Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus register map
Updated 19 November 2026
With the GLT licence active, the Novelan heating and heat pump controller is a Modbus TCP slave on port 502 at the controller's own IP address. Discrete inputs show utility block, smart-grid and compressor/heater states; input registers give temperatures, pressures, running hours, plant status, faults, output and 32-bit heat and energy counters; coils reset faults and force pumps on; holding registers take outdoor temperature, setpoints, operating modes, smart-grid state and heating-curve settings.
This page lists 95 Modbus registers for the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) — 37 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Novelan’s own free documentation (linked below) and checked against it.
- Manufacturer
- Novelan
- Model
- Novelan heat pump controller via Novelan GLT (Modbus TCP)
- Equipment type
- Heat pump
- Registers
- 95 (37 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Controller software V1.74/V2.74/V3.76/V4.76 or later for Modbus TCP
- Also known as
- Novelan GLT, 83055703, ait-deutschland GLT
Integration notes: Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)
License GLT with the supplied USB dongle, then poll input registers 0-59 and discrete inputs 0-7 over Modbus TCP and write holding registers 0-23 for outdoor temperature, setpoints and modes.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 37 | Anlagenstatus | UINT16 | Plant status | Read |
| IR 0 | Mitteltemperatur | INT16 | Mean outdoor temperature | Read |
| IR 1 | Vorlauftemperatur | INT16 | Flow temperature | Read |
| IR 2 | Rücklauftemperatur | INT16 | Return temperature | Read |
| IR 4 | Trinkwarmwassertemperatur | INT16 | Hot water temperature | Read |
| IR 46 | Fehlerspeicher | UINT16 | Active fault | Read |
| HR 1 | Rücklauf-Temperatur Soll | INT16 | Return temperature setpoint | Read/write |
| HR 7 | Betriebsart Heizung | UINT16 | Heating mode | Read/write |
| HR 14 | Smart Grid | UINT16 | Smart grid state | Read/write |
| CO 0 | Fehlerreset | BIT | Fault reset | Read/write |
Enable Modbus control & writes
Configure GLT with the Novelan GLT Tool, then insert the supplied USB dongle in the controller's USB port to unlock GLT permanently (otherwise only a test phase runs). Check Service > Informationen > GLT on the controller.
Byte order & addressing
- To stop forcing a value, write a value outside its limits (holding registers) or 0 (coils); otherwise the written value stays in force.
- Only the currently active fault is shown in input register 46.
Network setup
- Modbus TCP uses the controller's IP address and port 502; set the IP under Service > Systemsteuerung (DHCP server, DHCP client or fixed IP).
Watch out for
- Controllers with software older than the Modbus TCP versions listed can only use BACnet/IP.
Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0 | Fehlerreset | Write 1 to acknowledge the currently active fault. | BIT | Read/write | ||||
| CO | 2 | HUP | Force the HUP pump on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 3 | VEN | Force fan on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 4 | ZUP | Force auxiliary circulation pump on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 5 | BUP | Force hot water circulation pump on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 6 | BOSUP | Force well/brine pump on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 7 | ZIP | Force DHW circulation pump on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 8 | FUP2 | Force floor heating pump 2 on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 9 | FUP3 | Force floor heating pump 3 on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 10 | SLP | Force solar charge pump on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 11 | SUP | Force pool circulation pump on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 12 | VSK | Force the bypass flap (VSK) on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| CO | 13 | FRH | Force defroster heater contactor on | BIT | Read/write | 0 = Automatic; 1 = On | |||
| DI | 0 | EVU | Utility blocking time (EVU) input | BIT | Read | ||||
| DI | 1 | EVU2 | Smart grid input EVU2 | BIT | Read | ||||
| DI | 2 | SWT | Pool thermostat input | BIT | Read | ||||
| DI | 3 | VD1 | Compressor 1 | BIT | Read | ||||
| DI | 4 | VD2 | Compressor 2 | BIT | Read | ||||
| DI | 5 | ZWE1 | Auxiliary heater 1 | BIT | Read | ||||
| DI | 6 | ZWE2 | Auxiliary heater 2 | BIT | Read | ||||
