Pump (high-efficiency circulator) · Modbus register map

Wilo Stratos PICO plus with CIF module Modbus RTU Modbus register map

Updated 17 November 2026

Short answer

The Wilo Stratos PICO plus gets Modbus RTU through Wilo's plug-in CIF module. A master switches the pump on/off with the pump command word, selects the control mode and writes a relative duty point in 0.5 % steps; a bus command timer can fall back to preset values when communication stops. Read-only data covers head, flow, power, energy, speed, temperatures and status/error words. This map keeps only the points Wilo marks as supported on the Stratos PICO plus.

This page lists 37 Modbus registers for the Wilo Stratos PICO plus with CIF module Modbus RTU — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Wilo’s own free documentation (linked below) and checked against it.

Manufacturer
Wilo
Model
Stratos PICO plus with CIF module Modbus RTU
Equipment type
Pump (high-efficiency circulator)
Registers
37 (10 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
CIF module Modbus RTU 1.00-99.99 (module versions per register as noted)
Also known as
Wilo-Stratos PICO plus
Source document
WILO Modbus RTU · wilo194406
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Wilo Stratos PICO plus with CIF module Modbus RTU

Integration in brief

Set bus address, baud (parameter A) and frame (parameter C) in the pump menu, then write the control mode (H 42), the duty point (H 1) and the pump command (H 40). Poll status (I 404 if present), error code (I 940) and the measured values in the I 1-I 10 block.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 40Pump Command inBITMAP16On/off command (bit 3 = 1 when writing, if listed)Read/write
HR 42controlFunctionUINT16Control modeRead/write
HR 1dutyPointRelINT16Setpoint (duty point, 0.5 % steps)Read/write
IR 404Operation StatusBITMAP16Operation status flagsRead
IR 940warning/errorMessageUINT16Active warning/error codeRead
IR 1pressureUINT16Actual pressureRead
IR 2flowUINT16FlowRead
IR 4powerInputUINT16Power inputRead

Enable Modbus control & writes

Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.

Communication loss & watchdog

The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.

Byte order & addressing

Network setup

Watch out for

Wilo Stratos PICO plus with CIF module Modbus RTU Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

