Chiller (air-cooled chiller for data centres) · Modbus register map

Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus register map

Updated 19 November 2026

Short answer

The Liebert HPC is an air-cooled chiller family (with optional free cooling) for data-centre chilled-water loops. With a Liebert IntelliSlot Modbus card the iCOM controller is a Modbus slave. This map covers compressor states, head pressures and run hours for up to four compressors, condenser fan speeds, supply/return fluid temperatures and setpoints, free cooling, pumps, system on/off and status, and the alarm bits.

This page lists 151 Modbus registers for the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) — 30 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.

Manufacturer
Vertiv
Model
Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Equipment type
Chiller (air-cooled chiller for data centres)
Registers
151 (30 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
iCOM_SC31 / iCOM_SC100 (per the guide)
Also known as
Liebert HPC, HPC chiller, Liebert HPC iCOM
Source document
Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)

Integration in brief

Read 30483-30511 for status, fluid temperatures and utilisation, and the discrete inputs for compressor, condenser, pump and system alarms. Write 40487 to switch the chiller on/off and 40424 for the supply fluid setpoint (tenths of deg C).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 486System Info: System On/Off ControlUINT16System on/off controlRead/write
IR 483System Info: System Operating StateUINT16System operating stateRead
IR 482System Info: System StatusUINT16System statusRead
IR 492System Operations: Supply Fluid TemperatureINT16Supply fluid temperatureRead
IR 490System Operations: Return Fluid TemperatureINT16Return fluid temperatureRead
HR 423Supply (Outlet) Fluid: Supply Fluid Temp Set Point 1INT16Supply fluid temperature setpoint 1Read/write
IR 504System Operations: Compressor UtilizationUINT16Compressor utilisationRead
IR 505System Operations: Ambient Air TemperatureINT16Ambient air temperatureRead
HR 514System Event Acknowledge/ResetUINT16Acknowledge / reset eventsRead/write

Enable Modbus control & writes

Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.