| DI | 7 | ZWE3 | Auxiliary heater 3 | BIT | Read | ||||
| IR | 0 | Mitteltemperatur | Mean outdoor temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 1 | Vorlauftemperatur | Flow temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 2 | Rücklauftemperatur | Return temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 3 | Rücklauf extern | External return temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 4 | Trinkwarmwassertemperatur | Hot water temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 5 | Mischkreis 1 Vorlauf | Mixing circuit 1 flow temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 6 | Mischkreis 2 Vorlauf | Mixing circuit 2 flow temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 7 | Mischkreis 3 Vorlauf | Mixing circuit 3 flow temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 8 | Heissgastemperatur | Hot gas temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 9 | Wärmequelle Eintritt | Heat source inlet temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 10 | Wärmequelle Austritt | Heat source outlet temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 11 | Raumfernversteller 1 | Remote room unit 1 temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 12 | Raumfernversteller 2 | Remote room unit 2 temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 13 | Raumfernversteller 3 | Remote room unit 3 temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 14 | Solarkollektor | Solar collector temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 15 | Solarspeicher | Solar tank temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 16 | Externe Energiequelle | External energy source temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 17 | Zulufttemperatur | Supply air temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 18 | Ablufttemperatur | Extract air temperature | INT16 | × 0.1 | °C | Read | ||
| IR | 19 | Ansaugtemperatur Verdichter | Compressor suction temperature (LIN/Modbus units) | INT16 | × 0.1 | °C | Read | ||
| IR | 20 | Ansaugtemperatur Verdampfer | Evaporator suction temperature (LIN/Modbus units) | INT16 | × 0.1 | °C | Read | ||
| IR | 21 | Temperatur Verdichterheizung | Compressor heater temperature (LIN/Modbus units) | INT16 | × 0.1 | °C | Read | ||
| IR | 22 | Überhitzung | Superheat (LIN/Modbus units). | INT16 | × 0.1 | K | Read | ||
| IR | 23 | Überhitzung Soll | Superheat setpoint (LIN/Modbus units). | INT16 | × 0.1 | K | Read | ||
| IR | 24 | RBE Raumtemperatur Ist | Room control unit actual temperature. | INT16 | × 0.1 | °C | Read | ||
| IR | 25 | RBE Raumtemperatur Soll | Room control unit setpoint. | INT16 | × 0.1 | °C | Read | ||
| IR | 26 | Druck HD (Hochdruck) | High pressure (LIN/Modbus units). | UINT16 | × 0.01 | bar | Read | ||
| IR | 27 | Druck ND (Niederdruck) | Low pressure (LIN/Modbus units). | UINT16 | × 0.01 | bar | Read | ||
| IR | 28 | Betriebsstunden VD 1 | Compressor 1 hours | UINT16 | h | Read | |||
| IR | 29 | Betriebsstunden VD 2 | Compressor 2 hours | UINT16 | h | Read | |||
| IR | 30 | Betriebsstunden ZWE 1 | Aux heater 1 hours | UINT16 | h | Read | |||
| IR | 31 | Betriebsstunden ZWE 2 | Aux heater 2 hours | UINT16 | h | Read | |||
| IR | 32 | Betriebsstunden ZWE 3 | Aux heater 3 hours | UINT16 | h | Read | |||
| IR | 33 | Betriebsstunden Wärmepumpe | Heat pump hours | UINT16 | h | Read | |||
| IR | 34 | Betriebsstunden Heizung | Heating hours | UINT16 | h | Read | |||
| IR | 35 | Betriebsstunden Trinkwarmwasser | Hot water hours | UINT16 | h | Read | |||
| IR | 36 | Betriebsstunden SWoPV | Pool or photovoltaic (SWoPV) hours | UINT16 | h | Read | |||
| IR | 37 | Anlagenstatus | Plant status. | UINT16 | Read | 0 = Heating; 1 = Hot water; 2 = Swimming pool; 3 = Utility block (EVU); 4 = Defrost; 5 = Off; 6 = External energy source; 7 = Cooling | |||
| IR | 38doc 38-39 | Wärmemenge Heizung | Heat quantity, heating; High word at 38, Low word at 39. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 40doc 40-41 | Wärmemenge Trinkwarmwasser | Heat quantity, hot water; High word at 40, Low word at 41. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 42doc 42-43 | Wärmemenge Schwimmbad | Heat quantity, pool; High word at 42, Low word at 43. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 44doc 44-45 | Wärmemenge gesamt | Heat quantity, total; High word at 44, Low word at 45. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 46 | Fehlerspeicher | Number of the currently active fault only. | UINT16 | Read | ||||
