Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU) Modbus register map
Updated 17 November 2026
Ecoforest's geothermal and air-source heat pumps expose the 'API HP Client' list over Modbus RTU on the BMS2 RS-485 port. Every value is a single 16-bit holding register with a fixed gain. This map covers status, alarms, compressor counters, humidity, service powers and the read/write BUS control and setpoint registers; temperature and pressure readings are left out because the manual does not state their sign.
This page lists 110 Modbus registers for the Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU) — 54 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Ecoforest’s own free documentation (linked below) and checked against it.
- Manufacturer
- Ecoforest
- Model
- ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)
- Equipment type
- Heat pump
- Registers
- 110 (54 writable)
- Transport
- Modbus RTU
- Default unit ID
- 17
- Default serial
- 19200 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Firmware
- Heat pump software AWD24 / WWD24 / WWC24 and later; API HP24_V01.02
- Also known as
- ecoGEO, ecoGEO B&C, ecoGEO HP, ecoAIR, AWD24, WWD24, WWC24, API HP24_V01.02
Integration notes: Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)
Enable BUS control in the installer menu, connect to BMS2 at 19200 baud, no parity, 2 stop bits, address 17, and poll the status and alarm registers 2030-2073 with function 03. Write 2700 to switch the heat pump and the 2705-2715 BUS-control flags before writing setpoints 2720-2759.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2045 | Heat pump status | UINT16 | Heat pump on/off/emergency | Read |
| HR 2065 | Alarm level | UINT16 | Alarm level | Read |
| HR 2066 | Lock alarm code | UINT16 | Lock alarm code | Read |
| HR 2030 | DHW production mode status | UINT16 | DHW production status | Read |
| HR 2700 | Heat pump status command | UINT16 | Switch heat pump | Read/write |
| HR 2705 | DHW BUS control | UINT16 | DHW setpoint by BUS flag | Read/write |
| HR 2720 | DHW setpoint | UINT16 | DHW setpoint by BUS | Read/write |
Enable Modbus control & writes
Installer menu > Installation > Remote control > BUS Control > enable. Check the BMS2 port settings (protocol 'MB Extended') in the same Remote control submenu. On the source manager BUS control is always on.
Byte order & addressing
- All values are single 16-bit registers with a fixed gain (0.1 for temperatures, pressures, humidity and setpoints).
- Counters over 999 are split: value = high part x 1000 + low part (2103/2104, 2105/2106).
- BUS setpoints are clamped to their ranges and only apply when the matching BUS-control flag is set; the final setpoints in 2150-2164 show the result (not mapped here because their sign is not stated).
- Date/time writes need the matching confirmation register (2695-2699) set to 1.
Network setup
- RS-485 on the BMS2 port, 3-wire shielded twisted pair (Tx/Rx-, Tx/Rx+, GND).
- Defaults: 19200 baud, no parity, 2 stop bits; address 17 for a heat pump, 15 supervisor, 14 source manager.
- On ecoAIR outdoor units BMS2 links to the indoor unit, so an optional RS-485 card on the BMS port is needed for BUS access.
- Supported functions: 03, 06, 16.
Watch out for
- ecoAIR outdoor units serve this list only when configured as block slave or stand-alone.
- Check the API version shown in the user menu (Information) matches HP24_Client; older software uses a different list.
Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2000 | Year (system) | UINT16 | Read | |||||
| HR | 2001 | Month (system) | UINT16 | Read | |||||
| HR | 2002 | Day (system) | UINT16 | Read | |||||
| HR | 2003 | Hour (system) | UINT16 | Read | |||||
| HR | 2004 | Minute (system) | UINT16 | Read | |||||
| HR | 2005 | Software platform | UINT16 | Read | 7 = ESO22; 12 = AWD24; 13 = WWD24; 14 = WWC24; 15 = ESO24; 16 = ESB24 | ||||
| HR | 2006 | Product range | UINT16 | Read | 1 = HP; 2 = PS; 3 = EM; 4 = SM | ||||
| HR | 2026 | Device role | UINT16 | Read | 0 = None; 1 = Individual master (IDU) / stand-alone; 2 = ecoGEO block master; 3 = Block slave; 4 = Supervisor; 5 = Individual slave; 6 = ecoAIR block master | ||||
| HR | 2030 | DHW production mode status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2031 | Heating production mode status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2032 | Active cooling production mode status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2033 | Passive cooling production mode status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2034 | Pool production mode status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2035 | Anti-freeze production mode status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2036 | Dryfloor production mode status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2044 | Operation program | UINT16 | Read | 0 = Winter; 1 = Summer; 2 = Combined | ||||
| HR | 2045 | Heat pump status | UINT16 | Read | 0 = Off; 1 = On; 2 = Emergency | ||||
| HR | 2046 | Integrated auxiliary heater status (Aux 1) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2047 | Generic external auxiliary heater status (Aux 2) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2048 | DHW auxiliary heater status (Aux 3) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2049 | Buffer auxiliary heater status (Aux 4) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2050 | Generic external auxiliary chiller status (Aux 5) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2055 | DHW recirculation status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2056 | Group 1 status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2057 | Group 2 status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2058 | Group 3 status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2059 | Group 4 status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2060 | Group 5 status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 2065 | Alarm level | Most serious alarm level present. | UINT16 | Read | 0 = No alarm; 1 = Active alarm; 2 = Active alarm + recurrence; 3 = Recurrent alarm; 4 = Long time alarm; 5 = Lock-down due to alarm | |||
| HR | 2066 | Lock alarm code | Alarm code from the manual's Appendix 1 alarm list. | UINT16 | Read | ||||
| HR | 2067 | Long time alarm code | Alarm code from the manual's Appendix 1 alarm list. | UINT16 | Read | ||||
| HR | 2068 | Recurrence alarm code | Alarm code from the manual's Appendix 1 alarm list. | UINT16 | Read | ||||
| HR | 2069 | Active alarm code 1 | Alarm code from the manual's Appendix 1 alarm list. | UINT16 | Read | ||||
| HR | 2070 | Active alarm code 2 | Alarm code from the manual's Appendix 1 alarm list. | UINT16 | Read | ||||
| HR | 2071 | Active alarm code 3 | Alarm code from the manual's Appendix 1 alarm list. | UINT16 | Read | ||||
| HR | 2072 | Active alarm code 4 | Alarm code from the manual's Appendix 1 alarm list. | UINT16 | Read | ||||
| HR | 2073 | Active alarm code 5 | Alarm code from the manual's Appendix 1 alarm list. | UINT16 | Read | ||||
| HR | 2074 | Reset alarm by BUS | Write 1 to reset alarms. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2103 | Compressor starts (high part) | Starts = high x 1000 + low. | UINT16 | Read | ||||
| HR | 2104 | Compressor starts (low part) | UINT16 | Read | |||||
| HR | 2105 | Compressor operating hours (high part) | Hours = high x 1000 + low. | UINT16 | h | Read | |||
| HR | 2106 | Compressor operating hours (low part) | UINT16 | h | Read | ||||
| HR | 2170 | Zone 1 humidity | UINT16 | × 0.1 | % | Read | |||
| HR | 2171 | Zone 2 humidity | UINT16 | × 0.1 | % | Read | |||
| HR | 2172 | Zone 3 humidity | UINT16 | × 0.1 | % | Read | |||
| HR | 2173 | Zone 4 humidity | UINT16 | × 0.1 | % | Read | |||
| HR | 2174 | Zone 5 humidity | UINT16 | × 0.1 | % | Read | |||
