Chiller (air-cooled chiller for data centres) · Modbus register map
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus register map
Updated 19 November 2026
The Liebert HPC is an air-cooled chiller family (with optional free cooling) for data-centre chilled-water loops. With a Liebert IntelliSlot Modbus card the iCOM controller is a Modbus slave. This map covers compressor states, head pressures and run hours for up to four compressors, condenser fan speeds, supply/return fluid temperatures and setpoints, free cooling, pumps, system on/off and status, and the alarm bits.
This page lists 151 Modbus registers for the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) — 30 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vertiv
- Model
- Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
- Equipment type
- Chiller (air-cooled chiller for data centres)
- Registers
- 151 (30 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- iCOM_SC31 / iCOM_SC100 (per the guide)
- Also known as
- Liebert HPC, HPC chiller, Liebert HPC iCOM
Integration notes: Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Read 30483-30511 for status, fluid temperatures and utilisation, and the discrete inputs for compressor, condenser, pump and system alarms. Write 40487 to switch the chiller on/off and 40424 for the supply fluid setpoint (tenths of deg C).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 486 | System Info: System On/Off Control | UINT16 | System on/off control | Read/write |
| IR 483 | System Info: System Operating State | UINT16 | System operating state | Read |
| IR 482 | System Info: System Status | UINT16 | System status | Read |
| IR 492 | System Operations: Supply Fluid Temperature | INT16 | Supply fluid temperature | Read |
| IR 490 | System Operations: Return Fluid Temperature | INT16 | Return fluid temperature | Read |
| HR 423 | Supply (Outlet) Fluid: Supply Fluid Temp Set Point 1 | INT16 | Supply fluid temperature setpoint 1 | Read/write |
| IR 504 | System Operations: Compressor Utilization | UINT16 | Compressor utilisation | Read |
| IR 505 | System Operations: Ambient Air Temperature | INT16 | Ambient air temperature | Read |
| HR 514 | System Event Acknowledge/Reset | UINT16 | Acknowledge / reset events | Read/write |
Enable Modbus control & writes
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
Byte order & addressing
- Modicon numbering: subtract 40001 / 30001 / 10001 for the wire address.
- The same point names repeat for compressors 1-4 and condensers 1-4; the register name here is prefixed with the group heading from the guide.
Network setup
- RS-485 (2-wire) RTU settings for the IntelliSlot 485 card: 9600, 19200 or 38400 baud, 8 data bits, no parity, 1 stop bit.
- Each unit needs a unique Modbus slave address on the RS-485 line.
- For Modbus IP, use the IntelliSlot Modbus IP / BACnet IP card listed for the unit's controller in the guide's compatibility table.
Watch out for
- Several fluid setpoints and alarm thresholds (e.g. 40426, 40430, 40434, 40615-40621) are printed without a scale, unlike setpoint 1 (40424, x / 10). They are listed as printed; check one against the unit display before writing.
- Discrete inputs 10033, 10214 and 10234 are printed as a second 'Compressor Low Suction Pressure' for the same compressor; transcribed as printed.
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0doc 10001 | Compressor Not Stopping | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 1doc 10002 | Compressor Superheat Over Threshold | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 11doc 10012 | Compressor 1: Compressor Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 12doc 10013 | Compressor 1: Compressor High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 13doc 10014 | Compressor 1: Compressor Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 14doc 10015 | Compressor 1: Compressor Thermal Overload | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 15doc 10016 | Compressor 1: Compressor Low Oil Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 17doc 10018 | Compressor 1: Compressor Loss of Differential Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 18doc 10019 | Compressor 1: Compressor Capacity Reduced | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 19doc 10020 | Compressor 1: Compressor Capacity Normal | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 20doc 10021 | Compressor 1: Compressor Contactor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 28doc 10029 | Compressor 2: Compressor Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 29doc 10030 | Compressor 2: Compressor High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 30doc 10031 | Compressor 2: Compressor Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 31doc 10032 | Compressor 2: Compressor Thermal Overload | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 32doc 10033 | Compressor 2: Compressor Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 34doc 10035 | Compressor 2: Compressor Loss of Differential Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 35doc 10036 | Compressor 2: Compressor Capacity Reduced | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 36doc 10037 | Compressor 2: Compressor Capacity Normal | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 37doc 10038 | Compressor 2: Compressor Contactor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 45doc 10046 | Condensers 1: Condenser Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 46doc 10047 | Condensers 1: Low Condenser Refrigerant Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 47doc 10048 | Condensers 1: Condenser Max Fan Speed Override | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 57doc 10058 | Condensers 2: Condenser Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 58doc 10059 | Condensers 2: Low Condenser Refrigerant Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 59doc 10060 | Condensers 2: Condenser Max Fan Speed Override | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 61doc 10062 | Condensers 3: Condenser Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 62doc 10063 | Condensers 3: Low Condenser Refrigerant Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 63doc 10064 | Condensers 3: Condenser Max Fan Speed Override | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 65doc 10066 | Condensers 4: Condenser Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 66doc 10067 | Condensers 4: Low Condenser Refrigerant Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 67doc 10068 | Condensers 4: Condenser Max Fan Speed Override | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 69doc 10070 | Low Fluid Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 80doc 10081 | Supply (Outlet) Fluid: Supply Fluid Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 81doc 10082 | Supply (Outlet) Fluid: Supply Fluid Under Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 82doc 10083 | Supply (Outlet) Fluid: Supply Fluid Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 106doc 10107 | All Pumps Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 107doc 10108 | Pump 1 Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 108doc 10109 | Pump 2 Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 119doc 10120 | Pump 1: Pump Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 130doc 10131 | Pump 2: Pump Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 141doc 10142 | Free Cooling Valve Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 142doc 10143 | Free Cooling: Ambient Air Temperature Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 153doc 10154 | Evaporator Inlet Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 154doc 10155 | Evaporator Return Fluid Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 155doc 10156 | Evaporator Return Fluid Under Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 164doc 10165 | Evaporator 1: Evaporator Fluid Freeze - Auto Reset | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 165doc 10166 | Evaporator 1: Evaporator Fluid Freeze - Manual Reset Required | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 166doc 10167 | Evaporator 1: Supply Refrigerant Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 177doc 10178 | Evaporator 2: Evaporator Fluid Freeze - Auto Reset | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 178doc 10179 | Evaporator 2: Evaporator Fluid Freeze - Manual Reset Required | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 179doc 10180 | Evaporator 2: Supply Refrigerant Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 190doc 10191 | System Events: Customer Input 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 191doc 10192 | System Events: Customer Input 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 192doc 10193 | System Events: Unit On | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 193doc 10194 | System Events: Unit Off | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 194doc 10195 | System Events: Master Unit Communication Lost | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 195doc 10196 | System Events: Subgroup Event Occurred During Communication Loss | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 196doc 10197 | System Events: Humidifier Control Board Not Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 197doc 10198 | System Events: RAM Battery Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 198doc 10199 | System Events: Unit Code Missing | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 199doc 10200 | System Events: Unspecified General Event | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 209doc 10210 | Compressor 3: Compressor Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 210doc 10211 | Compressor 3: Compressor High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 211doc 10212 | Compressor 3: Compressor Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 212doc 10213 | Compressor 3: Compressor Thermal Overload | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 213doc 10214 | Compressor 3: Compressor Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 215doc 10216 | Compressor 3: Compressor Loss of Differential Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 216doc 10217 | Compressor 3: Compressor Capacity Reduced | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 217doc 10218 | Compressor 3: Compressor Capacity Normal | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 218doc 10219 | Compressor 3: Compressor Contactor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 229doc 10230 | Compressor 4: Compressor Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 230doc 10231 | Compressor 4: Compressor High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 231doc 10232 | Compressor 4: Compressor Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 232doc 10233 | Compressor 4: Compressor Thermal Overload | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 233doc 10234 | Compressor 4: Compressor Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 235doc 10236 | Compressor 4: Compressor Loss of Differential Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 236doc 10237 | Compressor 4: Compressor Capacity Reduced | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 237doc 10238 | Compressor 4: Compressor Capacity Normal | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 238doc 10239 | Compressor 4: Compressor Contactor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 249doc 10250 | System Events: Unit Shutdown Unspecified General Event | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 250doc 10251 | System Events: Customer Input 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 251doc 10252 | System Events: Customer Input 4 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| IR | 384doc 30385 | Server Class | UINT16 | Read | 1 = UPS; 2 = AIR; 3 = PMP; 4 = PDU | ||||
| IR | 393doc 30394 | Compressor 1: Compressor State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 394doc 30395 | Compressor 1: Compressor Capacity Control State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 395doc 30396 | Compressor 1: Compressor Head Pressure | UINT16 | × 0.1 | bar | Read | |||
| IR | 401doc 30402 | Compressor 2: Compressor State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 402doc 30403 | Compressor 2: Compressor Capacity Control State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 403doc 30404 | Compressor 2: Compressor Head Pressure | UINT16 | × 0.1 | bar | Read | |||
| IR | 409doc 30410 | Condensers 1: Condenser Fan Speed | UINT16 | % | Read | ||||
| IR | 413doc 30414 | Condensers 2: Condenser Fan Speed | UINT16 | % | Read | ||||
| IR | 415doc 30416 | Condensers 3: Condenser Fan Speed | UINT16 | % | Read | ||||
| IR | 416doc 30417 | Condenser 4: Condenser Fan Speed | UINT16 | % | Read | ||||
| IR | 417doc 30418 | Fluid Pressure | UINT16 | × 0.1 | bar | Read | |||
| IR | 461doc 30462 | Free Cooling Status | UINT16 | Read | 0 = off; 2 = on; 3 = No Support | ||||
| IR | 462doc 30463 | Free Cooling Valve Open Position | UINT16 | % | Read | ||||
| IR | 468doc 30469 | Evaporator Return Fluid Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 482doc 30483 | System Info: System Status | UINT16 | Read | 1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation | ||||
| IR | 483doc 30484 | System Info: System Operating State | UINT16 | Read | 0 = off; 1 = on; 2 = standby | ||||
| IR | 484doc 30485 | System Info: System Control Mode | UINT16 | Read | 0 = Internal (Auto); 1 = External (Manual) | ||||
| IR | 485doc 30486 | System Info: System Operating State Reason | UINT16 | Read | 0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display | ||||
| IR | 490doc 30491 | System Operations: Return Fluid Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 492doc 30493 | System Operations: Supply Fluid Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 494doc 30495 | System Operations: Actual Supply Fluid Temp Set Point | INT16 | × 0.1 | deg C | Read | |||
| IR | 496doc 30497 | System Operations: Condenser Inlet Water Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 498doc 30499 | System Operations: Condenser Outlet Water Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 502doc 30503 | System Operations: Free Cooling Utilization | UINT16 | % | Read | ||||
| IR | 503doc 30504 | System Operations: Reheat Utilization | UINT16 | % | Read | ||||
| IR | 504doc 30505 | System Operations: Compressor Utilization | UINT16 | % | Read | ||||
| IR | 505doc 30506 | System Operations: Ambient Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 507doc 30508 | System Operations: Compressor Economizer Utilization | UINT16 | % | Read | ||||
| IR | 508doc 30509 | System Operations: Condenser Adiabatic Cooling Utilization | UINT16 | % | Read | ||||
| IR | 509doc 30510 | System Operations: Pump 1 State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 510doc 30511 | System Operations: Pump 2 State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 529doc 30530 | Compressor 3: Compressor State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 530doc 30531 | Compressor 3: Compressor Capacity Control State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 531doc 30532 | Compressor 3: Compressor Head Pressure | UINT16 | × 0.1 | bar | Read | |||
| IR | 549doc 30550 | Compressor 4: Compressor State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 550doc 30551 | Compressor 4: Compressor Capacity Control State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 551doc 30552 | Compressor 4: Compressor Head Pressure | UINT16 | × 0.1 | bar | Read | |||
| HR | 388doc 40389 | Compressor Shut Down - Ambient Air Low Temp Limit | INT16 | deg C | Read/write | ||||
| HR | 396doc 40397 | Compressor 1: Compressor Hours | UINT16 | hr | Read/write | ||||
| HR | 397doc 40398 | Compressor 1: Compressor Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 404doc 40405 | Compressor 2: Compressor Hours | UINT16 | hr | Read/write | ||||
| HR | 405doc 40406 | Compressor 2: Compressor Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 418doc 40419 | Fluid Cooling Proportional Band | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 423doc 40424 | Supply (Outlet) Fluid: Supply Fluid Temp Set Point 1 | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 425doc 40426 | Supply (Outlet) Fluid: Supply Fluid Temp Set Point 2 | INT16 | deg C | Read/write | ||||
