; bit 2 = DO3 pulse enabled; bit 3 = DO4 pulse enabled; bit 4 = DO5 pulse enabled; bit 5 = DO6 pulse enabled; bit 6 = DO7 pulse enabled; bit 7 = DO8 pulse enabled; bit 8 = DO9 pulse enabled; bit 9 = DO10 pulse enabled; bit 10 = DO11 pulse enabled; bit 11 = DO12 pulse enabled; bit 12 = DO13 pulse enabled; bit 13 = DO14 pulse enabled; bit 14 = DO15 pulse enabled; bit 15 = DO16 pulse enabled | |||
| HR | 116doc *400117 | DO1 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 117doc *400118 | DO1 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 118doc *400119 | DO2 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 119doc *400120 | DO2 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 120doc *400121 | DO3 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 121doc *400122 | DO3 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 122doc *400123 | DO4 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 123doc *400124 | DO4 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 124doc *400125 | DO5 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 125doc *400126 | DO5 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 126doc *400127 | DO6 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 127doc *400128 | DO6 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 128doc *400129 | DO7 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 129doc *400130 | DO7 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 130doc *400131 | DO8 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 131doc *400132 | DO8 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 132doc *400133 | DO9 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 133doc *400134 | DO9 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 134doc *400135 | DO10 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 135doc *400136 | DO10 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 136doc *400137 | DO11 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 137doc *400138 | DO11 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 138doc *400139 | DO12 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 139doc *400140 | DO12 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 140doc *400141 | DO13 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 141doc *400142 | DO13 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 142doc *400143 | DO14 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 143doc *400144 | DO14 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 144doc *400145 | DO15 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 145doc *400146 | DO15 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 146doc *400147 | DO16 pulse on time | 0-255 x 50 ms; 0 keeps the output off. | UINT16 | × 50 | ms | Read/write | ||
| HR | 147doc *400148 | DO16 pulse off time | 5-255 x 50 ms (minimum 250 ms). | UINT16 | × 50 | ms | Read/write | ||
| HR | 65196doc 465197 | IP address part 1 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65197doc 465198 | IP address part 2 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65198doc 465199 | IP address part 3 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65199doc 465200 | IP address part 4 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65200doc 465201 | Network mask part 1 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65201doc 465202 | Network mask part 2 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65202doc 465203 | Network mask part 3 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65203doc 465204 | Network mask part 4 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65204doc 465205 | Gateway part 1 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65205doc 465206 | Gateway part 2 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65206doc 465207 | Gateway part 3 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65207doc 465208 | Gateway part 4 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65208doc 465209 | DNS1 part 1 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65209doc 465210 | DNS1 part 2 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65210doc 465211 | DNS1 part 3 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65211doc 465212 | DNS1 part 4 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65212doc 465213 | DNS2 part 1 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65213doc 465214 | DNS2 part 2 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65214doc 465215 | DNS2 part 3 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65215doc 465216 | DNS2 part 4 | One octet, 0-255. | UINT16 | Read/write | ||||
| HR | 65216doc 465217 | Ethernet IP options | UINT16 | Read/write | 0 = Static IP, no auto IP; 1 = DHCP, no auto IP; 2 = Static IP, auto IP if no DHCP/IP; 3 = DHCP, auto IP if no DHCP/IP | ||||
| HR | 65217doc 465218 | MAC address word 1 | UINT16 | Read | |||||
| HR | 65218doc 465219 | MAC address word 2 | UINT16 | Read | |||||
| HR | 65219doc 465220 | MAC address word 3 | UINT16 | Read |
Notes on this map
- Analog inputs: the register notes call them signed 16-bit counts, but the table gives full scale as 32768 = 5 V or 25 mA while the text says 32767 = 24 mA (4 mA = 5243, 20 mA = 26214). They are left as raw INT16 counts; calibrate against the stated 4-20 mA counts.
