Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus register map
Updated 17 November 2026
The Wilo-Control EC-WP is a switchgear for level- or pressure-dependent control of up to two fixed-speed pumps (float switch, electrodes, pressure switch or sensor). It has an RS485 ModBus RTU slave port. The holding registers cover pump enable, per-pump modes, pressure actual value and setpoints, general and float-switch status and the alarm history.
This page lists 17 Modbus registers for the Wilo Wilo-Control EC-WP switchgear (ModBus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Wilo’s own free documentation (linked below) and checked against it.
- Manufacturer
- Wilo
- Model
- Wilo-Control EC-WP switchgear (ModBus RTU)
- Equipment type
- Pump controller (switchgear)
- Registers
- 17 (7 writable)
- Transport
- Modbus RTU
- Default unit ID
- 10
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- SW102x
- Also known as
- Control EC-WP, Wilo Control EC WP, EC-WP
Integration notes: Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
Turn ModBus on in Menu 2.01, wire RS485 and poll unit 10 at 19200 baud, even parity. Read the actual pressure (40026), general status (40062) and float-switch status (40198); enable the pumps with Drives on/off (40015).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 25 | Actual value | INT16 | Actual pressure | Read |
| HR 26 | Current setpoint | INT16 | Current setpoint | Read |
| HR 61 | General status | BITMAP16 | Run and fault signals | Read |
| HR 14 | Drives on/off | UINT16 | Pumps on/off | Read/write |
| HR 67 | Setpoint 1 | UINT16 | Pressure setpoint | Read/write |
| HR 197 | Status of float switch | BITMAP16 | Float switch status | Read |
Enable Modbus control & writes
Menu 2.01 switches the ModBus RTU interface on (factory setting on). Baud in 2.02, address in 2.03, parity in 2.04, stop bits in 2.05.
Byte order & addressing
- Pressure values are INT16/UINT16 in 0.1 bar.
- Factory address is 10, not 1.
Network setup
- RS485 interface on the terminal strip; see the terminal diagram on the cover.
- Baud rate 9600, 19200 (default), 38400 or 76800; parity none, even (default) or odd; 1 (default) or 2 stop bits.
- The switchgear is terminated at the factory; remove jumper J2 if it is not at the end of the bus. Fit J3 and J4 if the bus needs polarisation.
Watch out for
- A 'Fault status' block (40139-40140) exists but is not in this map; read General status (40062) for the collective fault bit.
Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 (0) | Communication profile version | UINT16 | × 0.001 | Read | ||||
| HR | 1doc 40002 (1) | Wink service | Boolean; makes the switchgear identify itself. | UINT16 | Read/write | 0 = False / off; 1 = True / on | |||
| HR | 2doc 40003 (2) | Type of switchgear | UINT16 | Read | 8 = EC | ||||
| HR | 13doc 40014 (13) | BusCommandTimer | Bus command timer state. | UINT16 | Read/write | 0 = -; 1 = Off; 2 = Set; 3 = Active; 4 = Reset; 5 = Manual | |||
| HR | 14doc 40015 (14) | Drives on/off | Boolean; enables or disables the pumps. | UINT16 | Read/write | 0 = False / off; 1 = True / on | |||
| HR | 24doc 40025 (24) | Control mode | UINT16 | Read | 0 = p-c (constant pressure); 10 = Filling; 11 = Draining | ||||
| HR | 25doc 40026 (25) | Actual value | Measured pressure. | INT16 | × 0.1 | bar | Read | ||
| HR | 26doc 40027 (26) | Current setpoint | Setpoint now in force. | INT16 | × 0.1 | bar | Read | ||
| HR | 40doc 40041 (40) | Pump mode 1 | UINT16 | Read/write | 0 = Off; 1 = Manual; 2 = Auto | ||||
| HR | 41doc 40042 (41) | Pump mode 2 | UINT16 | Read/write | 0 = Off; 1 = Manual; 2 = Auto | ||||
| HR | 61doc 40062 (61) | General status | BITMAP16 | Read | bit 0 = SBM (run signal); bit 1 = SSM (collective fault); bit 8 = EBM pump 1; bit 9 = EBM pump 2 | ||||
| HR | 67doc 40068 (67) | Setpoint 1 | UINT16 | × 0.1 | bar | Read/write | |||
| HR | 73doc 40074 (73) | Application | Configured application; the table lists the element 2nd WP only. | UINT16 | Read | ||||
| HR | 140doc 40141 (140) | Acknowledge | Boolean fault acknowledge flag. | UINT16 | Read | 0 = False / off; 1 = True / on | |||
| HR | 141doc 40142 (141) | Alarm history index | Selects the alarm history entry to read. | UINT16 | Read/write | ||||
| HR | 142doc 40143 (142) | Fault number alarm history | Fault number of the selected history entry. | UINT16 | × 0.1 | Read | |||
| HR | 197doc 40198 (197) | Status of float switch | BITMAP16 | Read | bit 0 = Dry running; bit 1 = Pumps off; bit 2 = Pump 1 on; bit 3 = Pump 2 on; bit 4 = High water; bit 5 = Dry run 2; bit 6 = Pump 1 off; bit 7 = Pump 2 off |
Notes on this map
- The same parameter table is published as an HTML appendix page: https://cms.media.wilo.com/dcianimpfinder/wilo718556/9646785/en-GB/2228099211.html.