Byte order & addressing

Network setup

Watch out for

Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

151 of 151 shown
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
DI0doc 10001Compressor Not StoppingBITRead0 = Inactive; 1 = Active
DI1doc 10002Compressor Superheat Over ThresholdBITRead0 = Inactive; 1 = Active
DI11doc 10012Compressor 1: Compressor Hours ExceededBITRead0 = Inactive; 1 = Active
DI12doc 10013Compressor 1: Compressor High Head PressureBITRead0 = Inactive; 1 = Active
DI13doc 10014Compressor 1: Compressor Low Suction PressureBITRead0 = Inactive; 1 = Active
DI14doc 10015Compressor 1: Compressor Thermal OverloadBITRead0 = Inactive; 1 = Active
DI15doc 10016Compressor 1: Compressor Low Oil PressureBITRead0 = Inactive; 1 = Active
DI17doc 10018Compressor 1: Compressor Loss of Differential PressureBITRead0 = Inactive; 1 = Active
DI18doc 10019Compressor 1: Compressor Capacity ReducedBITRead0 = Inactive; 1 = Active
DI19doc 10020Compressor 1: Compressor Capacity NormalBITRead0 = Inactive; 1 = Active
DI20doc 10021Compressor 1: Compressor Contactor IssueBITRead0 = Inactive; 1 = Active
DI28doc 10029Compressor 2: Compressor Hours ExceededBITRead0 = Inactive; 1 = Active
DI29doc 10030Compressor 2: Compressor High Head PressureBITRead0 = Inactive; 1 = Active
DI30doc 10031Compressor 2: Compressor Low Suction PressureBITRead0 = Inactive; 1 = Active
DI31doc 10032Compressor 2: Compressor Thermal OverloadBITRead0 = Inactive; 1 = Active
DI32doc 10033Compressor 2: Compressor Low Suction PressureBITRead0 = Inactive; 1 = Active
DI34doc 10035Compressor 2: Compressor Loss of Differential PressureBITRead0 = Inactive; 1 = Active
DI35doc 10036Compressor 2: Compressor Capacity ReducedBITRead0 = Inactive; 1 = Active
DI36doc 10037Compressor 2: Compressor Capacity NormalBITRead0 = Inactive; 1 = Active
DI37doc 10038Compressor 2: Compressor Contactor IssueBITRead0 = Inactive; 1 = Active
DI45doc 10046Condensers 1: Condenser Fan IssueBITRead0 = Inactive; 1 = Active
DI46doc 10047Condensers 1: Low Condenser Refrigerant PressureBITRead0 = Inactive; 1 = Active
DI47doc 10048Condensers 1: Condenser Max Fan Speed OverrideBITRead0 = Inactive; 1 = Active
DI57doc 10058Condensers 2: Condenser Fan IssueBITRead0 = Inactive; 1 = Active
DI58doc 10059Condensers 2: Low Condenser Refrigerant PressureBITRead0 = Inactive; 1 = Active
DI59doc 10060Condensers 2: Condenser Max Fan Speed OverrideBITRead0 = Inactive; 1 = Active
DI61doc 10062Condensers 3: Condenser Fan IssueBITRead0 = Inactive; 1 = Active
DI62doc 10063Condensers 3: Low Condenser Refrigerant PressureBITRead0 = Inactive; 1 = Active
DI63doc 10064Condensers 3: Condenser Max Fan Speed OverrideBITRead0 = Inactive; 1 = Active
DI65doc 10066Condensers 4: Condenser Fan IssueBITRead0 = Inactive; 1 = Active
DI66doc 10067Condensers 4: Low Condenser Refrigerant PressureBITRead0 = Inactive; 1 = Active
DI67doc 10068Condensers 4: Condenser Max Fan Speed OverrideBITRead0 = Inactive; 1 = Active
DI69doc 10070Low Fluid PressureBITRead0 = Inactive; 1 = Active
DI80doc 10081Supply (Outlet) Fluid: Supply Fluid Over TempBITRead0 = Inactive; 1 = Active
DI81doc 10082Supply (Outlet) Fluid: Supply Fluid Under TempBITRead0 = Inactive; 1 = Active
DI82doc 10083Supply (Outlet) Fluid: Supply Fluid Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI106doc 10107All Pumps Loss of FlowBITRead0 = Inactive; 1 = Active
DI107doc 10108Pump 1 Loss of FlowBITRead0 = Inactive; 1 = Active
DI108doc 10109Pump 2 Loss of FlowBITRead0 = Inactive; 1 = Active
DI119doc 10120Pump 1: Pump Hours ExceededBITRead0 = Inactive; 1 = Active
DI130doc 10131Pump 2: Pump Hours ExceededBITRead0 = Inactive; 1 = Active
DI141doc 10142Free Cooling Valve Hours ExceededBITRead0 = Inactive; 1 = Active
DI142doc 10143Free Cooling: Ambient Air Temperature Sensor IssueBITRead0 = Inactive; 1 = Active
DI153doc 10154Evaporator Inlet Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI154doc 10155Evaporator Return Fluid Over TempBITRead0 = Inactive; 1 = Active
DI155doc 10156Evaporator Return Fluid Under TempBITRead0 = Inactive; 1 = Active
DI164doc 10165Evaporator 1: Evaporator Fluid Freeze - Auto ResetBITRead0 = Inactive; 1 = Active
DI165doc 10166Evaporator 1: Evaporator Fluid Freeze - Manual Reset RequiredBITRead0 = Inactive; 1 = Active
DI166doc 10167Evaporator 1: Supply Refrigerant Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI177doc 10178Evaporator 2: Evaporator Fluid Freeze - Auto ResetBITRead0 = Inactive; 1 = Active
DI178doc 10179Evaporator 2: Evaporator Fluid Freeze - Manual Reset RequiredBITRead0 = Inactive; 1 = Active
