Remote I/O module (engine / pump controller expansion) · Modbus register map

FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus register map

Updated 17 November 2026

Short answer

The MX5-R2 is FW Murphy's I/O and communications expansion module for Centurion controllers, with 24 digital inputs, 10 analog inputs, a magnetic pickup, 16 digital outputs and 4 analog outputs. In Standard IO mode it is a Modbus RTU server on two RS-485 ports and RS-232 and a Modbus TCP server on Ethernet, all using one holding-register table. This map covers the whole published table.

This page lists 127 Modbus registers for the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) — 89 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from FW Murphy’s own free documentation (linked below) and checked against it.

Manufacturer
FW Murphy
Model
Interchange Comm Control Module MX5-R2 (Standard IO mode)
Equipment type
Remote I/O module (engine / pump controller expansion)
Registers
127 (89 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
9600 baud
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
Date code S8 or later; pulse engine registers 4.4.10111 / date code U10 or later
Also known as
MX5-R2, Interchange MX5-R2, Enovation Controls MX5-R2
Source document
Interchange Comm Control Module MX5-R2 Series Operations Manual · 00-02-3003 · rev. 2025-02-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)

Integration in brief

Poll holding registers 400021-400038 for inputs, write 400061 and 400047-400050 for outputs, and set 400073 plus the comm-failure registers so outputs go to a safe state if the client stops polling.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 20Digital inputs 1-16BITMAP16Digital inputs 1-16Read
HR 21Digital inputs 17-24BITMAP16Digital inputs 17-24Read
HR 23Analog input 1INT16Analog input 1Read
HR 37Frequency inputUINT16Frequency inputRead
HR 60Digital outputs 1-16BITMAP16Digital outputs 1-16Read/write
HR 46Analog output 1 signalUINT16Analog output 1Read/write
HR 72Communication timeoutUINT16Comm timeoutRead/write
HR 0Hardware typeUINT16Hardware type check (33)Read

Enable Modbus control & writes

Standard IO mode is the default (COP LED code 4,2). To reload it: power up with DIP 5-8 closed and DIP 2 open, 1/3/4 closed. DIP 5-8 closed with 1-4 closed loads factory defaults (baud, Ethernet, channel configuration).

Communication loss & watchdog

Register 400073 sets a communication timeout in seconds; when no client talks on any port for that time, outputs go to the states in 400064 and 400069-400072. Pulse mode is also cancelled on comm loss.