| IR | 47 | Leistung Ist | Actual heating output. | UINT16 | × 0.01 | kW | Read | ||
| IR | 48doc 48-49 | Wärmemenge Kühlung | Heat quantity, cooling; High word at 48, Low word at 49. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 50doc 50-51 | Eingesetzte Energie Heizung | Energy used, heating; High word at 50, Low word at 51. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 52doc 52-53 | Eingesetzte Energie Trinkwarmwasser | Energy used, hot water; High word at 52, Low word at 53. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 54doc 54-55 | Eingesetzte Energie Kühlung | Energy used, cooling; High word at 54, Low word at 55. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 56doc 56-57 | Eingesetzte Energie Schwimmbad | Energy used, pool; High word at 56, Low word at 57. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| IR | 58doc 58-59 | Eingesetzte Energie gesamt | Energy used, total; High word at 58, Low word at 59. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 0 | Außentemperatur | Outdoor temperature sent by the BMS, -20.0 to 80.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1 | Rücklauf-Temperatur Soll | Return temperature setpoint, 15.0-80.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 2 | Mischkreis 1 Vorlauf Solltemperatur | Mixing circuit 1 flow setpoint, 15.0-80.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 3 | Mischkreis 2 Vorlauf Solltemperatur | Mixing circuit 2 flow setpoint, 15.0-80.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 4 | Mischkreis 3 Vorlauf Solltemperatur | Mixing circuit 3 flow setpoint, 15.0-80.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 5 | Trinkwarmwasser-Temperatur Wunschwert | Hot water setpoint, 15.0-80.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 6 | Sperre / Freigabe Wärmepumpe | Heat pump block / release. | UINT16 | Read/write | 0 = Heat pump blocked; 1 = Release 1 compressor; 2 = Release 2 compressors | |||
| HR | 7 | Betriebsart Heizung | Heating operating mode. | UINT16 | Read/write | 0 = Automatic; 1 = Additional heat generator; 2 = Party; 3 = Holiday; 4 = Off | |||
| HR | 8 | Betriebsart Trinkwarmwasser | Hot water operating mode. | UINT16 | Read/write | 0 = Automatic; 1 = Additional heat generator; 2 = Party; 3 = Holiday; 4 = Off | |||
| HR | 9 | Betriebsart Mischkreis 2 | Mixing circuit 2 mode. | UINT16 | Read/write | 0 = Automatic; 1 = Additional heat generator; 2 = Party; 3 = Holiday; 4 = Off | |||
| HR | 10 | Betriebsart Mischkreis 3 | Mixing circuit 3 mode. | UINT16 | Read/write | 0 = Automatic; 1 = Additional heat generator; 2 = Party; 3 = Holiday; 4 = Off | |||
| HR | 11 | Betriebsart Kühlung | Cooling mode. | UINT16 | Read/write | 0 = Off; 1 = Automatic | |||
| HR | 12 | Betriebsart Lüftung | Ventilation mode. | UINT16 | Read/write | 0 = Automatic; 1 = Party; 2 = Holiday; 3 = Off | |||
| HR | 13 | Betriebsart Schwimmbad | Swimming pool mode. | UINT16 | Read/write | 0 = Automatic; 1 = Not used; 2 = Party; 3 = Holiday; 4 = Off | |||
| HR | 14 | Smart Grid | UINT16 | Read/write | 0 = Utility block (EVU); 1 = Smart Grid Low; 2 = Standard; 3 = Smart Grid High | ||||
| HR | 15 | Heizkurve Heizung Endpunkt | Heating curve end point, 20.0-70.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 16 | Heizkurve Heizung Parallelverschiebung | Heating curve parallel shift, 5.0-35.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 17 | Heizkurve Mischkreis 1 Endpunkt | Mixing circuit 1 curve end point, 20.0-70.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 18 | Heizkurve Mischkreis 1 Parallelverschiebung | Mixing circuit 1 curve parallel shift, 5.0-35.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 19 | Heizkurve Mischkreis 2 Endpunkt | Mixing circuit 2 curve end point, 20.0-70.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 20 | Heizkurve Mischkreis 2 Parallelverschiebung | Mixing circuit 2 curve parallel shift, 5.0-35.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 21 | Heizkurve Mischkreis 3 Endpunkt | Mixing circuit 3 curve end point, 20.0-70.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 22 | Heizkurve Mischkreis 3 Parallelverschiebung | Mixing circuit 3 curve parallel shift, 5.0-35.0. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 23 | Temperatur + - | Temperature offset, -5.0 to 5.0. | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- ait-deutschland / Novelan do not appear to host this manual publicly; the link is an unaltered copy of the manufacturer's PDF posted on the ioBroker forum.
- The manual calls all registers integer values without stating signedness. Temperatures and the holding offset 23 are listed as INT16 because the holding outdoor temperature accepts -200 (= -20.0 °C) and the offset -50; the input-register temperatures have no printed range, so negative readings assume two's complement.
- 'Auflösung 10' means tenths (scale 0.1) and 'Auflösung 100' hundredths (scale 0.01). Heat and energy counters are printed in 'kW/h' and are taken as kWh.
- Each 32-bit counter is split into High and Low registers; the manual says to shift High 16 bits left and add Low, with High at the lower ID, so they are listed as UINT32 high word first.
- Data points marked * in the manual exist only on units with LIN and/or Modbus components; greyed points need a comfort/extension or ventilation board. Values for points not visible on the controller display are invalid.
- Discrete inputs exist only for IDs 0-7. Coil 1 is reserved and left out.
- Coils read 0 = off and 1 = on. Writing 1 forces the output on; writing 0 hands it back to automatic control.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)
What Modbus registers does the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) have?
This map lists 95 registers: 13 coils, 8 discrete inputs, 50 input registers, 24 holding registers. 37 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual warns that registers are 0-based: the printed ID is the wire address (input register 0 = mean outdoor temperature, holding register 0 = outdoor temperature).
What byte order does the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)?
Start with IR 37 Anlagenstatus (Plant status); IR 0 Mitteltemperatur (Mean outdoor temperature); IR 1 Vorlauftemperatur (Flow temperature); IR 2 Rücklauftemperatur (Return temperature); IR 4 Trinkwarmwassertemperatur (Hot water temperature); IR 46 Fehlerspeicher (Active fault); HR 1 Rücklauf-Temperatur Soll (Return temperature setpoint); HR 7 Betriebsart Heizung (Heating mode); HR 14 Smart Grid (Smart grid state); CO 0 Fehlerreset (Fault reset).
How do I enable Modbus control of the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)?
Configure GLT with the Novelan GLT Tool, then insert the supplied USB dongle in the controller's USB port to unlock GLT permanently (otherwise only a test phase runs). Check Service > Informationen > GLT on the controller.
Where is the official Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus documentation?
The source is Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT (Betriebsanleitung) (83055703hDE). Novelan doesn't publish it on its own website, so this map was re-typed from a free copy at https://forum.iobroker.net/assets/uploads/files/1732701258966-83055703hde_novelan_glt.pdf. It may be an older revision, so check it against the live unit.
Other pumps register maps
- Pump (high-efficiency circulator)
Wilo Atmos MAXO with CIF module Modbus RTU
Wilo Atmos MAXO pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Atmos MAXO - Pump (high-efficiency circulator)
Wilo Stratos PICO plus with CIF module Modbus RTU
Wilo Stratos PICO plus pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Stratos PICO plus - Heat pump
CTC CTC heat pumps and controllers via BMS (Modbus TCP)
CTC EcoHeat 400, EcoZenith i250/i350/i550, EcoVent i350F, GSi/GS, EcoPart 6xx M/Pro and EcoLogic controllers whose display has three ports (Ethernet), BMS document 16260016-3 (CR01143, 2026-02-02).
Also known as: CTC EcoHeat 400, CTC EcoZenith i250, CTC GSi, CTC GS, CTC EcoZenith i350, CTC EcoVent i350F, CTC EcoZenith i550, CTC EcoPart 600M, CTC EcoPart Pro, CTC EcoLogic, CTC EcoLogic S, 16260016-3 - Remote I/O module (engine / pump controller expansion)
FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)
FW Murphy MX5-R2 modules with date code S8 or later running the Standard IO application (default); pulse registers need firmware 4.4.10111 / date code U10 or later.
Also known as: MX5-R2, Interchange MX5-R2, Enovation Controls MX5-R2 - Pump (chemical dosing pump)
Grundfos SMART Digital DDA dosing pump (SoftCIM, CIM 200 / CIM 500)
Grundfos SMART Digital DDA dosing pumps: DDA model C with built-in SoftCIM Modbus RTU/TCP, and DDA XL (or others) through a CIM 200 Modbus RTU or CIM 500 Modbus TCP module in a CIU 900, per functional profile 98473491 (09.2026).
Also known as: DDA, DDA S, DDA XL, DDA-C, DDA model C, SMART Digital S, SMART Digital XL, CIM 200, CIM 500, 98473491 - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
All pumps Modbus register maps →
Source: Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT (Betriebsanleitung) · 83055703hDE · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.