37 of 37 shown
Wilo Stratos PICO plus with CIF module Modbus RTU Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR1pressureActual pressure (head) at the pump.UINT16× 10cm H₂ORead
IR2flowActual or calculated flow. Error value 9999 up to module 6.00, 65535 from 6.01.UINT16× 0.1m³/hRead
IR3energyConsumptionEnergy consumption counter.UINT16kWhRead
IR4powerInputElectrical power input.UINT16WRead
IR7speedMotor speed.INT161/minRead
IR8temperatureFluid@DeviceFluid temperature measured at the pump, in kelvin.UINT16× 0.1KRead
IR10controlFunctionActive control mode.UINT16Read1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 15 = INVALID; 80 = Gen_DA
IR18speed max-pres-valueMaximum speed.UINT161/minRead
IR19speed min-pres-valueMinimum speed.UINT161/minRead
IR24flow max-pres-valueMaximum (calculated) flow.UINT16× 0.1m³/hRead
IR36Error TypeLegacy register; prefer I 940 for new work.BITMAP16Readbit 3 = errorPresent
IR38Pump StatusLegacy controller status flags.BITMAP16Readbit 0 = device/functionOn; bit 5 = localOperation
IR39State DiagnosticsLegacy diagnostic flags.BITMAP16Readbit 0 = errorPresent; bit 8 = localOperation; bit 10 = device/functionOn
IR102Pump StatusStatus flags of the partner pump (twin-head).BITMAP16Readbit 5 = localOperation
IR200dutyPointRelSetpoint the pump is actually using (200 = 100 %). Module 3.00+.INT16× 0.5%Read
IR202dutyPointRel maximum-outputUpper limit of the active setpoint. Module 3.00+.INT16× 0.5%Read
IR204dutyPointRel minimum-outputLower limit; lower writes are limited to it. Module 3.00+.INT16× 0.5%Read
IR206dutyPoint100%ValEngineering value at 100 % in the current mode; unit in I 208. Module 3.00+.FLOAT32ABCDRead
IR208dutyPointRel unitsUnit code for I 206. Module 3.00+.UINT16Read3 = A; 19 = kWh; 47 = W; 73 = s; 95 = {noUnit}; 104 = min-1; 135 = m3/h
IR210setpointSignalSourceModule 3.00+.UINT16Read1 = IF-Module; 6 = Internal; 9 = INVALID
IR320voltageInputMains input voltage. Module 3.00+.UINT16× 0.1VRead
IR400dutyPointRelDuty point currently in use.INT16× 0.5%Read
IR402Pump Command activeCommand currently in effect.BITMAP16Readbit 0 = device/functionOn
IR404Operation StatusMain run / warning / error flags.BITMAP16Readbit 0 = ready4Operation; bit 1 = device/functionOn; bit 3 = warningPresent; bit 4 = errorPresent; bit 5 = finalErrorPresent
IR500heartbeatCountCounts pump-to-module heartbeats; resets on restart.UINT32ABCDRead
IR504busCmd.TimerTimeRemain.Seconds left before the bus command timer elapses (module 3.02+).UINT16sRead
IR940warning/errorMessageActive Wilo warning/error code.UINT16Read255 = INVALID
HR1dutyPointRelSetpoint in % of the active mode's 100 % value (200 = 100 %).INT16× 0.5%Read/write
HR40Pump Command inOn/off and override command word.BITMAP16Read/writebit 0 = device/functionOn; bit 4 = overrideOff (module 3.00+)
HR42controlFunctionControl mode; unsupported values are ignored.UINT16Read/write1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 15 = INVALID; 80 = Gen_DA
HR300busCmd.TimerBus command timer / fallback state machine.UINT16Read/write1 = OFF; 2 = SET; 3 = ACTIVE; 4 = RESET; 5 = MANUAL; 6 = SET_PRESET; 7 = ACTIVE_PRESET; 8 = RESET_PRESET; 9 = MANUAL_PRESET; 10 = INVALID
HR400busCmd.TimerTimeoutBus command timer timeout. Module 3.00+.UINT16sRead/write
HR401setpointSignalSourceWhere the setpoint comes from; write 1 for bus control.UINT16Read/write1 = IF-Module; 6 = Internal; 9 = INVALID
HR402dutyPointRel presetFallback setpoint used by the bus command timer.INT16× 0.5%Read/write
HR403controlFunction presetFallback control mode.UINT16Read/write1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 15 = INVALID; 80 = Gen_DA
HR404Pump Command presetFallback on/off command.BITMAP16Read/writebit 0 = device/functionOn preset
HR405setpointSignalSource presetFallback setpoint source.UINT16Read/write1 = IF-Module; 6 = Internal; 9 = INVALID

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Wilo Stratos PICO plus with CIF module Modbus RTU

What Modbus registers does the Wilo Stratos PICO plus with CIF module Modbus RTU have?

This map lists 37 registers: 27 input registers, 10 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Wilo Stratos PICO plus with CIF module Modbus RTU Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Wilo states that all register addresses are raw addresses as sent on the bus; its example frame 01 04 02 BC 00 01 reads input register 700 (0x02BC). Masters that count registers from 1 must add 1.

What byte order does the Wilo Stratos PICO plus with CIF module Modbus RTU use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Wilo Stratos PICO plus with CIF module Modbus RTU?

Start with HR 40 Pump Command in (On/off command (bit 3 = 1 when writing, if listed)); HR 42 controlFunction (Control mode); HR 1 dutyPointRel (Setpoint (duty point, 0.5 % steps)); IR 404 Operation Status (Operation status flags); IR 940 warning/errorMessage (Active warning/error code); IR 1 pressure (Actual pressure); IR 2 flow (Flow); IR 4 powerInput (Power input).

How do I enable Modbus control of the Wilo Stratos PICO plus with CIF module Modbus RTU?

Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.

What happens when the Wilo Stratos PICO plus with CIF module Modbus RTU loses Modbus communication?

The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.

Where is the official Wilo Stratos PICO plus with CIF module Modbus RTU Modbus documentation?

The source is WILO Modbus RTU (wilo194406), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo194406/11516106/wilo194406.html.