- WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
Heat pump (water-source heat pump controller) · Modbus register map
First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus register map
Updated 19 November 2026
First Co. water-source heat pumps can ship with a CB900 DDC controller that speaks BACnet MS/TP/IP and Modbus RTU/TCP. The Modbus side exposes pressure-switch, condensate, call-signal and compressor bits plus the operating code, machine mode and software version. This map lists those status points.
This page lists 21 Modbus registers for the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from First Co.’s own free documentation (linked below) and checked against it.
- Manufacturer
- First Co.
- Model
- WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
- Equipment type
- Heat pump (water-source heat pump controller)
- Registers
- 21 (0 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 9
- Default serial
- 38400 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- CB900, CB900-1, CB900-2, IOM8083D02, WSV series DDC, First Co. WSHP DDC controller, AE-Air WSHP DDC
Integration notes: First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
Read holding registers 3 (op code) and 5 (machine mode) for status and fault, and coils 0-10 for pressure switches, condensate, reversing valve, call signals and compressor state.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3 | Op code | UINT16 | Operating / fault code | Read |
| HR 5 | Mode of machine | UINT16 | Machine mode | Read |
| CO 0 | HP status | BIT | High-pressure switch | Read |
| CO 1 | LP status | BIT | Low-pressure switch | Read |
| CO 2 | Condensate status | BIT | Condensate | Read |
| CO 10 | Compressor status | BIT | Compressor status | Read |
Enable Modbus control & writes
On the controller (or the CB1000 HMI tool) set the communication mode to 'BacIp&ModRtu' for Modbus RTU; Modbus IP is always available. Modbus RTU and BACnet MS/TP cannot run together.
Byte order & addressing
- Temperatures have no published Modbus format, so they are not in this map.
Network setup
- Modbus RTU page: baud 9600-115200 (default 38400), device address 1-247 (default 9), parity default None, stop bits default 1.
- A soft restart is needed after changing communication settings.
- Communication menus need password level 2 or 3.
Watch out for
- BACnet MS/TP mode turns Modbus RTU off.
- Test mode shortens all wait times and turns itself off after 15 minutes.
First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0 | HP status | High-pressure switch (BV0) | BIT | Read | 0 = Normal; 1 = High pressure | |||
| CO | 1 | LP status | Low-pressure switch (BV1) | BIT | Read | 0 = Normal; 1 = Low pressure | |||
| CO | 2 | Condensate status | Drain pan condensate (BV2) | BIT | Read | 0 = Not detected; 1 = Condensate detected | |||
| CO | 3 | Reversing valve status | BV3 | BIT | Read | 0 = Off; 1 = On | |||
| CO | 4 | Y signal status | BV4 | BIT | Read | ||||
| CO | 5 | C signal status | BV5 | BIT | Read | ||||
| CO | 6 | O signal status | BV6 | BIT | Read | ||||
| CO | 8 | Test mode status | Shortened wait times; ends by itself after 15 min (BV8) | BIT | Read | 0 = Normal; 1 = Test mode | |||
| CO | 10 | Compressor status | BV10 | BIT | Read | ||||
| HR | 3 | Op code | Controller operating / fault code (MSV1) | UINT16 | Read | 11 = OK; 12 = High pressure; 13 = Low pressure; 14 = Low leaving water temperature; 15 = Low air coil temperature; 16 = Condensate detected; 18 = Swapped temperature sensors; 19 = Bad thermistor; 20 = Low cooling capacity; 21 = High cooling capacity; 22 = Low heating capacity; 23 = High heating capacity | |||
| HR | 5 | Mode of machine | MSV2 | UINT16 | Read | 1 = Standby; 2 = Fan only; 3 = Heat; 4 = Cool; 5 = Cool; 7 = Lockout; 8 = Diagnostic | |||
| HR | 6 | Fan mode | Fan status (MSV3); states not listed | UINT16 | Read | ||||
| HR | 7 | Machine enable | System enable/disable (MSV4); states not listed | UINT16 | Read | ||||
| HR | 11 | Program number 1st character | 1 = A, 2 = B, 3 = C ... | UINT16 | Read | ||||
| HR | 12 | Program number 2nd character | 1 = A, 2 = B, 3 = C ... | UINT16 | Read | ||||
| HR | 13 | Program number numeric part | 0 = 000, 1 = 001 ... | UINT16 | Read | ||||
| HR | 14 | Program revision | 1 = A, 2 = B, 3 = C ... | UINT16 | Read | ||||
| HR | 15 | Software revision x1 | Major change digit | UINT16 | Read | ||||
| HR | 16 | Software revision x2 | Hardware/wiring change digit | UINT16 | Read | ||||
| HR | 17 | Software revision x3 | Software-only change digit | UINT16 | Read | ||||
| HR | 18 | Software revision x4 | Minor change digit | UINT16 | Read |
Notes on this map
- Left out: exit water coil temperature (index 0), air coil temperature (1), supply air temperature (2) and the lockout retry count (4). The manual types them as analog values (BACnet AV) with no Modbus data type or scale, so the raw format is not known.
