- CTS602 controller with HMI350T panel (Modbus version 23)
Heat pump / ventilation unit controller (air handler) · Modbus register map
Nilan CTS602 controller with HMI350T panel (Modbus version 23) Modbus register map
Updated 17 November 2026
The Nilan CTS602 is the controller in Nilan's residential and light-commercial ventilation units and compact heat pumps (ventilation, heat recovery, hot water and optional central heating). Its RS-485 port COM1 is a Modbus RTU slave at fixed 19200 8E1. Input registers give temperatures T0-T18 (x0.01 °C), humidity, CO2, digital inputs, alarm list, run and control states, fan steps and differential-pressure flows; holding registers carry on/off, operation mode, ventilation step, temperature setpoint, hot water and central heating settings, outputs and the clock.
This page lists 262 Modbus registers for the Nilan CTS602 controller with HMI350T panel (Modbus version 23) — 165 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Nilan’s own free documentation (linked below) and checked against it.
- Manufacturer
- Nilan
- Model
- CTS602 controller with HMI350T panel (Modbus version 23)
- Equipment type
- Heat pump / ventilation unit controller (air handler)
- Registers
- 262 (165 writable)
- Transport
- Modbus RTU
- Default unit ID
- 30
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Firmware
- Modbus protocol version 23 (Bus.Version), CTS602 software 3.6.58 / 3.6.59
- Also known as
- CTS 602, CTS602 HMI350T, CTS602 w. HMI350T
Integration notes: Nilan CTS602 controller with HMI350T panel (Modbus version 23)
Connect to COM1 (CN7 pins 2/3/6) at 19200 8E1, slave 30. Read input registers 200-222 for temperatures and air quality, 1000-1002 for run/mode/state and 400 for alarms; command the unit with holding registers 1001 (on/off), 1002 (mode), 1003 (ventilation step) and 1004 (temperature setpoint, x0.01 °C).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1001 | User on / off select (equal to ON/OFF keys) | UINT16 | On/off | Read/write |
| HR 1002 | User operation mode select | UINT16 | Operation mode | Read/write |
| HR 1003 | User ventilation step select | UINT16 | Ventilation step | Read/write |
| HR 1004 | User temperature setpoint | INT16 | Temperature setpoint | Read/write |
| IR 1002 | Actual control state | UINT16 | Actual control state | Read |
| IR 208 | Outdoor temperature | INT16 | Outdoor temperature | Read |
| IR 203 | Room exhaust temperature | INT16 | Room exhaust temperature | Read |
| IR 400 | Alarm state bit mask | UINT16 | Alarm status | Read |
Enable Modbus control & writes
No enable step: the CTS602 always answers on COM1. Only the node address can be changed (holding register 50 or the panel); speed and framing are fixed.
Byte order & addressing
- Only function codes 03, 04 and 16 are supported; single-register write (06) is not, so write with function 16.
- Temperatures are x0.01, not x0.1.
- Packet size is limited to 255 bytes.
Network setup
- COM1 on connector CN7: pin 2 = Data+ (A), pin 3 = Data- (B), pin 6 = ground. COM2 (pins 4/5) is the user panel bus.
- Terminate both bus ends with 120 ohm; there is no opto-isolation on the CTS602, so all nodes need a common ground.
- Up to 200 m of shielded twisted pair; default node address 30, selectable 1-247.
Watch out for
- Holding register 1007 can restore factory defaults (1) or a backup; do not write it casually.
- Mode 4 (Service) in 1002 is read-only; service functions are selected through 1005.
Nilan CTS602 controller with HMI350T panel (Modbus version 23) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 000 | Protocol version number | Nilan variable Bus.Version. | UINT16 | Read | ||||
| IR | 4doc 004 | Application Id | Nilan variable Info.AppID. | UINT16 | Read | ||||
| IR | 5doc 005 | Application hardware Id | Nilan variable Info.HWType. | UINT16 | Read | ||||
| IR | 100 | User function | Digital input state; Nilan variable Input.UserFunc. | UINT16 | Read | ||||
| IR | 101 | Air filter alarm | Digital input state; Nilan variable Input.AirFilter. | UINT16 | Read | ||||
| IR | 102 | Door contact | Digital input state; Nilan variable Input.DoorOpen. | UINT16 | Read | ||||
| IR | 103 | Smoke alarm | Digital input state; Nilan variable Input.Smoke. | UINT16 | Read | ||||
| IR | 104 | Motor thermo fuse | Digital input state; Nilan variable Input.MotorThermo. | UINT16 | Read | ||||
| IR | 105 | Heating surface frost / overheat | Digital input state; Nilan variable Input.Frost_Overht. | UINT16 | Read | ||||
| IR | 106 | Airflow monitor | Digital input state; Nilan variable Input.AirFlow. | UINT16 | Read | ||||
| IR | 107 | High pressure switch | Digital input state; Nilan variable Input.P_HI. | UINT16 | Read | ||||
| IR | 108 | Low pressure switch | Digital input state; Nilan variable Input.P_LO. | UINT16 | Read | ||||
| IR | 109 | Hot water boiling | Digital input state; Nilan variable Input.Boil. | UINT16 | Read | ||||
| IR | 110 | Hot water 3-way valve position | Digital input state; Nilan variable Input.3WayPos. | UINT16 | Read | ||||
| IR | 111 | Hotgas defrost type selection | Digital input state; Nilan variable Input.DefrostHG. | UINT16 | Read | ||||
