Pump (submersible grinder pump pit) · Modbus register map

Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus) Modbus register map

Updated 19 November 2026

Short answer

SEG AUTOADAPT grinder pumps carry their own level sensing and control; a CIU box links up to four of them to a Modbus master. The map covers the pit commands and start/stop levels for single-pit and multi-pit operation, pit state and alarm bits, pit energy and run-time counters, and a 50-register block per pump with temperatures, voltage, current, power, energy, starts, level and alarm/warning bits.

This page lists 169 Modbus registers for the Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus) — 28 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Grundfos’s own free documentation (linked below) and checked against it.

Manufacturer
Grundfos
Model
SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)
Equipment type
Pump (submersible grinder pump pit)
Registers
169 (28 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
SEG AUTOADAPT, CIU 202, CIU 262, CIU 502, 96846341
Source document
Modbus for SEG AUTOADAPT - CIU 202 Modbus RTU, CIU 262 3G/4G Cellular, CIU 502 Ethernet for Modbus TCP - Functional profile and user manual · 96846341 0119 · rev. 2019-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)

Integration in brief

Read 00230-00235 for pump presence, running, alarm and the pit main status, 00301 for the pit level, and each pump block for current, power and alarm bits. Force pumps with 00122-00125 or use the PumpDown bits of PitControl 00101.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 230PitPumpsRunningBITMAP16Pumps running bitsRead
HR 231PitPumpsAlarmBITMAP16Pumps in alarm bitsRead
HR 234MainStatusBITMAP16Warning / alarm / manual summaryRead
HR 300WaterLevelUINT16Pit water levelRead
HR 100PitControlBITMAP16Reset and pump-down commandsRead/write
HR 403Pump1.AverageLineCurrentUINT16Pump 1 currentRead
HR 427Pump1.AlarmsBITMAP16Pump 1 alarm bitsRead

Enable Modbus control & writes

Set the CIU 202 address with the hex rotary switches and the speed and parity with the DIP switches; no setting is needed in the pumps. Write the pit levels only in the mode selected by PitMode (00203).

