- Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Pump (refrigerant pumping unit for Liebert XD rack cooling) · Modbus register map
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus register map
Updated 19 November 2026
The Liebert XDP takes building chilled water and pumps refrigerant to Liebert XD cooling modules. With a Liebert IntelliSlot Modbus card its iCOM controller exposes pump states, supply refrigerant and chilled-water temperatures, chilled-water valve position, dew point, system on/off and status, per-XD-system fan states, capacity and remote sensor values, and alarm bits.
This page lists 242 Modbus registers for the Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus) — 77 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vertiv
- Model
- Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
- Registers
- 242 (77 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Liebert XDP, XDP, Liebert XD pumping unit
Integration notes: Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Read 30385-30421 for pumps, refrigerant and chilled-water temperatures and status; write 40422 to switch the XDP on/off. Per-XD-system data starts at 30444 / 40445 for system 1.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 421 | System Information: System On/Off Control | UINT16 | System on/off control | Read/write |
| IR 391 | System Information: System Operating State | UINT16 | System operating state | Read |
| IR 390 | System Information: System Status | UINT16 | System status | Read |
| IR 386 | Supply Refrigerant Temperature | INT16 | Supply refrigerant temperature | Read |
| IR 388 | Supply Chilled Water Temperature | INT16 | Supply chilled water temperature | Read |
| IR 384 | Pump 1 State | UINT16 | Pump 1 state | Read |
| IR 1709 | Chilled Water Valve Open Position | UINT16 | Chilled water valve open position | Read |
| IR 448 | XD System 1: Cooling Capacity | UINT16 | XD system 1 cooling capacity | Read |
Enable Modbus control & writes
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
Byte order & addressing
- Modicon numbering: subtract 40001 / 30001 / 10001 for the wire address.
- The guide prints the XD-system event/fan blocks for systems 1, 2 and 20, and remote sensors 1, 2 and 4 for every system; unprinted blocks are not listed here.
Network setup
- RS-485 (2-wire) RTU settings for the IntelliSlot 485 card: 9600, 19200 or 38400 baud, 8 data bits, no parity, 1 stop bit.
- Each unit needs a unique Modbus slave address on the RS-485 line.
- For Modbus IP, use the IntelliSlot Modbus IP / BACnet IP card listed for the unit's controller in the guide's compatibility table.
Watch out for
- In the guide, the 'XD System 1 Temperature Sensor 2' heading repeats the secondary-fan points 31032 / 41033 instead of a sensor register, so system 1 has no sensor-2 entry here; 31032 / 41033 are listed as system 1 secondary fan points.
- Hot/cold aisle thresholds (40459-40465 etc.) are printed without a scale.
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0doc 10001 | Pump 1 Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 1doc 10002 | Pump 2 Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 2doc 10003 | System Events: Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 3doc 10004 | System Events: System Condensation Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 4doc 10005 | System Events: Customer Input 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 5doc 10006 | Supply Chilled Water Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 6doc 10007 | Supply Chilled Water Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 7doc 10008 | Supply Refrigerant Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 8doc 10009 | Supply Refrigerant Under Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 9doc 10010 | Supply Refrigerant Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 10doc 10011 | External Air: Ext Air Sensor A Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 11doc 10012 | External Air: Ext Air Sensor A Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 12doc 10013 | External Air: Ext Air Sensor A Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 13doc 10014 | External Air: Ext Air Sensor B Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 14doc 10015 | External Air: Ext Air Sensor B Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 15doc 10016 | External Air: Ext Air Sensor B Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 16doc 10017 | External Air: Ext Dew Point Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 17doc 10018 | Chilled Water Control Valve Position | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 18doc 10019 | System Events: Shutdown - Loss Of Power | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 19doc 10020 | Pump Short Cycle | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 20doc 10021 | System Events: Water Under Floor | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 21doc 10022 | System Events: Smoke Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 22doc 10023 | System Events: Service Required | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 29doc 10030 | Pump Hours 1: Pump Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 35doc 10036 | Pump Hours 2: Pump Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 41doc 10042 | XD System 1: Ext System Condensation Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 42doc 10043 | XD System 1: Ext Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 43doc 10044 | XD System 1: Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 44doc 10045 | XD System 1: Ext Remote Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 45doc 10046 | XD System 1: Hot Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 46doc 10047 | XD System 1: Cold Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 52doc 10053 | XD System 2: Ext System Condensation Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 53doc 10054 | XD System 2: Ext Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 54doc 10055 | XD System 2: Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 55doc 10056 | XD System 2: Ext Remote Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 56doc 