| IR | 112 | Defrost thermostat | Digital input state; Nilan variable Input.Defrost. | UINT16 | Read | ||||
| IR | 113 | User function 2 | Digital input state; Nilan variable Input.UserFunc_2. | UINT16 | Read | ||||
| IR | 114 | Air damper closed position switch | Digital input state; Nilan variable Input.DamperClosed. | UINT16 | Read | ||||
| IR | 115 | Air damper opened position switch | Digital input state; Nilan variable Input.DamperOpened. | UINT16 | Read | ||||
| IR | 116 | Combined FC and thermo alarm | Digital input state; Nilan variable Input.FCorThermoAl. | UINT16 | Read | ||||
| IR | 117 | Brine pressostat | Digital input state; Nilan variable Input.BrinePress. | UINT16 | Read | ||||
| IR | 200 | Controller board temperature | Nilan variable Input.T0_Controller. | INT16 | × 0.01 | °C | Read | ||
| IR | 201 | Fresh air intake temperature | Nilan variable Input.T1_Intake. | INT16 | × 0.01 | °C | Read | ||
| IR | 202 | Inlet temperature (before heater) | Nilan variable Input.T2_Inlet. | INT16 | × 0.01 | °C | Read | ||
| IR | 203 | Room exhaust temperature | Nilan variable Input.T3_Exhaust. | INT16 | × 0.01 | °C | Read | ||
| IR | 204 | Outlet temperature | Nilan variable Input.T4_Outlet. | INT16 | × 0.01 | °C | Read | ||
| IR | 205 | Condenser temperature | Nilan variable Input.T5_Cond. | INT16 | × 0.01 | °C | Read | ||
| IR | 206 | Evaporator temperature | Nilan variable Input.T6_Evap. | INT16 | × 0.01 | °C | Read | ||
| IR | 207 | Inlet temperature (after heater) | Nilan variable Input.T7_Inlet. | INT16 | × 0.01 | °C | Read | ||
| IR | 208 | Outdoor temperature | Nilan variable Input.T8_Outdoor. | INT16 | × 0.01 | °C | Read | ||
| IR | 209 | Heating surface temperature | Nilan variable Input.T9_Heater. | INT16 | × 0.01 | °C | Read | ||
| IR | 210 | External room temperature | Nilan variable Input.T10_Extern. | INT16 | × 0.01 | °C | Read | ||
| IR | 211 | Hot water top temperature | Nilan variable Input.T11_Top. | INT16 | × 0.01 | °C | Read | ||
| IR | 212 | Hot water bottom temperature | Nilan variable Input.T12_Bottom. | INT16 | × 0.01 | °C | Read | ||
| IR | 213 | EK return temperature | Nilan variable Input.T13_Return. | INT16 | × 0.01 | °C | Read | ||
| IR | 214 | EK supply temperature | Nilan variable Input.T14_Supply. | INT16 | × 0.01 | °C | Read | ||
| IR | 215 | User panel room temperature | Nilan variable Input.T15_Room. | INT16 | × 0.01 | °C | Read | ||
| IR | 216 | AUX temperature (Hotwater anode) | Nilan variable Input.T16. | INT16 | × 0.01 | °C | Read | ||
| IR | 217 | Preheater or earth tube air intake temperature | Nilan variable Input.T17_PreHeat. | INT16 | × 0.01 | °C | Read | ||
| IR | 218 | Pressure pibe temperature | Nilan variable Input.T18_PresPibe. | INT16 | × 0.01 | °C | Read | ||
| IR | 221 | Humidity sensor value | Nilan variable AirQual.RH. | UINT16 | × 0.01 | % | Read | ||
| IR | 222 | Carbon dioxide sensor value | Nilan variable AirQual.CO2. | UINT16 | ppm | Read | |||
| IR | 400 | Alarm state bit mask | Bit 7 (0x80) = alarms active; low nibble (0x0F) = number of alarms. | UINT16 | Read | ||||
| IR | 401 | Alarm 1 - Code | Nilan variable Alarm.List_1_ID. | UINT16 | Read | ||||
| IR | 402 | Alarm 1 - Date | Nilan variable Alarm.List_1_Date. | UINT16 | Read | ||||
| IR | 403 | Alarm 1 - Time | Nilan variable Alarm.List_1_Time. | UINT16 | Read | ||||
| IR | 404 | Alarm 2 - Code | Nilan variable Alarm.List_2_ID. | UINT16 | Read | ||||
| IR | 405 | Alarm 2 - Date | Nilan variable Alarm.List_2_Date. | UINT16 | Read | ||||
| IR | 406 | Alarm 2 - Time | Nilan variable Alarm.List_2_Time. | UINT16 | Read | ||||
| IR | 407 | Alarm 3 - Code | Nilan variable Alarm.List_3_ID. | UINT16 | Read | ||||
| IR | 408 | Alarm 3 - Date | Nilan variable Alarm.List_3_Date. | UINT16 | Read | ||||
| IR | 409 | Alarm 3 - Time | Nilan variable Alarm.List_3_Time. | UINT16 | Read | ||||
| IR | 1000 | Actual on/off state | Nilan variable Control.RunAct. | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 1001 | Actual operation mode | Nilan variable Control.ModeAct. | UINT16 | Read | 0 = Off; 1 = Heat; 2 = Cool; 3 = Auto; 4 = Service | |||
| IR | 1002 | Actual control state | Nilan variable Control.StateDisplay. | UINT16 | Read | 0 = Off; 1 = Shift; 2 = Stop; 3 = Start; 4 = Standby; 5 = Ventilation stop; 6 = Ventilation; 7 = Heating; 8 = Cooling; 9 = Hot water; 10 = Legionella; 11 = Cooling + hot water; 12 = Central heating; 13 = Defrost; 14 = Frost sequre; 15 = Service; 16 = Alarm; 17 = Heating + hot water | |||
| IR | 1003 | Actual time in state | Nilan variable Control.SecInState. | UINT16 | s | Read | |||
| IR | 1100 | Actual ventilation step set point | Nilan variable AirFlow.VentSet. | UINT16 | Read | ||||
| IR | 1101 | Actual inlet fan speed step | Nilan variable AirFlow.InletAct. | UINT16 | Read | ||||
| IR | 1102 | Actual exhaust fan speed step | Nilan variable AirFlow.ExhaustAct. | UINT16 | Read | ||||
| IR | 1103 | Days since last air filter change alarm | Nilan variable AirFlow.SinceFiltDay. | UINT16 | d | Read | |||
| IR | 1104 | Days to next air filter change alarm | Nilan variable AirFlow.ToFiltDay. | UINT16 | d | Read | |||