- The 400090-400097 polarity rows reuse the DI1-DI8 byte labels in the table; this map labels them by the register's channel pair (DI9-DI24).
- Factory-use registers 400002-400004, 400051-400052, 400084 and 400098-400115 are left out.
- Default serial framing: the module answers with 1 stop bit at addresses 1-31 and 2 stop bits at 32-239; parity is not stated.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)
What Modbus registers does the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) have?
This map lists 127 registers: 127 holding registers. 89 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed in 6-digit Modicon form (400001 = holding register 1). Wire address = number - 400001, e.g. digital inputs 400021 = address 20 and IP address 465197 = address 65196.
What byte order does the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)?
Start with HR 20 Digital inputs 1-16 (Digital inputs 1-16); HR 21 Digital inputs 17-24 (Digital inputs 17-24); HR 23 Analog input 1 (Analog input 1); HR 37 Frequency input (Frequency input); HR 60 Digital outputs 1-16 (Digital outputs 1-16); HR 46 Analog output 1 signal (Analog output 1); HR 72 Communication timeout (Comm timeout); HR 0 Hardware type (Hardware type check (33)).
How do I enable Modbus control of the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)?
Standard IO mode is the default (COP LED code 4,2). To reload it: power up with DIP 5-8 closed and DIP 2 open, 1/3/4 closed. DIP 5-8 closed with 1-4 closed loads factory defaults (baud, Ethernet, channel configuration).
What happens when the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) loses Modbus communication?
Register 400073 sets a communication timeout in seconds; when no client talks on any port for that time, outputs go to the states in 400064 and 400069-400072. Pulse mode is also cancelled on comm loss.
Where is the official FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus documentation?
The source is Interchange Comm Control Module MX5-R2 Series Operations Manual (00-02-3003), revision 2025-02-11, published free by FW Murphy at https://fwmurphy.com/wp-content/uploads/2025/02/00-02-3003.pdf.
Other pumps register maps
- Pump (chemical dosing pump)
Grundfos SMART Digital DDA dosing pump (SoftCIM, CIM 200 / CIM 500)
Grundfos SMART Digital DDA dosing pumps: DDA model C with built-in SoftCIM Modbus RTU/TCP, and DDA XL (or others) through a CIM 200 Modbus RTU or CIM 500 Modbus TCP module in a CIU 900, per functional profile 98473491 (09.2026).
Also known as: DDA, DDA S, DDA XL, DDA-C, DDA model C, SMART Digital S, SMART Digital XL, CIM 200, CIM 500, 98473491 - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Pump (high-efficiency inline circulator)
Wilo Stratos GIGA2.0 with CIF module Modbus RTU
Wilo Stratos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Stratos GIGA2.0-I, Stratos GIGA2.0-D, Wilo-Stratos GIGA2.0 - Heat pump (water-to-air heat pump controller)
Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
Bosch commercial water-to-air heat pumps fitted with the Control Air 5600 DDC controller running the water-to-air standard software (integration points list version 1.03).
Also known as: Control Air 5600, IPL WAZ, IPL_WAZ_1_03, Bosch water-to-air DDC controller, BTC 761601101 - Heat pump (packaged wall-mount)
Eubank EAH heat pump and HAH gas-heat AC control board (Modbus RTU)
Eubank EAH1020H-1060H / EAH2024H-2042H wall-mount heat pumps (I&O manual rev. 6); the HAH1024-1060 A/C with gas heat manual (rev. 5) prints the same table.
Also known as: EAH1020H, EAH1024H, EAH1030H, EAH1036H, EAH1042H, EAH1048H, EAH1060H, EAH2024H, EAH2042H, HAH1024A, HAH1030A, HAH1036A, HAH1042A, HAH1048A, HAH1060A, Eubank EAH heat pump, Eubank HAH
All pumps Modbus register maps →
Source: Interchange Comm Control Module MX5-R2 Series Operations Manual · 00-02-3003 · rev. 2025-02-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.