10057 | XD System 2: Hot Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 57doc 10058 | XD System 2: Cold Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 250doc 10251 | XD System 20: Ext System Condensation Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 251doc 10252 | XD System 20: Ext Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 252doc 10253 | XD System 20: Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 253doc 10254 | XD System 20: Ext Remote Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 254doc 10255 | XD System 20: Hot Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 255doc 10256 | XD System 20: Cold Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 261doc 10262 | System Events: Unit Communication Lost | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 262doc 10263 | System Events: RAM Battery Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 263doc 10264 | System Events: Master Unit Communication Lost | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 264doc 10265 | System Events: Remote Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 265doc 10266 | System Events: Unit Code Missing | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 271doc 10272 | Messages: Unit On | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 272doc 10273 | Messages: Unit Off | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 273doc 10274 | Messages: Unit Standby | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 274doc 10275 | Messages: Unit Partial Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 275doc 10276 | Messages: Unit Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 276doc 10277 | Messages: Maintenance Due | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 277doc 10278 | Messages: Maintenance Completed | BIT | Read | 0 = Inactive; 1 = Active | ||||
| IR | 384doc 30385 | Pump 1 State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 385doc 30386 | Pump 2 State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 386doc 30387 | Supply Refrigerant Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 388doc 30389 | Supply Chilled Water Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 390doc 30391 | System Information: System Status | UINT16 | Read | 1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation | ||||
| IR | 391doc 30392 | System Information: System Operating State | UINT16 | Read | 0 = off; 1 = on; 2 = standby | ||||
| IR | 392doc 30393 | External Air: Ext Air Sensor A Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 394doc 30395 | External Air: Ext Air Sensor A Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 395doc 30396 | External Air: Ext Air Sensor A Dew Point Temp | INT16 | × 0.1 | deg C | Read | |||
| IR | 397doc 30398 | External Air: Ext Air Sensor B Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 399doc 30400 | External Air: Ext Air Sensor B Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 400doc 30401 | External Air: Ext Air Sensor B Dew Point Temp | INT16 | × 0.1 | deg C | Read | |||
| IR | 414doc 30415 | External Air: Dew Point Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 417doc 30418 | System Information: System Control Mode | UINT16 | Read | 0 = Internal (Auto); 1 = External (Manual) | ||||
| IR | 418doc 30419 | System Information: Maintenance Ramp | UINT16 | % | Read | ||||
| IR | 419doc 30420 | System Information: Calculated Next Maintenance Month | UINT16 | Read | |||||
| IR | 420doc 30421 | System Information: Calculated Next Maintenance Year | UINT16 | Read | |||||
| IR | 443doc 30444 | XD System 1: Communication Status | UINT16 | Read | 0 = Connected; 1 = Not Connected | ||||
| IR | 445doc 30446 | XD System 1: Primary Fan Group State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 448doc 30449 | XD System 1: Cooling Capacity | UINT16 | % | Read | ||||
| IR | 449doc 30450 | XD System 1: Cooling Capacity | UINT16 | kW | Read | ||||
| IR | 471doc 30472 | XD System 2: Communication Status | UINT16 | Read | 0 = Connected; 1 = Not Connected | ||||
| IR | 473doc 30474 | XD System 2: Primary Fan Group State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 476doc 30477 | XD System 2: Cooling Capacity | UINT16 | % | Read | ||||
| IR | 477doc 30478 | XD System 2: Cooling Capacity | UINT16 | kW | Read | ||||
| IR | 975doc 30976 | XD System 20: Communication Status | UINT16 | Read | 0 = Connected; 1 = Not Connected | ||||
| IR | 977doc 30978 | XD System 20: Primary Fan Group State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 980doc 30981 | XD System 20: Cooling Capacity | UINT16 | % | Read | ||||
| IR | 981doc 30982 | XD System 20: Cooling Capacity | UINT16 | kW | Read | ||||
| IR | 1003doc 31004 | XD System 1 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1024doc 31025 | XD System 1 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1031doc 31032 | XD System 1 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1038doc 31039 | XD System 2 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1045doc 31046 | XD System 2 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1059doc 31060 | XD System 2 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1066doc 31067 | XD System 2 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1073doc 31074 | XD System 3 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1080doc 31081 | XD System 3 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1094doc 31095 | XD System 3 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1101doc 31102 | XD System 3 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1108doc 31109 | XD System 4 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1115doc 31116 | XD System 4 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1129doc 31130 | XD System 4 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1136doc 31137 | XD System 4 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1143doc 31144 | XD System 5 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1150doc 31151 | XD System 5 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1164doc 31165 | XD System 5 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1171doc 31172 | XD System 5 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1178doc 