| IR | 1200 | Summer state | Nilan variable AirTemp.IsSummer. | INT16 | Read | 0 = Off; 1 = On | |||
| IR | 1201 | Inlet temperature request (T7 setpoint) | Nilan variable AirTemp.TempInletSet. | INT16 | × 0.01 | °C | Read | ||
| IR | 1202 | Actual value for controlled temperature | Nilan variable AirTemp.TempControl. | INT16 | × 0.01 | °C | Read | ||
| IR | 1203 | Actual room temperature (T15 or T10) | Nilan variable AirTemp.TempRoom. | INT16 | × 0.01 | °C | Read | ||
| IR | 1204 | Passive heat exchanger efficiency calculation | Nilan variable AirTemp.EffPct. | INT16 | × 0.01 | % | Read | ||
| IR | 1205 | Requested capacity | Nilan variable AirTemp.CapSet. | INT16 | × 0.01 | % | Read | ||
| IR | 1206 | Actual capacity | Nilan variable AirTemp.CapAct. | INT16 | × 0.01 | % | Read | ||
| IR | 1500 | Compressor type | Nilan variable Compressor.Type. | UINT16 | Read | 0 = None; 1 = On/Off; 2 = Modulated hotgas valve | |||
| IR | 1700 | Hot water type | Nilan variable HotWater.Type. | UINT16 | Read | 0 = None; 1 = Only hot water (VGU); 2 = With ventilation (VP); 3 = With central heating (VGU180) | |||
| IR | 1701 | Hot water anode state | Nilan variable HotWater.AnodeState. | UINT16 | Read | 0 = OFF; 1 = OK; 2 = SERVICE; 3 = ERROR | |||
| IR | 1800 | Actual setpoint for external heating source | Nilan variable CentralHeat.HeatExtSet. | INT16 | × 0.01 | °C | Read | ||
| IR | 2100 | Remaining time for the pre-heater blocking function | Nilan variable PreHeat.BlockRemain. | UINT16 | s | Read | |||
| IR | 2200 | DPT in session | Nilan variable DPT.InSession. | UINT16 | Read | ||||
| IR | 2201 | Calculated air flow 1 | Nilan variable DPT.AirFlow1. | UINT16 | m3/h | Read | |||
| IR | 2202 | Calculated air flow 2 | Nilan variable DPT.AirFlow2. | UINT16 | m3/h | Read | |||
| IR | 2221 | Calculated air pressure 1 | Nilan variable DPT.Pressure1. | UINT16 | Pa | Read | |||
| IR | 2222 | Calculated air pressure 2 | Nilan variable DPT.Pressure2. | UINT16 | Pa | Read | |||
| IR | 2230 | DPT2 in session | Nilan variable DPT2.InSession. | UINT16 | Read | ||||
| IR | 2231 | DPT2 calculated air flow 1 | Nilan variable DPT2.AirFlow1. | UINT16 | m3/h | Read | |||
| IR | 2232 | DPT2 calculated air flow 2 | Nilan variable DPT2.AirFlow2. | UINT16 | m3/h | Read | |||
| IR | 2241 | DPT2 calculated air pressure 1 | Nilan variable DPT2.Pressure1. | UINT16 | Pa | Read | |||
| IR | 2242 | DPT2 calculated air pressure 2 | Nilan variable DPT2.Pressure2. | UINT16 | Pa | Read | |||
| IR | 3000 | Bypass damper | Nilan variable AirBypass.IsOpen. | UINT16 | Read | 0 = Closed; 1 = Open | |||
| IR | 3001 | After heating element | Nilan variable Output.AirHeatCap. | UINT16 | × 0.01 | % | Read | ||
| IR | 3002 | De-icing heat exchanger | Nilan variable Defrost.ExchDefrost. | UINT16 | Read | 0 = Off; 1 = On (Passive exchanger defrost is active) | |||
| IR | 3003 | CO2 sensor present in the system or not | Nilan variable AirQual.CO2_Enable. | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3004 | Stop at low room temperature | Nilan variable AirFlow.RoomReduce. | UINT16 | Read | ||||
| IR | 3005 | Date for last air damper self-test | Nilan variable AirFlow.LastTestDay. | UINT16 | Read | ||||
| IR | 3006 | Days since last air filter change | Nilan variable AirFlow.SinceFiltDay. | UINT16 | Read | ||||
| IR | 3007 | Low fan speed at low outdoor temperature | Nilan variable AirFLow.WinterReduce. | UINT16 | Read | ||||
| IR | 3008 | Actual resulting set-point for room temperature | Nilan variable AirTemp.TempSet. | INT16 | × 0.01 | °C | Read | ||
| IR | 3009 | Master sensor for the controlled temperature (room / inlet) | Nilan variable AirTemp.TempControl. | INT16 | × 0.01 | °C | Read | ||
| IR | 3075 | Operation states for Control module | Nilan variable Alarm.LogCtrState. | UINT16 | Read | 0 = OFF; 1 = SHIFTING; 2 = STOPPING; 3 = STARTING; 4 = STANDBY; 5 = VENT_STOP; 6 = AIR_EXCH; 7 = AIR_HEAT; 8 = AIR_COOL; 9 = HOTWATER; 10 = LEGIONELLA; 11 = AIR_COOL_HOT_WATER; 12 = CENT_HEAT; 13 = DEFROST; 14 = FROST; 15 = SERVICE; 16 = ALARM_SHUTDOWN; 17 = AIR_HEAT_HOT_WATER | |||
| IR | 3100 | Humidity average value. | Nilan variable AirQual.RH_Avg. | UINT16 | × 0.01 | % | Read | ||
| IR | 3101 | If expansion I/O board is present the value must be 12. | Nilan variable Opt9_1.BoardId. | UINT16 | Read | ||||
| IR | 3102 | Ventilation state | Nilan variable AirFlow.VentState. | UINT16 | Read | 0 = OFF; 1 = NORMAL; 2 = LOW_HUMIDITY; 3 = HIGH_HUMIDITY; 4 = HIGH_CO2; 5 = LOW_ROOM_TEMP; 6 = LOW_OUTDOOR_TEMP | |||
| HR | 50doc 050 | Protocol node address (default = 30) | Nilan variable Bus.Address. | UINT16 | Read/write | ||||
| HR | 100 | Air flap | Output state; Nilan variable Output.AirFlap. | UINT16 | Read/write | ||||
| HR | 101 | Smoke flap | Output state; Nilan variable Output.SmokeFlap. | UINT16 | Read/write | ||||
| HR | 102 | Bypass flap open | Output state; Nilan variable Output.BypassOpen. | UINT16 | Read/write | ||||
| HR | 103 | Bypass flap close | Output state; Nilan variable Output.BypassClose. | UINT16 | Read/write | ||||