Byte order & addressing

Network setup

Watch out for

Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

169 of 169 shown
Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 00001SlaveMinimumReplyDelayExtra reply delay 0-10000 ms (default 0).UINT16msRead/write
HR1doc 00002RegisterOffsetOffset added to addresses above 00100; default 0.UINT16Read/write
HR4doc 00005AutoAckControlBitsUINT16Read/write0 = Disabled; 1 = Enabled (default)
HR23doc 00024ActualModbusAddressUINT16Read
HR29doc 00030UnitFamilyUINT16Read
HR30doc 00031UnitTypeUINT16Read
HR31doc 00032UnitVersionUINT16Read
HR100doc 00101PitControlCommand bits, act on a 0 to 1 edge.BITMAP16Read/writebit 0 = ResetAlarm; bit 1 = ResetHistory; bit 2 = PitPump1ResetHistory; bit 3 = PitPump2ResetHistory; bit 4 = PitPump3ResetHistory; bit 5 = PitPump4ResetHistory; bit 6 = PitPump1ResetAlarm; bit 7 = PitPump2ResetAlarm; bit 8 = PitPump3ResetAlarm; bit 9 = PitPump4ResetAlarm; bit 10 = PitPump1PumpDown (pump down once, then level control stops it); bit 11 = PitPump2PumpDown (pump down once, then level control stops it); bit 12 = PitPump3PumpDown (pump down once, then level control stops it); bit 13 = PitPump4PumpDown (pump down once, then level control stops it)
HR101doc 00102SetSinglePitStopLevelSingle-pit mode only.UINT16× 0.01mRead/write
HR102doc 00103SetSinglePitStartLevelMaxSingle-pit mode only.UINT16× 0.01mRead/write
HR103doc 00104SetSinglePitStartLevelBandSingle-pit mode only.UINT16× 0.01mRead/write
HR104doc 00105SetSinglePitHighWaterLevelSingle-pit mode only.UINT16× 0.01mRead/write
HR105doc 00106SetMultiPitPump1StopLevelMulti-pit mode only.UINT16× 0.01mRead/write
HR106doc 00107SetMultiPitPump1StartLevelMaxMulti-pit mode only.UINT16× 0.01mRead/write
HR107doc 00108SetMultiPitPump1StartLevelBandMulti-pit mode only.UINT16× 0.01mRead/write
HR108doc 00109SetMultiPitPump1HighWaterLevelMulti-pit mode only.UINT16× 0.01mRead/write
HR109doc 00110SetMultiPitPump2StopLevelMulti-pit mode only.UINT16× 0.01mRead/write
HR110doc 00111SetMultiPitPump2StartLevelMaxMulti-pit mode only.UINT16× 0.01mRead/write
HR111doc 00112SetMultiPitPump2StartLevelBandMulti-pit mode only.UINT16× 0.01mRead/write
HR112doc 00113SetMultiPitPump2HighWaterLevelMulti-pit mode only.UINT16× 0.01mRead/write
HR113doc 00114SetMultiPitPump3StopLevelMulti-pit mode only.UINT16× 0.01mRead/write
HR114doc 00115SetMultiPitPump3StartLevelMaxMulti-pit mode only.UINT16× 0.01mRead/write
HR115doc 00116SetMultiPitPump3StartLevelBandMulti-pit mode only.UINT16× 0.01mRead/write
HR116doc 00117SetMultiPitPump3HighWaterLevelMulti-pit mode only.UINT16× 0.01mRead/write
HR117doc 00118SetMultiPitPump4StopLevelMulti-pit mode only.UINT16× 0.01mRead/write
HR118doc 00119SetMultiPitPump4StartLevelMaxMulti-pit mode only.UINT16× 0.01mRead/write
HR119doc 00120SetMultiPitPump4StartLevelBandMulti-pit mode only.UINT16× 0.01mRead/write
HR120doc 00121SetMultiPitPump4HighWaterLevelMulti-pit mode only.UINT16× 0.01mRead/write
HR121doc 00122PitPump1ControlUINT16Read/write0 = Auto; 1 = Forced start; 2 = Forced stop
HR122doc 00123PitPump2ControlUINT16Read/write0 = Auto; 1 = Forced start; 2 = Forced stop
HR123doc 00124PitPump3ControlUINT16Read/write0 = Auto; 1 = Forced start; 2 = Forced stop
HR124doc 00125PitPump4ControlUINT16Read/write0 = Auto; 1 = Forced start; 2 = Forced stop
HR202doc 00203PitModeUINT16Read0 = Single-pit; 1 = Multi-pit
HR203doc 00204SinglePitStopLevelUINT16× 0.01mRead
HR204doc 00205SinglePitStartLevelMaxUINT16× 0.01mRead
HR205doc 00206SinglePitStartLevelBandUINT16× 0.01mRead
HR206doc 00207SinglePitHighWaterLevelUINT16× 0.01mRead
HR207doc 00208MultiPitPump1StopLevelUINT16× 0.01mRead
HR208doc 00209MultiPitPump1StartLevelMaxUINT16× 0.01mRead
HR209doc 00210MultiPitPump1StartLevelBandUINT16× 0.01mRead
HR210doc 00211MultiPitPump1HighWaterLevelUINT16× 0.01mRead
HR211doc 00212MultiPitPump2StopLevelUINT16× 0.01mRead