- Fan mode and machine enable are multi-state values whose state numbers the manual does not list.
- The coil points are status values; the manual does not say whether any of them can be written.
- Op code value 17 and mode value 6 are not listed in the manual. Mode values 4 and 5 are both printed as 'Cool'.
- Software revision and program number are also exposed as BACnet state-text objects that have no Modbus index.
- For the LP status coil the manual prints "1-high pressure"; read 1 as the low-pressure switch tripped.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
What Modbus registers does the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) have?
This map lists 21 registers: 9 coils, 12 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives a 'Modbus Index' starting at 0 for both coils and holding registers (HP status is coil index 0). The index is used as the wire address.
What are the minimum Modbus registers to integrate the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)?
Start with HR 3 Op code (Operating / fault code); HR 5 Mode of machine (Machine mode); CO 0 HP status (High-pressure switch); CO 1 LP status (Low-pressure switch); CO 2 Condensate status (Condensate); CO 10 Compressor status (Compressor status).
How do I enable Modbus control of the First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)?
On the controller (or the CB1000 HMI tool) set the communication mode to 'BacIp&ModRtu' for Modbus RTU; Modbus IP is always available. Modbus RTU and BACnet MS/TP cannot run together.
Where is the official First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP) Modbus documentation?
The source is WSHP Series DDC Controller Installation, Operation and Maintenance Manual (no hot-gas reheat) (IOM8083D02 Rev. A), revision 2026-03, published free by First Co. at https://firstco.com/files/IOM/IOM8083D02-Water-Source-DDC-Controller-no-HGRH.pdf.
Other pumps register maps
- Pump (submersible grinder pump pit)
Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)
Up to four Grundfos SEG AUTOADAPT grinder pumps in one or more pits, connected to a CIU 202 (Modbus RTU), CIU 262 (cellular) or CIU 502 (Modbus TCP); functional profile 96846341 (2019-01).
Also known as: SEG AUTOADAPT, CIU 202, CIU 262, CIU 502, 96846341 - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Heat pump (air-to-water) Modbus interface
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Toshiba BMS-IFMB0UEW-E MB interface on ESTIA R410A 4 Series and 5 Series (WM type) and R32 1 Series (WM and AIO type) hydro units, user manual EEU-006 issued 31/05/2021.
Also known as: BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006 - Pump system
Wilo SiFresh with CIF module Modbus RTU
Wilo SiFresh pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-SiFresh - Heat pump Modbus interface
Airzone Aidoo Pro Modbus control for air-to-water heat pumps
Airzone Aidoo Pro units configured for Modbus output and connected to an air-to-water heat pump; register table 'Registers for Air-to-Water HP units' of the Aidoo - Modbus integration manual (v. 201).
Also known as: Aidoo Pro, Aidoo Pro Modbus air-to-water, Airzone Aidoo Modbus aerothermal - Heat pump
Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)
Ecoforest ecoGEO, ecoGEO HP and ecoAIR heat pumps on software AWD24, WWD24, WWC24 or later, register list API HP24_V01.02 (heat pump list only; supervisor and source-manager lists not included).
Also known as: ecoGEO, ecoGEO B&C, ecoGEO HP, ecoAIR, AWD24, WWD24, WWC24, API HP24_V01.02
All pumps Modbus register maps →
Source: WSHP Series DDC Controller Installation, Operation and Maintenance Manual (no hot-gas reheat) · IOM8083D02 Rev. A · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.