| HR | 104 | Air heat circulation pump | Output state; Nilan variable Output.AirCircPump. | UINT16 | Read/write | ||||
| HR | 105 | Air heating selected | Output state; Nilan variable Output.AirHeatAllow. | UINT16 | Read/write | ||||
| HR | 106 | Air heater relays | Output state; Nilan variable Output.AirHeat_1. | UINT16 | Read/write | ||||
| HR | 107 | AirHeat_2 | Output state; Nilan variable Output.AirHeat_2. | UINT16 | Read/write | ||||
| HR | 108 | AirHeat_3 | Output state; Nilan variable Output.AirHeat_3. | UINT16 | Read/write | ||||
| HR | 109 | Compressor | Output state; Nilan variable Output.Compressor. | UINT16 | Read/write | ||||
| HR | 110 | Compressor 2 | Output state; Nilan variable Output.Compressor_2. | UINT16 | Read/write | ||||
| HR | 111 | 4-way valve | Output state; Nilan variable Output.4WayCool. | UINT16 | Read/write | ||||
| HR | 112 | Hotgas valve - heat | Output state; Nilan variable Output.HotgasHeat. | UINT16 | Read/write | ||||
| HR | 113 | Hotgas valve - cool | Output state; Nilan variable Output.HotgasCool. | UINT16 | Read/write | ||||
| HR | 114 | Air condenser active | Output state; Nilan variable Output.CondOpen. | UINT16 | Read/write | ||||
| HR | 115 | Air condenser inactive | Output state; Nilan variable Output.CondClose. | UINT16 | Read/write | ||||
| HR | 116 | Hot water heater | Output state; Nilan variable Output.WaterHeat. | UINT16 | Read/write | ||||
| HR | 117 | Hot water 3-way valve | Output state; Nilan variable Output.3WayValve. | UINT16 | Read/write | ||||
| HR | 118 | EK circulation pump | Output state; Nilan variable Output.CenCircPump. | UINT16 | Read/write | ||||
| HR | 119 | EK heater relays | Output state; Nilan variable Output.CenHeat_1. | UINT16 | Read/write | ||||
| HR | 120 | CenHeat_2 | Output state; Nilan variable Output.CenHeat_2. | UINT16 | Read/write | ||||
| HR | 121 | CenHeat_3 | Output state; Nilan variable Output.CenHeat_3. | UINT16 | Read/write | ||||
| HR | 122 | External radiator heat | Output state; Nilan variable Output.CenHeatExt. | UINT16 | Read/write | ||||
| HR | 123 | User function active | Output state; Nilan variable Output.UserFunc. | UINT16 | Read/write | ||||
| HR | 124 | UserFunc_2 | Output state; Nilan variable Output.UserFunc_2. | UINT16 | Read/write | ||||
| HR | 125 | Defrost function active | Output state; Nilan variable Output.Defrosting. | UINT16 | Read/write | ||||
| HR | 126 | Alarm relay state | Output state; Nilan variable Output.AlarmRelay. | UINT16 | Read/write | ||||
| HR | 127 | Preheater or earth tube activation | Output state; Nilan variable Output.PreHeat. | UINT16 | Read/write | ||||
| HR | 128 | EHD or BAH active | Output state; Nilan variable Output.EHD_BAH. | UINT16 | Read/write | ||||
| HR | 200 | Exhaust fan speed | Nilan variable Output.ExhaustSpeed. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 201 | Inlet fan speed | Nilan variable Output.InletSpeed. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 202 | Air heater capacity | Nilan variable Output.AirHeatCap. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 203 | Central heater capacity | Nilan variable Output.CenHeatCap. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 204 | Compresor capacity | Nilan variable Output.CprCap. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 205 | Preheater capacity or earth tube air intake fan speed | Nilan variable Output.PreHeatCap. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 206 | Rotary heat exchanger | Nilan variable Output.RotorVeksler. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 300 | Second | Nilan variable Time.Second. | UINT16 | s | Read/write | |||
| HR | 301 | Minute | Nilan variable Time.Minute. | UINT16 | min | Read/write | |||
| HR | 302 | Hour | Nilan variable Time.Hour. | UINT16 | h | Read/write | |||
| HR | 303 | Day | Nilan variable Time.Day. | UINT16 | day | Read/write | |||
| HR | 304 | Month | Nilan variable Time.Month. | UINT16 | month | Read/write | |||
| HR | 305 | Year | Nilan variable Time.Year. | UINT16 | year | Read/write | |||
| HR | 400 | Alarm reset | Write 101-199 to clear display code 1-99, 255 to clear all alarms. | UINT16 | Read/write | 0 = No command; 255 = Clear all alarms | |||
| HR | 500 | Week program nb. select | Nilan variable Program.Select. | UINT16 | Read/write | 0 = None; 1 = Program 1; 2 = Program 2; 3 = Program 3; 4 = Erase | |||
| HR | 600 | User function active (See “UserFuncSet”) | Nilan variable Program.UserFuncAct. | UINT16 | Read/write | ||||
| HR | 601 | User function select | Nilan variable Program.UserFuncSet. | UINT16 | Read/write | 0 = None; 1 = Extend; 2 = Inlet; 3 = Exhaust; 4 = External heater offset; 5 = Ventilate; 6 = Cooker Hood | |||
| HR | 602 | User function period | Nilan variable Program.UserTimeSet. | UINT16 | min | Read/write | |||
| HR | 603 | User function ventilation step select | Nilan variable Program.UserVentSet. | UINT16 | Read/write | ||||
| HR | 610 | User function 2 active | Same meaning as register 600, for user function 2. Variable Program.User2FuncAct. | UINT16 | Read/write | ||||
| HR | 611 | User function 2 select | Same meaning as register 601, for user function 2. Variable Program.User2FuncSet. | UINT16 | Read/write | ||||