HR212doc 00213MultiPitPump2StartLevelMaxUINT16× 0.01mRead
HR213doc 00214MultiPitPump2StartLevelBandUINT16× 0.01mRead
HR214doc 00215MultiPitPump2HighWaterLevelUINT16× 0.01mRead
HR215doc 00216MultiPitPump3StopLevelUINT16× 0.01mRead
HR216doc 00217MultiPitPump3StartLevelMaxUINT16× 0.01mRead
HR217doc 00218MultiPitPump3StartLevelBandUINT16× 0.01mRead
HR218doc 00219MultiPitPump3HighWaterLevelUINT16× 0.01mRead
HR219doc 00220MultiPitPump4StopLevelUINT16× 0.01mRead
HR220doc 00221MultiPitPump4StartLevelMaxUINT16× 0.01mRead
HR221doc 00222MultiPitPump4StartLevelBandUINT16× 0.01mRead
HR222doc 00223MultiPitPump4HighWaterLevelUINT16× 0.01mRead
HR223doc 00224PitPump1OperationModeUINT16Read0 = Auto; 1 = Started; 2 = Stopped
HR224doc 00225PitPump2OperationModeUINT16Read0 = Auto; 1 = Started; 2 = Stopped
HR225doc 00226PitPump3OperationModeUINT16Read0 = Auto; 1 = Started; 2 = Stopped
HR226doc 00227PitPump4OperationModeUINT16Read0 = Auto; 1 = Started; 2 = Stopped
HR227doc 00228AlarmCodeGrundfos alarm code of the pit (see manual section 14.2).UINT16Read
HR228doc 00229WarningCodeGrundfos warning code of the pit.UINT16Read
HR229doc 00230PitPumpsPresentBITMAP16Readbit 0 = Pump 1 present; bit 1 = Pump 2 present; bit 2 = Pump 3 present; bit 3 = Pump 4 present
HR230doc 00231PitPumpsRunningBITMAP16Readbit 0 = Pump 1 running; bit 1 = Pump 2 running; bit 2 = Pump 3 running; bit 3 = Pump 4 running
HR231doc 00232PitPumpsAlarmBITMAP16Readbit 0 = Pump 1 alarm; bit 1 = Pump 2 alarm; bit 2 = Pump 3 alarm; bit 3 = Pump 4 alarm
HR232doc 00233PitPumpsCommFaultBITMAP16Readbit 0 = Pump 1 communication fault; bit 1 = Pump 2 communication fault; bit 2 = Pump 3 communication fault; bit 3 = Pump 4 communication fault
HR233doc 00234OperatingModeSingle-pit mode only.UINT16Read0 = Standby; 1 = Startup delay; 2 = Pumping (level control); 5 = Stopped (level control); 9 = Manual control; 11 = Mains supply failure; 13 = Alarm on all enabled pumps; 14 = All pumps out of operation
HR234doc 00235MainStatusBITMAP16Readbit 0 = Warning in pump or pit; bit 1 = Alarm in pump or pit; bit 3 = Manual pump control enabled
HR239doc 00240AlarmBitsBITMAP16Readbit 0 = External fault signal; bit 1 = Communication fault, pump; bit 3 = Pump 1 fault; bit 4 = Pump 2 fault; bit 5 = Pump 3 fault; bit 6 = Pump 4 fault; bit 7 = Sensor limit 2 exceeded (high level); bit 8 = Setup conflict
HR240doc 00241WarningBitsBITMAP16Readbit 1 = Communication fault, pump; bit 2 = Verification error (ROM, FLASH); bit 8 = Setup conflict
HR300doc 00301WaterLevelPit level estimated by the pumps; single-pit mode.UINT16× 0.01mRead
HR301doc 00302MaxWaterLevelHighest level seen; reset with ResetHistory.UINT16× 0.01mRead
HR302doc 00303PowerUINT32ABCDWRead
HR304doc 00305EnergyTripCntResettable with ResetHistory.UINT32ABCDkWhRead
HR306doc 00307OnTimeCntCIU power-on time; cannot be reset.UINT32ABCDminRead
HR308doc 00309OprTimeTripCntTime with one or more pumps running.UINT32ABCDminRead
HR310doc 00311PumpOperationTimePctShare of time pumping, last 30 days.UINT16× 0.01%Read
HR311doc 00312MultiPumpOperationTimePctShare of pumping time with several pumps, 30 days.UINT16× 0.01%Read
HR312doc 00313MultiPumpOperationTimeMaxLongest multi-pump run, last 30 days.UINT16sRead
HR313doc 00314DigitalInputBITMAP16Read
HR400doc 00401Pump1.MotorTemperatureIn 0.01 K (kelvin).UINT16× 0.01KRead
HR401doc 00402Pump1.ElectronicTemperatureIn 0.01 K (kelvin).UINT16× 0.01KRead
HR402doc 00403Pump1.AverageLineVoltageUINT16× 0.1VRead
HR403doc 00404Pump1.AverageLineCurrentUINT16× 0.1ARead
HR404doc 00405Pump1.AverageLineCurrentLatestCurrent during the last run.UINT16× 0.1ARead
HR405doc 00406Pump1.LineFrequencyUINT16× 0.1HzRead
HR406doc 00407Pump1.PhaseSequenceBoolean phase-sequence state.UINT16Read
HR407doc 00408Pump1.CosPhiUINT16× 0.01Read
HR408doc 00409Pump1.PowerUINT16WRead
HR409doc 00410Pump1.EnergyTripCounterUINT32ABCDkWhRead