| HR | 2185 | Instantaneous power units | Sets the gain of 2186-2194: W gain 1, kW or MW gain 0.1. | UINT16 | Read | 10 = W; 20 = kW; 30 = MW | |||
| HR | 2186 | Total heating power | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2187 | Heating service power | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2188 | DHW service power | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2189 | Pool service power | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2190 | Total cooling power | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2191 | Active cooling service power | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2192 | Passive cooling service power | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2193 | Total electric consumption | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2194 | Electric consumption in surplus mode | Raw value; unit and gain set by register 2185. | UINT16 | Read | ||||
| HR | 2690 | New year (last digits) | Then confirm with 2695. | UINT16 | Read/write | ||||
| HR | 2691 | New month | UINT16 | Read/write | |||||
| HR | 2692 | New day | UINT16 | Read/write | |||||
| HR | 2693 | New hour | UINT16 | Read/write | |||||
| HR | 2694 | New minute | UINT16 | Read/write | |||||
| HR | 2695 | Year replacement confirmation | Write 1 to apply the new value. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2696 | Month replacement confirmation | Write 1 to apply the new value. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2697 | Day replacement confirmation | Write 1 to apply the new value. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2698 | Hour replacement confirmation | Write 1 to apply the new value. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2699 | Minute replacement confirmation | Write 1 to apply the new value. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2700 | Heat pump status command | UINT16 | Read/write | 1 = Off; 2 = On; 3 = Emergency | ||||
| HR | 2701 | Operation program command | UINT16 | Read/write | 1 = Winter; 2 = Summer; 3 = Combined | ||||
| HR | 2705 | DHW BUS control | UINT16 | Read/write | 0 = No setpoint/offset by BUS; 1 = Setpoint/offset by BUS | ||||
| HR | 2706 | DHW recirculation BUS control | UINT16 | Read/write | 0 = No setpoint/offset by BUS; 1 = Setpoint/offset by BUS | ||||
| HR | 2707 | Pool BUS control | With pool probe: setpoint/offset by BUS; without probe: 1 = demand by BUS. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2708 | Group 1 demand | UINT16 | Read/write | 0 = No demand by BUS; 1 = Heating demand and setpoint by BUS; 2 = Cooling demand and setpoint by BUS; 11 = Heating demand by BUS, setpoint from HP; 12 = Cooling demand by BUS, setpoint from HP | ||||
| HR | 2709 | Group 2 demand | UINT16 | Read/write | 0 = No demand by BUS; 1 = Heating demand and setpoint by BUS; 2 = Cooling demand and setpoint by BUS; 11 = Heating demand by BUS, setpoint from HP; 12 = Cooling demand by BUS, setpoint from HP | ||||
| HR | 2710 | Group 3 demand | UINT16 | Read/write | 0 = No demand by BUS; 1 = Heating demand and setpoint by BUS; 2 = Cooling demand and setpoint by BUS; 11 = Heating demand by BUS, setpoint from HP; 12 = Cooling demand by BUS, setpoint from HP | ||||
| HR | 2711 | Group 4 demand | UINT16 | Read/write | 0 = No demand by BUS; 1 = Heating demand and setpoint by BUS; 2 = Cooling demand and setpoint by BUS; 11 = Heating demand by BUS, setpoint from HP; 12 = Cooling demand by BUS, setpoint from HP | ||||
| HR | 2712 | Group 5 demand | UINT16 | Read/write | 0 = No demand by BUS; 1 = Heating demand and setpoint by BUS; 2 = Cooling demand and setpoint by BUS; 11 = Heating demand by BUS, setpoint from HP; 12 = Cooling demand by BUS, setpoint from HP | ||||
| HR | 2713 | Heating buffer BUS control | UINT16 | Read/write | 0 = No setpoint/offset by BUS; 1 = Setpoint/offset by BUS | ||||
| HR | 2714 | Cooling buffer BUS control | UINT16 | Read/write | 0 = No setpoint/offset by BUS; 1 = Setpoint/offset by BUS | ||||
| HR | 2715 | HTR BUS control | UINT16 | Read/write | 0 = No setpoint by BUS; 1 = Setpoint by BUS (fixed 3 °C offset) | ||||