| HR | 612 | User function 2 period | Same meaning as register 602, for user function 2. Variable Program.User2TimeSet. | UINT16 | min | Read/write | |||
| HR | 613 | User function 2 ventilation step select | Same meaning as register 603, for user function 2. Variable Program.User2VentSet. | UINT16 | Read/write | ||||
| HR | 700 | Periodic data log interval select | Nilan variable Log.Interval. | UINT16 | min | Read/write | |||
| HR | 1000 | Machine type select (factory setting) | Nilan variable Control.Type. | UINT16 | Read/write | ||||
| HR | 1001 | User on / off select (equal to ON/OFF keys) | Nilan variable Control.RunSet. | UINT16 | Read/write | 0 = Off (user input functions can still activate operation); 1 = On | |||
| HR | 1002 | User operation mode select | Nilan variable Control.ModeSet. | UINT16 | Read/write | 0 = Off; 1 = Heat (no cooling active); 2 = Cool (no heating active); 3 = Auto; 4 = Service (readonly - write to register 1005) | |||
| HR | 1003 | User ventilation step select | Nilan variable Control.VentSet. | UINT16 | Read/write | ||||
| HR | 1004 | User temperature setpoint | Nilan variable Control.TempSet. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1005 | Service mode select | Nilan variable Control.ServiceMode. | UINT16 | Read/write | 0 = Off; 1 = Defrost; 2 = Flaps; 3 = Inlet; 4 = Exhaust; 5 = Compressor; 6 = Heating; 7 = Hot water; 8 = Central heat | |||
| HR | 1006 | Service mode capacity setpoint | Nilan variable Control.ServicePct. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 1007 | Request preset to default settings | Nilan variable Control.Preset. | UINT16 | Read/write | 0 = Ready; 1 = Standard (to factory defaults); 2 = Backup (to user file); 3 = Restore (from user file) | |||
| HR | 1100 | Air exchange mode | Nilan variable AirFlow.AirExchMode. | UINT16 | Read/write | 0 = Energy; 1 = Comfort; 2 = ComfortWater | |||
| HR | 1101 | Cooling high ventilation step | Nilan variable AirFlow.CoolVent. | UINT16 | Read/write | ||||
| HR | 1102 | Select a day for weekly air damper position self-test | Nilan variable AirFlow.TestSelect. | UINT16 | Read/write | 0 = Off; 1 = Monday; 2 = Tuesday; 3 = Wednesday; 4 = Thursday; 5 = Friday; 6 = Saturday; 7 = Sunday | |||
| HR | 1103 | Date of last air damper position test | Nilan variable AirFlow.LastTestDay. | UINT16 | Read/write | ||||
| HR | 1104 | Actual air damper position test state | Nilan variable AirFlow.TestState. | UINT16 | Read/write | 0 = Off; 1 = Standby; 2 = Start (Set to Start to run manual test); 3 = Closing; 4 = Opening; 5 = OK; 6 = Error | |||
| HR | 1105 | Air filter monitoring alarm type and period select | Nilan variable AirFlow.FiltAlmType. | UINT16 | Read/write | 0 = Pressure guard (input); 1 = 30 days; 2 = 90 days; 3 = 180 days; 4 = 360 days; 5 = 70 days and pressure guard | |||
| HR | 1200 | Cooling temperature setpoint select | Nilan variable AirTemp.CoolSet. | INT16 | Read/write | 0 = Off (No cooling allowed); 1 = Set + 0 °C (User setpoint plus 0 degrees); 2 = Set + 1 °C; 3 = Set + 2 °C; 4 = Set + 3 °C; 5 = Set + 4 °C; 6 = Set + 5 °C; 7 = Set + 7 °C; 8 = Set + 10 °C | |||
| HR | 1201 | Inlet temp. min. summer | Nilan variable AirTemp.TempMinSum. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1202 | Inlet temp. min. winter | Nilan variable AirTemp.TempMinWin. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1203 | Inlet temp. max. summer | Nilan variable AirTemp.TempMaxSum. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1204 | Inlet temp. max. winter | Nilan variable AirTemp.TempMaxWin. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1205 | Summer/winter limit | Nilan variable AirTemp.TempSummer. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1206 | Outdoor day temperature for night cooling activation | Nilan variable AirTemp.NightDayLim. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1207 | Free energy night cooling room setpoint | Nilan variable AirTemp.NightSet. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1208 | Control temperature sensor select | Nilan variable AirTemp.SensorSelect. | INT16 | Read/write | 0 = User panel; 1 = External sensor; 2 = Inlet channel; 3 = Exhaust channel | |||
| HR | 1209 | Heat source select | Nilan variable AirTemp.HeatSelect. | INT16 | Read/write | 0 = No heating active; 1 = Heat pump only; 2 = HP + after-heat; 3 = After-heat only; 4 = After-heat + HP | |||
| HR | 1500 | Condenser temperature curve low | Nilan variable Compressor.CondTempMin. | INT16 | × 0.01 | Read/write | |||
| HR | 1501 | Condenser temperature curve high | Nilan variable Compressor.CondTempMax. | INT16 | × 0.01 | Read/write | |||
| HR | 1502 | Low temperature compressor start | Nilan variable AirTemp.TempMinCpr. | INT16 | × 0.01 | Read/write | |||
| HR | 1700 | Top temperature setpoint (electric) | Nilan variable HotWater.TempSet_T11. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1701 | Bottom temperature setpoint (compressor) | Nilan variable HotWater.TempSet_T12. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1702 | Hot water priority | Nilan variable HotWater.Priority. | UINT16 | Read/write | 0 = Water; 1 = Inlet | |||