Byte order & addressing

Network setup

Watch out for

FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

127 of 127 shown
FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 400001Hardware typeModule ID; MX5-R2 returns 33.UINT16Read
HR4doc 400005Bootloader build versionUINT16Read
HR6doc 400007Firmware numberUINT16Read
HR7doc 400008Firmware build versionUINT16Read
HR8doc 400009-400010Firmware checksum32-bit; MSW in 400009, LSW in 400010.UINT32ABCDRead
HR10doc 400011Firmware major versionUINT16Read
HR11doc 400012Firmware minor versionUINT16Read
HR12doc 400013Bootloader major versionUINT16Read
HR13doc 400014Bootloader minor versionUINT16Read
HR20doc 400021Digital inputs 1-160 = open, 1 = closed; bit 0 = DI1.BITMAP16Readbit 0 = DI1 closed; bit 1 = DI2 closed; bit 2 = DI3 closed; bit 3 = DI4 closed; bit 4 = DI5 closed; bit 5 = DI6 closed; bit 6 = DI7 closed; bit 7 = DI8 closed; bit 8 = DI9 closed; bit 9 = DI10 closed; bit 10 = DI11 closed; bit 11 = DI12 closed; bit 12 = DI13 closed; bit 13 = DI14 closed; bit 14 = DI15 closed; bit 15 = DI16 closed
HR21doc 400022Digital inputs 17-240 = open, 1 = closed; bit 0 = DI17.BITMAP16Readbit 0 = DI17 closed; bit 1 = DI18 closed; bit 2 = DI19 closed; bit 3 = DI20 closed; bit 4 = DI21 closed; bit 5 = DI22 closed; bit 6 = DI23 closed; bit 7 = DI24 closed
HR22doc 400023System voltageSupply voltage; 320 = 32.0 V DC.UINT16× 0.1VRead
HR23doc 400024Analog input 1Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR24doc 400025Analog input 2Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR25doc 400026Analog input 3Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR26doc 400027Analog input 4Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR27doc 400028Analog input 5Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR28doc 400029Analog input 6Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR29doc 400030Analog input 7Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR30doc 400031Analog input 8Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR31doc 400032Analog input 9Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR32doc 400033Analog input 10Raw A/D counts; full scale depends on the channel type register.INT16countsRead
HR37doc 400038Frequency inputMagnetic pickup input, 0-10,000.UINT16HzRead
HR46doc 400047Analog output 1 signal0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428).UINT16countsRead/write
HR47doc 400048Analog output 2 signal0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428).UINT16countsRead/write
HR48doc 400049Analog output 3 signal0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428).UINT16countsRead/write
HR49doc 400050Analog output 4 signal0 = 0 mA, 65535 = 24 mA (4 mA = 10485, 20 mA = 52428).UINT16countsRead/write
HR52doc 400053RTC secondsRange 0-59; applied when 400060 = 1.UINT16sRead/write
HR53doc 400054RTC minutesRange 0-59; applied when 400060 = 1.UINT16minRead/write
HR54doc 400055RTC hoursRange 0-23; applied when 400060 = 1.UINT16hRead/write
HR55doc 400056RTC day of weekRange 1-7; applied when 400060 = 1.UINT16Read/write
HR56doc 400057RTC dayRange 1-31; applied when 400060 = 1.UINT16Read/write
HR57doc 400058RTC monthRange 1-12; applied when 400060 = 1.UINT16Read/write
HR58doc 400059RTC yearRange 2000-3000; applied when 400060 = 1.UINT16Read/write
HR59doc 400060Clock set enableWrite 1 to load 400053-400059 into the clock.UINT16Read/write0 = Disabled; 1 = Set clock
HR60doc 400061Digital outputs 1-16Bit 0 = DO1.BITMAP16Read/writebit 0 = DO1 on; bit 1 = DO2 on; bit 2 = DO3 on; bit 3 = DO4 on; bit 4 = DO5 on; bit 5 = DO6 on; bit 6 = DO7 on; bit 7 = DO8 on; bit 8 = DO9 on; bit 9 = DO10 on; bit 10 = DO11 on; bit 11 = DO12 on; bit 12 = DO13 on; bit 13 = DO14 on; bit 14 = DO15 on; bit 15 = DO16 on
HR62doc 400063Digital outputs at power-upStored state applied before any client talks; bit 0 = DO1.BITMAP16Read/writebit 0 = DO1 on; bit 1 = DO2 on; bit 2 = DO3 on; bit 3 = DO4 on; bit 4 = DO5 on; bit 5 = DO6 on; bit 6 = DO7 on; bit 7 = DO8 on; bit 8 = DO9 on; bit 9 = DO10 on; bit 10 = DO11 on; bit 11 = DO12 on; bit 12 = DO13 on; bit 13 = DO14 on; bit 14 = DO15 on; bit 15 = DO16 on
HR63doc 400064Digital outputs at comm failureState applied after the 400073 timeout; bit 0 = DO1.BITMAP16Read/writebit 0 = DO1 on; bit 1 = DO2 on; bit 2 = DO3 on; bit 3 = DO4 on; bit 4 = DO5 on; bit 5 = DO6 on; bit 6 = DO7 on; bit 7 = DO8 on; bit 8 = DO9 on; bit 9 = DO10 on; bit 10 = DO11 on; bit 11 = DO12 on; bit 12 = DO13 on; bit 13 = DO14 on; bit 14 = DO15 on; bit 15 = DO16 on
HR64doc 400065Analog output 1 at power-upD/A counts, 65535 = 24 mA; stored.UINT16countsRead/write
HR65doc 400066Analog output 2 at power-upD/A counts, 65535 = 24 mA; stored.UINT16countsRead/write
HR66doc 400067Analog output 3 at power-upD/A counts, 65535 = 24 mA; stored.UINT16countsRead/write
HR67doc 400068Analog output 4 at power-upD/A counts, 65535 = 24 mA; stored.UINT16countsRead/write
HR68doc 400069Analog output 1 at comm failureD/A counts, 65535 = 24 mA; stored.UINT16countsRead/write
HR69doc 400070Analog output 2 at comm failureD/A counts, 65535 = 24 mA; stored.UINT16countsRead/write
HR70doc 400071Analog output 3 at comm failureD/A counts, 65535 = 24 mA; stored.UINT16countsRead/write
HR71doc 400072Analog output 4 at comm failureD/A counts, 65535 = 24 mA; stored.UINT16countsRead/write
HR72doc 400073Communication timeoutSilence on all ports for this long switches outputs to their comm-failure states.UINT16sRead/write
HR73doc 400074Analog input 1 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA
HR74doc 400075Analog input 2 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA
HR75doc 400076Analog input 3 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA
HR76doc 400077Analog input 4 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA
HR77doc 400078Analog input 5 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA
HR78doc 400079Analog input 6 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA
HR79doc 400080Analog input 7 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA; 2 = 5 kohm resistive; 3 = 3 kohm resistive; 4 = 10 kohm resistive; 5 = 30 kohm resistive
HR80doc 400081Analog input 8 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA; 2 = 5 kohm resistive; 3 = 3 kohm resistive; 4 = 10 kohm resistive; 5 = 30 kohm resistive
HR81doc 400082Analog input 9 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA; 2 = 5 kohm resistive; 3 = 3 kohm resistive; 4 = 10 kohm resistive; 5 = 30 kohm resistive
