  4. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)

Heat pump (water-source heat pump controller) · Modbus register map

First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus register map

Updated 19 November 2026

Short answer

First Co. water-source heat pumps can ship with a CB900 DDC controller that speaks BACnet MS/TP/IP and Modbus RTU/TCP. The Modbus side exposes pressure-switch, condensate, call-signal and compressor bits plus the operating code, machine mode and software version. This map lists those status points.

This page lists 21 Modbus registers for the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from First Co.’s own free documentation (linked below) and checked against it.

Manufacturer
First Co.
Model
WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
Equipment type
Heat pump (water-source heat pump controller)
Registers
21 (0 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
9
Default serial
38400 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
CB900, CB900-1, CB900-2, IOM8083D02, WSV series DDC, First Co. WSHP DDC controller, AE-Air WSHP DDC
Source document
WSHP Series DDC Controller Installation, Operation and Maintenance Manual (no hot-gas reheat) · IOM8083D02 Rev. A · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)

Integration in brief

Read holding registers 3 (op code) and 5 (machine mode) for status and fault, and coils 0-10 for pressure switches, condensate, reversing valve, call signals and compressor state.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3Op codeUINT16Operating / fault codeRead
HR 5Mode of machineUINT16Machine modeRead
CO 0HP statusBITHigh-pressure switchRead
CO 1LP statusBITLow-pressure switchRead
CO 2Condensate statusBITCondensateRead
CO 10Compressor statusBITCompressor statusRead

Enable Modbus control & writes

On the controller (or the CB1000 HMI tool) set the communication mode to 'BacIp&ModRtu' for Modbus RTU; Modbus IP is always available. Modbus RTU and BACnet MS/TP cannot run together.

Byte order & addressing

Network setup

Watch out for

First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

21 of 21 shown
First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0HP statusHigh-pressure switch (BV0)BITRead0 = Normal; 1 = High pressure
CO1LP statusLow-pressure switch (BV1)BITRead0 = Normal; 1 = Low pressure
CO2Condensate statusDrain pan condensate (BV2)BITRead0 = Not detected; 1 = Condensate detected
CO3Reversing valve statusBV3BITRead0 = Off; 1 = On
CO4Y signal statusBV4BITRead
CO5C signal statusBV5BITRead
CO6O signal statusBV6BITRead
CO8Test mode statusShortened wait times; ends by itself after 15 min (BV8)BITRead0 = Normal; 1 = Test mode
CO10Compressor statusBV10BITRead
HR3Op codeController operating / fault code (MSV1)UINT16Read11 = OK; 12 = High pressure; 13 = Low pressure; 14 = Low leaving water temperature; 15 = Low air coil temperature; 16 = Condensate detected; 18 = Swapped temperature sensors; 19 = Bad thermistor; 20 = Low cooling capacity; 21 = High cooling capacity; 22 = Low heating capacity; 23 = High heating capacity
HR5Mode of machineMSV2UINT16Read1 = Standby; 2 = Fan only; 3 = Heat; 4 = Cool; 5 = Cool; 7 = Lockout; 8 = Diagnostic
HR6Fan modeFan status (MSV3); states not listedUINT16Read
HR7Machine enableSystem enable/disable (MSV4); states not listedUINT16Read
HR11Program number 1st character1 = A, 2 = B, 3 = C ...UINT16Read
HR12Program number 2nd character1 = A, 2 = B, 3 = C ...UINT16Read
HR13Program number numeric part0 = 000, 1 = 001 ...UINT16Read
HR14Program revision1 = A, 2 = B, 3 = C ...UINT16Read
HR15Software revision x1Major change digitUINT16Read
HR16Software revision x2Hardware/wiring change digitUINT16Read
HR17Software revision x3Software-only change digitUINT16Read
HR18Software revision x4Minor change digitUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)

What Modbus registers does the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) have?

This map lists 21 registers: 9 coils, 12 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives a 'Modbus Index' starting at 0 for both coils and holding registers (HP status is coil index 0). The index is used as the wire address.

What are the minimum Modbus registers to integrate the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)?

Start with HR 3 Op code (Operating / fault code); HR 5 Mode of machine (Machine mode); CO 0 HP status (High-pressure switch); CO 1 LP status (Low-pressure switch); CO 2 Condensate status (Condensate); CO 10 Compressor status (Compressor status).

How do I enable Modbus control of the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)?

On the controller (or the CB1000 HMI tool) set the communication mode to 'BacIp&ModRtu' for Modbus RTU; Modbus IP is always available. Modbus RTU and BACnet MS/TP cannot run together.

Where is the official First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus documentation?

The source is WSHP Series DDC Controller Installation, Operation and Maintenance Manual (no hot-gas reheat) (IOM8083D02 Rev. A), revision 2026-03, published free by First Co. at https://firstco.com/files/IOM/IOM8083D02-Water-Source-DDC-Controller-no-HGRH.pdf.

Other pumps register maps

All pumps Modbus register maps →

Source: WSHP Series DDC Controller Installation, Operation and Maintenance Manual (no hot-gas reheat) · IOM8083D02 Rev. A · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.