- BOOL registers are listed as UINT16 with 0/1; the manual treats any value above zero as true. ENUM registers are UINT16.
- Left out: Fault status 40139-40140 (BITMAP32 over two registers, bits 0-20) because the manual does not say which register holds the low bits.
- The data-type table describes BITMAP32 with the same 16-bit wording as BITMAP; this is a source wording issue.
- The scaling column prints 0.1 for 'Fault number alarm history'; it is copied as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
What Modbus registers does the Wilo Wilo-Control EC-WP switchgear (ModBus RTU) have?
This map lists 17 registers: 17 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The parameter table prints each holding register as 4xxxx with the protocol address in brackets, e.g. 40026 (25). The bracketed number goes on the wire.
What are the minimum Modbus registers to integrate the Wilo Wilo-Control EC-WP switchgear (ModBus RTU)?
Start with HR 25 Actual value (Actual pressure); HR 26 Current setpoint (Current setpoint); HR 61 General status (Run and fault signals); HR 14 Drives on/off (Pumps on/off); HR 67 Setpoint 1 (Pressure setpoint); HR 197 Status of float switch (Float switch status).
How do I enable Modbus control of the Wilo Wilo-Control EC-WP switchgear (ModBus RTU)?
Menu 2.01 switches the ModBus RTU interface on (factory setting on). Baud in 2.02, address in 2.03, parity in 2.04, stop bits in 2.05.
Where is the official Wilo Wilo-Control EC-WP switchgear (ModBus RTU) Modbus documentation?
The source is Wilo-Control EC-WP Installation and operating instructions (2552567 Ed.01/2024-08), revision 2024-08, published free by Wilo at https://cms.media.wilo.com/dcianimpfinder/wilo718556/9646785/Resources/pdf/6110468747__en.pdf.
More Wilo Modbus register maps
- Pump (high-efficiency circulator)
Wilo Atmos MAXO with CIF module Modbus RTU
Wilo Atmos MAXO pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Atmos MAXO - Pump (multistage pressure-boosting pump)
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
Wilo Helix2.0-VE pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Helix2.0-VE, Medana CH3-LE, Wilo-Medana CH3-LE - Pump (pressure-boosting pump)
Wilo Isar MODH1-E with CIF module Modbus RTU
Wilo Isar MODH1-E pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Isar MODH1-E - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Pump system
Wilo SiFresh with CIF module Modbus RTU
Wilo SiFresh pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-SiFresh - Pump (high-efficiency inline circulator)
Wilo Stratos GIGA2.0 with CIF module Modbus RTU
Wilo Stratos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Stratos GIGA2.0-I, Stratos GIGA2.0-D, Wilo-Stratos GIGA2.0 - Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080 - Pump (high-efficiency circulator)
Wilo Stratos PICO plus with CIF module Modbus RTU
Wilo Stratos PICO plus pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Stratos PICO plus - Pump (high-efficiency inline circulator)
Wilo Yonos GIGA2.0 with CIF module Modbus RTU
Wilo Yonos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Yonos GIGA2.0-I, Yonos GIGA2.0-D, Wilo-Yonos GIGA2.0
Other pumps register maps
- Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface - Heat pump (air-to-water)
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Gree Versati air-to-water heat pumps through the BMS port of the wired controller, per 'Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater'. The document itself does not name a generation or refrigerant; the distributor files it as the R32 Versati III protocol.
Also known as: Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5 - Heat pump (air-to-water)
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
LG THERMA V R32 Monobloc air-to-water heat pumps covered by installation manual MFL68026615 Rev.02 (North American models ZHBW041GA0 / ZHBW048GA0 / ZHBW055GA0), using the indoor PCB's own Modbus RTU slave port.
Also known as: ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615 - Heat pump / ventilation unit controller (air handler)
Nilan CTS602 controller with HMI350T panel (Modbus version 23)
Nilan ventilation, heat-recovery and compact heat pump units with the CTS602 board and HMI350T user panel, Modbus protocol version 23 (software 3.6.58/3.6.59).
Also known as: CTS 602, CTS602 HMI350T, CTS602 w. HMI350T - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+
All pumps Modbus register maps →
Source: Wilo-Control EC-WP Installation and operating instructions · 2552567 Ed.01/2024-08 · rev. 2024-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.