HR82doc 400083Analog input 10 typeStored setting.UINT16Read/write0 = 0-5 V DC; 1 = 0-25 mA; 2 = 5 kohm resistive; 3 = 3 kohm resistive; 4 = 10 kohm resistive; 5 = 30 kohm resistive
HR84doc 400085Serial port baud rateUINT16Read/write1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 115200
HR85doc 400086Digital input 1-2 polarityHigh byte DI1, low byte DI2: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR86doc 400087Digital input 3-4 polarityHigh byte DI3, low byte DI4: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR87doc 400088Digital input 5-6 polarityHigh byte DI5, low byte DI6: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR88doc 400089Digital input 7-8 polarityHigh byte DI7, low byte DI8: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR89doc 400090Digital input 9-10 polarityHigh byte DI9, low byte DI10: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR90doc 400091Digital input 11-12 polarityHigh byte DI11, low byte DI12: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR91doc 400092Digital input 13-14 polarityHigh byte DI13, low byte DI14: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR92doc 400093Digital input 15-16 polarityHigh byte DI15, low byte DI16: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR93doc 400094Digital input 17-18 polarityHigh byte DI17, low byte DI18: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR94doc 400095Digital input 19-20 polarityHigh byte DI19, low byte DI20: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR95doc 400096Digital input 21-22 polarityHigh byte DI21, low byte DI22: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR96doc 400097Digital input 23-24 polarityHigh byte DI23, low byte DI24: 0 closed DC-, 1 closed DC+, 2 open.UINT16Read
HR115doc *400116High-resolution pulse enableBit 0 = DO1; pulse on/off times then override 400061.BITMAP16Read/writebit 0 = DO1 pulse enabled; bit 1 = DO2 pulse enabled; bit 2 = DO3 pulse enabled; bit 3 = DO4 pulse enabled; bit 4 = DO5 pulse enabled; bit 5 = DO6 pulse enabled; bit 6 = DO7 pulse enabled; bit 7 = DO8 pulse enabled; bit 8 = DO9 pulse enabled; bit 9 = DO10 pulse enabled; bit 10 = DO11 pulse enabled; bit 11 = DO12 pulse enabled; bit 12 = DO13 pulse enabled; bit 13 = DO14 pulse enabled; bit 14 = DO15 pulse enabled; bit 15 = DO16 pulse enabled
HR116doc *400117DO1 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR117doc *400118DO1 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR118doc *400119DO2 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR119doc *400120DO2 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR120doc *400121DO3 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR121doc *400122DO3 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR122doc *400123DO4 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR123doc *400124DO4 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR124doc *400125DO5 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR125doc *400126DO5 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR126doc *400127DO6 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR127doc *400128DO6 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR128doc *400129DO7 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR129doc *400130DO7 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR130doc *400131DO8 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR131doc *400132DO8 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR132doc *400133DO9 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR133doc *400134DO9 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR134doc *400135DO10 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR135doc *400136DO10 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR136doc *400137DO11 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR137doc *400138DO11 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR138doc *400139DO12 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR139doc *400140DO12 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR140doc *400141DO13 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR141doc *400142DO13 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR142doc *400143DO14 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR143doc *400144DO14 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR144doc *400145DO15 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR145doc *400146DO15 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR146doc *400147DO16 pulse on time0-255 x 50 ms; 0 keeps the output off.UINT16× 50msRead/write
HR147doc *400148DO16 pulse off time5-255 x 50 ms (minimum 250 ms).UINT16× 50msRead/write
HR65196doc 465197IP address part 1One octet, 0-255.UINT16Read/write
HR65197doc 465198IP address part 2One octet, 0-255.UINT16Read/write
HR65198doc 465199IP address part 3One octet, 0-255.UINT16Read/write
HR65199doc 465200IP address part 4One octet, 0-255.UINT16Read/write
HR65200doc 465201Network mask part 1One octet, 0-255.UINT16Read/write
HR65201doc 465202Network mask part 2One octet, 0-255.UINT16Read/write
HR65202doc 465203Network mask part 3One octet, 0-255.UINT16Read/write
HR65203doc 465204Network mask part 4One octet, 0-255.UINT16Read/write
HR65204doc 465205Gateway part 1One octet, 0-255.UINT16Read/write
HR65205doc 465206Gateway part 2One octet, 0-255.UINT16Read/write
HR65206doc 465207Gateway part 3One octet, 0-255.UINT16Read/write
HR65207doc 465208Gateway part 4One octet, 0-255.UINT16Read/write
HR65208doc 465209DNS1 part 1One octet, 0-255.UINT16Read/write
HR65209doc 465210DNS1 part 2One octet, 0-255.UINT16Read/write
HR65210doc 465211DNS1 part 3One octet, 0-255.UINT16Read/write
HR65211doc 465212DNS1 part 4One octet, 0-255.UINT16Read/write
HR65212doc 465213DNS2 part 1One octet, 0-255.UINT16Read/write
HR65213doc 465214DNS2 part 2One octet, 0-255.UINT16Read/write
HR65214doc 465215DNS2 part 3One octet, 0-255.UINT16Read/write
HR65215doc 465216DNS2 part 4One octet, 0-255.UINT16Read/write
HR65216doc 465217Ethernet IP optionsUINT16Read/write0 = Static IP, no auto IP; 1 = DHCP, no auto IP; 2 = Static IP, auto IP if no DHCP/IP; 3 = DHCP, auto IP if no DHCP/IP
HR65217doc 465218MAC address word 1UINT16Read
HR65218doc 465219MAC address word 2UINT16Read
HR65219doc 465220MAC address word 3UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)