| HR | 429doc 40430 | Supply (Outlet) Fluid: Supply Fluid Over Temp Alarm Threshold | INT16 | deg C | Read/write | ||||
| HR | 433doc 40434 | Supply (Outlet) Fluid: Supply Fluid Under Temp Alarm Threshold | INT16 | deg C | Read/write | ||||
| HR | 449doc 40450 | Pump 1: Pump Hours | UINT16 | hr | Read/write | ||||
| HR | 450doc 40451 | Pump 1: Pump Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 454doc 40455 | Pump 2: Pump Hours | UINT16 | hr | Read/write | ||||
| HR | 455doc 40456 | Pump 2: Pump Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 459doc 40460 | Free Cooling External Temperature Delta | INT16 | deg C | Read/write | ||||
| HR | 463doc 40464 | Free Cooling Valve Hours | UINT16 | hr | Read/write | ||||
| HR | 464doc 40465 | Free Cooling Valve Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 473doc 40474 | Supply Brine Temp Set Point | INT16 | deg C | Read/write | ||||
| HR | 478doc 40479 | Standby Units | UINT16 | Read/write | |||||
| HR | 486doc 40487 | System Info: System On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 500doc 40501 | System Operations: Supply Heated Water Temp Set Point | INT16 | deg C | Read/write | ||||
| HR | 514doc 40515 | System Event Acknowledge/Reset | UINT16 | Read/write | 2 = Reset; 4 = Acknowledge | ||||
| HR | 532doc 40533 | Compressor 3: Compressor Hours | UINT16 | hr | Read/write | ||||
| HR | 533doc 40534 | Compressor 3: Compressor Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 552doc 40553 | Compressor 4: Compressor Hours | UINT16 | hr | Read/write | ||||
| HR | 553doc 40554 | Compressor 4: Compressor Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 614doc 40615 | Evaporator Return Fluid Over Temp Alarm Threshold | INT16 | deg C | Read/write | ||||
| HR | 616doc 40617 | Evaporator Return Fluid Over Temp Warning Threshold | INT16 | deg C | Read/write | ||||
| HR | 618doc 40619 | Evaporator Return Fluid Under Temp Warning Threshold | INT16 | deg C | Read/write | ||||
| HR | 620doc 40621 | Evaporator Return Fluid Under Temp Alarm Threshold | INT16 | deg C | Read/write |
Notes on this map
- Source: Emerson Network Power / Liebert reference guide SL-28170 (Rev 9). Vertiv does not host this guide publicly; the linked copy is the unaltered PDF on the Contemporary Controls support site.
- Scale column: 'x / 10' means the raw value is tenths (scale 0.1); '-' or blank means no scaling. Some temperature setpoints are printed without a scale while similar points use x / 10; they are transcribed exactly as printed.
- Most temperatures exist twice: once in deg C and once in deg F at a different register. Only the deg C registers are listed here.
- Points that the guide lists with both an input register (3xxxx) and a holding register (4xxxx) are the writable settings; we list the holding register (read/write). The same value can also be read at the matching 3xxxx input register (same offset).
- Signedness is not stated in the guide. Temperature values are listed as INT16 (they can be below zero); everything else as UINT16.
- Points that take two registers (date/time and schedule start/stop times, 32-bit values) are left out because the guide does not state their word order.
- Event/alarm discrete inputs read 1 while the event is active ('Active on Alarm').
- Points marked in the guide as iCOM_SC100-only (compressors 3 and 4, condensers 3 and 4, customer inputs 3 and 4) are not present on SC31 units.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
What Modbus registers does the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) have?
This map lists 151 registers: 83 discrete inputs, 38 input registers, 30 holding registers. 30 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.
What are the minimum Modbus registers to integrate the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)?
Start with HR 486 System Info: System On/Off Control (System on/off control); IR 483 System Info: System Operating State (System operating state); IR 482 System Info: System Status (System status); IR 492 System Operations: Supply Fluid Temperature (Supply fluid temperature); IR 490 System Operations: Return Fluid Temperature (Return fluid temperature); HR 423 Supply (Outlet) Fluid: Supply Fluid Temp Set Point 1 (Supply fluid temperature setpoint 1); IR 504 System Operations: Compressor Utilization (Compressor utilisation); IR 505 System Operations: Ambient Air Temperature (Ambient air temperature); HR 514 System Event Acknowledge/Reset (Acknowledge / reset events).
How do I enable Modbus control of the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)?
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
Where is the official Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus documentation?
The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.
More Vertiv Modbus register maps
- Sensor (battery monitoring system)
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Alber MPM-100 (firmware 1.20+) and BDS series (controller firmware 2.20+) battery monitors with BMDM software 4.10+, per protocol document SL-29417 Rev 7.05.
Also known as: Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417 - Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit
Other chillers & heat pumps register maps
- Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063
All chillers & heat pumps Modbus register maps →
Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.