HR411doc 00412Pump1.WaterLevelUINT16× 0.01mRead
HR412doc 00413Pump1.WaterLevelMaxUINT16× 0.01mRead
HR413doc 00414Pump1.MaxContinousTimeLongest continuous run, last 30 days.UINT16minRead
HR414doc 00415Pump1.TotalPoweredTimeUINT32ABCDminRead
HR416doc 00417Pump1.OperationTimeUINT32ABCDminRead
HR418doc 00419Pump1.OperationTimeTripCounterUINT32ABCDminRead
HR420doc 00421Pump1.NumberOfStartsUINT32ABCDRead
HR422doc 00423Pump1.NumberOfStartsTripCounterUINT32ABCDRead
HR424doc 00425Pump1.AlarmCodeGrundfos alarm code (manual section 14.2).UINT16Read
HR425doc 00426Pump1.WarningCodeGrundfos warning code.UINT16Read
HR426doc 00427Pump1.OperatingModeUINT16Read0 = Auto (power-on default); 1 = Forced start; 2 = Forced stop
HR427doc 00428Pump1.AlarmsBITMAP16Readbit 0 = Phase sequence reversed; bit 1 = Overvoltage; bit 2 = Undervoltage; bit 3 = Overload; bit 4 = Blocked motor/pump; bit 6 = Motor temperature; bit 7 = Control electronics temperature; bit 8 = Temperature relay 1 (e.g. Klixon); bit 9 = Temperature relay 2 (e.g. thermistor); bit 10 = Verification error (ROM, FLASH); bit 12 = Sensor fault
HR428doc 00429Pump1.WarningsBITMAP16Readbit 0 = Phase sequence reversed; bit 1 = Overvoltage; bit 2 = Undervoltage; bit 3 = Overload; bit 4 = Blocked motor/pump; bit 6 = Motor temperature; bit 7 = Control electronics temperature; bit 8 = Temperature relay 1 (e.g. Klixon); bit 9 = Temperature relay 2 (e.g. thermistor); bit 10 = Verification error (ROM, FLASH); bit 12 = Sensor fault
HR450doc 00451Pump2.MotorTemperatureIn 0.01 K (kelvin).UINT16× 0.01KRead
HR451doc 00452Pump2.ElectronicTemperatureIn 0.01 K (kelvin).UINT16× 0.01KRead
HR452doc 00453Pump2.AverageLineVoltageUINT16× 0.1VRead
HR453doc 00454Pump2.AverageLineCurrentUINT16× 0.1ARead
HR454doc 00455Pump2.AverageLineCurrentLatestCurrent during the last run.UINT16× 0.1ARead
HR455doc 00456Pump2.LineFrequencyUINT16× 0.1HzRead
HR456doc 00457Pump2.PhaseSequenceBoolean phase-sequence state.UINT16Read
HR457doc 00458Pump2.CosPhiUINT16× 0.01Read
HR458doc 00459Pump2.PowerUINT16WRead
HR459doc 00460Pump2.EnergyTripCounterUINT32ABCDkWhRead
HR461doc 00462Pump2.WaterLevelUINT16× 0.01mRead
HR462doc 00463Pump2.WaterLevelMaxUINT16× 0.01mRead
HR463doc 00464Pump2.MaxContinousTimeLongest continuous run, last 30 days.UINT16minRead
HR464doc 00465Pump2.TotalPoweredTimeUINT32ABCDminRead
HR466doc 00467Pump2.OperationTimeUINT32ABCDminRead
HR468doc 00469Pump2.OperationTimeTripCounterUINT32ABCDminRead
HR470doc 00471Pump2.NumberOfStartsUINT32ABCDRead
HR472doc 00473Pump2.NumberOfStartsTripCounterUINT32ABCDRead
HR474doc 00475Pump2.AlarmCodeGrundfos alarm code (manual section 14.2).UINT16Read
HR475doc 00476Pump2.WarningCodeGrundfos warning code.UINT16Read
HR476doc 00477Pump2.OperatingModeUINT16Read0 = Auto (power-on default); 1 = Forced start; 2 = Forced stop
HR477doc 00478Pump2.AlarmsBITMAP16Readbit 0 = Phase sequence reversed; bit 1 = Overvoltage; bit 2 = Undervoltage; bit 3 = Overload; bit 4 = Blocked motor/pump; bit 6 = Motor temperature; bit 7 = Control electronics temperature; bit 8 = Temperature relay 1 (e.g. Klixon); bit 9 = Temperature relay 2 (e.g. thermistor); bit 10 = Verification error (ROM, FLASH); bit 12 = Sensor fault
HR478doc 00479Pump2.WarningsBITMAP16Readbit 0 = Phase sequence reversed; bit 1 = Overvoltage; bit 2 = Undervoltage; bit 3 = Overload; bit 4 = Blocked motor/pump; bit 6 = Motor temperature; bit 7 = Control electronics temperature; bit 8 = Temperature relay 1 (e.g. Klixon); bit 9 = Temperature relay 2 (e.g. thermistor); bit 10 = Verification error (ROM, FLASH); bit 12 = Sensor fault
HR500doc 00501Pump3.MotorTemperatureIn 0.01 K (kelvin).UINT16× 0.01KRead
HR501doc 00502Pump3.ElectronicTemperatureIn 0.01 K (kelvin).UINT16× 0.01KRead
HR502doc 00503Pump3.AverageLineVoltageUINT16× 0.1VRead
HR503doc 00504Pump3.AverageLineCurrentUINT16× 0.1ARead
HR504doc 00505Pump3.AverageLineCurrentLatestCurrent during the last run.UINT16× 0.1ARead