DI179doc 10180Evaporator 2: Supply Refrigerant Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI190doc 10191System Events: Customer Input 1BITRead0 = Inactive; 1 = Active
DI191doc 10192System Events: Customer Input 2BITRead0 = Inactive; 1 = Active
DI192doc 10193System Events: Unit OnBITRead0 = Inactive; 1 = Active
DI193doc 10194System Events: Unit OffBITRead0 = Inactive; 1 = Active
DI194doc 10195System Events: Master Unit Communication LostBITRead0 = Inactive; 1 = Active
DI195doc 10196System Events: Subgroup Event Occurred During Communication LossBITRead0 = Inactive; 1 = Active
DI196doc 10197System Events: Humidifier Control Board Not DetectedBITRead0 = Inactive; 1 = Active
DI197doc 10198System Events: RAM Battery IssueBITRead0 = Inactive; 1 = Active
DI198doc 10199System Events: Unit Code MissingBITRead0 = Inactive; 1 = Active
DI199doc 10200System Events: Unspecified General EventBITRead0 = Inactive; 1 = Active
DI209doc 10210Compressor 3: Compressor Hours ExceededBITRead0 = Inactive; 1 = Active
DI210doc 10211Compressor 3: Compressor High Head PressureBITRead0 = Inactive; 1 = Active
DI211doc 10212Compressor 3: Compressor Low Suction PressureBITRead0 = Inactive; 1 = Active
DI212doc 10213Compressor 3: Compressor Thermal OverloadBITRead0 = Inactive; 1 = Active
DI213doc 10214Compressor 3: Compressor Low Suction PressureBITRead0 = Inactive; 1 = Active
DI215doc 10216Compressor 3: Compressor Loss of Differential PressureBITRead0 = Inactive; 1 = Active
DI216doc 10217Compressor 3: Compressor Capacity ReducedBITRead0 = Inactive; 1 = Active
DI217doc 10218Compressor 3: Compressor Capacity NormalBITRead0 = Inactive; 1 = Active
DI218doc 10219Compressor 3: Compressor Contactor IssueBITRead0 = Inactive; 1 = Active
DI229doc 10230Compressor 4: Compressor Hours ExceededBITRead0 = Inactive; 1 = Active
DI230doc 10231Compressor 4: Compressor High Head PressureBITRead0 = Inactive; 1 = Active
DI231doc 10232Compressor 4: Compressor Low Suction PressureBITRead0 = Inactive; 1 = Active
DI232doc 10233Compressor 4: Compressor Thermal OverloadBITRead0 = Inactive; 1 = Active
DI233doc 10234Compressor 4: Compressor Low Suction PressureBITRead0 = Inactive; 1 = Active
DI235doc 10236Compressor 4: Compressor Loss of Differential PressureBITRead0 = Inactive; 1 = Active
DI236doc 10237Compressor 4: Compressor Capacity ReducedBITRead0 = Inactive; 1 = Active
DI237doc 10238Compressor 4: Compressor Capacity NormalBITRead0 = Inactive; 1 = Active
DI238doc 10239Compressor 4: Compressor Contactor IssueBITRead0 = Inactive; 1 = Active
DI249doc 10250System Events: Unit Shutdown Unspecified General EventBITRead0 = Inactive; 1 = Active
DI250doc 10251System Events: Customer Input 3BITRead0 = Inactive; 1 = Active
DI251doc 10252System Events: Customer Input 4BITRead0 = Inactive; 1 = Active
IR384doc 30385Server ClassUINT16Read1 = UPS; 2 = AIR; 3 = PMP; 4 = PDU
IR393doc 30394Compressor 1: Compressor StateUINT16Read0 = off; 1 = on
IR394doc 30395Compressor 1: Compressor Capacity Control StateUINT16Read0 = off; 1 = on
IR395doc 30396Compressor 1: Compressor Head PressureUINT16× 0.1barRead
IR401doc 30402Compressor 2: Compressor StateUINT16Read0 = off; 1 = on
IR402doc 30403Compressor 2: Compressor Capacity Control StateUINT16Read0 = off; 1 = on
IR403doc 30404Compressor 2: Compressor Head PressureUINT16× 0.1barRead
IR409doc 30410Condensers 1: Condenser Fan SpeedUINT16%Read
IR413doc 30414Condensers 2: Condenser Fan SpeedUINT16%Read
IR415doc 30416Condensers 3: Condenser Fan SpeedUINT16%Read
IR416doc 30417Condenser 4: Condenser Fan SpeedUINT16%Read
IR417doc 30418Fluid PressureUINT16× 0.1barRead
IR461doc 30462Free Cooling StatusUINT16Read0 = off; 2 = on; 3 = No Support
IR462doc 30463Free Cooling Valve Open PositionUINT16%Read
IR468doc 30469Evaporator Return Fluid TemperatureINT16× 0.1deg CRead
IR482doc 30483System Info: System StatusUINT16Read1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation
IR483doc 30484System Info: System Operating StateUINT16Read0 = off; 1 = on; 2 = standby
IR484doc 30485System Info: System Control ModeUINT16Read0 = Internal (Auto); 1 = External (Manual)
IR485doc 30486System Info: System Operating State ReasonUINT16Read0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display
IR490doc 30491System Operations: Return Fluid TemperatureINT16× 0.1deg CRead
IR492doc 30493System Operations: Supply Fluid TemperatureINT16× 0.1deg CRead
IR494doc 30495System Operations: Actual Supply Fluid Temp Set PointINT16× 0.1deg CRead
IR496doc 30497System Operations: Condenser Inlet Water TemperatureINT16× 0.1deg CRead
IR498doc 30499System Operations: Condenser Outlet Water TemperatureINT16× 0.1deg CRead
IR502doc 30503System Operations: Free Cooling UtilizationUINT16%Read
