Pump controller (switchgear) · Modbus register map

Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Wilo-Control EC-WP is a switchgear for level- or pressure-dependent control of up to two fixed-speed pumps (float switch, electrodes, pressure switch or sensor). It has an RS485 ModBus RTU slave port. The holding registers cover pump enable, per-pump modes, pressure actual value and setpoints, general and float-switch status and the alarm history.

This page lists 17 Modbus registers for the Wilo Wilo-Control EC-WP switchgear (ModBus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Wilo’s own free documentation (linked below) and checked against it.

Manufacturer
Wilo
Model
Wilo-Control EC-WP switchgear (ModBus RTU)
Equipment type
Pump controller (switchgear)
Registers
17 (7 writable)
Transport
Modbus RTU
Default unit ID
10
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
SW102x
Also known as
Control EC-WP, Wilo Control EC WP, EC-WP
Source document
Wilo-Control EC-WP Installation and operating instructions · 2552567 Ed.01/2024-08 · rev. 2024-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Wilo Wilo-Control EC-WP switchgear (ModBus RTU)

Integration in brief

Turn ModBus on in Menu 2.01, wire RS485 and poll unit 10 at 19200 baud, even parity. Read the actual pressure (40026), general status (40062) and float-switch status (40198); enable the pumps with Drives on/off (40015).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 25Actual valueINT16Actual pressureRead
HR 26Current setpointINT16Current setpointRead
HR 61General statusBITMAP16Run and fault signalsRead
HR 14Drives on/offUINT16Pumps on/offRead/write
HR 67Setpoint 1UINT16Pressure setpointRead/write
HR 197Status of float switchBITMAP16Float switch statusRead

Enable Modbus control & writes

Menu 2.01 switches the ModBus RTU interface on (factory setting on). Baud in 2.02, address in 2.03, parity in 2.04, stop bits in 2.05.

Byte order & addressing

Network setup

Watch out for

Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

17 of 17 shown
Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001 (0)Communication profile versionUINT16× 0.001Read
HR1doc 40002 (1)Wink serviceBoolean; makes the switchgear identify itself.UINT16Read/write0 = False / off; 1 = True / on
HR2doc 40003 (2)Type of switchgearUINT16Read8 = EC
HR13doc 40014 (13)BusCommandTimerBus command timer state.UINT16Read/write0 = -; 1 = Off; 2 = Set; 3 = Active; 4 = Reset; 5 = Manual
HR14doc 40015 (14)Drives on/offBoolean; enables or disables the pumps.UINT16Read/write0 = False / off; 1 = True / on
HR24doc 40025 (24)Control modeUINT16Read0 = p-c (constant pressure); 10 = Filling; 11 = Draining
HR25doc 40026 (25)Actual valueMeasured pressure.INT16× 0.1barRead
HR26doc 40027 (26)Current setpointSetpoint now in force.INT16× 0.1barRead
HR40doc 40041 (40)Pump mode 1UINT16Read/write0 = Off; 1 = Manual; 2 = Auto
HR41doc 40042 (41)Pump mode 2UINT16Read/write0 = Off; 1 = Manual; 2 = Auto
HR61doc 40062 (61)General statusBITMAP16Readbit 0 = SBM (run signal); bit 1 = SSM (collective fault); bit 8 = EBM pump 1; bit 9 = EBM pump 2
HR67doc 40068 (67)Setpoint 1UINT16× 0.1barRead/write
HR73doc 40074 (73)ApplicationConfigured application; the table lists the element 2nd WP only.UINT16Read
HR140doc 40141 (140)AcknowledgeBoolean fault acknowledge flag.UINT16Read0 = False / off; 1 = True / on
HR141doc 40142 (141)Alarm history indexSelects the alarm history entry to read.UINT16Read/write
HR142doc 40143 (142)Fault number alarm historyFault number of the selected history entry.UINT16× 0.1Read
HR197doc 40198 (197)Status of float switchBITMAP16Readbit 0 = Dry running; bit 1 = Pumps off; bit 2 = Pump 1 on; bit 3 = Pump 2 on; bit 4 = High water; bit 5 = Dry run 2; bit 6 = Pump 1 off; bit 7 = Pump 2 off

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Wilo Wilo-Control EC-WP switchgear (ModBus RTU)

What Modbus registers does the Wilo Wilo-Control EC-WP switchgear (ModBus RTU) have?

This map lists 17 registers: 17 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The parameter table prints each holding register as 4xxxx with the protocol address in brackets, e.g. 40026 (25). The bracketed number goes on the wire.

What are the minimum Modbus registers to integrate the Wilo Wilo-Control EC-WP switchgear (ModBus RTU)?

Start with HR 25 Actual value (Actual pressure); HR 26 Current setpoint (Current setpoint); HR 61 General status (Run and fault signals); HR 14 Drives on/off (Pumps on/off); HR 67 Setpoint 1 (Pressure setpoint); HR 197 Status of float switch (Float switch status).

How do I enable Modbus control of the Wilo Wilo-Control EC-WP switchgear (ModBus RTU)?

Menu 2.01 switches the ModBus RTU interface on (factory setting on). Baud in 2.02, address in 2.03, parity in 2.04, stop bits in 2.05.

Where is the official Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus documentation?

The source is Wilo-Control EC-WP Installation and operating instructions (2552567 Ed.01/2024-08), revision 2024-08, published free by Wilo at https://cms.media.wilo.com/dcianimpfinder/wilo718556/9646785/Resources/pdf/6110468747__en.pdf.

More Wilo Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Wilo-Control EC-WP Installation and operating instructions · 2552567 Ed.01/2024-08 · rev. 2024-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.