31179 | XD System 6 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1185doc 31186 | XD System 6 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1199doc 31200 | XD System 6 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1206doc 31207 | XD System 6 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1213doc 31214 | XD System 7 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1220doc 31221 | XD System 7 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1234doc 31235 | XD System 7 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1241doc 31242 | XD System 7 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1248doc 31249 | XD System 8 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1255doc 31256 | XD System 8 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1269doc 31270 | XD System 8 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1276doc 31277 | XD System 8 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1283doc 31284 | XD System 9 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1290doc 31291 | XD System 9 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1304doc 31305 | XD System 9 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1311doc 31312 | XD System 9 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1318doc 31319 | XD System 10 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1325doc 31326 | XD System 10 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1339doc 31340 | XD System 10 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1346doc 31347 | XD System 10 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1353doc 31354 | XD System 11 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1360doc 31361 | XD System 11 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1374doc 31375 | XD System 11 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1381doc 31382 | XD System 11 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1388doc 31389 | XD System 12 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1395doc 31396 | XD System 12 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1409doc 31410 | XD System 12 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1416doc 31417 | XD System 12 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1423doc 31424 | XD System 13 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1430doc 31431 | XD System 13 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1444doc 31445 | XD System 13 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1451doc 31452 | XD System 13 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1458doc 31459 | XD System 14 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1465doc 31466 | XD System 14 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1479doc 31480 | XD System 14 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1486doc 31487 | XD System 14 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1493doc 31494 | XD System 15 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1500doc 31501 | XD System 15 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1514doc 31515 | XD System 15 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1521doc 31522 | XD System 15 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1528doc 31529 | XD System 16 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1535doc 31536 | XD System 16 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1549doc 31550 | XD System 16 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1556doc 31557 | XD System 16 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1563doc 31564 | XD System 17 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1570doc 31571 | XD System 17 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1584doc 31585 | XD System 17 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1591doc 31592 | XD System 17 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1598doc 31599 | XD System 18 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1605doc 31606 | XD System 18 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1619doc 31620 | XD System 18 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1626doc 31627 | XD System 18 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1633doc 31634 | XD System 19 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1640doc 31641 | XD System 19 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1654doc 31655 | XD System 19 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1661doc 31662 | XD System 19 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1668doc 31669 | XD System 20 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1675doc 31676 | XD System 20 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1689doc 31690 | XD System 20 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1696doc 31697 | XD System 20 Secondary Fans: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1703doc 31704 | System Information: System Operating State Reason | UINT16 | Read | 0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display | ||||
| IR | 1709doc 31710 | Chilled Water Valve Open Position | UINT16 | Read | |||||
| HR | 402doc 40403 | External Air: Minimum Room Temperature Set Point | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 404doc 40405 | External Air: Ext Air Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 406doc 40407 | External Air: Ext Air Under Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 408doc 40409 | External Air: Ext Dew Point Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 410doc 40411 | Refrigerant: Supply Refrig Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 412doc 40413 | Supply Chilled Water Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 416doc 40417 | System Information: Auto Restart Delay | UINT16 | sec | Read/write | ||||
| HR | 421doc 40422 | System Information: System On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 429doc 40430 | Pump Hours 1: Pump Hours | UINT16 | hr | Read/write | ||||
| HR | 430doc 40431 | Pump Hours 1: Pump Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 436doc 40437 | Pump Hours 2: Pump Hours | UINT16 | hr | Read/write | ||||