What Modbus registers does the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) have?

This map lists 127 registers: 127 holding registers. 89 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed in 6-digit Modicon form (400001 = holding register 1). Wire address = number - 400001, e.g. digital inputs 400021 = address 20 and IP address 465197 = address 65196.

What byte order does the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)?

Start with HR 20 Digital inputs 1-16 (Digital inputs 1-16); HR 21 Digital inputs 17-24 (Digital inputs 17-24); HR 23 Analog input 1 (Analog input 1); HR 37 Frequency input (Frequency input); HR 60 Digital outputs 1-16 (Digital outputs 1-16); HR 46 Analog output 1 signal (Analog output 1); HR 72 Communication timeout (Comm timeout); HR 0 Hardware type (Hardware type check (33)).

How do I enable Modbus control of the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)?

Standard IO mode is the default (COP LED code 4,2). To reload it: power up with DIP 5-8 closed and DIP 2 open, 1/3/4 closed. DIP 5-8 closed with 1-4 closed loads factory defaults (baud, Ethernet, channel configuration).

What happens when the FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) loses Modbus communication?

Register 400073 sets a communication timeout in seconds; when no client talks on any port for that time, outputs go to the states in 400064 and 400069-400072. Pulse mode is also cancelled on comm loss.

Where is the official FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode) Modbus documentation?

The source is Interchange Comm Control Module MX5-R2 Series Operations Manual (00-02-3003), revision 2025-02-11, published free by FW Murphy at https://fwmurphy.com/wp-content/uploads/2025/02/00-02-3003.pdf.