| HR | 1703 | Scald protection Temperature | Nilan variable HotWater.TempCprMax. | INT16 | × 0.01 | Read/write | |||
| HR | 1704 | Hot water electric supplement | Nilan variable HotWater.HeatType. | UINT16 | Read/write | 0 = OFF; 1 = El | |||
| HR | 1705 | Legionella day | Legionella day; list codes 0 = off to 7 = Sunday (Danish text). | UINT16 | Read/write | ||||
| HR | 1706 | Bypass offset | Nilan variable HotWater.TempPri. | INT16 | °C | Read/write | |||
| HR | 1800 | External heating offset from room temperature setpoint | Nilan variable CentralHeat.HeatExtern. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1801 | Central heat select | Nilan variable CentralHeat.HeatSelect. | UINT16 | Read/write | 0 = Only pump motion and frost protection; 1 = Always central heating; 2 = Only central heating when room temperature is low | |||
| HR | 1802 | Min supply temperature | Nilan variable CentralHeat.SupplyMin. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1803 | Max supply temperature | Nilan variable CentralHeat.SupplyMax. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1804 | Outdoor temperature compensation | Nilan variable CentralHeat.SupplyOffset. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 1805 | Temp. compensation curve | Nilan variable CentralHeat.CurveSelect. | UINT16 | Read/write | ||||
| HR | 1806 | Central heat circulation pump mode | Nilan variable CentralHeat.CircPumpMode. | UINT16 | Read/write | 0 = Only when heating is active; 1 = Continuous operation | |||
| HR | 1807 | Central heat type | Nilan variable CentralHeat.HeatType. | UINT16 | Read/write | 0 = OFF; 1 = El; 2 = Heatpump; 3 = Both (compressor first, then electric) | |||
| HR | 1808 | PID regulations time | Nilan variable CentralHeat.RegTime. | UINT16 | s | Read/write | |||
| HR | 1910 | Humidity low winter step select | Nilan variable AirQual.RH_VentLo. | UINT16 | Read/write | ||||
| HR | 1911 | Humidity high step select | Nilan variable AirQual.RH_VentHi. | UINT16 | Read/write | ||||
| HR | 1912 | Humidity limit for low ventilation | Nilan variable AirQual.RH_LimLo. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 1913 | Humidity max. time on high ventilation | Nilan variable AirQual.RH_TimeOut. | UINT16 | min | Read/write | |||
| HR | 1920 | CO2 high step select | Nilan variable AirQual.CO2_VentHi. | UINT16 | Read/write | ||||
| HR | 1921 | CO2 limit for normal ventilation | Nilan variable AirQual.CO2_LimLo. | UINT16 | ppm | Read/write | |||
| HR | 1922 | CO2 limit for high ventilation | Nilan variable AirQual.CO2_LimHi. | UINT16 | ppm | Read/write | |||
| HR | 2003 | HMI language | Nilan variable User.Language. | UINT16 | Read/write | 0 = English; 1 = German; 2 = French; 3 = Swedish; 4 = Danish; 5 = Norwegian; 6 = Finnish; 7 = Czech; 8 = Polish; 9 = Italian | |||
| HR | 2100 | Pre-heater block request | Nilan variable PreHeat.Block. | UINT16 | Read/write | 0 = No command; 1 = Request heater block (2 hours) | |||
| HR | 2200 | Calibrate DPT | Nilan variable DPT.DoCalibrate. | UINT16 | Read/write | 1 = Start calibration | |||
| HR | 2201 | Calibrate DPT2 | Nilan variable DPT2.DoCalibrate. | UINT16 | Read/write | 1 = Start calibration | |||
| HR | 2310 | Step 1 supply air flow | Nilan variable Pressure.Level1InFlow. | UINT16 | m3/h | Read/write | |||
| HR | 2311 | Step 2 supply air flow | Nilan variable Pressure.Level2InFlow. | UINT16 | m3/h | Read/write | |||
| HR | 2312 | Step 3 supply air flow | Nilan variable Pressure.Level3InFlow. | UINT16 | m3/h | Read/write | |||
| HR | 2313 | Step 4 supply air flow | Nilan variable Pressure.Level4InFlow. | UINT16 | m3/h | Read/write | |||
| HR | 2314 | Step 1 extract air flow | Nilan variable Pressure.Level1OuFlow. | UINT16 | m3/h | Read/write | |||
| HR | 2315 | Step 2 extract air flow | Nilan variable Pressure.Level2OuFlow. | UINT16 | m3/h | Read/write | |||
| HR | 2316 | Step 3 extract air flow | Nilan variable Pressure.Level3OuFlow. | UINT16 | m3/h | Read/write | |||
| HR | 2317 | Step 4 extract air flow | Nilan variable Pressure.Level4OuFlow. | UINT16 | m3/h | Read/write | |||
| HR | 2320 | Step 1 supply air pressure | Nilan variable Pressure.Level1InPres. | UINT16 | Pa | Read/write | |||
| HR | 2321 | Step 2 supply air pressure | Nilan variable Pressure.Level2InPres. | UINT16 | Pa | Read/write | |||
| HR | 2322 | Step 3 supply air pressure | Nilan variable Pressure.Level3InPres. | UINT16 | Pa | Read/write | |||
| HR | 2323 | Step 4 supply air pressure | Nilan variable Pressure.Level4InPres. | UINT16 | Pa | Read/write | |||
| HR | 2324 | Step 1 extract air pressure | Nilan variable Pressure.Level1OuPres. | UINT16 | Pa | Read/write | |||
| HR | 2325 | Step 2 extract air pressure | Nilan variable Pressure.Level2OuPres. | UINT16 | Pa | Read/write | |||
| HR | 2326 | Step 3 extract air pressure | Nilan variable Pressure.Level3OuPres. | UINT16 | Pa | Read/write | |||
| HR | 2327 | Step 4 extract air pressure | Nilan variable Pressure.Level4OuPres. | UINT16 | Pa | Read/write | |||