IR503doc 30504System Operations: Reheat UtilizationUINT16%Read
IR504doc 30505System Operations: Compressor UtilizationUINT16%Read
IR505doc 30506System Operations: Ambient Air TemperatureINT16× 0.1deg CRead
IR507doc 30508System Operations: Compressor Economizer UtilizationUINT16%Read
IR508doc 30509System Operations: Condenser Adiabatic Cooling UtilizationUINT16%Read
IR509doc 30510System Operations: Pump 1 StateUINT16Read0 = off; 1 = on
IR510doc 30511System Operations: Pump 2 StateUINT16Read0 = off; 1 = on
IR529doc 30530Compressor 3: Compressor StateUINT16Read0 = off; 1 = on
IR530doc 30531Compressor 3: Compressor Capacity Control StateUINT16Read0 = off; 1 = on
IR531doc 30532Compressor 3: Compressor Head PressureUINT16× 0.1barRead
IR549doc 30550Compressor 4: Compressor StateUINT16Read0 = off; 1 = on
IR550doc 30551Compressor 4: Compressor Capacity Control StateUINT16Read0 = off; 1 = on
IR551doc 30552Compressor 4: Compressor Head PressureUINT16× 0.1barRead
HR388doc 40389Compressor Shut Down - Ambient Air Low Temp LimitINT16deg CRead/write
HR396doc 40397Compressor 1: Compressor HoursUINT16hrRead/write
HR397doc 40398Compressor 1: Compressor Hours ThresholdUINT16hrRead/write
HR404doc 40405Compressor 2: Compressor HoursUINT16hrRead/write
HR405doc 40406Compressor 2: Compressor Hours ThresholdUINT16hrRead/write
HR418doc 40419Fluid Cooling Proportional BandINT16× 0.1deg CRead/write
HR423doc 40424Supply (Outlet) Fluid: Supply Fluid Temp Set Point 1INT16× 0.1deg CRead/write
HR425doc 40426Supply (Outlet) Fluid: Supply Fluid Temp Set Point 2INT16deg CRead/write
HR429doc 40430Supply (Outlet) Fluid: Supply Fluid Over Temp Alarm ThresholdINT16deg CRead/write
HR433doc 40434Supply (Outlet) Fluid: Supply Fluid Under Temp Alarm ThresholdINT16deg CRead/write
HR449doc 40450Pump 1: Pump HoursUINT16hrRead/write
HR450doc 40451Pump 1: Pump Hours ThresholdUINT16hrRead/write
HR454doc 40455Pump 2: Pump HoursUINT16hrRead/write
HR455doc 40456Pump 2: Pump Hours ThresholdUINT16hrRead/write
HR459doc 40460Free Cooling External Temperature DeltaINT16deg CRead/write
HR463doc 40464Free Cooling Valve HoursUINT16hrRead/write
HR464doc 40465Free Cooling Valve Hours ThresholdUINT16hrRead/write
HR473doc 40474Supply Brine Temp Set PointINT16deg CRead/write
HR478doc 40479Standby UnitsUINT16Read/write
HR486doc 40487System Info: System On/Off ControlUINT16Read/write0 = off; 1 = on
HR500doc 40501System Operations: Supply Heated Water Temp Set PointINT16deg CRead/write
HR514doc 40515System Event Acknowledge/ResetUINT16Read/write2 = Reset; 4 = Acknowledge
HR532doc 40533Compressor 3: Compressor HoursUINT16hrRead/write
HR533doc 40534Compressor 3: Compressor Hours ThresholdUINT16hrRead/write
HR552doc 40553Compressor 4: Compressor HoursUINT16hrRead/write
HR553doc 40554Compressor 4: Compressor Hours ThresholdUINT16hrRead/write
HR614doc 40615Evaporator Return Fluid Over Temp Alarm ThresholdINT16deg CRead/write
HR616doc 40617Evaporator Return Fluid Over Temp Warning ThresholdINT16deg CRead/write
HR618doc 40619Evaporator Return Fluid Under Temp Warning ThresholdINT16deg CRead/write
HR620doc 40621Evaporator Return Fluid Under Temp Alarm ThresholdINT16deg CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)

What Modbus registers does the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) have?

This map lists 151 registers: 83 discrete inputs, 38 input registers, 30 holding registers. 30 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.

What are the minimum Modbus registers to integrate the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)?

Start with HR 486 System Info: System On/Off Control (System on/off control); IR 483 System Info: System Operating State (System operating state); IR 482 System Info: System Status (System status); IR 492 System Operations: Supply Fluid Temperature (Supply fluid temperature); IR 490 System Operations: Return Fluid Temperature (Return fluid temperature); HR 423 Supply (Outlet) Fluid: Supply Fluid Temp Set Point 1 (Supply fluid temperature setpoint 1); IR 504 System Operations: Compressor Utilization (Compressor utilisation); IR 505 System Operations: Ambient Air Temperature (Ambient air temperature); HR 514 System Event Acknowledge/Reset (Acknowledge / reset events).

How do I enable Modbus control of the Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)?

Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.

Where is the official Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus) Modbus documentation?

The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.

More Vertiv Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.