HR505doc 00506Pump3.LineFrequencyUINT16× 0.1HzRead
HR506doc 00507Pump3.PhaseSequenceBoolean phase-sequence state.UINT16Read
HR507doc 00508Pump3.CosPhiUINT16× 0.01Read
HR508doc 00509Pump3.PowerUINT16WRead
HR509doc 00510Pump3.EnergyTripCounterUINT32ABCDkWhRead
HR511doc 00512Pump3.WaterLevelUINT16× 0.01mRead
HR512doc 00513Pump3.WaterLevelMaxUINT16× 0.01mRead
HR513doc 00514Pump3.MaxContinousTimeLongest continuous run, last 30 days.UINT16minRead
HR514doc 00515Pump3.TotalPoweredTimeUINT32ABCDminRead
HR516doc 00517Pump3.OperationTimeUINT32ABCDminRead
HR518doc 00519Pump3.OperationTimeTripCounterUINT32ABCDminRead
HR520doc 00521Pump3.NumberOfStartsUINT32ABCDRead
HR522doc 00523Pump3.NumberOfStartsTripCounterUINT32ABCDRead
HR524doc 00525Pump3.AlarmCodeGrundfos alarm code (manual section 14.2).UINT16Read
HR525doc 00526Pump3.WarningCodeGrundfos warning code.UINT16Read
HR526doc 00527Pump3.OperatingModeUINT16Read0 = Auto (power-on default); 1 = Forced start; 2 = Forced stop
HR527doc 00528Pump3.AlarmsBITMAP16Readbit 0 = Phase sequence reversed; bit 1 = Overvoltage; bit 2 = Undervoltage; bit 3 = Overload; bit 4 = Blocked motor/pump; bit 6 = Motor temperature; bit 7 = Control electronics temperature; bit 8 = Temperature relay 1 (e.g. Klixon); bit 9 = Temperature relay 2 (e.g. thermistor); bit 10 = Verification error (ROM, FLASH); bit 12 = Sensor fault
HR528doc 00529Pump3.WarningsBITMAP16Readbit 0 = Phase sequence reversed; bit 1 = Overvoltage; bit 2 = Undervoltage; bit 3 = Overload; bit 4 = Blocked motor/pump; bit 6 = Motor temperature; bit 7 = Control electronics temperature; bit 8 = Temperature relay 1 (e.g. Klixon); bit 9 = Temperature relay 2 (e.g. thermistor); bit 10 = Verification error (ROM, FLASH); bit 12 = Sensor fault
HR550doc 00551Pump4.MotorTemperatureIn 0.01 K (kelvin).UINT16× 0.01KRead
HR551doc 00552Pump4.ElectronicTemperatureIn 0.01 K (kelvin).UINT16× 0.01KRead
HR552doc 00553Pump4.AverageLineVoltageUINT16× 0.1VRead
HR553doc 00554Pump4.AverageLineCurrentUINT16× 0.1ARead
HR554doc 00555Pump4.AverageLineCurrentLatestCurrent during the last run.UINT16× 0.1ARead
HR555doc 00556Pump4.LineFrequencyUINT16× 0.1HzRead
HR556doc 00557Pump4.PhaseSequenceBoolean phase-sequence state.UINT16Read
HR557doc 00558Pump4.CosPhiUINT16× 0.01Read
HR558doc 00559Pump4.PowerUINT16WRead
HR559doc 00560Pump4.EnergyTripCounterUINT32ABCDkWhRead
HR561doc 00562Pump4.WaterLevelUINT16× 0.01mRead
HR562doc 00563Pump4.WaterLevelMaxUINT16× 0.01mRead
HR563doc 00564Pump4.MaxContinousTimeLongest continuous run, last 30 days.UINT16minRead
HR564doc 00565Pump4.TotalPoweredTimeUINT32ABCDminRead
HR566doc 00567Pump4.OperationTimeUINT32ABCDminRead
HR568doc 00569Pump4.OperationTimeTripCounterUINT32ABCDminRead
HR570doc 00571Pump4.NumberOfStartsUINT32ABCDRead
HR572doc 00573Pump4.NumberOfStartsTripCounterUINT32ABCDRead
HR574doc 00575Pump4.AlarmCodeGrundfos alarm code (manual section 14.2).UINT16Read
HR575doc 00576Pump4.WarningCodeGrundfos warning code.UINT16Read
HR576doc 00577Pump4.OperatingModeUINT16Read0 = Auto (power-on default); 1 = Forced start; 2 = Forced stop
HR577doc 00578Pump4.AlarmsBITMAP16Readbit 0 = Phase sequence reversed; bit 1 = Overvoltage; bit 2 = Undervoltage; bit 3 = Overload; bit 4 = Blocked motor/pump; bit 6 = Motor temperature; bit 7 = Control electronics temperature; bit 8 = Temperature relay 1 (e.g. Klixon); bit 9 = Temperature relay 2 (e.g. thermistor); bit 10 = Verification error (ROM, FLASH); bit 12 = Sensor fault
HR578doc 00579Pump4.WarningsBITMAP16Readbit 0 = Phase sequence reversed; bit 1 = Overvoltage; bit 2 = Undervoltage; bit 3 = Overload; bit 4 = Blocked motor/pump; bit 6 = Motor temperature; bit 7 = Control electronics temperature; bit 8 = Temperature relay 1 (e.g. Klixon); bit 9 = Temperature relay 2 (e.g. thermistor); bit 10 = Verification error (ROM, FLASH); bit 12 = Sensor fault

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)

What Modbus registers does the Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus) have?

This map lists 169 registers: 169 holding registers. 28 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual says registers numbered X are addressed in telegrams as X - 1 (00104 is sent as 103). Pump n's block starts at 00401 + 50 x (n-1).

What byte order does the Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)?

Start with HR 230 PitPumpsRunning (Pumps running bits); HR 231 PitPumpsAlarm (Pumps in alarm bits); HR 234 MainStatus (Warning / alarm / manual summary); HR 300 WaterLevel (Pit water level); HR 100 PitControl (Reset and pump-down commands); HR 403 Pump1.AverageLineCurrent (Pump 1 current); HR 427 Pump1.Alarms (Pump 1 alarm bits).

How do I enable Modbus control of the Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)?

Set the CIU 202 address with the hex rotary switches and the speed and parity with the DIP switches; no setting is needed in the pumps. Write the pit levels only in the mode selected by PitMode (00203).

Where is the official Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus) Modbus documentation?

The source is Modbus for SEG AUTOADAPT - CIU 202 Modbus RTU, CIU 262 3G/4G Cellular, CIU 502 Ethernet for Modbus TCP - Functional profile and user manual (96846341 0119), revision 2019-01, published free by Grundfos at https://api.grundfos.com/literature/Grundfosliterature-6012945.pdf.