| HR | 4000 | Regulation deadband external room heating | Nilan variable CentralHeat.HeatExtern. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4001 | High fan speed at high indoor temp (cooling demand) | Nilan variable AirFlow.CoolVent. | UINT16 | Read/write | ||||
| HR | 4002 | Low outdoor temperature | Nilan variable AirFlow.WinterTemp. | INT16 | °C | Read/write | |||
| HR | 4003 | Fan speed at low outdoor temperature | Nilan variable AirFlow.WinerVent. | UINT16 | Read/write | ||||
| HR | 4004 | Day for automatic test | Nilan variable AirFlow.TestSelect. | UINT16 | Read/write | ||||
| HR | 4005 | After heating type | Nilan variable AirHeat.Type. | UINT16 | Read/write | ||||
| HR | 4006 | Delay timer for after-heat activation | Nilan variable AirHeat.Delay. | UINT16 | min | Read/write | |||
| HR | 4007 | Summer minimum supply air temperature | Nilan variable AirTemp.TempMinSum. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4008 | Summer maximum supply air temperature | Nilan variable AirTemp.TempMaxSum. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4009 | Winter minimum supply air temperature | Nilan variable AirTemp.TempMinWin. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4010 | Winter maximum supply air temperature | Nilan variable AirTemp.TempMaxWin. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4011 | Room temperature regulation deadband | Nilan variable AirTemp.RoomNZ. | INT16 | × 0.01 | Read/write | |||
| HR | 4012 | Low room temperature for stepwise reduced ventilation | Nilan variable AirTemp.TempRoomLow. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4013 | After heating activation | Nilan variable AirHeat.SelectSet. | UINT16 | Read/write | ||||
| HR | 4015 | Min. inlet | Nilan variable AirFlow.InletMin. | UINT16 | Read/write | ||||
| HR | 4016 | Min exhaust | Nilan variable AirFlow.ExhaustMin. | UINT16 | Read/write | ||||
| HR | 4017 | Max exhaust | Nilan variable AirFlow.ExhaustMax. | UINT16 | Read/write | ||||
| HR | 4019 | Damper walkin time | Nilan variable AirBypass.WalkingTime. | UINT16 | s | Read/write | |||
| HR | 4020 | Frost protection or de-icing - Ventilation level | Nilan variable Defrost.Fans. | UINT16 | Read/write | ||||
| HR | 4021 | Frost protection or de-icing - Bypass position | Nilan variable Defrost.Bypass. | UINT16 | Read/write | ||||
| HR | 4022 | Frost protection or de-icing - Time between activations | Nilan variable Defrost.BlockMinutes. | UINT16 | min | Read/write | |||
| HR | 4023 | Frost protection or de-icing - Start criteria | Nilan variable Defrost.TempStart. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4024 | Frost protection or de-icing - Stop criteria | Nilan variable Defrost.TempStop. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 4025 | Frost protection or de-icing - Max duration compressor | Nilan variable Defrost.DurMaxCpr. | UINT16 | min | Read/write | |||
| HR | 4026 | Frost protection or de-icing - Max duration exchanger | Nilan variable Defrost.DurMaxExh. | UINT16 | min | Read/write | |||
| HR | 4027 | T6 min defrost time | Nilan variable Defrost.T6MinRunSec. | UINT16 | s | Read/write | |||
| HR | 4040 | External fire alarm auto reset | Nilan variable Control.RestartMode. | UINT16 | Read/write | ||||
| HR | 4041 | Enable power saving features | Nilan variable Control.PowerSave. | UINT16 | Read/write | ||||
| HR | 4100 | Inlet step 1 speed setup | Nilan variable AirFlow.InletSpd_1. | UINT16 | Read/write | ||||
| HR | 4101 | Inlet step 2 speed setup | Nilan variable AirFlow.InletSpd_2. | UINT16 | Read/write | ||||
| HR | 4102 | Inlet step 3 speed setup | Nilan variable AirFlow.InletSpd_3. | UINT16 | Read/write | ||||
| HR | 4103 | Inlet step 4 speed setup | Nilan variable AirFlow.InletSpd_4. | UINT16 | Read/write | ||||
| HR | 4104 | Exhaust step 1 speed setup | Nilan variable AirFlow.ExhaustSpd_1. | UINT16 | Read/write | ||||
| HR | 4105 | Exhaust step 2 speed setup | Nilan variable AirFlow.ExhaustSpd_2. | UINT16 | Read/write | ||||
| HR | 4106 | Exhaust step 3 speed setup | Nilan variable AirFlow.ExhaustSpd_3. | UINT16 | Read/write | ||||
| HR | 4107 | Exhaust step 4 speed setup | Nilan variable AirFlow.ExhaustSpd_4. | UINT16 | Read/write | ||||
| HR | 4108 | Enable Indoor Air Quality (IAQ) control function | Nilan variable AirQual.Type. | UINT16 | Read/write | ||||
| HR | 4109 | Heater output signal type (if not air channel type) | Nilan variable Control.AnaOutType. | UINT16 | Read/write | ||||
| HR | 4110 | Room temperature controller response type | Nilan variable AirTemp.RoomResponse. | INT16 | Read/write | ||||
| HR | 4111 | Nordic: Select anti frost also during evap. defrost | Nilan variable PreHeat.Defrost. | UINT16 | Read/write | ||||
| HR | 4112 | T4 start criteria when temperature controlled | Nilan variable PreHeat.TempSet. | INT16 | Read/write |
Notes on this map
- Nilan does not host this protocol description at a public URL we could find (its manuals say it can be downloaded from the Nilan website, but no direct link turned up). The linked copy, hosted by the home-automation vendor TapHome in its 'manufacturer' folder, is the unchanged Nilan document 52173104.