| HR | 437doc 40438 | Pump Hours 2: Pump Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 444doc 40445 | XD System 1: Fan On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 446doc 40447 | XD System 1: Fan Button Control | UINT16 | Read/write | 0 = enabled; 1 = disabled | ||||
| HR | 447doc 40448 | XD System 1: Visual ID Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 450doc 40451 | XD System 1: Ext System Condensation Detected - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 451doc 40452 | XD System 1: Ext System Condensation Detected - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 452doc 40453 | XD System 1: Ext Fan Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 453doc 40454 | XD System 1: Ext Fan Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 454doc 40455 | XD System 1: Sensor Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 455doc 40456 | XD System 1: Sensor Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 456doc 40457 | XD System 1: Ext Remote Shutdown - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 457doc 40458 | XD System 1: Ext Remote Shutdown - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 458doc 40459 | XD System 1: Hot Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 460doc 40461 | XD System 1: Hot Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 462doc 40463 | XD System 1: Cold Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 464doc 40465 | XD System 1: Cold Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 472doc 40473 | XD System 2: Fan On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 474doc 40475 | XD System 2: Fan Button Control | UINT16 | Read/write | 0 = enabled; 1 = disabled | ||||
| HR | 475doc 40476 | XD System 2: Visual ID Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 478doc 40479 | XD System 2: Ext System Condensation Detected - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 479doc 40480 | XD System 2: Ext System Condensation Detected - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 480doc 40481 | XD System 2: Ext Fan Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 481doc 40482 | XD System 2: Ext Fan Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 482doc 40483 | XD System 2: Sensor Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 483doc 40484 | XD System 2: Sensor Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 484doc 40485 | XD System 2: Ext Remote Shutdown - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 485doc 40486 | XD System 2: Ext Remote Shutdown - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 486doc 40487 | XD System 2: Hot Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 488doc 40489 | XD System 2: Hot Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 490doc 40491 | XD System 2: Cold Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 492doc 40493 | XD System 2: Cold Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 976doc 40977 | XD System 20: Fan On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 978doc 40979 | XD System 20: Fan Button Control | UINT16 | Read/write | 0 = enabled; 1 = disabled | ||||
| HR | 979doc 40980 | XD System 20: Visual ID Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 982doc 40983 | XD System 20: Ext System Condensation Detected - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 983doc 40984 | XD System 20: Ext System Condensation Detected - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 984doc 40985 | XD System 20: Ext Fan Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 985doc 40986 | XD System 20: Ext Fan Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 986doc 40987 | XD System 20: Sensor Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 987doc 40988 | XD System 20: Sensor Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 988doc 40989 | XD System 20: Ext Remote Shutdown - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 989doc 40990 | XD System 20: Ext Remote Shutdown - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 990doc 40991 | XD System 20: Hot Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 992doc 40993 | XD System 20: Hot Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 994doc 40995 | XD System 20: Cold Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 996doc 40997 | XD System 20: Cold Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 1032doc 41033 | XD System 1 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1067doc 41068 | XD System 2 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1102doc 41103 | XD System 3 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1137doc 41138 | XD System 4 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1172doc 41173 | XD System 5 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1207doc 41208 | XD System 6 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1242doc 41243 | XD System 7 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1277doc 41278 | XD System 8 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1312doc 41313 | XD System 9 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1347doc 41348 | XD System 10 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1382doc 41383 | XD System 11 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1417doc 41418 | XD System 12 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1452doc 41453 | XD System 13 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1487doc 41488 | XD System 14 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1522doc 41523 | XD System 15 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1557doc 41558 | XD System 16 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1592doc 41593 | XD System 17 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1627doc 41628 | XD System 18 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1662doc 41663 | XD System 19 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1697doc 41698 | XD System 20 Secondary Fans: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual |
Notes on this map
- Source: Emerson Network Power / Liebert reference guide SL-28170 (Rev 9). Vertiv does not host this guide publicly; the linked copy is the unaltered PDF on the Contemporary Controls support site.
- Scale column: 'x / 10' means the raw value is tenths (scale 0.1); '-' or blank means no scaling. Some temperature setpoints are printed without a scale while similar points use x / 10; they are transcribed exactly as printed.
- Most temperatures exist twice: once in deg C and once in deg F at a different register. Only the deg C registers are listed here.
- Points that the guide lists with both an input register (3xxxx) and a holding register (4xxxx) are the writable settings; we list the holding register (read/write). The same value can also be read at the matching 3xxxx input register (same offset).
- Signedness is not stated in the guide. Temperature values are listed as INT16 (they can be below zero); everything else as UINT16.
- Points that take two registers (date/time and schedule start/stop times, 32-bit values) are left out because the guide does not state their word order.
- Event/alarm discrete inputs read 1 while the event is active ('Active on Alarm').
- The 'SFA' rows in the guide (reserved/special-function points) are left out.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
What Modbus registers does the Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus) have?
This map lists 242 registers: 55 discrete inputs, 110 input registers, 77 holding registers. 77 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.
What are the minimum Modbus registers to integrate the Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)?
Start with HR 421 System Information: System On/Off Control (System on/off control); IR 391 System Information: System Operating State (System operating state); IR 390 System Information: System Status (System status); IR 386 Supply Refrigerant Temperature (Supply refrigerant temperature); IR 388 Supply Chilled Water Temperature (Supply chilled water temperature); IR 384 Pump 1 State (Pump 1 state); IR 1709 Chilled Water Valve Open Position (Chilled water valve open position); IR 448 XD System 1: Cooling Capacity (XD system 1 cooling capacity).
How do I enable Modbus control of the Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)?
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
Where is the official Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus documentation?
The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.
More Vertiv Modbus register maps
- Sensor (battery monitoring system)
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Alber MPM-100 (firmware 1.20+) and BDS series (controller firmware 2.20+) battery monitors with BMDM software 4.10+, per protocol document SL-29417 Rev 7.05.
Also known as: Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417 - Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller
Other pumps register maps
- Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080 - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+ - Heat pump (water-source heat pump controller)
First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
First Co. / AE-Air water-source heat pumps (WSV and related series) with the factory DDC controller CB900, without hot-gas reheat (IOM8083D02 rev. A).
Also known as: CB900, CB900-1, CB900-2, IOM8083D02, WSV series DDC, First Co. WSHP DDC controller, AE-Air WSHP DDC - Pump (submersible grinder pump pit)
Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)
Up to four Grundfos SEG AUTOADAPT grinder pumps in one or more pits, connected to a CIU 202 (Modbus RTU), CIU 262 (cellular) or CIU 502 (Modbus TCP); functional profile 96846341 (2019-01).
Also known as: SEG AUTOADAPT, CIU 202, CIU 262, CIU 502, 96846341 - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Heat pump (air-to-water) Modbus interface
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Toshiba BMS-IFMB0UEW-E MB interface on ESTIA R410A 4 Series and 5 Series (WM type) and R32 1 Series (WM and AIO type) hydro units, user manual EEU-006 issued 31/05/2021.
Also known as: BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006
All pumps Modbus register maps →
Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.