| HR | 2720 | DHW setpoint | BUS value, range 10.0-82.0 °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2721 | DHW recirculation setpoint | BUS value, range 0.0-99.9 °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2722 | Buffer tank heating setpoint | BUS value, range 20.0-T_lim °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2724 | HTR setpoint by BUS | BUS value, range 0.0-82.0 °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2725 | Offset DHW | BUS value, range 2.0-25.0 °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2726 | Offset DHW recirculation | BUS value, range 0.0-99.9 °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2727 | Offset heating buffer tank | BUS value, range 2.0-10.0 °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2728 | Offset cooling buffer tank | BUS value, range 2.0-10.0 °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2729 | HTR setpoint BUS | BUS value, range 0.5-20.0 °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2730 | Heating group 1 setpoint | BUS value, range 20.0-T_lim °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2732 | Heating group 2 setpoint | BUS value, range 20.0-T_lim °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2734 | Heating group 3 setpoint | BUS value, range 20.0-T_lim °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2736 | Heating group 4 setpoint | BUS value, range 20.0-T_lim °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2738 | Heating group 5 setpoint | BUS value, range 20.0-T_lim °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2740 | Pool setpoint | BUS value, range 20.0-T_lim °C; used only when BUS control is enabled. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2750 | Zone 1 BUS terminal on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2751 | Zone 2 BUS terminal on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2752 | Zone 3 BUS terminal on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2753 | Zone 4 BUS terminal on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2754 | Zone 5 BUS terminal on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2755 | Zone 1 ambient temperature setpoint | Range 5.0-35.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2756 | Zone 2 ambient temperature setpoint | Range 5.0-35.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2757 | Zone 3 ambient temperature setpoint | Range 5.0-35.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2758 | Zone 4 ambient temperature setpoint | Range 5.0-35.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2759 | Zone 5 ambient temperature setpoint | Range 5.0-35.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2765 | Maximum compressor reference | Caps compressor modulation, 0-100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 2775 | Surplus control enabled by BUS | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2776 | Maximum consumption enabled by BUS | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2777 | Surplus regulation setpoint | Range -99.9 to 99.9 kW. | INT16 | × 0.1 | kW | Read/write | ||
| HR | 2778 | Maximum consumption setpoint | Range -99.9 to 99.9 kW. | INT16 | × 0.1 | kW | Read/write |
Notes on this map
- Ecoforest does not appear to host this manual publicly; the link is an unaltered copy of the Ecoforest manual on the TapHome integration site.
- The manual calls every BUS register a 16-bit analog value but never states whether it is signed, and prints no range for the temperature, pressure, DT, superheat and final-setpoint readings. Those readings (2080-2102, 2130-2144, 2150-2164) are therefore left out, as are the cooling setpoints 2723 and 2731-2739 whose lower limit is only given as T_lim. Writable setpoints whose printed range is entirely positive are listed as UINT16 (identical decoding inside that range); only 2777/2778, printed as -99.9 to 99.9 kW, are INT16. Humidity 2170-2174 is listed as UINT16 because relative humidity cannot be negative.
- Instantaneous powers 2186-2194 are left unscaled because their gain depends on register 2185 (W = 1, kW or MW = 0.1).
- Left out: the energy-meter block 2200-2461 (gain depends on per-period unit registers) and e-MANAGER power readings 2501-2508, model-code digit registers 2010-2023 and software version letters 2007-2009, and the duplicate 'Zone n temperature' entries at 2175-2179 whose meaning differs from 2140-2144 but is not explained.
- The heat pump status read (2045: 0 off, 1 on, 2 emergency) and the command register (2700: 1 off, 2 on, 3 emergency) use different codes; operation program likewise (2044 0-2, 2701 1-3).
- Software older than AWD24 / WWD24 / WWC24 is not compatible with this register list.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)
What Modbus registers does the Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU) have?
This map lists 110 registers: 110 holding registers. 54 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in decimal and go on the wire unchanged: the manual's read example for outdoor temperature (address 2080) sends start register 08 20 hex, and the write example for heat pump status (2700) sends 0A 8C hex.
What are the minimum Modbus registers to integrate the Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)?
Start with HR 2045 Heat pump status (Heat pump on/off/emergency); HR 2065 Alarm level (Alarm level); HR 2066 Lock alarm code (Lock alarm code); HR 2030 DHW production mode status (DHW production status); HR 2700 Heat pump status command (Switch heat pump); HR 2705 DHW BUS control (DHW setpoint by BUS flag); HR 2720 DHW setpoint (DHW setpoint by BUS).
How do I enable Modbus control of the Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)?
Installer menu > Installation > Remote control > BUS Control > enable. Check the BMS2 port settings (protocol 'MB Extended') in the same Remote control submenu. On the source manager BUS control is always on.
Where is the official Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU) Modbus documentation?
The source is APIs BUS Client Manual (API HP Client manual) (V03), revision 2024-12. Ecoforest doesn't publish it on its own website, so this map was re-typed from a free copy at https://taphome.com/compatibility/devices/ecoforest-hp24/manufacturer/manual-api-bus-client.pdf. It may be an older revision, so check it against the live unit.
Other pumps register maps
- Pump protection / monitoring module (Sensor)
Grundfos IO 113 pump protection module (Modbus RTU)
Grundfos IO 113 interface module for wastewater and sewage pumps (with or without the SM 113 sensor board) set to Modbus with DIP switch 9; document edition 1.7, January 2015.
Also known as: IO113, IO 113 with SM 113, 98288208 - Heat pump (packaged wall-mount / classroom unit)
Marvair MAH heat pump and VAH/VDH Vanguard control board (Modbus RTU)
Marvair MAH1020H-1060H and MAH2024H-2060H wall-mount heat pumps (I&O manual rev. 6); the GAH1024-1060 gas-heat AC manual (rev. 5) and the VAH/VDH Vanguard classroom unit appendices (08/2026) print the same table.
Also known as: MAH1020H, MAH1024H, MAH1030H, MAH1036H, MAH1042H, MAH1048H, MAH1060H, MAH2024H, MAH2030H, MAH2036H, MAH2042H, MAH2048H, MAH2060H, Vanguard VAH, Vanguard VDH, VAH2030, VDH2060, GAH1024, GAH1030, GAH1036, GAH1042, GAH1048, GAH1060, Marvair GAH, Scholar 2 VAH/VDH, Scholar QR VAH/VDH - Heat pump Modbus interface
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
RTD-LT/CA on the P1/P2 bus of Daikin Altherma Split LT CA hydroboxes (heating only and heating/cooling), with an EKRUCAL1 as main controller; all modes except Sequencer. Instructions 22570-2.09.12.
Also known as: RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA - Pump (pressure-boosting pump)
Wilo Isar MODH1-E with CIF module Modbus RTU
Wilo Isar MODH1-E pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Isar MODH1-E - Pump (high-efficiency inline circulator)
Wilo Yonos GIGA2.0 with CIF module Modbus RTU
Wilo Yonos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Yonos GIGA2.0-I, Yonos GIGA2.0-D, Wilo-Yonos GIGA2.0 - Heat pump (air-to-water) Modbus interface
Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)
Daikin HomeHub EKRHH in use case 3 (Modbus for Daikin Altherma air-to-water heat pumps) and use case 4 (Modbus smart-grid control of air-to-air heat pumps), installer reference guide 4P744838-1E (2026.01).
Also known as: EKRHH, Daikin HomeHub, 4P744838-1E, Daikin Altherma 3 Modbus, Altherma Smart Grid Modbus
All pumps Modbus register maps →
Source: APIs BUS Client Manual (API HP Client manual) · V03 · rev. 2024-12 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.