- Scale column: '100' means the raw value is divided by 100 (e.g. temperatures and % values with two decimals). Registers without a scale are whole numbers.
- Signedness is not stated per register; temperatures and temperature settings are typed INT16 because they can be negative (the list shows ranges down to -40.00 °C), everything else UINT16.
- Left out: software version text registers (1-3, two ASCII characters each), suction/discharge pressure (219/220, no scale given), registers scaled by 60 (1503, 4018) whose unit is unclear, user-function temperature/offset (604/605 and their user-function-2 copies 614/615) and fan-scaling (4098/4099) which have no scale, the pressure-control P/I settings (2300-2304), the alarm log detail block (3050-3074), week-program editing registers (4030-4036) and the menu-open flag (2002).
- Enumerations are only given where the list prints the full value set; several holding registers in the display section (e.g. 4003-4005, 4012, 4013, 4020, 4021, 4041, 4108-4112) are listed without their complete value lists and are left without values.
- Some holding-register descriptions in the source are in Danish (2300-2327 'Trin n tilluft/fraluft' = step n supply/extract air flow or pressure, 1209 heat source select); they are translated in the names here.
- The document does not mark which holding registers are read-only; the output registers 100-206 and the clock 300-305 report states rather than commands.
- All input registers can also be read as holding registers with function 03 at address + 10000 (read only).
- External fire alarm auto reset (holding 4040) is left without value labels: the printed table shows codes 0-2, but the cell is cut off and the document's text layer holds a further code 3 that is not visible.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Nilan CTS602 controller with HMI350T panel (Modbus version 23)
What Modbus registers does the Nilan CTS602 controller with HMI350T panel (Modbus version 23) have?
This map lists 262 registers: 97 input registers, 165 holding registers. 165 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Nilan CTS602 controller with HMI350T panel (Modbus version 23) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Nilan lists the addresses exactly as sent in the Modbus request, without the 30001/40001 global offset: reading input register 100 with function 04 is global address 30101. Use the printed number directly as the wire address.
What are the minimum Modbus registers to integrate the Nilan CTS602 controller with HMI350T panel (Modbus version 23)?
Start with HR 1001 User on / off select (equal to ON/OFF keys) (On/off); HR 1002 User operation mode select (Operation mode); HR 1003 User ventilation step select (Ventilation step); HR 1004 User temperature setpoint (Temperature setpoint); IR 1002 Actual control state (Actual control state); IR 208 Outdoor temperature (Outdoor temperature); IR 203 Room exhaust temperature (Room exhaust temperature); IR 400 Alarm state bit mask (Alarm status).
How do I enable Modbus control of the Nilan CTS602 controller with HMI350T panel (Modbus version 23)?
No enable step: the CTS602 always answers on COM1. Only the node address can be changed (holding register 50 or the panel); speed and framing are fixed.
Where is the official Nilan CTS602 controller with HMI350T panel (Modbus version 23) Modbus documentation?
The source is Protocol description - Nilan CTS602 with HMI350T - Modbus version 23 (52173104), revision 2023-11-22. Nilan doesn't publish it on its own website, so this map was re-typed from a free copy at https://taphome.com/compatibility/devices/nilan-cts602-heat-pump/manufacturer/CTS602_HMI350T_Modbus_v23.pdf. It may be an older revision, so check it against the live unit.
Other pumps register maps
- Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit - Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080 - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+ - Heat pump (water-source heat pump controller)
First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
First Co. / AE-Air water-source heat pumps (WSV and related series) with the factory DDC controller CB900, without hot-gas reheat (IOM8083D02 rev. A).
Also known as: CB900, CB900-1, CB900-2, IOM8083D02, WSV series DDC, First Co. WSHP DDC controller, AE-Air WSHP DDC - Pump (submersible grinder pump pit)
Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)
Up to four Grundfos SEG AUTOADAPT grinder pumps in one or more pits, connected to a CIU 202 (Modbus RTU), CIU 262 (cellular) or CIU 502 (Modbus TCP); functional profile 96846341 (2019-01).
Also known as: SEG AUTOADAPT, CIU 202, CIU 262, CIU 502, 96846341 - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB