  4. Novelan heat pump controller via Novelan GLT (Modbus TCP)

Heat pump · Modbus register map

Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus register map

Updated 19 November 2026

Short answer

With the GLT licence active, the Novelan heating and heat pump controller is a Modbus TCP slave on port 502 at the controller's own IP address. Discrete inputs show utility block, smart-grid and compressor/heater states; input registers give temperatures, pressures, running hours, plant status, faults, output and 32-bit heat and energy counters; coils reset faults and force pumps on; holding registers take outdoor temperature, setpoints, operating modes, smart-grid state and heating-curve settings.

This page lists 95 Modbus registers for the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) — 37 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Novelan’s own free documentation (linked below) and checked against it.

Manufacturer
Novelan
Model
Novelan heat pump controller via Novelan GLT (Modbus TCP)
Equipment type
Heat pump
Registers
95 (37 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
Controller software V1.74/V2.74/V3.76/V4.76 or later for Modbus TCP
Also known as
Novelan GLT, 83055703, ait-deutschland GLT
Source document
Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT (Betriebsanleitung) · 83055703hDE · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)

Integration in brief

License GLT with the supplied USB dongle, then poll input registers 0-59 and discrete inputs 0-7 over Modbus TCP and write holding registers 0-23 for outdoor temperature, setpoints and modes.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 37AnlagenstatusUINT16Plant statusRead
IR 0MitteltemperaturINT16Mean outdoor temperatureRead
IR 1VorlauftemperaturINT16Flow temperatureRead
IR 2RücklauftemperaturINT16Return temperatureRead
IR 4TrinkwarmwassertemperaturINT16Hot water temperatureRead
IR 46FehlerspeicherUINT16Active faultRead
HR 1Rücklauf-Temperatur SollINT16Return temperature setpointRead/write
HR 7Betriebsart HeizungUINT16Heating modeRead/write
HR 14Smart GridUINT16Smart grid stateRead/write
CO 0FehlerresetBITFault resetRead/write

Enable Modbus control & writes

Configure GLT with the Novelan GLT Tool, then insert the supplied USB dongle in the controller's USB port to unlock GLT permanently (otherwise only a test phase runs). Check Service > Informationen > GLT on the controller.

Byte order & addressing

Network setup

Watch out for

Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

95 of 95 shown
Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0FehlerresetWrite 1 to acknowledge the currently active fault.BITRead/write
CO2HUPForce the HUP pump onBITRead/write0 = Automatic; 1 = On
CO3VENForce fan onBITRead/write0 = Automatic; 1 = On
CO4ZUPForce auxiliary circulation pump onBITRead/write0 = Automatic; 1 = On
CO5BUPForce hot water circulation pump onBITRead/write0 = Automatic; 1 = On
CO6BOSUPForce well/brine pump onBITRead/write0 = Automatic; 1 = On
CO7ZIPForce DHW circulation pump onBITRead/write0 = Automatic; 1 = On
CO8FUP2Force floor heating pump 2 onBITRead/write0 = Automatic; 1 = On
CO9FUP3Force floor heating pump 3 onBITRead/write0 = Automatic; 1 = On
CO10SLPForce solar charge pump onBITRead/write0 = Automatic; 1 = On
CO11SUPForce pool circulation pump onBITRead/write0 = Automatic; 1 = On
CO12VSKForce the bypass flap (VSK) onBITRead/write0 = Automatic; 1 = On
CO13FRHForce defroster heater contactor onBITRead/write0 = Automatic; 1 = On
DI0EVUUtility blocking time (EVU) inputBITRead
DI1EVU2Smart grid input EVU2BITRead
DI2SWTPool thermostat inputBITRead
DI3VD1Compressor 1BITRead
DI4VD2Compressor 2BITRead
DI5ZWE1Auxiliary heater 1BITRead
DI6ZWE2Auxiliary heater 2BITRead
DI7ZWE3Auxiliary heater 3BITRead
IR0MitteltemperaturMean outdoor temperatureINT16× 0.1°CRead
IR1VorlauftemperaturFlow temperatureINT16× 0.1°CRead
IR2RücklauftemperaturReturn temperatureINT16× 0.1°CRead
IR3Rücklauf externExternal return temperatureINT16× 0.1°CRead
IR4TrinkwarmwassertemperaturHot water temperatureINT16× 0.1°CRead
IR5Mischkreis 1 VorlaufMixing circuit 1 flow temperatureINT16× 0.1°CRead
IR6Mischkreis 2 VorlaufMixing circuit 2 flow temperatureINT16× 0.1°CRead
IR7Mischkreis 3 VorlaufMixing circuit 3 flow temperatureINT16× 0.1°CRead
IR8HeissgastemperaturHot gas temperatureINT16× 0.1°CRead
IR9Wärmequelle EintrittHeat source inlet temperatureINT16× 0.1°CRead
IR10Wärmequelle AustrittHeat source outlet temperatureINT16× 0.1°CRead
IR11Raumfernversteller 1Remote room unit 1 temperatureINT16× 0.1°CRead
IR12Raumfernversteller 2Remote room unit 2 temperatureINT16× 0.1°CRead
IR13Raumfernversteller 3Remote room unit 3 temperatureINT16× 0.1°CRead
IR14SolarkollektorSolar collector temperatureINT16× 0.1°CRead
IR15SolarspeicherSolar tank temperatureINT16× 0.1°CRead
IR16Externe EnergiequelleExternal energy source temperatureINT16× 0.1°CRead
IR17ZulufttemperaturSupply air temperatureINT16× 0.1°CRead
IR18AblufttemperaturExtract air temperatureINT16× 0.1°CRead
IR19Ansaugtemperatur VerdichterCompressor suction temperature (LIN/Modbus units)INT16× 0.1°CRead
IR20Ansaugtemperatur VerdampferEvaporator suction temperature (LIN/Modbus units)INT16× 0.1°CRead
IR21Temperatur VerdichterheizungCompressor heater temperature (LIN/Modbus units)INT16× 0.1°CRead
IR22ÜberhitzungSuperheat (LIN/Modbus units).INT16× 0.1KRead
IR23Überhitzung SollSuperheat setpoint (LIN/Modbus units).INT16× 0.1KRead
IR24RBE Raumtemperatur IstRoom control unit actual temperature.INT16× 0.1°CRead
IR25RBE Raumtemperatur SollRoom control unit setpoint.INT16× 0.1°CRead
IR26Druck HD (Hochdruck)High pressure (LIN/Modbus units).UINT16× 0.01barRead
IR27Druck ND (Niederdruck)Low pressure (LIN/Modbus units).UINT16× 0.01barRead
IR28Betriebsstunden VD 1Compressor 1 hoursUINT16hRead
IR29Betriebsstunden VD 2Compressor 2 hoursUINT16hRead
IR30Betriebsstunden ZWE 1Aux heater 1 hoursUINT16hRead
IR31Betriebsstunden ZWE 2Aux heater 2 hoursUINT16hRead
IR32Betriebsstunden ZWE 3Aux heater 3 hoursUINT16hRead
IR33Betriebsstunden WärmepumpeHeat pump hoursUINT16hRead
IR34Betriebsstunden HeizungHeating hoursUINT16hRead
IR35Betriebsstunden TrinkwarmwasserHot water hoursUINT16hRead
IR36Betriebsstunden SWoPVPool or photovoltaic (SWoPV) hoursUINT16hRead
IR37AnlagenstatusPlant status.UINT16Read0 = Heating; 1 = Hot water; 2 = Swimming pool; 3 = Utility block (EVU); 4 = Defrost; 5 = Off; 6 = External energy source; 7 = Cooling
IR38doc 38-39Wärmemenge HeizungHeat quantity, heating; High word at 38, Low word at 39.UINT32ABCD× 0.1kWhRead
IR40doc 40-41Wärmemenge TrinkwarmwasserHeat quantity, hot water; High word at 40, Low word at 41.UINT32ABCD× 0.1kWhRead
IR42doc 42-43Wärmemenge SchwimmbadHeat quantity, pool; High word at 42, Low word at 43.UINT32ABCD× 0.1kWhRead
IR44doc 44-45Wärmemenge gesamtHeat quantity, total; High word at 44, Low word at 45.UINT32ABCD× 0.1kWhRead
IR46FehlerspeicherNumber of the currently active fault only.UINT16Read
IR47Leistung IstActual heating output.UINT16× 0.01kWRead
IR48doc 48-49Wärmemenge KühlungHeat quantity, cooling; High word at 48, Low word at 49.UINT32ABCD× 0.1kWhRead
IR50doc 50-51Eingesetzte Energie HeizungEnergy used, heating; High word at 50, Low word at 51.UINT32ABCD× 0.1kWhRead
IR52doc 52-53Eingesetzte Energie TrinkwarmwasserEnergy used, hot water; High word at 52, Low word at 53.UINT32ABCD× 0.1kWhRead
IR54doc 54-55Eingesetzte Energie KühlungEnergy used, cooling; High word at 54, Low word at 55.UINT32ABCD× 0.1kWhRead
IR56doc 56-57Eingesetzte Energie SchwimmbadEnergy used, pool; High word at 56, Low word at 57.UINT32ABCD× 0.1kWhRead
IR58doc 58-59Eingesetzte Energie gesamtEnergy used, total; High word at 58, Low word at 59.UINT32ABCD× 0.1kWhRead
HR0AußentemperaturOutdoor temperature sent by the BMS, -20.0 to 80.0.INT16× 0.1°CRead/write
HR1Rücklauf-Temperatur SollReturn temperature setpoint, 15.0-80.0.INT16× 0.1°CRead/write
HR2Mischkreis 1 Vorlauf SolltemperaturMixing circuit 1 flow setpoint, 15.0-80.0.INT16× 0.1°CRead/write
HR3Mischkreis 2 Vorlauf SolltemperaturMixing circuit 2 flow setpoint, 15.0-80.0.INT16× 0.1°CRead/write
HR4Mischkreis 3 Vorlauf SolltemperaturMixing circuit 3 flow setpoint, 15.0-80.0.INT16× 0.1°CRead/write
HR5Trinkwarmwasser-Temperatur WunschwertHot water setpoint, 15.0-80.0.INT16× 0.1°CRead/write
HR6Sperre / Freigabe WärmepumpeHeat pump block / release.UINT16Read/write0 = Heat pump blocked; 1 = Release 1 compressor; 2 = Release 2 compressors
HR7Betriebsart HeizungHeating operating mode.UINT16Read/write0 = Automatic; 1 = Additional heat generator; 2 = Party; 3 = Holiday; 4 = Off
HR8Betriebsart TrinkwarmwasserHot water operating mode.UINT16Read/write0 = Automatic; 1 = Additional heat generator; 2 = Party; 3 = Holiday; 4 = Off
HR9Betriebsart Mischkreis 2Mixing circuit 2 mode.UINT16Read/write0 = Automatic; 1 = Additional heat generator; 2 = Party; 3 = Holiday; 4 = Off
HR10Betriebsart Mischkreis 3Mixing circuit 3 mode.UINT16Read/write0 = Automatic; 1 = Additional heat generator; 2 = Party; 3 = Holiday; 4 = Off
HR11Betriebsart KühlungCooling mode.UINT16Read/write0 = Off; 1 = Automatic
HR12Betriebsart LüftungVentilation mode.UINT16Read/write0 = Automatic; 1 = Party; 2 = Holiday; 3 = Off
HR13Betriebsart SchwimmbadSwimming pool mode.UINT16Read/write0 = Automatic; 1 = Not used; 2 = Party; 3 = Holiday; 4 = Off
HR14Smart GridUINT16Read/write0 = Utility block (EVU); 1 = Smart Grid Low; 2 = Standard; 3 = Smart Grid High
HR15Heizkurve Heizung EndpunktHeating curve end point, 20.0-70.0.INT16× 0.1°CRead/write
HR16Heizkurve Heizung ParallelverschiebungHeating curve parallel shift, 5.0-35.0.INT16× 0.1°CRead/write
HR17Heizkurve Mischkreis 1 EndpunktMixing circuit 1 curve end point, 20.0-70.0.INT16× 0.1°CRead/write
HR18Heizkurve Mischkreis 1 ParallelverschiebungMixing circuit 1 curve parallel shift, 5.0-35.0.INT16× 0.1°CRead/write
HR19Heizkurve Mischkreis 2 EndpunktMixing circuit 2 curve end point, 20.0-70.0.INT16× 0.1°CRead/write
HR20Heizkurve Mischkreis 2 ParallelverschiebungMixing circuit 2 curve parallel shift, 5.0-35.0.INT16× 0.1°CRead/write
HR21Heizkurve Mischkreis 3 EndpunktMixing circuit 3 curve end point, 20.0-70.0.INT16× 0.1°CRead/write
HR22Heizkurve Mischkreis 3 ParallelverschiebungMixing circuit 3 curve parallel shift, 5.0-35.0.INT16× 0.1°CRead/write
HR23Temperatur + -Temperature offset, -5.0 to 5.0.INT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)

What Modbus registers does the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) have?

This map lists 95 registers: 13 coils, 8 discrete inputs, 50 input registers, 24 holding registers. 37 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual warns that registers are 0-based: the printed ID is the wire address (input register 0 = mean outdoor temperature, holding register 0 = outdoor temperature).

What byte order does the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)?

Start with IR 37 Anlagenstatus (Plant status); IR 0 Mitteltemperatur (Mean outdoor temperature); IR 1 Vorlauftemperatur (Flow temperature); IR 2 Rücklauftemperatur (Return temperature); IR 4 Trinkwarmwassertemperatur (Hot water temperature); IR 46 Fehlerspeicher (Active fault); HR 1 Rücklauf-Temperatur Soll (Return temperature setpoint); HR 7 Betriebsart Heizung (Heating mode); HR 14 Smart Grid (Smart grid state); CO 0 Fehlerreset (Fault reset).

How do I enable Modbus control of the Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP)?

Configure GLT with the Novelan GLT Tool, then insert the supplied USB dongle in the controller's USB port to unlock GLT permanently (otherwise only a test phase runs). Check Service > Informationen > GLT on the controller.

Where is the official Novelan Novelan heat pump controller via Novelan GLT (Modbus TCP) Modbus documentation?

The source is Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT (Betriebsanleitung) (83055703hDE). Novelan doesn't publish it on its own website, so this map was re-typed from a free copy at https://forum.iobroker.net/assets/uploads/files/1732701258966-83055703hde_novelan_glt.pdf. It may be an older revision, so check it against the live unit.

Other pumps register maps

All pumps Modbus register maps →

Source: Zubehör für Wärmepumpen - Anbindung an eine Gebäudeleittechnik via BACnet/IP | ModBus/TCP - Novelan GLT (Betriebsanleitung) · 83055703hDE · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.